- Industrial & lab equipment
- Personal safety & protection
- Fire protection
- Bosch
- FPC-500 -2
- Installation Guide
- 82 Pages
Bosch FPC-500 -2, -4, -8 fire panel Installation Guide
Below you will find brief information for fire panel FPC-500 FPC-500-2, fire panel FPC-500 FPC-500-4, fire panel FPC-500 FPC-500-8. The Bosch fire panel FPC-500 is a versatile system that can be configured to meet the needs of a variety of applications. The fire panel FPC-500 is a conventional fire panel that has been designed and tested according to EN 54-2 and EN 54-4. You can use the FPC-500 series for smaller and larger projects. The panel offers up to eight supervised zones and incorporates two notification appliances that can be used to activate the audible notification appliances and visual notification appliances.
advertisement
Assistant Bot
Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.
Conventional Fire Panel
FPC-500-2 / FPC-500-4 / FPC-500-8 en Installation Guide
Conventional Fire Panel Table of Contents | en 3
Table of contents
Bosch Sicherheitssysteme GmbH
Batteries, 24 V Emergency Power Supply
2014.06 | 7.0 | F.01U.172.980
4 en | Table of Contents Conventional Fire Panel
Information as per EN 54‑4, chapter 7.1
Options with requirements as per EN 54‑2:1997/A1:2006
Brief Overview, Operating Level 1 and 2
Brief Overview, Operating Level 3
2014.06 | 7.0 | F.01U.172.980
Bosch Sicherheitssysteme GmbH
Conventional Fire Panel
Table of Contents | en 5
Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980
6 en | Safety Instructions Conventional Fire Panel
1
!
Safety Instructions
Danger!
The fire panel may only be operated with the housing closed because of the danger of an electric shock.
Danger!
Only perform installation work when the panel has no voltage.
There is a danger of an electric shock.
Caution!
Installation may only be performed by authorized qualified personnel in order to ensure that the system is not damaged and operates properly.
Notice!
Note local regulations when connecting to 230 V power supplies.
Notice!
Please observe the country-specific regulations and guidelines during planning, installation and programming of the fire panel.
Notice!
In line with EN 54-13 (BOSEC certificate TCC 2 - 977), each conventional line must be terminated with EOL modules for the operation of fire detection systems.
The AUX power supply must also be terminated with EOL modules when using four-wire detectors.
2014.06 | 7.0 | F.01U.172.980
Bosch Sicherheitssysteme GmbH
Conventional Fire Panel Safety Instructions | en 7
Notice!
The fire panel has been designed for operation in closed rooms.
Please note the permissible environmental conditions in the technical specifications.
Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980
8 en | System Overview Conventional Fire Panel
2 System Overview
A LARM
P re-Alarm
F ault
System Fault
Earth Fault
Power Fault
NAC Fault / Disabled
Notification Appliance Silent
Day Mode
1 2 3 4 5 6 7 8
2
EVAC i
A CK
ESC
RESET Power
1
1
2
3
4
4
LED display
LCD display with zone numbers
Zone keys and zone status LEDs
Operating panel
3
7
8
5
6
3
4
1
2
2014.06 | 7.0 | F.01U.172.980
Bosch Sicherheitssysteme GmbH
Conventional Fire Panel System Overview | en 9
Inputs
– Zones
– Prog. inputs
Outputs
– Prog. AUX (500 mA)
– Alarm device, 500 mA each
– Relay
Extensions
– Open collector (20 mA)
– Relay (via OC)
LCD, 2 x 16 characters
FPC-500-
2
FPC-500-
4
2
1
4
1
1
2
2
FPC-500-
8
8
2 no 1 x 4
Yes
2 x 4
Z1
.
.
.
Z8
IN1
IN2
ALARM RLY
FAULT RLY
OC (0, 4, 8)
AUX
24 V DC
230
VAC
Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980
10 en | System Overview Conventional Fire Panel
Conventional detectors
Conventional manual call point
Visual or audible notification appliances
Z1 ... Z8
IN
Conventional zones 1 to 8
(max. 2 on FPC-500-2, max. 4 on FPC-500-4)
Inputs (max. 1 on FPC‑500‑2 and FPC‑500‑4, max. 2 on FPC‑500‑8)
Alarm relay
ALARM RLY
Fault relay
FAULT RLY
OC
AUX 24 VDC
Transistor output for extension cards
(0 on FPC‑500‑2, 4 on FPC‑500‑4, 8 on
FPC‑500‑8)
AUX power supply
Features
– Alarm verification: The user is prompted to verify the alarm.
– Intermediate alarm storage: an alarm triggered by an automatic detector is reset automatically after 20 seconds
(adjustable) by the panel. If there is an additional alarm within 10 minutes in this zone, the notification appliances are enabled. Otherwise the pre-alarm is reset automatically.
– Dual-zone dependency on neighboring zones.
2014.06 | 7.0 | F.01U.172.980
Bosch Sicherheitssysteme GmbH
Conventional Fire Panel System Overview | en 11
– Dual-detector dependency for detectors in a zone.
– Alarm counter for 999 alarms.
– Event memory for 1000 entries.
– Three operating levels, two of them protected with freely selected code.
– Up to 8 monitored detector zones depending on panel version.
– Up to 2 monitored inputs available depending on panel version.
– One alarm and one fault relay.
– Up to 8 additional transistor or relay outputs, freely programmable, depending on panel version.
– Quick and easy programming using the keypad and LCD display.
– Easy operation for the end user.
– Two monitored notification appliance outputs.
– EN 54-13 (BOSEC certificate TCC 2 - 977) compliant system by using EOL modules.
– Power supply via power supply unit with thermal fuse.
– Emergency power supply using batteries, up to 7.2 Ah, reverse polarity protected.
– Removable quick guide for the user on the panel.
Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980
12 en | System Overview Conventional Fire Panel
2.1
Operating Levels
This fire panel has three operating levels. You can only perform certain actions depending on operating level.
Level 1 – Display information
– Read out event memory
– Display faults and deactivations
– Perform display test
Level 2 – Change language and time/date
– Switch key tones on/off
– Put zones in test mode and take zones out of test mode
– Switch off/on zones, notification appliances, relay and transistor outputs
– Trigger evacuations
– Reset panel
– Switch between day/night mode
– All actions of level 1
Level 3 – All settings for installing and programming the system.
Code inputs are necessary for accessing level 2 and 3.
2014.06 | 7.0 | F.01U.172.980
Bosch Sicherheitssysteme GmbH
Conventional Fire Panel Installation | en 13
3
3.1
3.2
3.2.1
!
Installation
Scope of Delivery
The fire panel packaging contains the following components:
– Fire panelFPC‑500‑2/FPC‑500‑4/FPC‑500‑8
– EOL resistors for zones and inputs
– Battery cable set
– Cable ties for strain relief on power supply feeder
– Labeling strips for zones and LEDs
– Quick Installation Guide
– Quick Operation Guide
– CD
– Two plastic foam blocks for securing the batteries
Installation
Notice!
Install the fire panel in a location easily accessible to emergency response teams (e.g. fire department).
Note permissible environmental conditions.
Install the fire panel at a height above the ground that permits convenient operation by the user and easy reading of the LCD display.
Inserting the Cable
Route the necessary cables for zones, inputs and outputs, as well as the power supply, etc., and carefully punch out the cable entries needed for this.
Warning!
Electrostatic discharge (ESD)! Electronic components could become damaged. Ground yourself using a wrist strap or take other suitable measures.
Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980
14 en | Installation Conventional Fire Panel
Remove the PC board if necessary. This is secured in the housing with a grounding screw and snap-fit hook.
For cable entry on the upper side of the housing, use the preformed round holes. For more stable insertion, M 20 x 1.5 screw joints (PG13.5) can be used.
The cable entries on the rear are intended for direct cable entry of flush mounted cables.
3.2.2
Opening the Housing
Remove the cover of the fire panel. Loosen both screws on the underside of the housing, lift up the cover approx. 20° and remove it.
2014.06 | 7.0 | F.01U.172.980
Bosch Sicherheitssysteme GmbH
Conventional Fire Panel Installation | en 15
3.2.3
Installing the Housing
Use the panel housing to draw drill holes at the desired location on the wall (arrows in figure below). As an option, you can use the mounting dimensions indicated on the back of the housing.
Ensure that the housing is aligned horizontally and draw on the holes using the built-in spirit level in the upper left corner. The dimensions can be taken from the drilling jib on the rear of the housing. Drill the holes.
Guide the cables routed under plaster through the punched out cable ducts on the rear of the housing into the housing. Mount the housing to the wall using screws. Make sure that cables are not pinched.
Then guide the cables routed on plaster through the cable entries to the upper side of the housing.
Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980
16 en | Installation Conventional Fire Panel
3.2.4
Mains Supply
The fire panel requires a 230 V mains supply for the power supply. Route the power supply so that the line does not cross or touch the signal line.
Use the left M 20 x 1.5 screw joint (PG13.5) on the upper side of the panel for the 230 V mains supply.
Notice!
Note local regulations when connecting to 230 V power supplies.
Wire up the 230 V power supply to the screw clamp provided on the power supply unit board. Use a cable tie to ensure strain relief of the power supply feeder in the housing above the power supply unit.
Danger!
Only perform installation work when the panel has no voltage.
There is a danger of an electric shock.
230 VAC
50 - 60 Hz
2014.06 | 7.0 | F.01U.172.980
N L
Bosch Sicherheitssysteme GmbH
Conventional Fire Panel Installation | en 17
3.2.5
Batteries, 24 V Emergency Power Supply
You can use two 12 V batteries with maximum 7.2 Ah each in the housing as emergency power supply.
The batteries are connected in series. If the mains power fails, they are used to ensure interruption-free power supply of the fire panel and the components fed by them.
Notice!
The fire panel can also only be started with the batteries if the power supply is disconnected.
After you have placed the batteries in the housing, secure them using the plastic foam blocks provided.
Position the plastic foam blocks in between the top of the batteries and the housing.
There are different emergency current back-up times depending on the battery capacity used and the current consumption of the components connected to the panel. You can calculate this using the battery calculator included on the CD.
After troubleshooting a mains fault and operating the fire panel via emergency current, the power supply unit switches back to mains operation automatically. The batteries are charged again automatically.
Notice!
Note the polarity of the batteries.
If the batteries are connected with the polarity reversed, the thermal fuse on the main board of the fire panel reacts.
Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980
18 en | Installation Conventional Fire Panel
BAT
- +
3.2.6
Secure the batteries with the plastic foam blocks provided so that they cannot move.
Extensions
Notice!
Note that the maximum line resistance for transistor outputs is
22.5 Ohm.
The extensions are connected to the left side of the main board.
Simply connect the board to the plugs. Make sure that the plug engages correctly.
2014.06 | 7.0 | F.01U.172.980
Bosch Sicherheitssysteme GmbH
Conventional Fire Panel Installation | en 19
There is a groove on the top of the extensions. Make sure that the board has been correctly installed.
Notice!
A maximum of two extensions can be connected:
FPC-500‑2: No extension can be connected
FPC-500‑4: One extension can be connected
FPC-500‑8: Two extensions can be connected
3.3
Wiring
External components such as zones, notification appliances, inputs, etc. are wired to screw terminals attached to the upper side of the board.
1 2 3 4 5
.
No Meaning
1 Inputs
2 Zones
3 Aux power supply
4 Notification appliance
5 Alarm and fault relay
Bosch Sicherheitssysteme GmbH
FPC‑500
-2
FPC‑500
-4
FPC‑500
-8
1 1 2
2 8 4
1
2
1/1
2014.06 | 7.0 | F.01U.172.980
20 en | Installation Conventional Fire Panel
Notice!
The screw terminals are designed for a cable diameter of
0.8 mm and for cable cross sections of up to 1.5 mm 2 .
The fire panel is designed for unshielded cable. If you do use shielded cable, only connect the cable shielding to the earth bar on one side above the power supply unit.
Terminal resistances
The zones of the fire panels must be terminated. Use either resistors or in case of EN 54-13 (BOSEC certificate TCC 2 - 977) the EOL modules.
Notice!
Only use resistors with a maximum 1% tolerance.
The 3.9 kOhm resistors are supplied.
3.3.1
Inputs
820Ω ± 5%
The fire panel offers two control inputs. You can assign different
functions to these depending on programming (see Configuring
The connection terminals IN1 and IN2 are available.
Notice!
Note that the maximum line resistance for inputs is 22.5 ohm.
Use 820 Ohm ±5% resistors for the alarm resistance (not included in scope of delivery).
2014.06 | 7.0 | F.01U.172.980
Bosch Sicherheitssysteme GmbH
Conventional Fire Panel Installation | en 21
Notice!
Only use buttons (no locking element) if you have programmed inputs as Drill/Evacuate, Silence, or Reset Panel.
Access levels as per EN 54‑2 must be observed.
3.3.2
Zones
Notice!
Do not connect the zone- with any power+ like for example:
AUX power, external power supply or batteries for emergency power supply.
b+ ab+ a-
EOL
3,9kΩ
EOL
EN 54‑13 (BOSEC certificate TCC 2 - 977)
Each zone must be completed with a terminal element.
You can either use a 3.9 kΩ ± 1% resistor or EOL modules for an
EN 54-13 (BOSEC certificate TCC 2 - 977) compliant termination.
Unused zones must also be terminated with a terminal element.
Mixing different terminal elements is not allowed.
Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980
22 en | Installation Conventional Fire Panel
Notice!
Note that the maximum line resistance for conventional zones is
22.5 Ohm.
The voltage of the zones is 20 VDC ±1 V.
The maximum current of the zones is 100 mA ±5 mA.
Notice!
Observe local regulations for the maximum number of detectors in a zone.
When using the FLM-320-EOL4W Module, use the battery calculator included on the CD.
Notice!
The last zone of the fire panel supports the use of 4-wire detectors.
The fire panel does not support dual-detector dependency with
4-wire detectors.
Please use permissible external power supply units depending on power consumption.
Notice!
Activating a manual call point in a zone programmed as "No
Delay" triggers an immediate alarm.
Notice!
Only use manual call points in zones which are programmed as
No Delay.
2014.06 | 7.0 | F.01U.172.980
Bosch Sicherheitssysteme GmbH
Conventional Fire Panel Installation | en 23
3.3.3
Aux power
Non-EN54-13
3,9kΩ b+ a-
+
4W
-
EOL b+ a-
+
-
4W
FLM-320-EOL4W
EN54-13 (BOSEC certificate TCC 2 - 977)
The fire panel allows you to use 4-wire (4W) elements on the last zone. These must be supplied with power by the auxiliary power supply or an external power source. Both the zone and the auxiliary power must be terminated by a terminal element.
For EN 54-13 (BOSEC certificate TCC 2 - 977) compliant connection of 4‑wire elements, the AUX and zone lines must be routed in separate cables.
You can either use a 3.9 kΩ ±1% resistor or EOL modules for
EN 54-13 (BOSEC certificate TCC 2 - 977) compliant termination.
Program the reset behavior of the auxiliary power as described
Notice!
Note that the maximum line resistance for the auxiliary power is
22.5 Ohm.
Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980
24 en | Installation
3.3.4
Notification Appliances
Conventional Fire Panel
A- B+ A- B+
OUT IN
NAC1
A- B+ A- B+
OUT IN
NAC2
Notice!
Each notification appliance output provides connected notification appliances with a maximum current of 500 mA at
24 VDC. The permissible voltage range of the output is 21–
29 VDC.
Notice!
Note that the maximum line resistance for notification appliances is 22.5 Ohm.
The fire panel offers you two notification appliance circuit lines that can be used to activate the audible notification appliances and visual notification appliances. When there is a fire alarm, the notification appliance circuit lines are activated depending on programming.
2014.06 | 7.0 | F.01U.172.980
Bosch Sicherheitssysteme GmbH
Conventional Fire Panel Installation | en 25
Notice!
Connect the notification appliances to the terminals NAC1 and/or NAC2. This connection is EN 54‑13 (BOSEC certificate
TCC 2 - 977) compliant.
3.3.5
Relay Outputs
NO C NC
ALARM
NO C NC
FAULT
Notice!
The fault relay is activated in a normal state. It is opened in the event of a fault.
The fire panel has two relay outputs. The relays work as potential-free change-over contacts.
The alarm relay is activated by every fire alarm.
Notice!
A transmission device must be installed in the immediate vicinity (without a space) of the FPC‑500‑x.
The connecting line between the fire panel and the transmission device must not be exposed, as it is not monitored.
Notice!
Both relay outputs "ALARM" and "FAULT" can switch a maximum of 1 A @ 30 VDC each.
Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980
26 en | Installation Conventional Fire Panel
Notice!
Note that the maximum line resistance for the relay outputs is
22.5 Ohm.
3.3.6
Extensions
The extension modules offer four connections activated by transistors or relay.
Notice!
The relay outputs can switch a maximum of 1 A @ 30 VDC each.
The transistor outputs switch a maximum of 20 mA @ 24 VDC each. Inductive loads are not permitted.
3.3.7
External power supply
You can use the FPP-5000 as an external power source for the
FPC-500 Fire Panel.
Notice!
Note that the FPP‑5000 housing must be installed in the direct vicinity (without a space) of the FPC‑500‑x. The connecting line between the FPP-5000 and the transmission device must not be exposed, as it is not monitored.
FPC‑500‑2 and FPC‑500‑4
Wire the FPP-5000 as shown in FPC‑500‑2 and FPC‑500‑4, page
Program input 1 to Ext PS Fault (see Input 1, page 48). The
relay is not included in the scope of delivery.
2014.06 | 7.0 | F.01U.172.980
Bosch Sicherheitssysteme GmbH
Conventional Fire Panel
Relais
24VDC/1A
NC C NO
3k9
1 2
MAIN POWER
MAIN POWER
TROUBLE
BATTERY 1
TROUBLE
BATTERY 2
TROUBLE
MAIN BAT1 BAT2 FAULT
Installation | en 27
12 V 12 V FPP--5000
FPC‑500‑8
Wire the FPP-5000 as shown in FPC‑500‑8, page 27.
Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980
28 en | Installation Conventional Fire Panel
Program input 1 to Ext PS Fault and input 2 to Ext Batt Fault
(see Input 1, page 48). The relays are not included in the scope
of delivery.
+ - + -
24V 24V
1 2
MAIN POWER
MAIN POWER
TROUBLE
BATTERY 1
TROUBLE
BATTERY 2
TROUBLE
MAIN BAT1 BAT2 FAULT
Relais
24VDC/1A
Relais
24VDC/1A
NC C NO NC C NO
3k9 3k9
12 V 12 V FPP--5000
2014.06 | 7.0 | F.01U.172.980
Bosch Sicherheitssysteme GmbH
Conventional Fire Panel Installation | en 29
3.4
3.4.1
Initial Start-Up
As soon as the fire panel is connected to the power for the first time, an LED and buzzer test begins. This is completed the first time a key is pressed.
In the initial start-up, you must make the following basic settings:
– Set the language
– Set the time and date
Setting the Language
To set the language, proceed as follows:
Use the arrow keys to set the desired language.
i
3.4.2
ACK
Confirm your selection in the menu with the ACK key.
Setting the Time and Date
Set the current time and date. The current time and date are important for functions such as
– Event memory and
– Automatic switching to night mode.
Use the arrow keys to set the current day.
i
ACK
Confirm your selection in the menu with the ACK key.
Repeat this procedure to set the correct values for the month, year and time.
Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980
30 en | Installation Conventional Fire Panel
Notice!
Summer and winter time settings are not made automatically.
Make these settings manually.
If there is a total power failure, you must make the settings for the date and time again.
2014.06 | 7.0 | F.01U.172.980
Bosch Sicherheitssysteme GmbH
Conventional Fire Panel System Configuration | en 31
4 System Configuration
To be able to perform the actions in operating level 3, you will need a code you can enter with the zone keys.
Notice!
The following codes are programmed in delivery status:
Operating level 2: 1234
Operating level 3: 3333
The basic settings can be found in Default Settings, page 74.
Calling up operating level 3
Press the "Code input" key.
You will be prompted to enter a code.
C O D E /
Enter the code with zone keys 1 to 8.
!
You are in the programming menu of the system.
Caution!
In operating level 3, the fire panel is not operational. None of the inputs and outputs are monitored.
Automatic exit of level 3
If you are in level 3 and no key has been pressed for 10 minutes, the system will exit level 3 automatically.
One minute before exiting level 3, a pulse tone of the internal buzzer indicates the time. The time up to the automatic exit of level 3 is displayed in the LCD display.
Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980
32 en | System Configuration Conventional Fire Panel
Exiting operating level 3
Notice!
When you exit operating level 3, the fire panel automatically switches to night mode.
If you are in operating level 3, proceed as follows.
RESET
ACK RESET
Press the RESET key.
You exit operating level 3 when you are at the top level of the menu. The configuration is stored and the inputs and outputs are activated.
– Press the ACK key to exit operating level 3.
– If you do not want to exit operating level 3, press the RESET key.
Menu
Operating level 3 of the fire panel offers you the following setting options:
– 1-System Config
– 2-Delay Config
– 3-Zone Config
– 4-Input Config
– 5-Output Config
– 6-View Config
– 7-Output Control
– 8-Config Reset
Notice!
The structure and description of menus of operating levels 1 and 2 can be found in the operating instructions.
2014.06 | 7.0 | F.01U.172.980
Bosch Sicherheitssysteme GmbH
Conventional Fire Panel System Configuration | en 33
Notice!
The menus are described in these instructions as follows:
A hyphen between the number and the menu description "-" shows you that it is a menu item with a submenu.
An equals sign between the number and the menu description
"=" represents a set value.
A space between the number and the menu description " " is a value that can be set.
Preset values are always shown in bold.
Operation
You have different options for navigating in the menu of the fire panel.
Using autoscrolling
ACK
The menus scroll automatically every 2.5 seconds to the next menu item. If you would like to select the menu item currently shown, simply confirm with the
ACK key.
Navigating with the zone keys
1
...
8
In the menu, each menu item has a number from 1 to 8 preceding it. Use the zone keys to select the desired menu item in the menu. The desired menu item does not have to be shown in the display.
Navigating with the arrow keys i
Use the arrow keys to navigate in the menu.
Using the arrow keys stops autoscrolling in the menus.
ACK
Confirm your selection in the menu with the ACK key.
Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980
34 en | System Configuration Conventional Fire Panel
4.1
4.1.1
4.1.2
Exiting submenus
RESET
ESC In the menu and in the submenus, you can jump to a higher level or cancel the setting using the RESET
(ESC) key.
Hold the RESET (ESC) key down for 2 seconds to jump to the uppermost level.
System Configuration
In the System Config menu, you can specify basic settings for your fire panel.
Setting the Date/Time
1
Press zone key 1. This takes you to the System
Config menu.
1
Press zone key 1.
You can now set the date and time.
ACK
To save the currently displayed value, press the ACK key.
Repeat the steps to set the month, year, hour, and minute.
Buzzer Beep
1
Press zone key 1. This takes you to the System
Config menu.
2
1
...
2
Press zone key 2.
This takes you to the Keypad Tone submenu.
Press zone keys 1 or 2:
– 1=On (default setting)
– 2 Off
2014.06 | 7.0 | F.01U.172.980
Bosch Sicherheitssysteme GmbH
Conventional Fire Panel System Configuration | en 35
4.1.3
4.1.4
EOL Elements
You can use EOL Devices to specify whether you want to use resistors or EOL modules for zone termination.
1
Press zone key 1. This takes you to the System
Config menu.
3
1
...
3
Press zone key 3.
This takes you to the EOL Devices submenu.
Press zone keys 1 to 3:
– 1=Resistor (default setting, not EN 54‑13 compliant)
– 2 Only 2W Module
– 3 With 4W Module
1 2 3 4 5 6 7 8
CS TH: mA
If you select With 4W Module, you must specify the threshold for the creeping short-circuit.
You can calculate this using the battery calculator included on the CD.
Resetting Zones
In this menu, you can specify the delay times for resetting zones. You can specify how long the zones can be disconnected from the power and how long the stabilization time of the detector should last. This setting is used for the zone test, restarting the fire panel and intermediate alarm storage.
Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980
36 en | System Configuration Conventional Fire Panel
Cut For
1
Press zone key 1. This takes you to the System
Config menu.
4
1
Press zone key 4.
This takes you to the Zone Reset submenu.
Press zone key 1.
This takes you to the Cut For submenu.
1
...
5
Press zone keys 1 to 5.
– 1 1s
– 2=5s (default setting)
– 3 10s
– 4 15s
– 5 20s
Stabilize for
1
Press zone key 1. This takes you to the System
Config menu.
4
2
1
...
5
Press zone key 4.
This takes you to the Zone Reset submenu.
Press zone key 2.
This takes you to the Stabilize For submenu.
Press zone keys 1 to 5.
– 1 1s
– 2=5s (default setting)
– 3 10s
– 4 15s
– 5 20s
2014.06 | 7.0 | F.01U.172.980
Bosch Sicherheitssysteme GmbH
Conventional Fire Panel System Configuration | en 37
4.1.5
4.1.6
Aux Power
The With Zone setting relates to the last zone of the fire panel.
If the last zone is reset after a pre-alarm or alarm, the AUX power supply is reset simultaneously.
The With Panel setting also resets the power supply each time the fire panel is reset.
If you select Never, the auxiliary power supply is never reset.
1
Press zone key 1. This takes you to the System
Config menu.
5
1
...
3
Press zone key 5.
This takes you to the Aux Power submenu.
Press zone keys 1 to 3.
– 1=With Zone (default setting)
– 2 With Panel
– 3 Never
Faults
The Faults setting specifies whether faults on the fire panel are to be displayed until the fire panel is manually reset.
Notice!
This setting does not apply to system faults.
System faults can only be reset manually.
Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980
38 en | System Configuration Conventional Fire Panel
4.1.7
1
Press zone key 1. This takes you to the System
Config menu.
6
1
...
2
Press zone key 6.
This takes you to the Faults submenu.
Press zone key 1 or 2.
– 1=Latching (default setting)
– 2 Non Latching
Level Code
In the Level Code menu, you can specify new codes for operating levels 2 and 3. The new code must be 4 characters long and is displayed during entry.
Notice!
The following codes are programmed in delivery status:
Operating level 2: 1234
Operating level 3: 3333
1
Press zone key 1. This takes you to the System
Config menu.
7
1
...
2
Press zone key 7.
This takes you to the Code submenu.
– 1- Level 2 Code
– 2- Level 3 Code
1 2 3 4 5 6 7 8
Level 2 Code
Set to: ____
You are prompted to enter the new code.
2014.06 | 7.0 | F.01U.172.980
Bosch Sicherheitssysteme GmbH
Conventional Fire Panel System Configuration | en 39
1 2 3 4 5 6 7 8
Level 2 Code
Confirm: ____
You then have to confirm the new code by entering it again.
The procedure for changing the code for operating level 3 is exactly the same.
Notice!
If you have forgotten your code, contact your Bosch partner.
4.1.8
4.2
Test Log
You can decide whether or not the fire panel creates a Test
History.
1
Press zone key 1. This takes you to the System
Config menu.
8
1
...
2
Press zone key 8.
This takes you to the Test History submenu.
Use zone keys 1 or 2.
– 1=Log Enabled (default setting)
– 2 Log Disabled
Configuring Delays
In the Delay Config menu, you can program different delay times for different zone programs, outputs and fault types.
2
Press zone key 2. This takes you to the Delay Config menu.
Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980
40 en | System Configuration Conventional Fire Panel
4.2.1
Deactivating Day Mode
Specify whether you want day mode (zones with alarm verification start a verification time in the event of an alarm) to be exited manually by the user or automatically at a defined time. You can program the time in this submenu.
Notice!
Day mode must always be started manually; it is not possible to configure an automatic start.
2
Press zone key 2. This takes you to the Delay Config menu.
1
Press zone key 1.
This takes you to the Day Mode Off submenu.
1
...
2
Use zone keys 1 or 2.
– 1=Manual (default setting)
– 2 Automatic
If you set Day Mode Off to Automatic, you must program the changeover time from day to night mode.
1 2 3 4 5 6 7 8
Off Time: :17:00
Confirm with
Set the time with the arrow keys and confirm using the ACK key.
Alarm Verification 4.2.2
Notice!
This setting only applies to zones that are programmed as alarm verification.
Note that the delay settings are only effective in day mode. In night mode, the alarm is triggered immediately.
2014.06 | 7.0 | F.01U.172.980
Bosch Sicherheitssysteme GmbH
Conventional Fire Panel System Configuration | en 41
In the Alarm Verific menu, you set the times within which the user must confirm a triggered alarm (ACK Within). The Invest
Time submenu specifies the time available to the user to enter the alarm triggering area before the notification appliance is activated. You can also use NAC 1 to specify whether:
– Alert switches NAC 1 on immediately in the event of an alarm. NAC 1 is then switched off during the verification time and switched on again after the verification time.
– With Evacuate, NAC 1 is switched off during the delay time and only activated during the actual alarm.
Time setting for alarm acknowledgement
2
Press zone key 2. This takes you to the Delay Config menu.
2
1
Press zone key 2.
This takes you to the Alarm Verific submenu.
Press zone key 1.
This takes you to the ACK Within submenu.
1
...
4
Use the zone keys to set the respective delay.
– 1 30 s
– 2= 60 s (default setting)
– 3 90 s
– 4 120s
Time setting for verification time
2
Press zone key 2. This takes you to the Delay Config menu.
2
Press zone key 2.
This takes you to the Alarm Verific submenu.
Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980
42 en | System Configuration Conventional Fire Panel
4.2.3
2
1
...
8
Press zone key 2.
This takes you to the Invest Time submenu.
Use the zone keys to set the respective delay.
– 1 1 min (default setting)
– 2 2 min
– 3 3 min
– 4 4 min
– 5 5 min
– 6 6 min
– 7 7 min
– 8 8 min
Notification appliance 1
2
Press zone key 2. This takes you to the Delay Config menu.
2
3
1
...
2
Press zone key 2.
This takes you to the Alarm Verific submenu.
Press zone key 3.
This takes you to the NAC 1 submenu.
Press zone key 1 or 2.
– 1 Alert
– 2=Evacuate (default setting)
Intermediate Alarm Storage
Intermediate alarm storage is an automatic procedure designed to rule out false alarms as far as possible. The entire procedure lasts up to 60 seconds:
– Ten seconds after a fire is detected, the zone is reset
(setting Reset After).
–
The zone is reset for x seconds (setting Cut For, Cut For ,
2014.06 | 7.0 | F.01U.172.980
Bosch Sicherheitssysteme GmbH
Conventional Fire Panel System Configuration | en 43
!
– There is an x second stabilization phase for the elements in
the zone (setting Stabilize For, Stabilize for, page 36).
Caution!
Detectors of the FCP-320 series must not be used with intermediate alarm storage because the detector calculates a new standby value after the reset. This can generate an increased alarm threshold. If there is a fire, this can thus delay the trigger of an alarm.
Before using automatic fire detectors, find out from the manufacturer whether they can be used for intermediate alarm storage.
In this menu you can change the pre-set time values indicated above.
Reset after
2
Press zone key 2. This takes you to the Delay Config menu.
3
1
1
...
4
Press zone key 3.
This takes you to the Int Alarm Stor submenu.
Press zone key 1.
This takes you to the Reset After submenu.
Use the zone keys to set the respective delay.
– 1 1 s
– 2 5 s
– 3= 10 s (default setting)
– 4 15s
– 5 20 s
Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980
44 en | System Configuration Conventional Fire Panel
4.2.4
4.3
Display total delay
2
Press zone key 2. This takes you to the Delay Config menu.
3
Press zone key 3.
This takes you to the Int Alarm Stor submenu.
2
Press zone key 2.
This takes you to the Total Delay submenu.
The total delay is displayed.
Delay for Mains Fault
The Power Fault menu option enables you to specify the delay after which an error message indicating a power supply failure
(mains or battery) is to be displayed. If the fault is resolved before the time set here, it is no longer displayed.
2
Press zone key 2. This takes you to the Delay Config menu.
4
1
...
5
Press zone key 4.
This takes you to the Power Fault submenu.
Use the zone keys to set the respective delay.
– 1=No Delay (default setting)
– 2 1 min
– 3 5 min
– 4 10 min
– 5 15 min
Zone Configuration
In the Zone Config menu, you can program the individual zones of the fire panel. Depending on the panel, you can set 2, 4 or 8 zones. The following zone types are available:
2014.06 | 7.0 | F.01U.172.980
Bosch Sicherheitssysteme GmbH
Conventional Fire Panel System Configuration | en 45
No delay (No Delay)
A zone programmed as No Delay triggers an alarm immediately.
If you are using manual call points, they must be set as No
Delay.
Notice!
Only use manual call points in zones which are programmed as
No Delay.
Int Alarm StorIntermediate alarm storage
A zone triggers an alarm. This is evaluated by the fire panel as a pre-alarm and is not displayed. The zone is reset automatically.
If it triggers an alarm again, the panel switches immediately to alarm. If a second alarm is not triggered, the fire panel reverts to its normal state after 10 minutes.
Alarm verification (Alarm Verific)
Notice!
Note that the delay is only effective in day mode. In night mode, the alarm is triggered immediately.
Notice!
If the fire panel automatically switches to night mode during an ongoing verification time, an alarm is triggered immediately.
Notice!
If during the verification time in one zone an alarm is triggered in another zone, which is programmed as alarm verification, an alarm is triggered immediately.
If a zone programmed as alarm verification detects an alarm, it triggers an alarm, which is delayed.
Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980
46 en | System Configuration Conventional Fire Panel
!
The LCD display prompts you to verify the alarm. You must confirm the alarm within a pre-defined time using the ACK key.
After this pre-defined time the verification time begins. Within this time you must investigate the alarm triggering area and, if necessary, trigger an alarm.
During the verification time, the panel can be reset without triggering an alarm. After the verification time has expired, the panel goes into the alarm state.
Dual-detector dependency (2-Det Depend)
Caution!
Detectors with connected remote displays must not be used with the dual-detector dependency.
Dual-detector dependency only works with detectors that use an alarm resistance of 820 ohm +/- 5% or 910 ohm +/- 5%.
Otherwise, in the event of a fire, proper functioning of the fire panel cannot be guaranteed.
Notice!
The fire panel does not support dual-detector dependency with
4-wire detectors.
The zone must contain more than one detector. If one of the detectors in the zone triggers, this is evaluated as a pre-alarm. If an additional detector in the same zone is activated, an alarm is triggered. The panel automatically attempts to reset the prealarm every 10 minutes. However, this is not possible if a detector remains active. This procedure is repeated until no more detectors are active and the panel returns to its normal state, or until a second detector becomes active, thus elevating the pre-alarm to an alarm.
Dual-zone dependency (2-Zone Depend)
Applies to adjacent zones, for example zones 1 and 2.
If a zone detects an alarm, this is evaluated as a pre-alarm. An alarm is only triggered when the second zone detects an alarm.
2014.06 | 7.0 | F.01U.172.980
Bosch Sicherheitssysteme GmbH
Conventional Fire Panel
4.4
System Configuration | en 47
Possible zone dependencies:
– FPC‑500-2: 1&2
– FPC‑500‑4: 1&2, 3&4
– FPC‑500‑8: 1&2, 3&4, 5&6, 7&8
If you set a zone to dual-zone dependency, the other associated zone is also changed automatically.
Zones 1 to 8
3
Press zone key 3. This takes you to the Zone Config menu.
1
Press zone key 1.
This takes you to the zone 1 submenu.
1
...
6
Use the zone keys to program the zone.
– 1=No Delay (default setting)
– 2 Int Alarm Stor
– 3 Alarm Verific
– 4 2-Det Depend
– 5 2-Zone Depend
Zones 2 to 8 are pre-programmed in the same way as zone 1.
You can change the settings as with zone 1.
Notice!
Zones 3 and 4 are only available on the FPC‑500‑4 and
FPC‑500‑8 panels. Zones 5–8 are only available on the
FPC‑500‑8.
Configuring Inputs
In the Input Config menu, you can program the behavior of the inputs.
Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980
48 en | System Configuration Conventional Fire Panel
Notice!
Only use buttons (no locking element) if you have programmed inputs as Drill/Evacuate, Silence, or Reset Panel.
Access levels as per EN 54‑2 must be observed.
Notice!
Depending on the panel, there is one input on the FPC‑500‑2 and FPC‑500‑4, and two inputs on the FPC‑500‑8.
4.4.1
4
Press zone key 4.
This takes you to the Input Config menu.
Input 1
4
Press zone key 4.
This takes you to the Input Config menu.
1
1
...
7
Press zone key 1.
This takes you to the Input 1 submenu.
Use the zone keys to set the programming for input
1.
– 1= Not Used (default setting)
– 2 Drill/Evacuate
– 3 Silence
– 4 Level 2
– 5 Reset Panel
– 6 Ext PS Fault
– 7 Ext Batt Fault
Notice!
You do not have to confirm the input functions on the panel.
Thus use a key switch if possible to activate inputs.
2014.06 | 7.0 | F.01U.172.980
Bosch Sicherheitssysteme GmbH
Conventional Fire Panel System Configuration | en 49
4.4.2
4.5
4.5.1
!
Input 2 (FPC-500‑8 only)
4
Press zone key 4.
This takes you to the Input Config menu.
2
Press zone key 2.
This takes you to the Input 2 submenu.
Additional settings correspond to those for Input 1.
Configuring Outputs
In the Output Config menu, you can program the behavior of the individual fire panel outputs.
Notification Appliances
In the NAC submenu, you specify the behavior of the notification appliances. You can use NAC Zones to assign the notification appliances to particular zones. Reactive NAC specifies whether silenced notification appliances are reactivated by a new alarm in another zone. You can use NAC in test to specify whether the notification appliances are activated for 15 seconds when a zone test is performed.
Caution!
When assigning the zones to notification appliances, make sure that each zone of the fire panel is assigned to at least one notification appliance.
Zones not assigned do not trigger any alarm signaling via the notification appliance if there is a fire.
Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980
50 en | System Configuration Conventional Fire Panel
Notification appliance 1 zone assignment
5
Press zone key 5.
This takes you to the Output Config menu.
1
1
1
...
8
Press zone key 1.
This takes you to the NAC submenu.
Press zone key 1.
This takes you to the NAC Zones submenu.
Use the zone keys to select the corresponding zones whose alarm you want to activate notification appliance 1.
You can select multiple zones. If you press the zone key again, the selection is cancelled.
Confirm your selection.
ACK
Notification appliance 2 zone assignment
See "Notification appliance 1 zone assignment", Notification
appliance 1 zone assignment, page 50.
Reactivating notification appliances
5
Press zone key 5.
This takes you to the Output Config menu.
1
3
1
...
2
Press zone key 1.
This takes you to the NAC submenu.
Press zone key 3.
This takes you to the Reactive NAC submenu.
Press zone keys 1 or 2.
1=By Other Zone (default setting)
2 No Reactivate
2014.06 | 7.0 | F.01U.172.980
Bosch Sicherheitssysteme GmbH
Conventional Fire Panel System Configuration | en 51
4.5.2
Notification appliance behavior in zone test
5
Press zone key 5.
This takes you to the Output Config menu.
1
4
1
...
2
Press zone key 1.
This takes you to the NAC submenu.
Press zone key 4.
This takes you to the NAC in test submenu.
Press zone keys 1 or 2.
1 Activation
2=No Activation (default setting)
Alarm Relay
In the Alarm Relay submenu, you can specify the properties of the alarm relay. These include the Silencable and Drillable settings. You can use Silencable to specify whether the relay can be silenced manually. Drillable specifies whether the alarm relay is also activated during a manual alarm (Drill/Evac).
Alarm relay can be muted
5
Press zone key 5.
This takes you to the Output Config menu.
2
1
1
...
2
Press zone key 2.
This takes you to the Alarm Relay submenu.
Press zone key 1.
This takes you to the Silencable submenu.
Press zone keys 1 or 2.
1 Silencable
2=Not Silencable (default setting)
Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980
52 en | System Configuration Conventional Fire Panel
4.5.3
Alarm relay follows manual alarm
5
Press zone key 5.
This takes you to the Output Config menu.
2
2
1
...
2
Press zone key 2.
This takes you to the Alarm Relay submenu.
Press zone key 2.
This takes you to the Drillable submenu.
Press zone keys 1 or 2.
1 Drillable
2= Not Drillable (default setting)
OC/Relay Extensions
In the OC/Relay Ext menu, you can individually set the properties of all OC/Relay outputs. The possible settings for the
OC/Relay outputs 2 to 8 correspond to those for the first OC/
Relay . The following settings are possible:
– Zone = Alarm: The output is activated if the zone triggers an alarm. Here zone 1 is assigned to output 1, etc.
– Zone Normal: If the zone is not in a normal state, the output is activated. Assignment: zone 1 to output 1 etc.
– Sum Alarm: When the fire panel is in an alarm state, this output is activated regardless of the zone.
– Sum PreAlarm: When the fire panel is in a pre-alarm state, this output is activated regardless of the zone.
– Sum Fault: This output is activated if there is a fault.
– Sum Disable: If a fire panel element is disabled, this output is activated (zones, notification appliances, relays).
– Sum Test: This output is activated if a zone in the fire panel is in test mode.
– Not Used: The output is not used.
2014.06 | 7.0 | F.01U.172.980
Bosch Sicherheitssysteme GmbH
Conventional Fire Panel
4.6
System Configuration | en 53
5
Press zone key 5.
This takes you to the Output Config menu.
3
Press zone key 3.
This takes you to the OC/Relay Ext submenu.
Press zone key 1 to choose Open Collector 1.
1
1
...
8
Use the zone keys to make the corresponding setting.
– 1=Zone = Alarm (default setting)
– 2 Zone Normal
– 3 Sum Alarm
– 4 Sum PreAlarm
– 5 Sum Fault
– 6 Sum Disable
– 7 Sum Test
– 8 Not Used
The procedure for OC/Relay 2 to 8 is the same.
Displaying the Configuration
In the View Config menu, you can display the programming of the fire panel.
6
Press zone key 6.
This takes you to the View Config menu.
i
Use arrow keys to scroll more quickly through the displayed programming.
Hold the arrow key down to scroll through the menu in increments of 10 steps.
To exit the display, press the ESC key.
RESET
Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980
54 en | System Configuration Conventional Fire Panel
4.7
4.7.1
4.7.2
Controlling Outputs
In the Output Control menu you can activate and deactivate the individual outputs for test purposes. When you exit operating level 3, all activations of the outputs are reset to the normal state again.
Notification appliance 1
7
Press zone key 7.
This takes you to the Output Control menu.
1
ACK RESET
Press zone key 1.
This takes you to the NAC 1 submenu.
– Press the ACK key.
Notification appliance 1 is activated.
– Press the RESET key.
Notification appliance 1 is deactivated.
Notification appliance 2
7
Press zone key 7.
This takes you to the Output Control menu.
2
ACK RESET
Press zone key 2.
This takes you to the NAC 2 submenu.
– Press the ACK key.
Notification appliance 2 is activated.
– Press the RESET key.
Notification appliance 2 is deactivated.
2014.06 | 7.0 | F.01U.172.980
Bosch Sicherheitssysteme GmbH
Conventional Fire Panel System Configuration | en 55
4.7.3
4.7.4
4.7.5
Alarm Relay
7
Press zone key 7.
This takes you to the Output Control menu.
3
ACK RESET
Press zone key 3.
This takes you to the Alarm Relay submenu.
– Press the ACK key.
The alarm relay is activated.
– Press the RESET key.
The alarm relay is deactivated.
Fault Relay
7
Press zone key 7.
This takes you to the Output Control menu.
4
ACK RESET
Press zone key 4.
This takes you to the Fault Relay submenu.
– Press the ACK key.
The fault relay is activated.
– Press the RESET key.
The fault relay is deactivated.
OC/Relay Extension
7
Press zone key 7.
This takes you to the Output Control menu.
5
Press zone key 5.
This takes you to the OC/Relay Ext submenu.
Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980
56 en | System Configuration Conventional Fire Panel
4.7.6
4.8
1
Press zone key 1.
This takes you to the OC/Relay 1 submenu.
ACK
RESET
– Press the ACK key.
The OC/Relay 1 output is activated.
– Press the RESET key.
The OC/Relay 1 output is deactivated.
Continue in the same way for the Open Collector outputs 2 to 8.
Control all outputs
7
Press zone key 7.
This takes you to the Output Control menu.
6
ACK RESET
Press zone key 6.
This takes you to the All submenu.
– Press the ACK key.
All outputs are activated.
– Press the RESET key.
All outputs are deactivated.
Resetting To Delivery State
You can use Config Reset to reset the programming of the fire panel to the default values set when delivered.
Notice!
Resetting the fire panel deletes all of your changes to the programming. The panel is reset to the default programming,
see Default Settings, page 74.
2014.06 | 7.0 | F.01U.172.980
Bosch Sicherheitssysteme GmbH
Conventional Fire Panel System Configuration | en 57
8
Press zone key 8.
This takes you to the Config Reset menu.
ACK RESET
– Press the ACK key.
The fire panel is reset to the delivery state.
– Press the RESET key.
You exit the menu without making changes.
Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980
58 en | Fault Diagnosis
5 Fault Diagnosis
Conventional Fire Panel
Thermal fuse, power supply unit monitoring
The integrated power supply unit is equipped with a thermal fuse. If there is an overload this will switch off the power supply.
After the fuse cools off, it will switch the power on again.
There is a green LED on the power supply unit. This flashes when there is an error in the power supply unit.
Thermal fuse, battery monitoring
There is a thermal fuse on the motherboard that monitors the battery current and protects against reverse polarity.
When the fuse cools off, the battery current is switched on again.
Updating the panel software (firmware) via USB
You can update the panel software using the USB port on the lower left side of the main board. To do this, connect the USB port to your computer and install the programming software supplied on the CD. Follow the on-screen instructions.
2014.06 | 7.0 | F.01U.172.980
Bosch Sicherheitssysteme GmbH
Conventional Fire Panel Technical Data | en 59
6
6.1
Technical Data
Zones
Max. number of detectors in accordance with EN 54‑2
Max. number of detectors per zone in accordance with
EN 54‑2
Max. number of extensions
Prog. inputs
AUX output
Alarm device output
Relay
Electrical Data
Power supply voltage
Current consumption
AC power consumption
Operating voltage
I min
I max, a
I max, b
FPC-500
‑2
FPC-500
‑4
FPC-500
-8
2
64
4
128
8
256
0
1
32
1
1
2
2
2
2
FPC-500
‑2
FPC-500
‑4
FPC-500
-8
230 VAC +10%/-15%, 50–
60 Hz
275 mA 312 mA 375 mA
80 W
21.4 VDC to 29 VDC
70 mA
0.7 A
2.3 A
Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980
60 en | Technical Data Conventional Fire Panel
Zones
–
–
–
AUX
–
–
Voltage
Max. output current
Max. line resistance
– Voltage
– Max. output current
Max. line resistance
Fuse
Notification appliance outputs
– Voltage
– Max. output current
– Max. line resistance
– Fuse
Relay outputs
– Breaking capacity
– Max. line resistance
Transistor outputs
– Breaking capacity
– Max. line resistance
Recommended cable type
Batteries
– Max. inner resistance
– Max. current consumption
– Fuse
End-point voltage
FPC-500
‑2
FPC-500
‑4
FPC-500
-8
20 VDC ±1VDC
100 mA ±5 mA
22.5 Ohm
21 VDC to 29 VDC
500 mA ±10%
22.5 Ohm
0.75 A @ 60 V
21 VDC to 29 VDC
500 mA ±10% per output
22.5 Ohm
0.75 A @ 60 V
1 A @ 30 VDC
22.5 Ohm
No inductive loads
20 mA @ 24 VDC
22.5 Ohm
Unshielded cable, 0.8-mm cable diameter, cable cross section up to 1.5 mm 2
800 mOhm
2.3 A
5 A @ 60 V
21.4 V
2014.06 | 7.0 | F.01U.172.980
Bosch Sicherheitssysteme GmbH
Conventional Fire Panel Technical Data | en 61
6.1.1
Communication parameters
Notification appliances
Standby
– A-
– B+
Alarm state
– A-
– B+
Inputs
FPC-500
‑2
FPC-500
‑4
FPC-500
-8
10 V to 15 V
0 V to 0.5 V
0 V to 1 V
21 V to 29 V
– Alarm resistor 820 ohm ±5%
– EOL Resistor 3900 ohm ±1%
Zones (with resistance combination)
– Alarm resistor
– EOL Resistor
Zones (with EOL modules)
820 ohm ±5%
910 ohm ±5%
No 2-Det Depend: 680 ohm
±5%
3900 ohm ±1%
– Alarm resistor 820 ohm ±5%
910 ohm ±5%
No 2-Det Depend: 680 ohm
±5%
Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980
62 en | Technical Data Conventional Fire Panel
6.2
6.3
Mechanical
Dimensions (H x W x D)
Weight
Housing material
– Front
– Back
Housing color
– Front
– Back
FPC-500
‑2
FPC-500
‑4
FPC-500
-8
351 x 351 x 90 mm
2200 g, without batteries
ABS+PC
ABS-FR
RAL 9003 (Signal White)
PANTONE 10 C (Cool Grey)
Environmental Conditions
FPC-500
‑2
IP 30
FPC-500
‑4
FPC-500
-8
Protection category according to EN 60529
Protection class as per
EN 60950
EMC interference immunity, emissions
EMC interference immunity
Vibrations
Permitted operating temperature
II
EN 61000-6-3
EN 50130-4
EN 60068-2-6
0 °C to +40 °C
Permitted storage temperature -10 °C to +55 °C (14 °F to 131
°F)
Relative humidity Max. 95% non-condensing
2014.06 | 7.0 | F.01U.172.980
Bosch Sicherheitssysteme GmbH
Conventional Fire Panel Technical Data | en 63
6.4
Information as per EN 54‑4, chapter 7.1
a) This is a power supply unit that is installed in the FPC‑500
Fire Panel. It provides power to the device and the connected peripherals and is used to charge the two connectable batteries.
b) Technical data
61 W 1) Recommended power output
2) Power supply
Operating voltage
3) Communication parameters
4) Fuse values
5) Batteries
230 VAC +10%/-15%, 50–60 Hz
26 VDC to 29 VDC
None
3.15 A/250 V
2 x 7.0–7.2 Ah (max.) lead gel battery
2.3 A 6) Max. current consumption
7) Max. battery inner resistance
8) I min
I max, a
I max, b
9) Cable parameters
Battery
Board power supply
230-V power supply
800 mOhm
70 mA
0.7 A
2.3 A
Cable enclosed
Wired ex works
1.5-mm 2 standard cable
Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980
64 en | Technical Data
6.5
Conventional Fire Panel c) The power supply unit is a component of the FPC‑500 Fire
Panel and is supplied preinstalled. No additional installation instructions are necessary.
1) Please refer to the information on environmental conditions in this document.
2) The power supply unit is supplied preinstalled – assembly instructions are not required.
3) For connection instructions, please refer to the FPC‑500 installation instructions.
d) The power supply unit is a component of the FPC‑500 Fire
Panel – there are no additional operating instructions.e) The power supply unit is a component of the FPC‑500 Fire Panel – no operation is required.f) Have maintenance and installation work carried out regularly by trained, qualified personnel. Bosch
Sicherheitssysteme GmbH recommends carrying out a functional and visual check at least once a year. Replace the batteries on a regular basis. Please observe the appropriate requirements stipulated by the local authorities etc.
Options with requirements as per EN
54‑2:1997/A1:2006
The FPC‑500 provides the following options with requirements under EN 54‑2:1997/A1:2006
– Alarm counter
– Test status
– Output for activation of fire alarm devices
– Transmission delay
– Dependency of fire detection status on more than one alarm signal
– Type A dependency
– Type B dependency
2014.06 | 7.0 | F.01U.172.980
Bosch Sicherheitssysteme GmbH
Conventional Fire Panel
7
7.1
Appendix
Appendix | en 65
Brief Overview, Operating Level 1 and 2
Submenu
1 2
Menu operating level 1 and 2 i
1 Current
Events
1 Faults
2 Disablements
3 Test
4 PreAlarm
1 Event History 2 History
2 Test History
3 Alarm Counter -
4 System Info 1 SW Release
-
-
-
3
-
-
-
-
-
-
-
-
2 Operation Days -
Menu operating level 2 – code required i
5 View Config -
6 System Config 1 Date/Time
2 Keypad Tone
-
1 On
2 Off
3 Language 1 1-A - L
2 2-M - Z
Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980
66 en | Appendix Conventional Fire Panel
7.2
Test menu
Submenu
1
Test menu
1 Test MMI
2 Test Zones
2 3
3 Dis/Enable
2014.06 | 7.0 | F.01U.172.980
-
1 Zone 1
2 Zone 2
3 Zone 3
4 Zone 4
5 Zone 5
6 Zone 6
7 Zone 7
8 Zone 8
1 Zones
2 NAC
3 Relays
4 All
- -
- -
- -
- -
- -
- -
- -
- -
- -
1 Zone 1
2 Zone 2
3 Zone 3
4 Zone 4
5 Zone 5
6 Zone 6
7 Zone 7
8 Zone 8
ACK =YES ESC=No
ACK =YES ESC=No
ACK =YES ESC=No
Bosch Sicherheitssysteme GmbH
Conventional Fire Panel Appendix | en 67
7.3
Brief Overview, Operating Level 3
Submenu
1
1 - System Config
1 1 Date/Time
2 Keypad Tone
2 3
3 EOL Devices
4 Zone Reset
5 Aux Power
6 Faults
1 On
2 Off
1 Resistor
- -
- -
- -
2 Only 2W Module - -
3 With 4W Module - -
1 Cut For 1 1 s
2 5 s
2 Stabilize For
3 10 s
4 15 s
5 20 s
1 1 s
2 5 s
3 10 s
1 With Zone
2 With Panel
3 Never
1 Latching
- -
- -
- -
4 15 s
5 20 s
- -
Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980
68 en | Appendix Conventional Fire Panel
Submenu
1
7 Code
8 Test History
2
2 Non Latching
1 Level Code 2
2 Level Code 3
1 Log Enabled
2 Log Disabled
Submenu
1
2 - Delay Config
2
2 1 Day Mode Off 1 Manual
2 Automatic
2 Alarm Verific 1 ACK Within
2014.06 | 7.0 | F.01U.172.980
2 Invest Time
3
3
- -
- -
- -
- -
- -
- -
Off Time: : 17:00
1 30 s
2 60 s
3 90 s
4 120 s
1 1 min Delay
2 2 min Delay
3 3 min Delay
4 4 min Delay
5 5 min Delay
6 6 min Delay
7 7 min Delay
8 8 min Delay
Bosch Sicherheitssysteme GmbH
Conventional Fire Panel Appendix | en 69
Submenu
1
3 Int Alarm Stor
2 Zone 2
Bosch Sicherheitssysteme GmbH
2
3 NAC 1
1 Reset After
4 Power Fault
2 Total Delay
1 No Delay
2 1 min Delay
3 5 min Delay
4 10 min Delay
5 15 min Delay
Submenu
1
3 - Zone Config
3 1 Zone 1
2
- -
- -
- -
3
1 Alert
2 Evacuate
1 1 s
2 5 s
3 10 s
4 15 s
5 20 s
- -
- -
- -
3
1 No Delay
2 Int Alarm Stor
3 Alarm Verific
4 2-Det Depend
5 2-Zone Depend - -
1 No Delay - -
- -
- -
- -
- -
2014.06 | 7.0 | F.01U.172.980
70 en | Appendix Conventional Fire Panel
Submenu
1
3 Zone 3
4 Zone 4
5 Zone 5
6 Zone 6
7 Zone 7
8 Zone 8
4 - Input Config
4 1 Input 1
2 3
No Delay (FPC‑500‑4 /-8)
No Delay (FPC‑500‑4 /-8)
No Delay (FPC‑500‑8)
No Delay (FPC‑500‑8)
No Delay (FPC‑500‑8)
No Delay (FPC‑500‑8)
2 Input 2
Submenu
1
5 - Output Config
5 1 NAC
2
2014.06 | 7.0 | F.01U.172.980
1 Not Used
2 Drill/Evacuate
3 Silence
4 Level 2
5 Reset Panel
6 Ext PS Fault
7 Ext Batt Fault - -
See Input 1 (FPC‑500‑8)
- -
- -
- -
- -
- -
- -
3
1 NAC Zones 1
2 NAC Zones 2
3 Reactive NAC
- -
- -
1 By Other Zone
2 No Reactivate
Bosch Sicherheitssysteme GmbH
Conventional Fire Panel
Submenu
1 2
4 NAC in test
2 Alarm Relay 1 Silencable
2 Drillable
3 OC/Relay Ext 1 OC/Relay 1
2 OC/Relay
3 OC/Relay
4 OC/Relay
5 OC/Relay
6 OC/Relay
7 OC/Relay
8 OC/Relay
Appendix | en 71
3
1 Activation
2 No Activation
1 Silencable
2 Not Silencable
1 Drillable
2 Not Drillable
1 Zone = Alarm
2 Zone Normal
3 Sum Alarm
4 Sum PreAlarm
5 Sum Fault
6 Sum Disable
7 Sum Test
8 Not Used
See OC/Relay 1
See OC/Relay 1
See OC/Relay 1
See OC/Relay 1
See OC/Relay 1
See OC/Relay 1
See OC/Relay 1
6 - View Config
Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980
72 en | Appendix Conventional Fire Panel
Submenu
1
7 - Output Control
7 1 NAC 1
2 NAC 2
3 Alarm Relay
4 Fault Relay
5 OC/Relay Ext
2
3 OC/Relay 3
4 OC/Relay 4
5 OC/Relay 5
6 OC/Relay 6
7 OC/Relay 7
3
ACK =On ESC=Off - -
ACK =On ESC=Off - -
ACK =On ESC=Off - -
ACK =On ESC=Off - -
1 OC/Relay 1 ACK =On ESC=Off
2 OC/Relay 2 ACK =On ESC=Off
ACK =On ESC=Off
ACK =On ESC=Off
ACK =On ESC=Off
ACK =On ESC=Off
ACK =On ESC=Off
6 All
8 - Config Reset
Navigation in the menu
8 OC/Relay 8 ACK =On ESC=Off
ACK =On ESC=Off - -
Press the arrow key to scroll up in the menu.
i
Press the arrow key to scroll down in the menu.
Press the ACK key to confirm your selection.
ACK
2014.06 | 7.0 | F.01U.172.980
Bosch Sicherheitssysteme GmbH
Conventional Fire Panel Appendix | en 73
RESET
RESET
ESC
ESC
1
...
8
Press the ESC key to exit the selection without making a change or to jump up a menu level.
Hold the ESC key down for 2 seconds to jump to the uppermost menu level.
In the menu, each menu item has a number from 1 to 8 preceding it. Use the zone keys to select the desired menu item in the menu.
Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980
74 en | Appendix Conventional Fire Panel
7.4
Default Settings
Menu item
1 System Config
2 Keypad Tone
3 EOL Devices
4 Zone Reset
1 Cut For
2 Stabilize For
5 Aux Power
6 Faults
8 Test History
2 Delay Config
1 Day Mode Off
2 Alarm Verific
1 ACK Within
2 Invest Time
3 NAC 1
3 Int Alarm Stor
3 Zone Config
1 Reset After
4 Power Fault
1 Zone 1
...
4 Input Config
2014.06 | 7.0 | F.01U.172.980
1 min
Evacuate
10 s
No Delay
No Delay
Default setting
On
Resistor
5 s
5 s
With Zone
Latching
Log Enabled
Manual
60 s
Bosch Sicherheitssysteme GmbH
Conventional Fire Panel Appendix | en 75
Menu item
1 Input 1
...
5 Output Config
1 NAC
1 NAC Zones
2 NAC Zones
Default setting
Not Used
All zones
3 Reactive NAC By Other Zone
4 NAC in test
2 Alarm Relay
1 Silencable
2 Drillable
3 OC/Relay Ext
1 OC/Relay 1
All zones
No Activation
Not Silencable
Not Drillable
Zone = Alarm
Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980
76 en | Appendix Conventional Fire Panel
7.5
Event Memory
Message Meaning
Drill/Evacuate A manual alarm has been triggered on the panel.
Zone Alarm Zone # has triggered an alarm.
Zone PreAlarm Zone # has triggered a pre-alarm.
Zone Open
Zone Short
Zone # is interrupted.
Zone # has a short-circuit.
Zone Normal Zone # is in the normal state. (Fault or alarm eliminated)
Zone Disabled Zone # was enabled.
Zone Enabled
Input Open
Input Short
Input Normal
Aux Power
Short
Aux Power
Normal
NAC Open
NAC Short
NAC Normal
NAC Enabled
NAC Disabled
Zone # was enabled.
Input # interrupted.
Input # short-circuit.
Input # normal.
Short-circuit in the AUX power supply
Error in the AUX power supply eliminated.
Notification appliance #, line interrupted
Notification appliance #, short-circuit on line.
Notification appliance # normal. (Fault was eliminated)
Notification appliances re-enabled.
Notification appliances disabled.
2014.06 | 7.0 | F.01U.172.980
Bosch Sicherheitssysteme GmbH
Conventional Fire Panel Appendix | en 77
Message Meaning
Relays Enabled Relays re-enabled.
Relays Disabled Relays disabled.
Battery Fault Fault in the battery power supply.
Battery Restore Battery power supply was restored.
Mains Fault Fault in the 230 V power supply.
Mains Restore 230 V power supply was restored.
Ext PS Fault Fault in external power supply unit.
Ext PS Normal Fault in external power supply unit resolved.
Ext BATT Fault Fault in external battery.
Ext BATT
Normal
Fault in external battery resolved.
Sys Load Fault Current consumption of panel and all connected peripherals is above 3.5 A.
Sys Load
Normal
Current consumption is back in permitted range.
System Fault
Panel boot-up
Reset Panel
Night Mode
Day Mode
Earth Fault
Earth Normal
Level Enter
Level Exit
System fault
Panel has been restarted.
Panel has been reset.
Panel has switched to night mode.
Panel has switched to day mode.
Grounding fault.
Fault in grounding resolved.
Operating level # entered.
Operating level # exited.
Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980
78 en | Appendix
7.6
Conventional Fire Panel
Message
Silenced
Unsilenced
Meaning
An alarm has been silenced.
A silenced alarm has been reactivated.
Test Memory Messages
Message
Zone Start
Zone Test
Zone End
Meaning
Zone # set to test mode.
Zone # successfully tested.
Zone # test mode exited.
2014.06 | 7.0 | F.01U.172.980
Bosch Sicherheitssysteme GmbH
Conventional Fire Panel
Index
A
Alarm relay
B
Buzzer beep
C
Code
Confirmation time
D
Date/Time
Delay
Power supply fault;Power
E
Emergency power
F
Fault handling;Store faults, 37
Index | en 79
H
Housing
I
Intermediate alarm storage
Invest time
M
N
Navigating
Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980
80 en | Index
O
Operating level 3
Outputs
Programming;Transistor outputs:Programming;Relay
P
Programming
Resetting to delivery state, 56
R
Relay outputs;Alarm relay;Fault
S
Submenus
T
Terminal resistance;Terminal element;EOL module;End-Of-
Test log
Conventional Fire Panel
Z
Zone reset
Zone termination
dual-detector dependency;dual-detector
Dual-zone dependency;dual-
Intermediate alarm storage;Intermediate alarm
Manual alarm verification;Manual alarm
Zones
2014.06 | 7.0 | F.01U.172.980
Bosch Sicherheitssysteme GmbH
Bosch Sicherheitssysteme GmbH
Robert-Bosch-Ring 5
85630 Grasbrunn
Germany www.boschsecurity.com
© Bosch Sicherheitssysteme GmbH,
2014
advertisement
Key Features
- Up to 8 monitored detector zones
- Two monitored notification appliance outputs
- Alarm verification
- Intermediate alarm storage
- EN 54-13 compliant (BOSEC certificate TCC 2 - 977),
- Three operating levels
- Emergency power supply using batteries
Frequently Answers and Questions
How many zones can I monitor with the FPC-500-2?
What is the maximum current of the notification appliance outputs?
How do I set the language on the fire panel?
Related manuals
advertisement
Table of contents
- 1 Title Page
- 3 Table of Contents
- 6 Safety Instructions
- 8 System Overview
- 12 Operating Levels
- 13 Installation
- 13 Scope of Delivery
- 13 Installation
- 13 Inserting the Cable
- 14 Opening the Housing
- 15 Installing the Housing
- 16 Mains Supply
- 17 Batteries, 24 V Emergency Power Supply
- 18 Extensions
- 19 Wiring
- 20 Inputs
- 21 Zones
- 23 Aux power
- 24 Notification Appliances
- 25 Relay Outputs
- 26 Extensions
- 26 External power supply
- 29 Initial Start-Up
- 29 Setting the Language
- 29 Setting the Time and Date
- 31 System Configuration
- 34 System Configuration
- 34 Setting the Date/Time
- 34 Buzzer Beep
- 35 EOL Elements
- 35 Resetting Zones
- 37 Aux Power
- 37 Faults
- 38 Level Code
- 39 Test Log
- 39 Configuring Delays
- 40 Deactivating Day Mode
- 40 Alarm Verification
- 42 Intermediate Alarm Storage
- 44 Delay for Mains Fault
- 44 Zone Configuration
- 47 Configuring Inputs
- 48 Input 1
- 49 Input 2 (FPC-500‑8 only)
- 49 Configuring Outputs
- 49 Notification Appliances
- 51 Alarm Relay
- 52 OC/Relay Extensions
- 53 Displaying the Configuration
- 54 Controlling Outputs
- 54 Notification appliance 1
- 54 Notification appliance 2
- 55 Alarm Relay
- 55 Fault Relay
- 55 OC/Relay Extension
- 56 Control all outputs
- 56 Resetting To Delivery State
- 58 Fault Diagnosis
- 59 Technical Data
- 59 Electrical Data
- 61 Communication parameters
- 62 Mechanical
- 62 Environmental Conditions
- 63 Information as per EN 54‑4, chapter 7.1
- 64 Options with requirements as per EN 54‑2:1997/A1:2006
- 65 Appendix
- 65 Brief Overview, Operating Level 1 and 2
- 66 Test menu
- 67 Brief Overview, Operating Level 3
- 74 Default Settings
- 76 Event Memory
- 78 Test Memory Messages
- 79 Index
- 81 Back Page