Karta katalogowa SEM1801XTC i SEM1802XTC 2013-07

Karta katalogowa SEM1801XTC i SEM1802XTC  2013-07
RAIL MOUNTED I.S. APPROVED THERMOCOUPLE TRANSMITTER
SEM1801XTC, SEM1802XTC
K, J, N, E, T, R, S, L, U, B, C(W5), D(W3), G(W)
ATEX AND IECEx APPROVED VERSION
SINGLE AND DUAL CHANNEL VERSIONS
SENSOR
(4 to 20) mA LOOP POWERED
SENSOR OFFSET AND OUTPUT ALIGNMENT
ISOLATION INPUT TO OUTPUT
OUTPUT
V
SENSOR
OUTPUT
V
PROGRAMMABLE BURNOUT
INTRODUCTION
The SEM1801/2XTC Din rail temperature transmitter accepts thermocouple temperature sensors and converts the
sensor output over a configured range to a standard industrial (4 to 20) mA transmission signal. Two versions are
available; single or dual channel ATEX / IECEx approved for hazardous areas.
PC configuration allows the user to select TC type, Range, Filter, units, linearization and Burnout direction, without
requiring calibration equipment. Additionally, the user may read live process data when connected to the PC (in the
safe area), this allows for sensor offset, and output alignment calibration, where the user can enter values to match
the actual process and therefore reducing system errors.
If required, the desired range can be specified at the time of order, removing the need for user configuration.
If the range is not specified then the transmitter will be shipped with the default range of (0 to 1000) °C type K.
RAIL MOUNTED I.S. APPROVED THERMOCOUPLE TRANSMITTER
SPECIFICATION @20 °C
THERMOCOUPLE INPUT
Standard TC
Types K,J,E,N,T,R,S,L,U,B,C(w5),D(W3),G(W),library
USER INTERFACE
Type
USB 2.0
Thermal Drift
Thermocouple offset 0.1 °C/°C, span 0.05 °C/°C
Baud rate
1200 baud
Cold Junction
Range (-40 to 85) °C, Accuracy ± 0.2 °C, ± 0.05 °C/°C
Equipment
PC running windows XP or later, USB configurator.
THERMOCOUPLE ACCURACY
Accuracy ±0.1 % of full scale ± 0.5 °C (plus sensor error)
K (-200 to 1370), J (-100 to 1200), E (-200 to 1000), N (-180 to 1300)
L (-100 to 600), U (0 to 600), B (0 to 1800), C – D – W (0 to 2300)
USER INTERFACE FUNCTIONS
Scaling
User signal to process value scaling, for simplified
setup.
Filter
Adjustable time constant (0 to100) Seconds.
Accuracy ±0.2 % of full scale ± 0.5 °C (plus sensor error)
T (-200 to 400)
Process Units
4 Characters (signal input only)
Temperature units
°C or °F (TC inputs only)
Accuracy ± 0.1 % of full scale plus ± 0.5 °C (range 800 to 1600)
R (0 to 1760), S (0 to 1760)
Tag Number
20 Characters
Process Output
Range in process units
OUTPUT
Type
Two wire (4 to 20) mA current Loop
Range
(4 to 20) mA ;
Upscale burnout 21.5 mA ; Downscale Burnout 3.8 mA
Accuracy
(mA Out/ 2000) or 5 uA which ever is the greater,
Drift 1 uA/°C
User offset
Enter sensor offset (Temperature mode only).
Active scaling
Set output process range against active sensor input
ENVIRONMENT
Operating Ambient
(-40 to 70) °C; (10 to 90) % RH (non condensing)
Storage Ambient
(-50 to 70) °C; (10 to 90) % RH (non condensing)
(10 to 30) °C
Loop Effect
± 0.2 uA/ V
Configuration Ambient
Max output load
[(Vsupply-10)/20] K Ohms / per channel
(Example 700 Ohms @ 24 V)
Installation Enclosure
>= IP65.
APPROVALS
CE
BS EN 61326
SUPPLY
Loop Supply
(10 to 30) VDC per channel
Power
< 1W Full Power per channel
MECHANICAL
Dimensions
Weight
GENERAL
Response time
Start up 5 seconds, Update 160 mS, Response 500 mS
Warm up
2 minutes.
Isolation
Input to output 500 V dc.
Connections
Screw terminals 2.5 mm Maximum
120 mm deep; 107.3 mm height; 22.5 mm wide
110 g – SEM1801XTC
141 g – SEM1802XTC
SEM1801XTC, SEM1802XTC ATEX / IECEx special conditions for safe use.
1.
2.
3.
4.
5.
6.
For gas applications, the SEM1801XTC, SEM1802XTC temperature transmitters must be mounted in a metallic enclosure rated for IP54 and located in area where
the enclosure will not be subject to impact of friction.
For dust applications, the SEM1801XTC, SEM1802XTC temperature transmitters must be mounted in a suitably ATEX or IECEx certified enclosure appropriate for
the zone of end use .
The equipment shall only be configured by means of the USB connection outside the hazardous area.
If the equipment is mounted in an enclosure with separate IS circuits, appropriate segregation shall be provided in accordance with IEC 60079-11 Clause 6.2.1.
SEM1801XTC, SEM1802XTC - Only for connection to suitable thermocouples. These shall conform to the requirements for simple apparatus as defined in IEC
The ambient temperature range of the enclosure will limit the permitted ambient range of the overall equipment. Refer to enclosure certification.
Order code:
Status Instruments Ltd
Status Business Park
Gannaway Lane, Tewkesbury
Gloucestershire, UK
GL20 8FD
Tel: +44 (0)1684 296818
Fax: +44 (0)1684 293746
Email: sales@status.co.uk
Website: www.status.co.uk
D2557-01-02 SEM1801_2XTC CN5110 Data Sheet