E50H2
Installation Guide
Power Monitoring
TM
E50H2, E50H5
·
Compact Power and Energy Meters
With BACnet MS/TP Support
Product Overview
B
A C n et
·
G
A
T
E S T I N
Compliant
®
O R I E S
T
RoHS
The E50H2 and E50H5 DIN rail power meters provide a solution for measuring energy data with a single device.
Inputs include control power, CT, and 3-phase voltage. Both models support BACnet MS/TP protocol. The E50H2
has one pulse contact input and a phase loss alarm output. The E50H5 has data logging capability and two pulse
contact inputs. The LCD screen on the faceplate allows instant output viewing.
L A
R
B O
E50H2 only
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
•
•
•
•
•
•
•
•
•
Follow safe electrical work practices. See NFPA 70E in the USA, or applicable local codes.
This equipment must only be installed and serviced by qualified electrical personnel.
Read, understand and follow the instructions before installing this product.
Turn off all power supplying equipment before working on or inside the equipment.
Product may use multiple voltage/power sources. Disconnect all sources of power
before servicing.
Use a properly rated voltage sensing device to confirm power is off.
DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION.
Current transformer secondaries must be shorted or connected to a burden at all times.
Products rated only for basic insulation must be installed on insulated conductors.
Replace all doors, covers and protective devices before powering the equipment.
Failure to follow these instructions will result in death or serious injury.
A qualified person is one who has skills and knowledge related to the construction and
operation of this electrical equipment and installations, and has received safety
training to recognize and avoid the hazards involved.
NEC2014 Article 100
No responsibility is assumed by Veris Industries for any consequences arising out of the
use of this material.
Control system design must consider the potential failure modes of control paths and, for
certain critical control functions, provide a means to acheive a safe state during and after a
path failure. Examples of critical control functions are emergency stop and over-travel stop.
WARNING
The meter is housed in a plastic enclosure suitable for installation on T35 DIN rail according to EN50022. It can be
mounted with any orientation over the entire ambient temperature range, either on a DIN rail or in a panel. The
E50Hx meters are not sensitive to CT orientation, reducing installation errors.
Product Identification
BACnet MS/TP
Protocol Output
Alarm
Output
Full Data
Set
E50H2
n
n
n
E50H5
n
Model
n
NEMA ICS 1.1 (latest edition). Safety Guidelins for the Application, Installation, and Maintenance
of Solid-State Control or its equivalent in your specific country, language, and/or location.
NOTICE
Real Power and Energy
Reactive Power and Energy
Current
n
n
(2 pulses)
FCC PART 15 INFORMATION
NOTE: This equipment has been tested by the manufacturer and found to
comply with the limits for a class B digital device, pursuant to part 15 of
the FCC Rules. These limits are designed to provide reasonable protection
against harmful interference when the equipment is operated in a
residential environment. This equipment generates, uses, and can radiate
radio frequency energy and, if not installed and used in accordance with
the instruction manual, may cause harmful interference to radio
communications. This device complies with part 15 of the FCC Rules.
Operation is subject to the following two conditions:
(1) This device may not cause harmful interference, and
(2) this device must accept any interference received, including
interference that may cause undesired operation.
Modifications to this product without the express authorization of the
manufacturer nullify this statement.
For use in a Pollution Degree 2 or better environment only. A Pollution Degree 2 environment must
control conductive pollution and the possibility of condensation or high humidity. Consider the
enclosure, the correct use of ventilation, thermal properties of the equipment, and the relationship with
the environment. Installation category: CAT II or CAT III. Provide a disconnect device to disconnect the
meter from the supply source. Place this device in close proximity to the equipment and within easy
reach of the operator, and mark it as the disconnecting device. The disconnecting device shall meet the
relevant requirements of IEC 60947-1 and IEC 60947-3 and shall be suitable for the application. In the US
and Canada, disconnecting fuse holders can be used. Provide overcurrent protection and disconecting
device for supply conductors with approved current limiting devices suitable for protecting the wiring.
If the equipment is used in a manner not specified by the manufacturer, the protection provided by the
device may be impaired.
IEC 62053-22 Class 0.2S, ANSI C12.20 0.2%
IEC 62053-23 Class 2, 2%
0.4% (+0.015% per °C deviation from 25°C) from 5% to 100% of
range;
0.8% (+0.015% per °C deviation from 25°C) from 1% to 5% of range
Voltage
Sample Rate
This product is not intended for life or safety applications.
Do not install this product in hazardous or classified locations.
The installer is responsible for conformance to all applicable codes.
Mount this product inside a suitable fire and electrical enclosure.
Page 1 of 28
n
Specifications
1For additional information about anticipated transmission delays or failures of the link, refer to
ZL0071-0E
Pulse
Input
MEASUREMENT ACCURACY
LOSS OF CONTROL
∙ Assure that the system will reach a safe state during and after a control path failure.
∙ Separate or redundant control paths must be provided for critical control functions.
∙ Test the effect of transmission delays or failures of communication links.1
∙ Each implementation of equipment using communication links must be individually
and thoroughly tested for proper operation before placing it in service.
Failure to follow these instructions may cause injury, death or equipment damage.
•
•
•
•
Data
Logging
Data Update Rate
Type of Measurement
0.4% (+0.015% per °C deviation from 25°C) from 90VL-N to 600VACL-L
2520 samples per second
1 sec
True RMS up to the 21st harmonic 60 Hz; One to three phase AC
system
INPUT VOLTAGE CHARACTERISTICS
Measured AC Voltage
Minimum 90VL-N (156VL-L) for stated accuracy;
UL Maximum: 600VL-L (347VL-N ); CE Maximum: 300VL-N
Metering Over-Range
Impedance
Frequency Range
+20%
2.5 MΩ L-N /5 MΩ L-L
45 to 65 Hz
INPUT CURRENT CHARACTERISTICS
CT Scaling
Measurement Input Range
Impedance
Primary: Adjustable from 5 A to 32,000 A
0 to 0.333 VAC or 0 to 1.0 VAC (+20% over-range), rated for use with
Class 1 voltage inputs
10.6 kΩ (1/3 V mode) or 32.1 kΩ (1 V mode)
©2014 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide
Power Monitoring
E50H2, E50H5
Specifications
(cont.)
TM
CONTROL POWER
AC
5 VA max.; 90V min.
UL Maximum: 600VL-L (347VL-N ); CE Maximum: 300VL-N
DC*
Ride Through Time
3 W max.; UL and CE: 125 to 300VDC
100 msec at 120VAC
INPUT
Pulse
Solid-state or mechanical contacts (current less than 1 mA);
E50H2: 1 pulse input; E50H5: 2 pulse inputs
Minimum Pulse Width
20 msec
OUTPUT
Alarm Contacts (E50H2 only)
RS-485 Port
N.C., static output; (30VAC/DC, 100mA [email protected]°C, derate 0.56mA
per °C above 25°C)
2-wire, 9600 to 115.2 kbaud, BACnet MS/TP
MECHANICAL CHARACTERISTICS
Weight
0.62 lb (0.28 kg)
IP Degree of Protection
(IEC 60529)
IP40 front display; IP20 Meter
Display Characteristics
Back-lit blue LCD
Terminal Block Screw Torque
Terminal Block Wire Size
Rail
0.37 to 0.44 ft-lb (0.5 to 0.6 N·m)
24 to 14 AWG (0.2 to 2.1 mm2)
T35 (35mm) DIN Rail per EN50022
OPERATING CONDITIONS
Operating Temperature Range
-30° to 70°C (-22° to 158°F)
Storage Temperature Range
-40° to 85°C (-40° to 185°F)
Humidity Range
Altitude of Operation
<95% RH noncondensing
3000 m
COMPLIANCE INFORMATION
US and Canada
CAT III, Pollution degree 2;
for distribution systems up to 347VL-N /600VACL-L
CE
CAT III, Pollution degree 2;
for distribution systems up to 300VL-N
Dielectric Withstand
Per UL 508, EN61010
Conducted and Radiated
Emissions
FCC part 15 Class B, EN55011/EN61000 Class B (residential and light
industrial)
Conducted and Radiated
Immunity
EN61000 Class A (heavy industrial)
US and Canada (cULus)
Europe (CE)
UL508 (open type device)/CSA 22.2 No. 14-05
EN61010-1
* External DC current limiting is required, see fuse recommendations.
ZL0071-0E
Page 2 of 28
©2014 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide
Power Monitoring
E50H2, E50H5
Table of Contents
ZL0071-0E
Page 3 of 28
TM
Dimensions
4
Data Outputs
4
Product Diagram
5
Display Screen Diagram
5
Installation
6
Supported System Types
7
Wiring Symbols
7
Wiring
8
Control Power Diagrams
9
Quick Setup Instructions
10
Pulse Contact Input
11
User Interface Menu Abbreviations Defined
11
User Interface for Data Configuration
12
Alert/Reset Information
13
User Interface for Setup
14
RS-485 Communications
16
BACnet Default Settings
17
BACnet Programming Information
18
Troubleshooting
28
China RoHS Compliance Information (EFUP Table)
28
©2014 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide
Power Monitoring
E50H2, E50H5
TM
Dimensions
1.8”
(45mm)
1.9”
(48mm)
2.3”
(59mm)
1.5”
(39mm)
3.6”
(91mm)
4.2”
(107mm)
Bottom View (DIN Mount Option)
Bottom View (Screw Mount Option)
2.4 “
(61 mm)
4.2 “
(107 mm)
+
3.6 “
(91 mm)
0.2 “
(4 mm)
1.2 “
(31 mm)
+
3.9“
(99 mm)
4.3 “
(109 mm)
+
Data Outputs
0.3 “
(8 mm)
0.4 “
(10 mm)
Full Data Set (FDS):
Power (kW)
Energy (kWh)
Configurable for CT & PT ratios, system type, and passwords
Diagnostic alerts
Current: 3-phase average
Volts: 3-phase average
Current: by phase
Volts: by phase Line-Line and Line-Neutral
Power: Real, Reactive, and Apparent 3-phase total and per phase
Power Factor: 3-phase average and per phase
Frequency
Power Demand: Most Recent and Peak
Demand Configuration: Fixed, Rolling Block, and External Sync
Real Time Clock: uses BACnet Time Synchronization services
Data Logging (E50H5 only; includes all FDS outputs, plus):
3 BACnet Log_Events: each buffer holds 5760 time-stamped 32-bit entries
(User configures which 3 data points are stored in these buffers)
User configurable logging interval
(When configured for a 15 minute interval, each buffer holds 60 days of data)
Continuous and Single Shot logging modes: user selectable
ZL0071-0E
Page 4 of 28
©2014 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide
Power Monitoring
E50H2, E50H5
TM
(X2) A (X1) (X2) B (X1) (X2) C (X1)
CT Inputs
+ - S
+


Alarm
UL: 90V L-N - 600V L-L
N
1
2
Control
Power
Earth
C
CONTROL POWER
0.1A 50/60 Hz
CE: 90V L-N - 300V L-N
Neutral
B
–
Energy
VC
A
VB
VOLTAGE INPUTS
CAT III 50/60 Hz
VA
The red Alarm LED lights
when any of the 3 phase
voltages drop below the
selected threshold.
The green Energy LED is not
used on the E5xH2A.
RS-485
1 or 0.333 VAC
Two 5-character rows
of display text.
Top row alphanumeric;
Bottom row numeric only
Shield
BACnet
X2 X1 X2 X1 X2 X1
Pulse Input
IC
IB
IA
Phase Loss
Alarm Output
E50H2
Product Diagrams
(X2) A (X1) (X2) B (X1) (X2) C (X1)
CT Inputs
Two 5-character rows
of display text.
Top row alphanumeric;
Bottom row numeric only
1 or 0.333 VAC
Display Screen
Diagram
Shield
1
+ - S
2


B
C
N
VB
VC
Neutral
CONTROL POWER
0.1A 50/60 Hz
CE: 90V L-N - 300V L-N
1
Earth
A
VA
UL: 90V L-N - 600V L-L
2
Control
Power
VOLTAGE INPUTS
CAT III 50/60 Hz
–
Energy
Buttons:
Screen Name or Units
Logo
Numeric Data
Page 5 of 28
RS-485
LCD Screen:
Diagnostic Alert:
indicates that one or
more of the alarm
bits (Binary_Objects
1-15) are active.
ZL0071-0E
Pulse Inputs
+
Alarm
The red Alarm LED lights
when any of the 3 phase
voltages drop below the
selected threshold.
The green Energy LED lights
when the pulse 1 input
contacts are active or closed.
BACnet
X2 X1 X2 X1 X2 X1
Pulse Input 2
Pulse Input 1
IC
IB
IA
E50H5
+
Alive Indicator


♥
Tx
Rx
ERR
RS-485 Equipped Units Only:
Transmit Data
Receive Data
Receive Data Error
(Up)
Select
(Left)
Back
(Right)
Next
–
(Down)
Select
©2014 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide
Power Monitoring
E50H2, E50H5
TM
Disconnect power prior to installation.
Installation
Reinstall any covers that are displaced during the installation before powering the unit.
Mount the meter in an appropriate electrical enclosure near equipment to be monitored.
Do not install on the load side of a Variable Frequency Drive (VFD), aka Variable Speed Drive (VSD)
or Adjustable Frequency Drive (AFD).
The meter can be mounted in two ways: on standard 35 mm DIN rail or screw-mounted to the interior surface of the enclosure.
A. DIN Rail Mounting
1. Attach the mounting clips to the underside of the housing by sliding them into the slots from the inside. The stopping pegs
must face the housing, and the outside edge of the clip must be flush with the outside edge of the housing.
2. Snap the clips onto the DIN rail. See the diagram of the underside of the housing (below).
Clip flush with
outside edge
Insert clips from inside
Snap onto
DIN rail
3. To reduce horizontal shifting across the DIN rail, use two Veris AV02 end stop clips.
B. Screw Mounting
1. Attach the mounting clips to the underside of the housing by sliding them into the slots from the outside. The stopping pegs
must face the housing, and the screw hole must be exposed on the outside of the housing.
2. Use three #8 screws (not supplied) to mount the meter to the inside of the enclosure. See the diagram of the underside of the
housing (below).
Insert clips from outside
Screw holes
exposed for
mounting
ZL0071-0E
Page 6 of 28
©2014 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide
Power Monitoring
E50H2, E50H5
TM
Supported System
Types
The E50HxA power meters have a number of different possible system wiring configurations (see Wiring section). To configure the
meter, set the System Type via the User Interface or by writing the Present_Value of AV2 with the System Type value in the table
below. The System Type tells the meter which of its current and voltage inputs are valid, which are to be ignored, and if neutral
is connected. Setting the correct System Type prevents unwanted energy accumulation on unused inputs, selects the formula
to calculate the Theoretical Maximum System Power, and determines which phase loss algorithm is to be used. The phase loss
algorithm is configured as a percent of the Line-to-Line System Voltage (except when in System Type 10) and also calculates the
expected Line to Neutral voltages for system types that have Neutral (12 & 40).
Values that are not valid in a particular System Type display as “----” on the User Interface or as QNAN in the BACnet objects.
CTs
Number
of wires
Qty
Voltage Connections
System Type
ID
Qty
ID
Type
BACnet object User Interface:
AV2
SETUP>S SYS
Phase Loss Measurements
VLL
VLN
Balance
Wiring
Diagram
Diagram
number
Single-Phase Wiring
2
1
A
2
A, N
L-N
10
1L + 1n
AN
2
1
A
2
A, B
L-L
11
2L
AB
3
2
A, B
3
A, B, N
L-L with N 12
2L + 1n
AB
Delta
31
3L
AB, BC, CA
40
3L + 1n
AB, BC, CA
1
2
AN, BN
AN-BN
3
AB-BC-CA
4
AN-BN-CN &
AB-BC-CA
5, 6
Three-Phase Wiring
3
3
A, B, C
3
A, B, C
4
3
A, B, C
4
A, B, C, N Grounded
Wye
Wiring Symbols
AN, BN, CN
To avoid distortion, use parallel wires for control power and voltage inputs.
The following symbols are used in the wiring diagrams on the following pages.
Symbol
Description
Voltage Disconnect Switch
Fuse (installer is responsible for ensuring compliance with local requirements. No
fuses are included with the meter.)
Earth ground
X1
Current Transducer
X2
Potential Transformer
Protection containing a voltage disconnect switch with a fuse or disconnect circuit
breaker. The protection device must be rated for the available short-circuit current at
the connection point.
CAUTION
RISK OF EQUIPMENT DAMAGE
• This product is designed only for use with 1V or 0.33V current
transducers (CTs).
• DO NOT USE CURRENT OUTPUT (e.g. 5A) CTs ON THIS PRODUCT.
• Failure to follow these instructions can result in overheating and
permanent equipment damage.
ZL0071-0E
Page 7 of 28
©2014 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide
Power Monitoring
E50H2, E50H5
TM
Wiring
WARNING
RISK OF ELECTRIC SHOCK OR PERMANENT EQUIPMENT DAMAGE
CT negative terminals are referenced to the meter’s neutral and may be at elevated voltages
· Do not contact meter terminals while the unit is connected
· Do not connect or short other circuits to the CT terminals
Failure to follow these instructions may cause injury, death or equipment damage.
Diagram 1: 1-Phase Line-to-Neutral 2- Wire
System 1 CT
Use System Type 10 (1L + 1n)
N L1
Diagram 2: 1-Phase Line-to-Line 2-Wire
System 1 CT
Use System Type 11 (2L)
L1 L2
A
B
C
N
X1
White
Black
X2
A
B
C
N
X1
X1
A
X2
X1
X2 B
X1
X2 C
L1
Use System Type 12 (2L + 1n)
L2
X1
X2 A
X1
X2 B
X1
X2 C
X2
Diagram 3: 1-Phase Direct Voltage Connection 2 CT
N
White
Black
Diagram 4: 3-Phase 3-Wire 3 CT no PT
Use System Type 31 (3L)
L1 L2 L3
A
B
C
N
X1
X2
White
Black
X1
A
B
C
N
White
Black
X2
White
Black
X1
X1
X2 A
X1
X2 B
X1
X2 C
X2
X1
X2
X1
White
Black
X1
X2 A
X1
X2 B
X1
X2 C
White
Black
X2
Diagram 5: 3-Phase 4-Wire Wye Direct Voltage Input
Connection 3 CT
Use System Type 40 (3L + 1n)
N
L1 L2 L3
Diagram 6: 3-Phase 4-Wire Wye Connection 3 CT
3 PT
Use System Type 40 (3L + 1n)
N
L1 L2 L3
A
B
C
N
White
Black
X1
X2
X1
X2
X1
X2
ZL0071-0E
Page 8 of 28
White
Black
White
Black
X1
X2 A
X1
X2 B
X1
X2 C
A
B
C
N
X1
X2
White
Black
X1
X2
X1
White
Black
White
Black
X2
X1
A
X2
X1
B
X2
X1
C
X2
©2014 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide
Power Monitoring
E50H2, E50H5
Control Power
TM
Direct Connect Control Power (Line to Line)
L1 L2 L3
Direct Connect Control Power (Line to Neutral)
G 1 2
N L1 L2 L3
Line to Line from 90 VAC to 600 VAC (UL). In UL installations the
lines may be floating (such as a delta). If any lines are tied to an
earth (such as a corner grounded delta), see the Line to Neutral
installation limits. In CE compliant installations, the lines must
be neutral (earth) referenced at less than 300 VACL-N
Line to Neutral from 90 VAC to 347 VAC (UL) or 300 VAC (CE)
Direct Connect Control Power (DC Control Power)
G 1 2
G 1 2
Control Power Transformer (CPT) Connection
G 1 2
N L1 L2 L3
DC Control Power from 125 VDC to 300 VDC
(UL and CE max.)
The Control Power Transformer may be wired L-N or L-L. Output to
meet meter input requirements
Fuse Recommendations
Keep the fuses close to the power source (obey local and national code requirements).
For selecting fuses and circuit breakers, use the following criteria:
•
•
•
•
S elect current interrupt capacity based on the installation category and fault current capability.
Select over-current protection with a time delay.
Select a voltage rating sufficient for the input voltage applied.
Provide overcurrent protection and disconnecting means to protect the wiring. For AC installations, use Veris AH02,
AH03, AH04, or equivalent. For DC installations, provide external circuit protection. Suggested: 0.5 A, time delay fuses.
• The earth connection (G) is required for electromagnetic compatibility (EMC) and is not a protective earth ground.
ZL0071-0E
Page 9 of 28
©2014 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide
Power Monitoring
E50H2, E50H5
Quick Setup
Instructions
TM
Use this section to enter:
- BACnet communication parameters
- CT (Current Transducer) output voltage and input current ranges
- The service type to be monitored
These instructions assume the meter is set to factory defaults. If it has been previously configured, check all optional values.
A. To Navigate to the Setup screens:
1. Press
++
or – repeatedly until SETUP screen appears.
2. Press
to get to the PASWD screen.
3. Press
to move through the digits. Use the
4. Press
to move to the first Setup screen (S BAC)
5. Use
+
+
++
or – buttons to enter your password (the default is 00000).
or – to select the parameter screen you want to set.
++
6. After you set the parameters you want, use
SETUP).
or – to select the next Setup screen or
to exit the Setup screens (return to
B. To Enter BACnet communication parameters
1. Navigate to the S BAC (set BACnet) Setup screen (see section A above).
2. Press to go to the MAC screen and through the address digits. Use
001).
3. Press
to accept the value and go to the KBAUD screen. Use
++
++
or – to select the BACnet MAC address (default is
or – to select the baud rate (default is 76.8K).
+
4. Press to go to the ID1 screen and through the upper four digits of the Device Instance. Use + or – to select the ID digits.
The setup screen splits the Device ID into two parts, the most significant four digits (ID1) and the least significant three digits
(ID2). The E50Hx supports BACnet Device ID values from 1 to 4,193,999. Units are shipped with a factory default setting that is
pseudo-randomly generated in the range from 1,000,000 to 3,097,151.
5. Press to accept the value and go to the ID2 screen and through the lower three digits of the Device Instance. Use
select the ID digits.
6. Press
++
or – to
to accept the value and go back to the S BAC screen.
C. To Enter the CT (Current Transducer) output voltage and input current ranges:
1. Navigate to the S CT (Set Current Transducer) Setup screen (see section A above).
2. Press to go to the CT V screen. Use
1.00).
++
or – to select the voltage mode Current Transducer output voltage (default is
3. Press to go to the CT SZ screen and through the digits. Use
the value and
4. Press
++
or – to select the CT size in amps (default is 100). accept
to accept the value and go back to the S CT screen.
D. To Enter the service type to be monitored:
1. Navigate to the S SYS (Set System) Setup screen (see section A above).
++
2. Press
to go to the SYSTM screen. Use
3. Press
to go back to the S SYS screen.
or – to select the configuration (see wiring diagrams - default is 3LN-1N).
For full setup instructions, see the configuration instructions on the following pages.
ZL0071-0E
Page 10 of 28
©2014 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide
Power Monitoring
E50H2, E50H5
Pulse Contact Input
TM
The E50H5 has two inputs with pulse accumulators for solid state or mechanical contacts in other sensors, such as water or gas
flow meters. These inputs are isolated from the measured circuits and referenced to the communication signal ground. Use with
contacts that do not require current to remove oxidation.
Pulse Input
Contacts
Comm
Output
~10 kΩ
4-10 VDC
nominal
+
S
Equivalent
Circuit
Comm
Ground
The E50H2 has one input with pulse accumulator as described above, and one phase loss alarm output terminal.
Phase Loss
Alarm Output
Pulse Input
Comm
Output
~10 kΩ
4-10 VDC
nominal
User Interface (UI)
Menu Abbreviations
Defined
ZL0071-0E
Page 11 of 28
+
S
Comm
Ground
Equivalent
Circuit
The user can set the display mode to either IEC or IEEE notation in the SETUP menu.
Main Menu
IEC
IEEE
Main Menu
Description
IEC
IEEE
Description
D
D
Demand
F ERR
F ERR
Frequency Error
MAX
M
Maximum Demand
I OVR
I OVR
Over Current
P
W
Present Real Power
V OVR
V OVR
Over Voltage
Q
VAR
Present Reactive Power
PULSE
PULSE
S
VA
Present Apparent Power
kWh Pulse Output Overrun
(configuration error)
A
A
Amps
_PHASE
_PHASE
Summary Data for 1, 2, or 3
active phases
UAB, UBC, UAC
VAB, VBC, VAC
Voltage Line to Line
ALERT
ALERT
Diagnostic Alert Status
V
VLN
Voltage Line to Neutral
INFO
INFO
Unit Information
PF
PF
Power Factor
MODEL
MODEL
Model Number
U
VLL
Voltage Line to Line
OS
OS
Operating System
HZ
HZ
Frequency
RS
RS
Reset System
KSh
KVAh
Accumulated Apparent
Energy
SN
SN
Serial Number
KQh
KVARh
Accumulated Reactive
Energy
RESET
RESET
Reset Data
PASWD
PASWD
KPh
KWh
Accumulated Real Energy
Enter Reset or Setup
Password
PLOSS
PLOSS
Phase Loss
ENERG
ENERG
Reset Energy Accumulators
LOWPF
LOWPF
Low Power Factor Error
DEMND
DEMND
Reset Demand Maximums
©2014 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
ZL0071-0E
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Page 12 of 28
A
3
APHAS
Phase A:
All Systems
1, 2, or 3 Phase
_PHAS
Summary Data
To:
ALERT
A
A
A
3 VLN
A VLN
B VLN
C VLN
Accumulated
Reactive Energy
(Qh)
KVARh
Accumulated
Apparent Energy
(Sh)
KVAh
Volts Line-Line (U) Volts Line-Neutral (V)
(Average of Active
(Average of Active
Phases)
Phases)
3 VLL
A VAB
B VBC
C VAC
Present
Apparent Power
Demand (S)
D KVA
KW
KW
KW
KW
KW
Total Reactive
Power (Q)
3KVAR
AKVAR
BKVAR
CKVAR
Maximum
Reactive Power
Demand (Q)
MKVAR
Total Apparent
Power (S)
3 KVA
A KVA
B KVA
C KVA
Maximum
Apparent Power
Demand (S)
M KVA
Input Pulse Counter
PULS1
ENRGY
Pulse Counter 2
(not used on E50H2)
PULS2
>>> Scroll When Idle >>>
Total Real
Power (P)
3
A
B
C
Maximum
Real Power
Demand (P)
M
The units for all Power and Energy screens change to preserve resolution
as the accumulated totals increase. For example, energy starts out as
Wh, then switches to kWh, MWh, and eventually GWh as the accumulated value increases.
Accumulated
Real Energy
(Ph)
KWh
Amps (A)
(Average of
Active Phases)
B
Phase B:
2 & 3 Phase BPHAS
Systems Only
A
Present
Reactive Power
Demand (Q)
DKVAR
PF
PF
PF
PF
Power Factor
(Average of
Active Phases)
3
A
B
C
DEMND
Accumulated
Real Energy
3 KWh
A KWh
B KWh
C KWh
HZ
Frequency
APHAS
BPHAS
CPHAS
_PHAS
User Interface for
Data Configuration
Energy
Accumulators ENRGY
and Counters
KW
Present
Real Power
Demand (P)
D
C
DEMND
Phase C:
CPHAS
3 Phase
Systems Only
Demand
To:
SETUP
Installation Guide
Power Monitoring
E50H2, E50H5
TM
©2014 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]
Installation Guide
Power Monitoring
E50H2, E50H5
TM
Alert/Reset
Information
To: ENRGY
Alert Status
(check if
Wrench on
LCD)
PLOSS
-------AbC
LOWPF
-------AbC
Phase Loss
ABC
Low Power Factor
ABC
ALERT
F ERR
-------A
Frequency Out
of Range
A
I OVR
-------AbC
V OVR
-------AbC
PULSE
-------n0nE
Current
Out of Range
ABC
Voltage
Out of Range
ABC
Not used on
E5xHx
Display “nOnE” if no alerts
Unit
Information
INFO
MODEL
OS
Model
Number
Operating
System
RS
Reset
System
SN
Serial
Number
Back
Reset
Data
Setup
Meter
RESET
SETUP
PASWD
-------00000
ENERG
-------rES
Enter Reset
Password
Reset Energy
Accumulators to 0
PASWD
-------00000
DEMND
-------rES
Reset Demand
Maximums to Present
ALERT
COUNT
-------rES
Reset Pulse
Counters to 0
INFO
PASWD – Enter the Reset Password
(configured in the setup menu).
ENERG – Reset all Energy
Accumulators (Wh, VARh, VAh) to 0.
Press “+” or “-“ to Reset.
DEMND – Reset all Maximum
RESET Demand (W, VAR, VA) to the present
Demand. Hit “+” or “-“ to Reset.
COUNT – Reset the pulse counters.
Press “+” or “-“ to Reset.
To Setup
Enter Setup
Password
To: DEMND
ZL0071-0E
Page 13 of 28
©2014 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide
Power Monitoring
E50H2, E50H5
TM
UI for Setup
To: SPASS
S BAC
Back
KBAUD
-------115.2
76.8
38.4
19.2
9.6
MAC
-------001
ID1
-------0000
From:
SETUP > PASWD
Next
Back
S CT
Current
Transformer
Back
ID2
-------000
S SYS
System
Type
CT V
-------1.0
.33
CT SZ
-------100
Back To SETUP
S PT
Potential
Transformer
S
Back
Set System Configuration:
SYSTM: + or – to step through the following System Type options:
System Reg 130 CTs Description
3L-1n
40
3
Wye Three Phase: A, B, & C with Neutral (Default).
3L
31
3
Delta Three Phase: A, B & C; no Neutral
2L-1n
12
2
Single Split Phase: A & B with Neutral
2L
11
1
Single Phase: A & B; no Neutral
1L-1n
10
1
Single Phase: A to Neutral
SYSTM
-------3L-1n
3L
2L-1n
2L
1L+1n
Set Potential Transfomer Ratio:
RATIO – Potential transformer step down is RATIO:1. Default is 1:1
(No PT installed). See Install for wiring diagrams. This value must be
set before the System Voltage (if used).
RATIO
-------001.00
Next
V
Sytem
Voltage
Back
Set Current Transducer:
CT V - CT Input Voltage: + or – to Select 1.0 or .33V.
CT SZ - CT Size: in Amps. Maximum is 32000 Amps.
Next
Next
Back
Set Communications Parameters:
ADDR – BACnet MS/TP MAC Address: 0 – 127.
+ increments the selected (blinking) digit.
– selects the digit to the left.
BAUD - Baud Rate: 9600 – 115200 Baud
BACnet ID: These two screens set the 7 digit
BACnet device ID. Screen ID1 is the most
significant 4 digits and ID2 the least significant
three digits. This is in the range of 0 - 4,194,302.
S PWR
Sytem
Voltage
Set System Voltage:
V LL – The nominal Line to Line Voltage for the system. This is used
by the meter to calculate the theoretical maximum system power, and
as the reference voltage for setting the Phase Loss threshold.
Maximum is 32000 Volts. For system type 1+N (10), this is a Line to
Neutral Voltage, indicated by “V LN”. Note: the meter will reject settings
that are not within the meter’s operating range when divided by the PT
ratio.
V LL
-------00600
Next
System Power:
MX KW – The theoretical Maximum System Power is calculated by the
meter from the System Voltage, CT size, and System Type. Power
Factor is assumed to be unity. The value of System Power is used to
determine which combinations of pulse weight and duration are valid
and will keep up with the maximum power the meter will see. This value
is read only.
MX KW
-------103.92
Next
To Setup p. 2 “SPLOS”
Note: Bold is the Default.
ZL0071-0E
Page 14 of 28
©2014 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide
Power Monitoring
E50H2, E50H5
TM
UI for Setup (cont.)
To Setup p. 1 “S PWR”
SPLOS
Back
Phase
Loss
Back
SDMND
S DIS
Display
Units
Back
IMBAL
-------0.25
Next
Demand
Back
VOLTS
-------0.10
INTRV
-------6
5
4
3
2
1
SEC
-------00900
Set Phase Loss:
VOLTS - Phase Loss Voltage: The fraction of the system
voltage below which Phase Loss Alarm is on. For system
types with neutral, the Line to Neutral voltage is also
calculated and tested. If the System Voltage is 600 and the
fraction is set to 0.10, then the Phase Loss threshold will be
60 volts.
IMBAL - Phase Loss Imbalance: The fractional difference
in Line to Line voltages above which Phase Loss Alarm is
on. For system types with neutral, the Line to Neutral
voltages are also tested. For system types 1+N (10) and 2
(11) , imbalance is not tested.
Set Demand Interval:
INTRV - The number of Sub-Intervals (1 to 6) in a
Demand Interval. Default is 1 (block demand).
SEC - Sub-Interval length in seconds. Default is
900 (15 minutes). Set to 0 for external sync-tocomms.
Next
UNITS
-------IEEE
IEC
Set Display Units: +/- to switch between:
IEEE – VLL VLN W VAR VA Units.
IEC - U V P Q S Units.
Next
SPASS
Setup
Passwords
SETUP
-------00000
RESET
-------00000
Set Passwords:
SETUP - The Password to enter the SETUP menu.
RESET - The Password to enter the RESET menu.
Next
To Setup page 1 “S BAC”
ZL0071-0E
Page 15 of 28
©2014 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide
Power Monitoring
E50H2, E50H5
RS-485
Communications
TM
Daisy-chaining Devices to the Power Meter
The RS-485 slave port allows the power meter to be connected in a daisy chain with up to 63 2-wire devices.
120 Ω terminator on the first and last
device of the daisy chain
+
–
S
Shield wire
Notes
• The terminal’s voltage and current ratings are compliant with the requirements of the EIA RS-485 communications
standard.
• The RS-485 transceivers are ¼ unit load or less.
• RS-485+ has a 47 kΩ pull up to +5V, and RS-485- has a 47 kΩ pull down to Shield (RS-485 signal ground).
• Wire the RS-485 bus as a daisy chain from device to device, without any stubs. Use 120 Ω termination resistors at each
end of the bus (not included).
• Shield is not internally connected to Earth Ground.
• Connect Shield to Earth Ground somewhere on the RS-485 bus.
For all terminals:
• When tightening terminals, apply the correct torque: 0.37 to 0.44
ft·lb (0.5-0.6 N·m).
• Use 14-24 gauge (2.1-0.2 mm2) wire.
ZL0071-0E
Page 16 of 28
0.37–0.44 ft•lb
(0.5–0.6 N•m)
©2014 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Use 14-24 gau
Installation Guide
Power Monitoring
E50H2, E50H5
BACnet Default
Settings
TM
Setting
Default Value*
BACnet Object
Setup Password
00000
n/a
Reset Password
00000
n/a
System Type
40 (3 + N) Wye
AV2
CT Primary Ratio
100A
AV3
CT Secondary Ratio
1V
AV4
PT Ratio
1:1 (none)
AV5
System Voltage
600 V L-L
AV6
Max. Theoretical Power
Calculated from AV2, AV3, AV5 & AV6 (with all default settings, this would be
103.92 kW)
AI45
Display Mode
1 (IEEE Units)
AV7
Phase Loss Voltage Threshold 10% of System Voltage
AV8
Phase Loss Voltage Threshold 25% Phase to Phase Imbalance
AV9
Demand: number of
subintervals per interval
1 (block mode)
AV10
Demand: sub-interval length 900 sec (15 min)
(AV11 default value is 90000 [1/100 seconds])
AV11
BACnet MAC Address
001
n/a
BACnet MS/TP Baud Rate
76.8 kBaud
n/a
BACnet MS/TP Max_Master
127
Device
BACnet Device_ID
Pseudo-random value
from 1,000,000 to 3,097,151
Device
BACnet Device Location
Installed location not yet identified
Device
Trend_Log Object 1
Log_Device_Object_
Property **
AI1 (Real Energy)
TL1
Trend_Log Object 2
Log_Device_Object_
Property **
AI27 (Reactive Energy)
TL2
Trend_Log Object 3
Log_Device_Object_
Property **
AI34 (Total Real Present Demand)
TL3
* Default values are preset at the factory. Once changed, there is no way to automatically reset defaults. They must be restored individually. The baud rate and
MAC address are set through the user-interface screens, and the others are set by re-writing each Object (see BACnet Programming Information section, next
page).
** These values are available only on the E50H5. The E50H2 does not support the data logging functions.
ZL0071-0E
Page 17 of 28
©2014 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide
Power Monitoring
E50H2, E50H5
BACnet
Programming
Information
TM
The E50Hx is programmable via BACnet protocol and can easily be connected to a BACnet MS/TP network using an off-the shelf
BACnet router. It uses five types of BACnet objects. A standard PICS (below) describes the required characteristics of the BACnet
implementation, but this additional descriptive context may be helpful to the integrator.
In addition to the required properties, the device object utilizes some optional properties to support other functionality, Time
Synchronization (primarily used for data/trend logging on the device) and Description and Location properties to simplify
installation and maintenance. Configure all of the meter’s functions, other than Data Logging and writable Device Properties, by
writing the Present_Value of the 11 Analog_Value objects. These values (except for the configuration register, AV1, which always
returns zero when read) are all readable and stored in nonvolatile memory so that they are retained if power to the device is
interrupted.
Data values other than log information and alerts are all accessed by reading the Present_Value of the 52 Analog_Input objects.
Most of these values are instantaneous readings of measured service parameters. Some of them, (AI1, AI26, AI27, AI37-AI45, AI47,
AI50 and AI51) represent accumulated values and are stored in nonvolatile memory as well. If power to the device is interrupted,
these values are retained, but no additional information accumulates until the device completes its re-initialization.
Alerts are used to indicate conditions of potential concern to the installer or the system, such as input voltage or current on any
phase that exceeds the meter’s measurement range, phase voltage below the Phase Loss Threshold set by the user, or Power
Factor below 0.5 on any phase. Alerts are accessible individually by reading the Present_Value of the Binary_Input objects or as a
group by reading the Present_Value of Analog_Input object 52. Alerts are not latched and do not generate events to system. They
indicate presence of these conditions at the time they are read, but the device does not latch and store them until they are read (if
the condition changes before they are read, the alert will go away).
All Analog_Value, Analog_Input, and Binary_Input objects implement the reliability property and use it to indicate that the
Present_Value properties are functional, valid and current. For complete assurance, check the Reliabilty property for a No_Fault_
Detected status before reading the Present_Value of any AV, AI or BI objects.
The E50H5 includes data logging capability, which is implemented using three Trend_Log objects. These are described in more
detail in the section on data logging.
BACnet Protocol Implementation Conformance Statement (PICS)
Date:
January 1, 2013
Vendor Name:
Veris Industries, LLC
Product Name:
E50Hx Energy Meter
Product Model Number:
E50Hx
Applications Software Version:
1
Firmware Revision:
x.xxx
BACnet Protocol Revision:
4
Product Description:
3-phase electrical energy meter
BACnet Standardized Device Profile (Annex L): BACnet Application Specific Controller (B-ASC)
List all BACnet Interoperability Building Blocks Supported (Annex K): DS-RP-B, DS-RPM-B, DS-WP-B, DM-DDB-B, DM-DOB-B,
DM-DCC-B, T-VMT-I-B (E50H5 only),
DM-TS-B, DM-RD-B
Segmentation Capability: Segmentation not supported
ZL0071-0E
Page 18 of 28
©2014 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide
Power Monitoring
E50H2, E50H5
BACnet
Programming
Information
(cont.)
TM
Standard Object Types Supported: No dynamic Creation or Deletion supported; no proprietary properties or object types
1. Device Object:
Optional Properties Supported: Max_Master, Max_Info_Frames, Description, Location, Local_Time, Local_Date
Writable Properties: Object_Identifier, Object_Name, Max_Master, Location
Property Range Restrictions: Object_Identifier – May only write values from 1 to 4,193,999; Location – (limited to 64
characters); Max_Master – May only write values from 1 to 127
2. Analog_Input Objects:
Optional Properties Supported: Description, Reliability
No Writable Properties.
3. Analog_Value Objects:
Optional Properties Supported: Description, Reliability
Writable Properties: Only the Present_Value is writable.
Property Range Restrictions:
AV1: May only write 30078, 21211, 21212 and 16498.
AV2: May only write 10, 11, 12, 31 and 40.
AV3: May only write values from 5 to 32000.
AV4: May only write values 1 and 3.
AV5: May only write values from 0.01 to 320.0
AV6: May only write values such that AV6/AV5 is from 82 to 660 (absolute range is 82-32000). To ensure AV6 accepts/rejects
the proper values, set AV5 first.
AV7: May only write values 0 and 1.
AV8: May only write values from 1 to 99.
AV9: May only write values from 1 to 99.
AV10: May only write values from 1 to 6.
AV11: May only write the value 0 or a value from 1000 to 3276700 in multiples of 100.
The Record_Count of the Trend_Logs (TL1 to TL3) is reset when this object is written (E50H5 only).
4. Binary_Input Objects:
Optional Properties Supported: Description, Reliability
No Writable Properties
5. Trend_Log Objects (E50H5 only):
Optional Properties Supported: Description,
Writable Properties: Log_Enable, Start_Time, Stop_Time, Log_DeviceObjectProperty, Log_Interval, Stop_When_Full,
Record_Count
Property Range Restrictions:
Log_DeviceObjectProperty: May only be set to the Present_Value of local objects AI1 through AI75 (only the Present_
Value of objects AI1 through AI75 may be logged).
Log_Interval: May only write the value 0 or values from 1000 to 3276700 in multiples of 100.
Data Link Layer Options: MS/TP master (Clause 9), baud rate(s): 9600, 19200, 38400, 76800, 115200
Device Address Binding: Static device binding is not supported. (No client functionality is included).
Networking Options: None
Character Sets Supported: ANSI X3.4
ZL0071-0E
Page 19 of 28
©2014 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide
Power Monitoring
E50H2, E50H5
TM
Legend
BACnet
Programming
Information
(cont.)
R/W R=read only; R/W=read or write
NV
Value is stored in non-volatile memory. The value are still available if the meter experiences a power loss and reset.
Units
Lists the physical units that a register holds.
Device Object
Property
R/W
NV
Value Returned
Additional information
Object_Identifier
R/W
NV
Device<n>
Object_Type
R
NV
Device (8)
Object_Name
R
NV
Veris E50 Series Energy Meter - S/N: <serial
number>
Vendor_Name
R
NV
Veris Industries, LLC
Vendor_Identifier
R
NV
133
Model_Name
R
NV
E50Hx Energy Meter
Firmware_Revision
R
NV
<Current Revision #>
“xyyy”.
This is the BACnet processor firmware version in the format <xyyy>, with an implied
decimal point between the first two digits (x.yyy)
Application_Software_ Version
R
NV
<Current version #>
“RS= xyyy, OS=xyyy, BACnet Gateway=xyyy”
The format <xyyy> has an implied decimal point between the first two digits (x.yyy)
Location
R/W
NV
<Location>
Limted to 64 Characters - Default value is “Installed location not yet identified”
Description
R
NV
Veris E50Hx DIN-Rail Energy Meter S/N:
<serial number>
Protocol_Version
R
NV
1
BACnet Protocol Version 1
Protocol_Revsion
R
NV
4
BACnet Protocol Revision 4
Local_Date
R
Date
Set via BACnet Time Synchronization only - reverts to Jan 1, 2000 if control power drops
Local_Time
R
Time
Set via BACnet Time Synchronization only - reverts to 12:00:00 AM if control power
drops
Segmentation_Supported
R
NV
NO_SEGMENTATION (3)
Segmentation is not supported
Max_Master
R/W
NV
1-127 (Factory Default is 127)
Highest possible MAC Address for Master nodes on the local MS/TP network
Max_Info_Frames
R
NV
1
Maximum number of information frames allowed before passing the MS/TP token
Max_APDU_Length_Accepted
R
NV
480
APDU_Timeout
R
NV
60000
Number_of_APDU_Retries
R
NV
0
System_Status
R
NV
Operational (0)
Protocol_Sevices_Supported
R
NV
0b0000000000001011010000000000000
011110000
Protocol_Object_Types_Supported
R
NV
0b1011000010000000000010000000000
ZL0071-0E
Page 20 of 28
n is the 7 digit ID # set in the ID1 & ID2 setup screens on the meter. The BACnet Device
ID is a decimal number from 1 to 4,193,999 that can be entered or viewed on the user
screens or through this property. The default value set at the factory is a psuedorandom number from 1,000,000 to 3,097,151 to reduce the likelihood of conflicts if
multiple units are installed using their default IDs.
©2014 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide
Power Monitoring
E50H2, E50H5
TM
BACnet Programming Information (cont.)
Property
R/W
NV
Value Returned
Additional information
Object_List
R
NV
DE1,AI1,AI2,AI3,AI4,AI5,AI6,AI7,AI8,AI9,AI1 BI15, TL1, TL2, and TL3 are present in the E50H5 only.
0,AI11,AI12,AI13,AI14,AI15,AI16,AI17,AI1
8,AI19,AI20,AI21,AI22,AI23,AI24,AI25,AI2
6,AI27,AI28,AI29,AI30,AI31,AI32,AI33,AI3
4,AI35,AI36,AI37,AI38,AI39,AI40,AI41,AI4
2,AI43,AI44,AI45,AI46,AI47,AI48,AI49,AI5
0,AI51,AI52,AV1,AV2,AV3,AV4,AV5,AV6,AV
7,AV8,AV9,AV10,AV11,BI1,BI2,BI3,BI4,BI5,
BI6,BI7,BI8,BI9,BI10,BI11,BI12,BI13,BI14,B
I15,TL1,TL2,TL3
Device_Address_Binding
R
NV
{}
Database_Revsion
R
NV
0
Analog_Value Objects
Use the Present_Value property of the Analog_Value object for all writable variables in the meter other than those used specifically for BACnet configuration, Time
Synchronization (in the Device Object), or Data Logging (in the Trend_Log objects).
Values are checked when written, and errors are returned for invalid entries. This table describes how the meter uses those variables, what values are valid, and what their
defaults are. When writing values to the Present_Value properties of Analog_Value BACnet objects, there is a delay of up to about two seconds to validate and store the new
value. An immediate read of the same property before that delay has elapsed can return the prior value (even if the new value was accepted). To read a value immediately after
writing it, check the Reliability property first. When it reports a No_Fault_Detected status, the Present_Value of the object is current.
These objects support the Description and Reliability object properties and all required Analog_Value object properties, but Present_Value is the only writable property.
#
Name
Description
R/W
AV1
Config
AV2
System_Type System Type
R/W
AV3
CT_Ratio_
Primary
CT Ratio Primary
AV4
CT_Ratio_
Secondary
AV5
PT_Ratio
ZL0071-0E
NV
Configuration R/W
Units
Range
Factory
Default
Value
Additional information
n/a
n/a
Always
returns
”0” when
read
Command Register:
- Write 30078 (0x757E) to clear all energy accumulators to 0 (All).
- Write 21211 (0x52DB) to begin new Demand Sub-Interval calculation cycle and log
another data value on Trend_Log objects TL1-TL3 (when the meter is in Manual “Syncto Comms” mode). This takes effect at the end of the next 1 second calculation cycle.
Write no more frequently than every 10 seconds. Trend_Log values are only present on
the E50H5 model.
- Write 21212 (0x52DC) to reset Max Demand values to Present Demand Values. Takes
effect at the end of the next 1 second calculation cycle. Write no more frequently than
every 10 seconds.
- Write 16498 (0x4072) to clear pulse counters to 0.
NV
n/a
40, 31, 12,
11, 10
40
System_Type:
- Write 10 for Single-Phase: A + N
- Write 11 for Single-Phase: A + B
- Write 12 for Split-Phase: A + B + N
- Write 31 for 3-Phase Δ: A + B + C, no N
- Write 40 for 3-Phase Y: A + B + C + N
R/W
NV
Amps
5-32000
100
Current Transducer Size - Primary Current Range (Default is set for 100 A CTs)
CT Ratio Secondary
R/W
NV
1/Volts
1,3
1
Current Transducer Type – Secondary Interface
- Enter 1 for CTs with 1V outputs (Default)
- Enter 3 for CTs with 1/3V outputs
PT Ratio
R/W
NV
Value
0.01 - 320.0
1
Potential Transformer Ratio - The default is 1.00 (1:1), which is no PT attached. Set this
value before setting the System Voltage (below).
Page 21 of 28
©2014 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide
Power Monitoring
E50H2, E50H5
TM
BACnet Programming Information (cont.)
#
Name
Description
R/W
NV
Units
Range
Factory
Default
Value
Additional information
AV6
System_
Voltage
System
Voltage
R/W
NV
Volts
from 82 (times
the PT_Ratio
in AV5) to
660 (times
the PT_Ratio
in AV5 absolute
limits are
82-32000)
600
System Voltage – This voltage is Line to Line unless in System Type 10 (in object AV2), in
which case it is Line to Neutral. This value is used to by the meter to calculate the full
scale power for the analog outputs and pulse configuration (see below), and as full
scale for phase loss (in object AV8). Do not set the meter to voltages outside the range
of 82-660 volts times the PT Ratio in object AV5.
AV7
Display_
Units
Display Units
R/W
NV
n/a
0,1
1
Display Units: 0 = IEC (U, V, P, Q, S), 1 = IEEE (default: VLL, VLN, W, VAR, VA)
AV8
Phase_Loss_ Phase Loss
Voltage_
Voltage
Threshold
Threshold
R/W
NV
Percent
1-99
10
Phase Loss Voltage Threshold in percent of System Voltage (in object AV6). Default is
10 (10%). Any phase (as configured in AV2) whose level drops below this threshold
triggers a Phase Loss alert - i.e. if the System voltage is set to 480 V L-L, the L-N
voltage for each phase should be 277 V. When the threshold is set to 10%, if any phase
drops more than 10% below 277 V, (less than 249 V), or if any L-L voltage drops more
than 10% below 480 V (less than 432 V) the corresponding phase loss alarm bit will
be true.
AV9
Phase_Loss_ Phase Loss
Imbalance_ Imbalance
Threshold
Threshold
R/W
NV
Percent
1-99
25
Phase Loss Imbalance Threshold in Percent. Default is 25% phase to phase difference.
For a 3-phase Y (3 + N) system type (40 in object AV2), both Line to Neutral and Line
to Line voltages are tested. In a 3-phase ∆ System type (31 in object AV2), only Line to
Line voltages are examined. In a single split-phase (2 + N) system type (12 in object
AV2), only the line to neutral voltage are compared.
AV10 Subintervals
Number
R/W
Subintervals
Per Demand
Interval
NV
1-6
1
Number of Sub-Intervals per Demand Interval. Sets the number of sub-intervals that
make a single demand interval. For block demand, set this to 1. Default is 1. When
Sub-Interval Length (in object AV11) is set to 0 (sync-to-comms mode), the meter
ignores this value.
AV11 Subinterval_
Length
Subinterval
Length
NV
0,
10-32767
90000
Sub-Interval Length in hundredths of a second. For sync-to-comms mode, which allows
manual triggerring of demand intervals and the logging of another Trend_Log record,
set this value to 0 and write 21211 to the reset register (object AV1) each time the
sub-interval must be externally reset. Default is 90000 (15 minutes). This variable is
tied directly to the Log_Interval property of all three Trend_Log objects (their value
is always the same as this one). Changing any of these four properties changes all of
them.
Trend_Log values are only used on the E50H5 model.
ZL0071-0E
R/W
Page 22 of 28
hundreths
of a
second
©2014 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide
Power Monitoring
E50H2, E50H5
TM
BACnet Programming Information (cont.)
Analog_Input Objects
Use the Present_Value property of the Analog_Input objects for all read-only numeric variables in the meter other than those used specifically for device configuration (in the
Device Object) or data logging (in the Trend_Log objects). Only the E50H5 supports the data logging capability.
These objects support the Description and Reliability object properties and all required Analog_Input object properties. None of them are writable. The values that are not
instantaneous (i.e., Accumulated Energy, Max Demand, Pulse Input Counts) are non-volatile. They are not updated while control power is inactive, but their past values are
retained when power is restored. The Present_Value of the accumulated data objects (AI1, AI26-AI27 and AI42-AI44) use floating-point data types (all AI objects use floating
point data points). The resolution of the accumulated values decreases as the value grows larger over time and more of the significant digits precede the decimal point. If the
size of the value limits the resolution unacceptably, read and store the current value offline and reset the accumulators to restore finer resolution.
For complete assurance, check the Reliabilty property for a No_Fault_Detected status before reading the Present_Value. If the line voltage or input frequency of the system
being monitored falls out of the supported range, the corresponding alert bits (BI1-BI7) are set and the reliability property of any values that cannot be accurately measured
under those conditions returns Unreliable_Other.
#
Object_Name
Description
R/W
NV
NV
AI1
Energy
Real Energy
Consumption
R
AI2
kW_Total
Total Real Power
AI3
kVAR_Total
Total Reactive Power
AI4
kVA_Total
AI5
Units
Range
Additional information
kWh
0 - 3.4+E38
R
kW
0 - Max_Power (AI45)
R
kVAR
0 - Max_Power (AI45)
Total Apparent Power R
kVA
0 - Max_Power (AI45)
PF_Total
Total Power Factor
R
Power
Factor
0.00 - 1.00
AI6
Volts_LL_Avg
Voltage L-L Average
R
Volts
AI7
Volts_LN_Avg
Voltage L-N Average
R
Volts
AI8
Current_Avg
Current Average
R
Amps
AI9
kW_A
Real Power Phase A
R
kW
0 - Max_Power (AI45)
AI10
kW_B
Real Power Phase B
R
kW
0 - Max_Power (AI45)
AI11
kW_C
Real Power Phase C
R
kW
0 - Max_Power (AI45)
AI12
PF_A
Power Factor Phase A R
Power
Factor
0.00 - 1.00
1.00 for 100%
AI13
PF_B
Power Factor Phase B
R
Power
Factor
0.00 - 1.00
1.00 for 100%
AI14
PF_C
Power Factor Phase C
R
Power
Factor
0.00 - 1.00
1.00 for 100%
AI15
Volts_AB
Votlage Phase A-B
R
Volts
AI16
Volts_BC
Voltage Phase B-C
R
Volts
AI17
Volts_AC
Voltage Phase A-C
R
Volts
AI18
Volts_AN
Voltage Phase A-N
R
Volts
AI19
Volts_BN
Voltage Phase B-N
R
Volts
AI20
Volts_CN
Voltage Phase C-N
R
Volts
AI21
Current_A
Current Phase A
R
Amps
AI22
Current_B
Current Phase B
R
Amps
AI23
Current_C
Current Phase C
R
Amps
AI24
Reserved_AI24
Reserved
R
n/a
AI25
Frequency
Frequency
R
Hz
ZL0071-0E
Page 23 of 28
1.00 for 100%
Returns QNAN or any value
45.0-65.0
Returns QNAN if frequency is out of range (or no voltage
input present on Phase A)
©2014 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide
Power Monitoring
E50H2, E50H5
TM
BACnet Programming Information (cont.)
#
Object_Name
Description
R/W
NV
Units
Range
Additional information
AI26
kVAh
Apparent Energy
Consumption
R
NV
kVAh
0 - 3.4+E38
The UNITS property of object AI26 reports that these units
are kWh because there is no unit type in the BACnet
standard for kVAh.
AI27
kVARh
Reactive Energy
Consumption
R
NV
kVARh
0 - 3.4+E38
The UNITS property of object AI27 reports that these units
are kWh because there is no unit type in the BACnet
standard for kVARh.
AI28
kVA_A
Apparent Power
Phase A
R
kVA
0 - Max_Power (AI45)
AI29
kVA_B
Apparent Power
Phase B
R
kVA
0 - Max_Power (AI45)
AI30
kVA_C
Apparent Power
Phase C
R
kVA
0 - Max_Power (AI45)
AI31
KVAR_A
Reactive Power
Phase A
R
kVAR
0 - Max_Power (AI45)
AI32
KVAR_B
Reactive Power
Phase B
R
kVAR
0 - Max_Power (AI45)
AI33
KVAR_C
Reactive Power
Phase C
R
kVAR
0 - Max_Power (AI45)
AI34
KW_Present_
Demand
Total Real Power
Present Demand
R
kW
0 - Max_Power (AI45)
AI35
KVAR_Present_
Demand
Total Reactive Power
Present Demand
R
kVAR
0 - Max_Power (AI45)
AI36
KVA_Present_
Demand
Total Apparent Power R
Present Demand
kVA
0 - Max_Power (AI45)
AI37
KW_Max_
Demand
Total Real Power
Maximum Demand
R
NV
kW
0 - Max_Power (AI45)
This retains the largest value measured for Total Real
Power Demand (AI34) for any single demand interval
since the Max Demand was last explicitly reset via
AV1 (this is also reset when the demand interval is
changed).
AI38
KVAR_Max_
Demand
Total Reactive Power
Maximum Demand
R
NV
kVAR
0 - Max_Power (AI45)
This retains the largest value measured for Total Reactive
Power Demand (AI35) for any single demand interval
since the Max Demand was last explicitly reset via
AV1 (this is also reset when the demand interval is
changed).
AI39
KVA_Max_
Demand
Total Apparent Power R
Maximum Demand
NV
kVA
0 - Max_Power (AI45)
This retains the largest value measured for Total Apparent
Power Demand (AI36) for any single demand interval
since the Max Demand was last explicitly reset via
AV1 (this is also reset when the demand interval is
changed).
AI40
E50H2: Pulse
Count
E50H5: Pulse_
Count_1
E50H2: Pulse Count
E50H5: Pulse Count
#1
R
NV
#
0 - 4294967040
Running count of contact closures on Pulse1 input since
last reset. Write 16498 (0x4072) to the Present_Value
property of Analog_Value object AV1 to reset both
Pulse Counters to 0.
AI41
E50H2: Reserved
E50H5: Pulse_
Count_2
E50H2: Reserved
E50H5: Pulse Count
#2
R
NV
#
0 - 4294967040
E50H2: Reserved
E50H5: Pulse Count 2; Running count of contact closures
on Pulse2 input since last reset. Write 16498 (0x4072)
to the Present_Value property of Analog_Value object
AV1 to reset both Pulse Counters to 0.
AI42
KWH_A
Real Energy
Consumption
Phase A
R
NV
kWh
0 - 3.4+E38
AI43
KWH_B
Real Energy
Consumption
Phase B
R
NV
kWh
0 - 3.4+E38
ZL0071-0E
Page 24 of 28
©2014 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide
Power Monitoring
E50H2, E50H5
TM
BACnet Programming Information (cont.)
R/W
NV
AI44
#
KWH_C
Object_Name
Real Energy
Consumption
Phase C
Description
R
NV
kWh
Units
0 - 3.4+E38
Range
Additional information
AI45
Max_Power
Theoretical
Maximum System
Power
R
NV
kW
0 - 1.84467e19
AI46
Reserved_AI46
Reserved
R
AI47
Energy Resets
Count of Energy
Accumulator Resets
R
AI48
Reserved_AI48
Reserved
R
Returns QNAN or any value
AI49
Reserved_AI49
Reserved
R
Returns QNAN or any value
AI50
Power Up Count
Power Up Counter
R
NV
0 - 32767
Running count of product power-up cycles (Control
Power)
AI51
Ouput Config
Ouput Configuration
R
NV
0 - 15
E50H2 returns “11”
E50H5 returns “10”
AI52
Alarm_Bitmap
Alarm_Bitmap
R
0 - 32767
This contains a decimal value that represents the status
of all Binary_Object alert values in one number that can
be read without having to access mulitple objects (the
E50H2 has 14 values, the E50H5 has 15). It is a decimal
representation of a 14-bit or 15-bit hexidecimal value
produced by combining the alert bits into one number,
where the bit value of Object BI1 is the least significant
bit and BI14 or BI15 is the most significant bit.
Theoretical Maximum System Power – This is the
theoretical maximum power the meter expects to see
on a service. It is calculated by the meter from the
System Type (in object AV2), CT Size (in object AV3),
and System Voltage (in object AV6) - Power Factor is
assumed to be unity. The register is updated whenever
the user changes any of these parameters.
Returns QNAN or any value
NV
0 - 32767
Running count of how many times the energy counter
has been reset
Binary_Input Objects
Use the Present_Value properties of the Binary_Input objects as alerts for conditions of potential concern regarding to the system measurement. These values are dynamic
and are not latched, so if the condition is resolved, the alert will go inactive, whether it has been read or not.
These objects support the Description and Reliability object properties and all required Binary_Input object properties. None of them are writable. For complete assurance,
check the Reliabilty property for a No_Fault_Detected status before reading the Present_Value.
To test the meter’s alert status, read the Present_Value of each of the Binary_Input objects representing the alert bits of interest, or read the Present_Value of AI52, which
combines all these bits into a single decimal value. AI52 represents the status of all 14 or 15 Binary_Object alert values in one number that can be read without having to
access mulitple objects. The bit value of Object BI1 is the least significant bit and BI14 or BI15 is the most significant bit (BI15 is only present on the E50H5).
#
Name
BI1
Volts_Error_A
Voltage Out of Range Phase A
R
0=INACTIVE, 1=ACTIVE
Phase A Input Voltage exceeds meter’s measurement range
BI2
Volts_Error_B
Voltage Out of Range Phase B
R
0=INACTIVE, 1=ACTIVE
Phase B Input Voltage exceeds meter’s measurement range
BI3
Volts_Error_C
Voltage Out of Range Phase C
R
0=INACTIVE, 1=ACTIVE
Phase C Input Voltage exceeds meter’s measurement range
BI4
Current_Error_A
Current Out of Range Phase A
R
0=INACTIVE, 1=ACTIVE
Phase A Current out of range
BI5
Current_Error_A
Current Out of Range Phase B
R
0=INACTIVE, 1=ACTIVE
Phase B Current out of range
BI6
Current_Error_A
Current Out of Range Phase C
R
0=INACTIVE, 1=ACTIVE
Phase C Current out of range
BI7
Frequency_Error
Frequency Error
R
0=INACTIVE, 1=ACTIVE
Phase A Frequency out of range
BI8
Reserved_BI8
Reserved
R
0=INACTIVE, 1=ACTIVE
Returns “INACTIVE”
ZL0071-0E
Description
Page 25 of 28
R/W
Range
Additional information
©2014 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide
Power Monitoring
E50H2, E50H5
TM
BACnet Programming Information (cont.)
#
Name
Description
R/W
Range
Additional information
BI9
Phase_Loss_A
Phase Loss Phase A
R
0=INACTIVE, 1=ACTIVE
Phase Loss - Phase A voltage dropped below the Phase Loss Threshold set by
user
BI10
Phase_Loss_B
Phase Loss Phase B
R
0=INACTIVE, 1=ACTIVE
Phase Loss - Phase B voltage dropped below the Phase Loss Threshold set by
user
BI11
Phase_Loss_C
Phase Loss Phase C
R
0=INACTIVE, 1=ACTIVE
Phase Loss - Phase C voltage dropped below the Phase Loss Threshold set by
user
BI12
Power_Factor_A
Low Power Factor Phase A
R
0=INACTIVE, 1=ACTIVE
Phase A Power Factor less than 50% (commonly due to mis-wiring of CTs/PTs
to meter)
BI13
Power_Factor_B
Low Power Factor Phase B
R
0=INACTIVE, 1=ACTIVE
Phase B Power Factor less than 50% (commonly due to mis-wiring of CTs/PTs
to meter)
BI14
Power_Factor_C
Low Power Factor Phase C
R
0=INACTIVE, 1=ACTIVE
Phase C Power Factor less than 50% (commonly due to mis-wiring of CTs/PTs
to meter)
BI15
RTC_Reset
(E50H5 only)
RTC Reset
R
0=INACTIVE, 1=ACTIVE
Real-Time Clock reset. This activates when the meter is powered after an
interruption (since it does not use a battery backup). It indicates that the
real-time clock has re-initialized to a default setting (00:00:00:00 on Jan 1,
2000) and should not be relied upon. The clock runs, the meter operates and
even logs data (E50H5A only), but the date and time are not correct until a
Time_Synchronization occurs.
Data Logging (E50H5 only)
The E50H5 includes a data logging feature that records three meter parameters, accessible via BACnet using Trend_Log objects. All three Trend_Log objects utilize shared
data logging resources in the meter, so all three are controlled in unison. All writable properties other than Log_Device_Property_Object are common to all three Trend_Log
obects. Changes to these properties (Log_Enable, Start_Time, Stop_Time, Log_Interval, Stop_When_Full or Record Count) for any one of the objects will be reflected in
the corresponding property of all three objects. The Log_Interval property is also common with the Demand_Subinterval (Present_Value of AV11), since logging records are
updated synchronously with demand calculations.
Default settings cause logging to begin immediately, with 15 minute intervals and no stop time. When full, the buffer will wrap and overwrite the oldest data first (unless the
Stop_When_Full property is used).
Configuration:
Use Log_Device_Object_Property to select the meter parameter to log with each object. Set this property to point to Present_Value property of any of the Analog_Input
objects. The default the values for the Log_Device_Object_Property of the three Trend_Log objects are set as follows:
• TL1 = Real Energy Consumption (AI1 Present_Value)
• TL2 = Reactive Energy Consumption (AI27 Present_Value)
• TL3 = Total Real Power Present Demand (AI34 Present_Value)
The Log_Interval (& Demand Subinterval) can be set from 10 seconds to 32767 seconds (values of 1000 to 3276700). The subinterval timer, which determines how often the
meter’s demand accumulators are updated, also triggers writing to the Trend_Log log buffers. Use the Log_Interval property to set the data logging time subinterval, in units
of hundredths of a second (0.01 seconds). The default subinterval is 15 minutes (a value of 90000 in the Log_Interval property). The Buffer_Length is fixed at 5760, so at a 15
minute interval setting, the buffers hold 60 days of data.
Use the Stop_When_Full property to select either Single Shot (Stop_When_Full = TRUE) or Continuous mode (Stop_When_Full = FALSE) for data logging. The default mode
is Continuous. In Single Shot mode, the meter records data only until the buffer is full. Data for this time period is kept, but newer energy information is lost. In Continuous
mode, the meter continues to record energy data as long as the meter is operating. The buffer can only hold 5760 entries at one time, however, so when the number of records
exceeds 5760, the oldest entry is deleted to make room for the newest.
To start data logging with any of the three Trend_Log objects, set the Log_Enable property to TRUE or set the Start_Time and Stop_Time properties appropriately and wait
for logging to commence at Start_Time.
ZL0071-0E
Page 26 of 28
©2014 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide
Power Monitoring
E50H2, E50H5
TM
BACnet Programming Information (cont.)
By default, the Record_Count property of the Trend_Log objects is initialized to Zero.
Reading Data:
Access logged data with corresponding timestamps via the Log_Buffer property of the Trend_Log object using the BACnet ReadRange service. The E50H5 supports both the
“by Position” and “by Sequence Number” modes of the ReadRange service, but not the “by Time” mode.
Trend_Log Objects
Trend_Log Properties
Used
R/W
Units
Additional information
Object_Name
R
Trend_Log_<n>
Where n is 1-3 (there are three instances of Trend_Log objects available)
Description
R
Trend_Log <n>
Where n is 1-3 (there are three instances of Trend_Log objects available)
Log_Enable
W
Binary
Set this to TRUE to enable logging or FALSE to disable logging. The default is TRUE.
The value is set to FALSE internally if logging stops for other reasons (i.e. buffer is full).
Start_Time
W
Date/Time
Sets the Date/Time when data logging will Start (if Log_enable is TRUE). Set to a Date/Time earlier
than the Local_Date/Local_Time properites of the Device object and Set Log_Enable TRUE to start
logging immediately.
Stop_Time
W
Date/Time
Sets the Date/Time when data Logging will STOP (if still running).
Stop_Time will be ignored if ”wildcard” values are used in any of the fields.
Log_Device_Object_
Property
W
BACnetDeviceObjectProptertyReference
Set (point) this to the Present_Value of any of objects AI1 through AI49
to establish which parameter to log. Default values are:
TL1 = Real Energy Consumption (Array of AI1 Present_Value)
TL2 = Reactive Energy Consumption (Array of AI27 Present_Value)
TL3 = Total Real Power Present Demand (Array of AI34 Present_Value)
Log_Interval
W
0.01 seconds
Logging period in hundredths of a second.
Default is 90000 (15 minute intervals); minimum value is 1000 (10 seconds). This property can also
be set to Zero, which changes all three Trend_Logs and the Demand calculation to a manual mode
(sometimes referred to as “Sync to Comms”). In manual mode, the demand interval is updated and
another record is logged upon a manual command, which is issued by writing the value 21211 to the
Present_Value of object AV1.
Stop_When_Full
W
Binary
Set this to TRUE to stop logging when the buffer is full (single-shot mode) or FALSE to continue when
full (wrap & overwtrite oldest data entries).
Buffer_Size
R
5760
Length of Log Data buffer (# of records).
Log_Buffer
R
List of BACnetLongRecord
Contains the data values logged, with timestamps
Record_Count
W
Unsigned 32-bit integer
This is an integer count of how many records logged since the Trend_Log objects were last reset.
Writing a Zero to this property resets the logs of all three objects. This value defaults to Zero, but, by
default, logging starts automatically at 15 minute intervals.
Total_Record_Count
R
Unsigned 32-bit integer
This is an integer count of how many records logged since the Trend_Log objects were created (the
factory state of the meter). This count is unaffected by resetting the Record Count or by power
failures.
Event_State
R
Binary
ZL0071-0E
Page 27 of 28
©2014 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide
Power Monitoring
E50H2, E50H5
TM
Troubleshooting
Problem
Cause
Solution
The maintenance
wrench icon appears
in the power meter
display.
There is a problem with the
inputs to the power meter.
See the Alert sub-menu or the Diagnostic Alert BACnet Binary_Input objects
The display is blank
after applying control
power to the meter.
The meter is not receiving
adequate power.
Verify that the meter control power is receiving the required voltage.
Verify that the heart icon is blinking.
Check the fuse.
Incorrect setup values
Verify the values entered for power meter setup parameters (CT and PT ratings,
system type, etc.). See the Setup section.
Incorrect voltage inputs
Check power meter voltage input terminals to verify adequate voltage.
Power meter is wired
improperly.
Check all CTs and PTs to verify correct connection, PT polarity, and adequate power.
See the Wiring Diagrams section for more information.
Power meter address is
incorrect.
Verify that the meter is correctly addressed. See the Setup section.
Power meter baud rate is
incorrect.
Verify that the baud rate of the meter matches that of all other devices on its
communications link (see Setup section).
Communications lines are
improperly connected.
Verify the power meter communications connections. See the Communications
section.
Verify the terminating resistors are properly installed on both ends of a chain of
units. Do not use a terminator on units in the middle of a chain.
Verify shield ground connection between all units.
The data displayed is
inaccurate.
Cannot communicate
with power meter
from a remote
personal computer.
China RoHS Compliance Information
(EFUP Table)
产品中有毒有害物质或元素的名称及含量Substances
部件名称
铅 (Pb) 汞 (Hg)
电子线路板
X
O
镉 (Cd)
六价铬 (Cr(VI))
多溴联苯(PBB)
多溴二苯醚(PBDE)
O
O
O
O
O = 表示该有毒有害物质在该部件所有均质材料中的含量均在 SJ/T11363-2006 标准规定的限量要求以下.
X = 表示该有毒有害物质至少在该部件的某一均质材料中的含量超出SJ/T11363-2006标准规定的限量要求.
Z000057-0A
ZL0071-0E
Page 28 of 28
©2014 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertisement