Data Sheet: Category 5e 110Connect Patch Panels

Data Sheet: Category 5e 110Connect Patch Panels
Category 5e 110Connect Patch Panels
CommScope’s Category 5e 110Connect patch panels exceed ANSI/
TIA 568-C.2 and ISO requirements for Enhanced Category 5 performance.
The CommScope Category 5e System complies with all of the performance
requirements for current and proposed applications such as Gigabit Ethernet
(1000BASE-Tx), 10/100BASE-Tx, token ring, 155 Mbps ATM, 100 Mbps
TP-PMD, ISDN, analog (broadband [550 MHz] and baseband) and digital
video and analog and digital voice (VoIP).
CommScope’s Category 5e 110Connect patch panels feature universal wiring labels which
permit field installation to either T568A or T568B wiring, simplifying both ordering and inventory.
110Connect patch panel punchdown blocks are compatible with standard 110 and CommScope
single-wire tools as well as standard 110 5-pair tools. CommScope’s Category 5e 110Connect patch
panels are designed with “6-pack” modules that accept 9mm and 12mm (included) labels as well as
colored icons. These 6-pack modules may also be replaced individually if necessary. CommScope’s
patch panels mount to standard 19” racks.
1
For more information, visit commscope.com
Category 5e 110Connect Patch Panels
Specification (text in brackets [ ] requires a choice)
Patch panels shall be [1U, 2U, 4U or 10in], and provide [12, 24, 48 or 96] RJ-45 (8-position – 4-pair) modular jack ports. Patch
panels shall utilize replaceable, 6-port PCB modules. Each module shall be capable of accepting 9 – 12mm labels. Each port on
a module shall be capable of accepting an icon to indicate its function. Patch panels shall terminate building cabling on 110-style
insulation displacement connectors and shall be provided with color-coded labeling for both T568A and T568B wiring. Patch
panels shall be wired to [T568A or T568B]. Patch panels shall meet ANSI/TIA 568-C.2 requirements for Category 5e component
performance as well as the performance requirements listed in the table below. Patch panels shall be UL Listed under file number
E81956. Patch panels shall be part number(s) [406330-1, 406331-1, 406332-1, 406390-1 and/or 406981-1].
Part Numbers
Description
Number of Ports
Height
Part Numbers
12
*
406390-1
12
1.75"
406981-1
24
1.75"
406330-1
48
3.50"
406331-1
96
7.00"
406332-1
Category 5e 110Connect Patch Panel
*Mini patch panel dimensions: 10.0” H x 2.3” D. Mounts vertically on 89D bracket (included).
Typical Worst-Case Performance Characteristics (exceed ANSI/TIA 568-C.2 Category 5e).
Frequency,
MHz
Attenuation, dB
NEXT, dB
PS NEXT, dB
FEXT, dB
Return Loss, dB
Standard
Max.
Standard
Min.
Standard
Min.
Standard
Min.
Standard
Min.
1
0.1
0.05
65.0
85.9
-
83.9
65.0
83.5
35.0
54.2
4
0.1
0.05
65.0
72.7
-
70.9
63.1
73.1
35.0
47.8
8
0.1
0.05
64.0
66.9
-
65.0
57.0
67.5
35.0
42.8
10
0.1
0.05
63.0
64.9
-
63.0
55.1
65.5
35.0
41.0
16
0.2
0.10
58.9
60.7
-
58.9
51.0
61.5
35.0
37.2
20
0.2
0.10
57.0
58.9
-
57.1
49.1
59.8
34.0
35.5
25
0.2
0.10
55.0
56.9
-
55.1
47.1
57.8
32.0
33.7
31.25
0.2
0.10
53.1
54.9
-
53.0
45.2
55.8
30.1
31.8
62.5
0.3
0.15
47.1
49.0
-
46.7
39.2
50.2
24.2
26.2
100
0.4
0.20
43.0
44.5
-
41.9
35.1
45.9
20.0
22.6
155
-
0.26
-
36.5
-
36.2
-
28.3
-
16.2
200
-
0.29
-
32.0
-
34.0
-
26.1
-
14.0
250
-
0.32
-
27.8
-
32.0
-
24.1
-
12.0
300
-
0.36
-
26.0
-
30.5
-
22.6
-
10.5
350
-
0.38
-
23.5
-
29.1
-
21.2
-
9.1
2
For more information, visit commscope.com
Category 5e 110Connect Patch Panels
Technical Details
Materials
Panel (406390 and 406332):
Black anodized aluminum
Panel (406330 and 331, 332):
Black powder-coated steel
Jack Housing:
Polyphenylene oxide, 94V-0 rated
110 Blocks:
Polycarbonate, 94V-0 rated
Jack Contacts:
Phosphorous bronze, plated with 1.27µm [.000050in] thick gold in localized
area and 3.81µm [.000150in] minimum thick tin-lead in solder area over
1.27µm [.000050in] minimum thick nickel underplate.
Packaging
406330:
1 per box/5 boxes per carton, 9 lbs
406331:
1 per box/5 boxes per carton, 13 lbs
406332:
1 per box, 4.26 lbs
406390:
1 per box, 1 lb
406981:
1 per box/5 boxes per carton, 8 lbs
Durability
Modular Jack:
750 mating cycles
110 Blocks:
200 termination cycles
UL Listed
File Number:
E81956
www.commscope.com
Visit our website or contact your local CommScope representative for more information.
© 2015 CommScope, Inc. All rights reserved.
All trademarks identified by ® or ™ are registered trademarks or trademarks, respectively, of CommScope, Inc.
This document is for planning purposes only and is not intended to modify or supplement any specifications or
warranties relating to CommScope products or services.
PS-317956.1-AE (11/15)
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertising