ES8000 V-LOCK
WITH 30MM FACEPLATE
INSTALLATION INSTRUCTIONS
SELECTING THE MODE CONFIGURATION
1
STEP 1
- Loosen both screws on side of lock
body.
- With some force, slide screws in direction
STEP 2
- Rotate Latch Plate screw beneath
the red re-sealable sticker according to
orientation shown below:
required until stop at end of slot is reached.
- Hold in position and re-tighten screws.
PTL
PTO
Bolt Label
SPECIFICATIONS AND NOTES
Parameter
Specification
Door Gap
Ideally 3mm to 8mm only. 8mm maximum.
Lock Monitor Output
Voltage free changeover switch contacts rated for
48VDC / 100mA
Turn counter-clockwise
180o for Power-to-Open
(Fail Secure)
Holding Force
AS4145.2 - 1993: Passed S3 (611kg for 1 minute)
Capable of 1000kg if strike plate is fully supported
Turn clockwise 180o for
Power-to-Lock (Fail Safe)
Release under Side Load
15kg max at bolt with motorised unlocking (3 wire control)
3kg max at bolt with Power-To-Lock (Fail Safe) unlocking
and 2 wire control
Bolt Dimensions
Diameter = 11mm
Projection = 20.5mm
Power Supply (12-24VDC)
Regulation better than +/- 2%
1Amp Power supply required
Current Draw
Power to Lock holding current 130mA
Power to Open holding current 30mA
Initial locking and unlocking current draw higher
Misalignment tolerance
+/- 3.5mm
Operating Temperature
-10oC to +50oC at 90% RH
STEP 3
- Change jumper position on Printed
Circuit Board beneath the red
re-sealable sticker as shown below:
Power-to-Open
(Fail Secure)
Durability
Power-to-Lock
(Fail Safe)
> 300,000 cycles
Certifications
•Up to 2-hour fire rating depending on doorset used, in accordance with
AS1905.1 - 1997, Part 1: Fire Resistant Doors
•CE compliant
•SCEC endorsed (high security strike bracket required)
WARNING!
• Lock mode configuration set to Power To Lock (Fail Safe). Ensure the correct
mode is set before applying power: you may be charged for incorrect
installation.
• Discard Bolt Label once correct mode is selected.
• If the lock had been installed or previously operated, the latch plate
screw (STEP 2) will not be visible. To change lock mode configuration,
contact your distributor for additional information.
• Ensure all re-sealable stickers and screws are re-attached after configuration
to prevent ingress of dust.
• V-Lock must ONLY be used in weather protected areas.
• V-Lock can ONLY be installed vertically or horizontally ABOVE the door
(not on or under the floor).
• V-Lock WILL NOT operate without strike plate. Strike plate MUST be
correctly aligned and in front of the M logo on the faceplate.
DOOR PREPARATION FOR STRIKE AND JAMB
2
DOOR JAMB PREPARATION
3
Line 2
Line 1
Lock
Faceplate
Line 2
Door
Door Jamb
256
210
256
Door Jamb
50
15
24
30
door
imum
mm
gap 8
15
M
30
Max
• Before starting with the installation make sure the gap between the
door and the door jamb does not exceed 8mm
• Mark Line 1 corresponding to mid-plane of Door
• Mark Line 2 corresponding with Line 1 on the Door Jamb
Note: Make sure the Line 1 and Line 2 are aligned when the door is in
the closed position.
DRAWINGS NOT NOT TO SCALE. INFORMATION IN THIS DATASHEET MAY BE CHANGED WITHOUT NOTICE.
• Mark cutout of V-Lock symmetrically about Line 2.
• Cutout size for faceplate must be 256mm x 30mm
• Prepare door jamb appropriately as shown.
Note: Thickness of faceplate - 3mm
42
ELECTRICAL SPECIFICATION
3 Wire Control
Power To Open (PTO) Wiring Connections
BLACK
BLUE
- 0 volts d.c.
- Access Control (PTO)
RED
- Positive Continuous Supply
PURPLE - (COM)
WHITE - (NO)
ORANGE - (NC)
The V-Lock is designed to be controlled with a minimum of 2 wires. However, it is recommended that 3 wire
control be used:
3
•
•
•
•
NC
NO
DC Power
+
Bolt Position
Monitor
•
•
•
•
Power To Lock (PTL) Wiring Connections
BLACK
- 0 volts d.c.
BLUE
- Access Control (PTL)
RED
- Positive Continuous Supply
NC
PURPLE - (COM)
WHITE - (NO)
NO
DC Power
+
2 Wire Control:
In Power-To-Lock (Fail Safe) configuration, it is possible to operate the V-Lock using 2 control wires only. With
2 wire control, the lock relies on the Fail Safe spring mechanism to unlock, which reduces the lock’s
capability to open under side load to only 3kg. Hence, 2 wire control is NOT RECOMMENDED and should be
avoided wherever possible. For retrofit applications where only 2 control wires may exist, connect the BLUE
and RED wires on the lock together and join them to the positive supply voltage. Connect the negative supply
voltage to the BLACK wire on the lock
Bolt Position
Monitor
ORANGE - (NC)
2 Wire Control
Power To Lock 2 Wire Control - NOT RECOMMENDED
BLACK
BLUE
-
- 0 volts d.c.
+
RED
PURPLE - (COM)
WHITE - (NO)
ORANGE - (NC)
4
Wire Control:
Positive voltage should be connected to the RED wire providing permanent power.
Negative voltage should be connected to the BLACK wire.
Positive voltage should be connected to the BLUE wire providing a lock/unlock signal.
When connected with 3 wires the motor will provide power assisted unlocking allowing the bolt to
retract with up to 15kg of side load.
Voltage-free changeover switch contacts are provided for bolt position monitoring.
When locked, the monitor switch (COM - PURPLE) is connected to (NC - ORANGE).
The V-Lock is multi-voltage and operates with either 12 to 24VDC power.
The V-Lock has in-built Reverse Polarity Protection for installer safety.
DC Power
Voltage:
Voltage Tolerance:
Current:
Bolt Position
Monitor
DOOR PREPARATION AND INSTALLATION OF STRIKE PLATE
12 to 24VDC
12V (+15% - 0%) 24V(+/- 15%)
Minimum 1 Amp Regulated Supply
PTL Holding current 130mA
PTO Holding current 30mA
INSTALLING VLOCK IN DOOR JAMB
5
Line 1
(Half thickness of door)
Door Jamb
D22 x 20 Deep
Door
p
or ga
o
um d
Maxim 8mm
7
27
Line 3
2
24
48
1
Magnet
256
2
M
132
242
1
V-Lock Unit
Face Plate
1
2
Strike Plate
Strike Plate
3mm Thickness
Mounting Tabs (supplied)
Required for Flush
Mounting only
Mounting Nuts (supplied)
Required for Flush
Mounting only
Magnet and M must line
up for V-Lock to operate
Door
• On the door, mark Line 3 corresponding to the top edge of the lock
faceplate (step3)
• Mark and recess cutout of strike plate on door symmetrically, using
Line 1 as the centre guide and Line 3 as the height guide
• Cut out the 22mm wide and 20mm deep cavity for the bolt as
shown above.
• Install the strike plate on the door, ensure the door gap is not more
than 8mm between the strike plate and the faceplate on the V-Lock
• Ensure strike plate is securely fastened to increase overall holding
force and security of installation.
• Ensure all wiring connections are correct and are insulated, make
sure the wires do not rub on the any sharp edges or do not interfere
with any of the locking mechanism.
• Install the V-Lock into the door jamb as shown above
• Power up lock, then let the door open and close normally with door
closer. When the strike plate magnet comes within locking range, the
V-Lock will lock as long as the lock bolt closes within target locking
range (see Detail A)
Note: Thickness of strike plate - 3mm
ACCESSORIES AVAILABLE:
ASSA ABLOY Australia guarantees the product for a period of 5 years in accordance with the
standard TRICARE warranty against defects in manufacture, workmanship or materials,
provided that all electrical and mechanical installation requirements are adhered to as per this
datasheet. All third party and consequential claims are expressly excluded from the warranty.
• ES8000 Glass Door Kit
• Strike plate with magnet
• Mounting bracket for high security applications
N13900
2
ASSA ABLOY Australia Pty Ltd, 235 Huntingdale Rd, Oakleigh VIC 3166, Australia, www.assaabloy.com.au
DA0076, ES8000 Datasheet, Issue 9, January 2010