Datasheet_MR_41_42
Memory & latching relays MR-41, MR-42
! Latching relays, controlled by buttons from several locations can replace three way switches or cross bar switches
thanks to control by buttons (unlimited number, connected in parallel by 2 wires), installation gets more transparent
and faster for mounting.
! Relays MR-41/UNI, MR-42/UNI memorize its last state even after supply failure. During the failure relay will turn off and
after re-energizing will automatically turns on.
! MR-41
- output contact: 1x changeover / SPDT 16 A
! MR-42
- options - 2x parallel contacts or the other relay is latching
- function selected via external jumper between B1 - B2
- output contact: 2x changeover /SPDT 16 A
EAN code
MR-41 /230V: 8595188115889
MR-41 /UNI: 8595188115896
MR-42 /230V: 8595188115902
MR-42 /UNI: 8595188115919
! Supply voltage AC 230 V or AC/DC 12-240 V
! 1-MODULE version, DIN rail mounting, controlling by buttons
MR-41
Number of functions:
Supply terminals:
Voltage range:
Burden:
Voltage range:
Consumption (apparent/loss):
Supply voltage tolerance:
Supply indication:
Output
Number of contacts:
Current rating:
Breaking capacity:
Inrush current:
Switching voltage:
Min. breaking capacity DC:
Output indication:
Mechanical life:
Electrical life (AC1):
Controlling
Consumption of input:
Load between A2-ON/OFF:
Control. terminals:
Glow tubes connetions:
Max. amount of glow lamps
connected to controlling input:
Impulse length:
Other data
Operating temperature:
Storage temperature:
Electrical strength:
Operating position:
Mounting/DIN rail:
Protection degree:
Overvoltage category:
Pollution degree:
Max. cable size (mm2):
Dimensions:
Weight:
Standards:
1
230
UNI
Technical parameters
MR-42
2
A1 - A2
AC/DC 12 - 240 V (AC 50 - 60 Hz)
AC 0.17 - 3 VA / DC 0.1 - 1.2 W
AC 0.17 - 12 VA / DC 0.11 - 1.9 W
AC 230 V / 50 - 60 Hz
AC max. 12 VA / 1.2 W
AC max. 12 VA / 1.9 W
-15 %; +10 %
green LED
1x changeover / SPDT (AgSnO2)
2x changeover/ SPDT (AgSnO2)
16 A / AC1
4000 VA / AC1, 384 W / DC
30 A / <3 s
250 V AC1 / 24 V DC
500 mW
red LED
3x10 7
0.7x10 5
Symbol
MR-42
MR-41
12
A1
14
11
ON/OFF A2
MR-41
L
N
L
N
+
A1
+
A1
ON
OFF
A2
B1
ON
OFF
A2
B2
21 22 24
11 12 14
11 12 14
Function
MR-41
A1 - A2
ON/OFF
11 - 14
MR-42
A1 - A2
ON/OFF
B1
B2
B1
B2
21 - 24
11 - 14
21 - 24
14
11
MR-42
11 - 14
62
ON/OFF A2
Connection
AC 0.025 - 0.2 VA / DC 0.1 - 0.7 W (UNI), AC 0.53 VA (AC 230 V)
Yes
A1 - ON/OFF
230 V - Yes / UNI - No
UNI - glow lamps cannot connected,
230V - max. amount 5 pcs (measured with glow lamp 0.68mA/230V AC)
min. 25 ms / max. unlimited
-20 °C to +55 °C (-4 °F to 131 °F)
-30 °C to +70 °C (-22 °F to 158 °F)
4 kV (supply - output)
any
DIN rail EN 60715
IP 40 from front panel / IP 20 terminals
III.
2
solid wire max.1x 2.5 or 2x1.5/ with sleeve max. 1x2.5 (AWG 12)
90 x 17.6 x 64 mm (3.5˝ x 0.7˝ x 2.5˝)
(UNI) - 62 g, (230) - 60 g
(UNI) - 89 g, (230) - 85 g
EN 61810-1, EN 61010-1
12