AL1012M220 Multi-Output Access Control Power Supply/Charger Overview

AL1012M220 Multi-Output Access Control Power Supply/Charger Overview
AL1012M220
Multi-Output Access Control Power Supply/Charger
Rev. DSAL1012M220_02142013
Overview
AL1012M220
AL1012M220 multi-output access control power supply/charger is specifically
designed for use with access control systems and accessories. This unit converts a 220VAC 50/60Hz input into five (5) individual PTC protected 12VDC
outputs (see specifications). Each output will route power to a variety of access
control hardware devices including Mag Locks, Electric Strikes, Magnetic Door
Holders, etc. These outputs will operate in both Fail-Safe and Fail-Secure modes.
Controlled trigger input is achieved through normally open (N.O.) or normally
closed (N.C.) supervised input or the polarity reversal from an FACP (Fire Alarm
Control Panel). A form “C” dry output relay enables HVAC Shutdown, Elevator
Recall or may be used to trigger auxiliary devices.
Input:
Specifications
Supervision:
• Input 220VAC 50/60Hz, 1.6 amp.
• Input fuse rated @ 3.5 amp/250V.
• Fire Alarm Panel or Access Control System trigger
inputs. N.O. or N.C. supervised trigger input and
polarity reversal trigger input.
Output:
• 12VDC outputs.
• 10 amp supply current.
• Five (5) individual PTC protected outputs,
rated @ 2 amp.
• Output relay energizes when unit is triggered
(form “C” contact rated 1 amp @ 28VDC).
• Filtered and electronically regulated output.
• Short circuit and thermal overload protection.
• Current limit is 2 amp per output.
Battery Backup:
• Built-in charger for sealed lead acid or
gel type batteries.
• Automatic switch over to stand-by battery
when AC fails (zero voltage drop).
• Maximum charge current 0.7 amp.
• AC fail supervision (form “C” contact).
• Low battery supervision (form “C” contact).
• Battery presence supervision (form “C” contact).
• Power fail supervision relay (form “C” contact rated
1 amp @ 28VDC).
Visual Indicators:
• DC output LED indicator.
• LEDs indicate condition of power outputs.
• Power & input trigger LEDs.
Electrical:
• Operating temperature: 0º C to 49º C ambient.
• BTU/Hr.: 61.42 BTU/hr.
• System AC input VA requirement: 352VA.
Mechanical:
• Enclosure Dimensions (H x W x D approx.):
15.5” x 12” x 4.5” (394mm x 305mm x 114mm)
- Combination knockouts are 1” (25.4mm) and
0.75” (19mm).
- Accommodates up to one (1) 12VDC/12AH battery.
• Product weight (approx.): 8.95 lbs. (4.06 kg).
• Shipping weight (approx.): 10.25 lbs. (4.65 kg).
Enclosure Dimensions (H x W x D approximate):
15.5” x 12” x 4.5” (394mm x 305mm x 114mm)
1.5”
(38.1mm)
4.615”
(117.22mm)
4.615”
(117.22mm)
1.5”
(38.1mm)
1.75”
(44.45mm)
1.375”
(34.925mm)
1.125”
(28.575mm)
1.25”
(31.75mm)
4.5”
(114.3mm)
12.23”
(310.64mm)
1.1”
(27.94mm)
0.91”
(23.114mm)
1.5”
(38.1mm)
4.5”
(114.3mm)
1.1”
(27.94mm)
1.25”
(31.75mm)
0.91”
(23.114mm)
2.0”
(50.8mm)
1.5”
(38.1mm)
15.5”
(393.7mm)
2.0”
(50.8mm)
5.0”
(127.0mm)
5.0”
(127.0mm)
1.1”
(27.94mm)
1.25”
(31.75mm)
0.79”
(20.06mm)
1.75”
(44.45mm)
1.5”
(38.1mm)
4.615”
(117.22mm)
4.615”
(117.22mm)
Altronix Corp. - 140 58th Street, Brooklyn, NY 11220 • 718-567-8181 • 888-258-7669 • altronix.com
1.5”
(38.1mm)
1.25”
(31.75mm)
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertising