i2 600 Controller

Continuum ®
IN
F I N E Family
T II ™
BACnet
600 Series Local Controllers
The i2600 series controllers are designed for monitoring a small or large
concentration of input points from a single controller. Choose the i2600
model with the input configuration that matches your application:
• Compact, Cost-Effective Input
Monitoring Controller
• Powerful, Flexible System
Controller for the Most
Demanding Applications
• Ideal for Monitoring Small or
Large Groups of Inputs in a
Concentrated Area
• Universal Inputs Can be
Configured as a Supervised
Input for Monitoring Open
Wires or Short Circuits
• Non-Volatile Flash Memory
Provides Utmost Reliability —
Stores Both Application
Program and Operating
System
• The i2608, with eight Universal inputs, is designed for standalone equipment monitoring for a small concentration of input
points. This controller is also configurable for Supervised Input
monitoring to determine broken wire detection or shorts. The
i2608 is ideal for Security applications (motion detection, glass
break detection, intrusion detection) or traditional control
applications (temperature, humidity, etc).
• The i2624 provides the same functionality as the the i2608 and
in the same small footprint of the i2608, but with three times
the number of input points (24) for monitoring various device
signals. With the small footprint and high point count, the
i2624 is ideal for large concentration of inputs, reducing the
number of controllers required in the system, and decreasing
cost, complexity, and maintenance requirements.
The i2600 series also features Flash memory, increased user memory,
and a fast (32-bit) processor for faster scan times, with plenty of memory
available for data logging of your critical data.
The i2600 series communicates with the entire Andover Controls Infinet™
RS-485 field bus; i.e., both Infinet and Infinet II controllers, and is
compatible with the Continuum® CyberStation Version 1.5 front-end. Up to
254 Infinet devices can be networked to any Andover network controller.
• Local, Extended Storage of
Log Data
• Local, On-Board Service Port
INCREASED RELIABILITY WITH FLASH MEMORY
The i2600’s non-volatile Flash memory stores your operating system and
application programs, so that in the event of a power loss, your
application will be restored when power is returned. In addition, the Flash
memory allows for easy upgrades of your operating system via software
downloads, eliminating the need to swap out proms. The i2600 controllers
include an on-board battery to safeguard your runtime data — protecting
all point data and log data from being lost if power is removed.
WE'RE BUILDING SMART
INPUTS
The input configuration on the i2600 series consists
of eight (or twenty-four) full range, 10-bit Universal
inputs that accept voltage (0-5VDC), digital (on/off),
counter signals (up to 4Hz), temperature signals, or
supervised alarm circuits for security applications or
broken wire detection.
SOFTWARE CAPABILITIES
The dynamic memory of the i2600 can be allocated
for any combination of programs, scheduling,
alarming, and data logging using the powerful
Andover Controls Plain English® programming
language. Our object-oriented Plain English
language with intuitive keywords provides an easy
method to tailor the controller to meet your exact
requirements. Programs are entered into the i2600
®
using the Continuum CyberStation . Programs are
then stored and executed by the i2600 controllers.
Programming multiple i2600 series controllers is
inherently easy with Plain English. A complete copy
of one i2600’s programs can be loaded directly into
other i2600s without changing any point names or
programs.
1
3
4
2
Dimensional Drawing
1 Power Drawing
2 Communications Drawing
4 i2624
3 i2608 and i2624
Inputs Drawings
S P E C I F I C AT I O N S
600 Series Local Controllers
ELECTRICAL
CONNECTIONS
Power:
Power:
Inputs:
24VAC, 12-24VDC - auto sensing, +10% 15%, 50/60 Hz
Power Consumption:
25 VA
Overload Protection:
Fused with 3 amp fuse. MOV protected.
Software Real-Time Clock: Synchronized through Infinet by network
controller
b3624 only:
Inputs 9-16:
12-position fixed screw terminal connector
Inputs 17-24:
12-positon fixed screw terminal connector
MECHANICAL
Operating Environment:
Size:
Weight:
Enclosure Type:
Mounting:
32°–120°F (0–49°C), 10–95% RH (noncondensing)
9.03"H x 6.01”W x 2.14"D (229 H x
153 W x 54 D) mm
1.19 lbs. (.54 kg)
UL Open class, IP 10. Flammability rating of
UL94-5V
Panel mount
3-position fixed screw terminal connector
Inputs 1-8 (both b3608 and b3624):
12-position fixed screw terminal connector
Communications:
Service Port:
3-position removable screw terminal
connector
4-position shrouded connector
USER LEDS/SWITCHES
Status Indicator LEDS:
CPU
TD
RD
CPU Active
Transmit Data
Receive Data
BATTERY
Battery Backup:
Replaceable, non-rechargeable, lithium
battery. Provides 5 years typical
accumulated power failure backup of RAM
memory
Switches:
RESET
Input Pull-up Resistor Switch (per input)
GENERAL
COMMUNICATIONS
Communications Interface: Through Infinet RS-485 field bus to
network controller
Communications Speed:
1200 to 19.2K baud
Bus Length:
4,000 ft. (1,220m) standard for Infinet, i2
Infilink module allows extension to longer
distances and is required after every group
of 32 units on the network.
Bus Media:
Infinet: twisted, shielded pair, low
capacitance cable
Comm. Error Checking:
International Standard CRC 16
Compatibility:
Continuum CyberStation Version 1.5
Memory:
Processor:
128K SRAM, 1MB FLASH
Motorola 32-bit Coldfire
Note: i2600 Series REQUIRES Continuum V1.5 version (or later) of
software
AGENCY LISTINGS
UL/CUL 916, FCC CFR 47 Part 15, ICES-003,
EN55022, AS/NZS 3548, Class A, CE
OPTIONS
UL864, Smoke Control System Equipment, UUKL (i2608-S, i2624-S)
INPUTS
Inputs:
b3608: 8 Universal inputs
b3624: 24 Universal inputs
Voltage (0-5.115 VDC); Temperature -30°F
to 230°F (-34°C to 110°C), Digital (on/off),
Counter (up to 4Hz at 50% duty cycle, 125
ms min. pulse width). Supervised Alarm
(single or double resistor). Current input (0 20 mA) using external 250 ohm resistor
Input Voltage Range:
Input Impedance:
0-5.115 volts DC
10K ohm to 5.120V or 5M ohm with pullup resistor disabled
Input Resolution:
5.0 mV
Input Accuracy:
±15mV (±0.56°C from -23°C to +66°C or
±1°F from -10°F to +150°F)
Andover Controls Corp.
World Headquarters
300 Brickstone Square
Andover, Massachusetts 01810 USA
Tel: +1 978 470 0555 Fax: +1 978 470 0946
Andover Controls Europe
Smisby Road
Ashby-de-la-Zouch
Leicestershire LE65 2UG England
Tel: +44 1530 417733
Fax: +44 1530 415436
Andover Controls Germany
Am Seerhein 8
D-78467 Konstanz
Germany
Tel: +49 7531 99370
Fax: +49 7531 993710
Andover Controls France
Immeuble Dolomites 2
58 Rue Roger Salengro
94126 Fontenay Sous Bois
France
Tel: +33 1 53 99 16 16
Fax: +33 1 53 99 16 15
Andover Controls Poland
Radzikowskiego 56
31-315 Krakow
Poland
Tel: +48 126385500
Fax: +48 126385501
Andover Controls Asia
Unit 1201-02, Phase 1, Cheuk Nang Centre
9 Hillwood Road,
Tsim Sha Tsui East
Kowloon, Hong Kong
Tel: +852 2739 5497
Fax: +852 2739 7350
Andover Controls Mexico
Insurgentes Sur 1722-501
Col. Florida
Mexico D.F. 01030, Mexico
Tel: +5255 5661 5672
Fax: +5255 5661 5415
www.andovercontrols.com
WE'RE BUILDING SMART
A Balfour Beatty Company
©2004 Andover Controls Corporation • All brand names, trademarks and registered trademarks are the property of their respective holders. DS-I-I2600-C
Download PDF