Bosch FPC-500 -2, -4, -8 fire panel Installation Guide

Bosch FPC-500 -2, -4, -8 fire panel Installation Guide
Add to My manuals

Below you will find brief information for fire panel FPC-500 FPC-500-2, fire panel FPC-500 FPC-500-4, fire panel FPC-500 FPC-500-8. The Bosch fire panel FPC-500 is a versatile system that can be configured to meet the needs of a variety of applications. The fire panel FPC-500 is a conventional fire panel that has been designed and tested according to EN 54-2 and EN 54-4. You can use the FPC-500 series for smaller and larger projects. The panel offers up to eight supervised zones and incorporates two notification appliances that can be used to activate the audible notification appliances and visual notification appliances.

advertisement

Assistant Bot

Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.

Bosch Fire Panel FPC-500 Installation Guide | Manualzz

Conventional Fire Panel

FPC-500-2 / FPC-500-4 / FPC-500-8 en Installation Guide

Conventional Fire Panel Table of Contents | en 3

Table of contents

3.3.7

3.4

3.4.1

3.4.2

4

4.1

4.1.1

4.1.2

4.1.3

4.1.4

3.2.4

3.2.5

3.2.6

3.3

3.3.1

3.3.2

3.3.3

3.3.4

3.3.5

3.3.6

4.1.5

4.1.6

4.1.7

4.1.8

1

2

2.1

3

3.1

3.2

3.2.1

3.2.2

3.2.3

Bosch Sicherheitssysteme GmbH

Safety Instructions

System Overview

Operating Levels

Installation

Scope of Delivery

Installation

Inserting the Cable

Opening the Housing

Installing the Housing

Mains Supply

Batteries, 24 V Emergency Power Supply

Extensions

Wiring

Inputs

Zones

Aux power

Notification Appliances

Relay Outputs

Extensions

External power supply

Initial Start-Up

Setting the Language

Setting the Time and Date

System Configuration

System Configuration

Setting the Date/Time

Buzzer Beep

EOL Elements

Resetting Zones

Aux Power

Faults

Level Code

Test Log

6

34

34

34

35

35

26

29

29

29

31

37

37

38

39

13

13

13

14

15

8

12

13

19

20

21

23

16

17

18

24

25

26

2014.06 | 7.0 | F.01U.172.980

4 en | Table of Contents Conventional Fire Panel

4.5.2

4.5.3

4.6

4.7

4.7.1

4.7.2

4.7.3

4.7.4

4.7.5

4.7.6

4.8

5

4.2

4.2.1

4.2.2

4.2.3

4.2.4

4.3

4.4

4.4.1

4.4.2

4.5

4.5.1

7

7.1

7.2

7.3

7.4

6

6.1

6.1.1

6.2

6.3

6.4

6.5

Configuring Delays

Deactivating Day Mode

Alarm Verification

Intermediate Alarm Storage

Delay for Mains Fault

Zone Configuration

Configuring Inputs

Input 1

Input 2 (FPC-500‑8 only)

Configuring Outputs

Notification Appliances

Alarm Relay

OC/Relay Extensions

Displaying the Configuration

Controlling Outputs

Notification appliance 1

Notification appliance 2

Alarm Relay

Fault Relay

OC/Relay Extension

Control all outputs

Resetting To Delivery State

Fault Diagnosis

Technical Data

Electrical Data

Communication parameters

Mechanical

Environmental Conditions

Information as per EN 54‑4, chapter 7.1

Options with requirements as per EN 54‑2:1997/A1:2006

Appendix

Brief Overview, Operating Level 1 and 2

Test menu

Brief Overview, Operating Level 3

Default Settings

2014.06 | 7.0 | F.01U.172.980

Bosch Sicherheitssysteme GmbH

54

55

55

55

56

51

52

53

54

54

56

58

59

59

61

62

62

63

64

44

44

47

48

49

49

49

39

40

40

42

65

65

66

67

74

Conventional Fire Panel

7.5

7.6

Event Memory

Test Memory Messages

Index

Table of Contents | en 5

76

78

79

Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980

6 en | Safety Instructions Conventional Fire Panel

1

!

Safety Instructions

Danger!

The fire panel may only be operated with the housing closed because of the danger of an electric shock.

Danger!

Only perform installation work when the panel has no voltage.

There is a danger of an electric shock.

Caution!

Installation may only be performed by authorized qualified personnel in order to ensure that the system is not damaged and operates properly.

Notice!

Note local regulations when connecting to 230 V power supplies.

Notice!

Please observe the country-specific regulations and guidelines during planning, installation and programming of the fire panel.

Notice!

In line with EN 54-13 (BOSEC certificate TCC 2 - 977), each conventional line must be terminated with EOL modules for the operation of fire detection systems.

The AUX power supply must also be terminated with EOL modules when using four-wire detectors.

2014.06 | 7.0 | F.01U.172.980

Bosch Sicherheitssysteme GmbH

Conventional Fire Panel Safety Instructions | en 7

Notice!

The fire panel has been designed for operation in closed rooms.

Please note the permissible environmental conditions in the technical specifications.

Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980

8 en | System Overview Conventional Fire Panel

2 System Overview

A LARM

P re-Alarm

F ault

System Fault

Earth Fault

Power Fault

NAC Fault / Disabled

Notification Appliance Silent

Day Mode

1 2 3 4 5 6 7 8

2

EVAC i

A CK

ESC

RESET Power

1

1

2

3

4

4

LED display

LCD display with zone numbers

Zone keys and zone status LEDs

Operating panel

3

7

8

5

6

3

4

1

2

2014.06 | 7.0 | F.01U.172.980

Bosch Sicherheitssysteme GmbH

Conventional Fire Panel System Overview | en 9

Inputs

– Zones

– Prog. inputs

Outputs

– Prog. AUX (500 mA)

– Alarm device, 500 mA each

– Relay

Extensions

– Open collector (20 mA)

– Relay (via OC)

LCD, 2 x 16 characters

FPC-500-

2

FPC-500-

4

2

1

4

1

1

2

2

FPC-500-

8

8

2 no 1 x 4

Yes

2 x 4

Z1

.

.

.

Z8

IN1

IN2

ALARM RLY

FAULT RLY

OC (0, 4, 8)

AUX

24 V DC

230

VAC

Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980

10 en | System Overview Conventional Fire Panel

Conventional detectors

Conventional manual call point

Visual or audible notification appliances

Z1 ... Z8

IN

Conventional zones 1 to 8

(max. 2 on FPC-500-2, max. 4 on FPC-500-4)

Inputs (max. 1 on FPC‑500‑2 and FPC‑500‑4, max. 2 on FPC‑500‑8)

Alarm relay

ALARM RLY

Fault relay

FAULT RLY

OC

AUX 24 VDC

Transistor output for extension cards

(0 on FPC‑500‑2, 4 on FPC‑500‑4, 8 on

FPC‑500‑8)

AUX power supply

Features

– Alarm verification: The user is prompted to verify the alarm.

– Intermediate alarm storage: an alarm triggered by an automatic detector is reset automatically after 20 seconds

(adjustable) by the panel. If there is an additional alarm within 10 minutes in this zone, the notification appliances are enabled. Otherwise the pre-alarm is reset automatically.

– Dual-zone dependency on neighboring zones.

2014.06 | 7.0 | F.01U.172.980

Bosch Sicherheitssysteme GmbH

Conventional Fire Panel System Overview | en 11

– Dual-detector dependency for detectors in a zone.

– Alarm counter for 999 alarms.

– Event memory for 1000 entries.

– Three operating levels, two of them protected with freely selected code.

– Up to 8 monitored detector zones depending on panel version.

– Up to 2 monitored inputs available depending on panel version.

– One alarm and one fault relay.

– Up to 8 additional transistor or relay outputs, freely programmable, depending on panel version.

– Quick and easy programming using the keypad and LCD display.

– Easy operation for the end user.

– Two monitored notification appliance outputs.

– EN 54-13 (BOSEC certificate TCC 2 - 977) compliant system by using EOL modules.

– Power supply via power supply unit with thermal fuse.

– Emergency power supply using batteries, up to 7.2 Ah, reverse polarity protected.

– Removable quick guide for the user on the panel.

Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980

12 en | System Overview Conventional Fire Panel

2.1

Operating Levels

This fire panel has three operating levels. You can only perform certain actions depending on operating level.

Level 1 – Display information

– Read out event memory

– Display faults and deactivations

– Perform display test

Level 2 – Change language and time/date

– Switch key tones on/off

– Put zones in test mode and take zones out of test mode

– Switch off/on zones, notification appliances, relay and transistor outputs

– Trigger evacuations

– Reset panel

– Switch between day/night mode

– All actions of level 1

Level 3 – All settings for installing and programming the system.

Code inputs are necessary for accessing level 2 and 3.

2014.06 | 7.0 | F.01U.172.980

Bosch Sicherheitssysteme GmbH

Conventional Fire Panel Installation | en 13

3

3.1

3.2

3.2.1

!

Installation

Scope of Delivery

The fire panel packaging contains the following components:

– Fire panelFPC‑500‑2/FPC‑500‑4/FPC‑500‑8

– EOL resistors for zones and inputs

– Battery cable set

– Cable ties for strain relief on power supply feeder

– Labeling strips for zones and LEDs

– Quick Installation Guide

– Quick Operation Guide

– CD

– Two plastic foam blocks for securing the batteries

Installation

Notice!

Install the fire panel in a location easily accessible to emergency response teams (e.g. fire department).

Note permissible environmental conditions.

Install the fire panel at a height above the ground that permits convenient operation by the user and easy reading of the LCD display.

Inserting the Cable

Route the necessary cables for zones, inputs and outputs, as well as the power supply, etc., and carefully punch out the cable entries needed for this.

Warning!

Electrostatic discharge (ESD)! Electronic components could become damaged. Ground yourself using a wrist strap or take other suitable measures.

Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980

14 en | Installation Conventional Fire Panel

Remove the PC board if necessary. This is secured in the housing with a grounding screw and snap-fit hook.

For cable entry on the upper side of the housing, use the preformed round holes. For more stable insertion, M 20 x 1.5 screw joints (PG13.5) can be used.

The cable entries on the rear are intended for direct cable entry of flush mounted cables.

3.2.2

Opening the Housing

Remove the cover of the fire panel. Loosen both screws on the underside of the housing, lift up the cover approx. 20° and remove it.

2014.06 | 7.0 | F.01U.172.980

Bosch Sicherheitssysteme GmbH

Conventional Fire Panel Installation | en 15

3.2.3

Installing the Housing

Use the panel housing to draw drill holes at the desired location on the wall (arrows in figure below). As an option, you can use the mounting dimensions indicated on the back of the housing.

Ensure that the housing is aligned horizontally and draw on the holes using the built-in spirit level in the upper left corner. The dimensions can be taken from the drilling jib on the rear of the housing. Drill the holes.

Guide the cables routed under plaster through the punched out cable ducts on the rear of the housing into the housing. Mount the housing to the wall using screws. Make sure that cables are not pinched.

Then guide the cables routed on plaster through the cable entries to the upper side of the housing.

Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980

16 en | Installation Conventional Fire Panel

3.2.4

Mains Supply

The fire panel requires a 230 V mains supply for the power supply. Route the power supply so that the line does not cross or touch the signal line.

Use the left M 20 x 1.5 screw joint (PG13.5) on the upper side of the panel for the 230 V mains supply.

Notice!

Note local regulations when connecting to 230 V power supplies.

Wire up the 230 V power supply to the screw clamp provided on the power supply unit board. Use a cable tie to ensure strain relief of the power supply feeder in the housing above the power supply unit.

Danger!

Only perform installation work when the panel has no voltage.

There is a danger of an electric shock.

230 VAC

50 - 60 Hz

2014.06 | 7.0 | F.01U.172.980

N L

Bosch Sicherheitssysteme GmbH

Conventional Fire Panel Installation | en 17

3.2.5

Batteries, 24 V Emergency Power Supply

You can use two 12 V batteries with maximum 7.2 Ah each in the housing as emergency power supply.

The batteries are connected in series. If the mains power fails, they are used to ensure interruption-free power supply of the fire panel and the components fed by them.

Notice!

The fire panel can also only be started with the batteries if the power supply is disconnected.

After you have placed the batteries in the housing, secure them using the plastic foam blocks provided.

Position the plastic foam blocks in between the top of the batteries and the housing.

There are different emergency current back-up times depending on the battery capacity used and the current consumption of the components connected to the panel. You can calculate this using the battery calculator included on the CD.

After troubleshooting a mains fault and operating the fire panel via emergency current, the power supply unit switches back to mains operation automatically. The batteries are charged again automatically.

Notice!

Note the polarity of the batteries.

If the batteries are connected with the polarity reversed, the thermal fuse on the main board of the fire panel reacts.

Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980

18 en | Installation Conventional Fire Panel

BAT

- +

3.2.6

Secure the batteries with the plastic foam blocks provided so that they cannot move.

Extensions

Notice!

Note that the maximum line resistance for transistor outputs is

22.5 Ohm.

The extensions are connected to the left side of the main board.

Simply connect the board to the plugs. Make sure that the plug engages correctly.

2014.06 | 7.0 | F.01U.172.980

Bosch Sicherheitssysteme GmbH

Conventional Fire Panel Installation | en 19

There is a groove on the top of the extensions. Make sure that the board has been correctly installed.

Notice!

A maximum of two extensions can be connected:

FPC-500‑2: No extension can be connected

FPC-500‑4: One extension can be connected

FPC-500‑8: Two extensions can be connected

3.3

Wiring

External components such as zones, notification appliances, inputs, etc. are wired to screw terminals attached to the upper side of the board.

1 2 3 4 5

.

No Meaning

1 Inputs

2 Zones

3 Aux power supply

4 Notification appliance

5 Alarm and fault relay

Bosch Sicherheitssysteme GmbH

FPC‑500

-2

FPC‑500

-4

FPC‑500

-8

1 1 2

2 8 4

1

2

1/1

2014.06 | 7.0 | F.01U.172.980

20 en | Installation Conventional Fire Panel

Notice!

The screw terminals are designed for a cable diameter of

0.8 mm and for cable cross sections of up to 1.5 mm 2 .

The fire panel is designed for unshielded cable. If you do use shielded cable, only connect the cable shielding to the earth bar on one side above the power supply unit.

Terminal resistances

The zones of the fire panels must be terminated. Use either resistors or in case of EN 54-13 (BOSEC certificate TCC 2 - 977) the EOL modules.

Notice!

Only use resistors with a maximum 1% tolerance.

The 3.9 kOhm resistors are supplied.

3.3.1

Inputs

820Ω ± 5%

The fire panel offers two control inputs. You can assign different

functions to these depending on programming (see Configuring

Inputs, page 47).

The connection terminals IN1 and IN2 are available.

Notice!

Note that the maximum line resistance for inputs is 22.5 ohm.

Use 820 Ohm ±5% resistors for the alarm resistance (not included in scope of delivery).

2014.06 | 7.0 | F.01U.172.980

Bosch Sicherheitssysteme GmbH

Conventional Fire Panel Installation | en 21

Notice!

Only use buttons (no locking element) if you have programmed inputs as Drill/Evacuate, Silence, or Reset Panel.

Access levels as per EN 54‑2 must be observed.

3.3.2

Zones

Notice!

Do not connect the zone- with any power+ like for example:

AUX power, external power supply or batteries for emergency power supply.

b+ ab+ a-

EOL

3,9kΩ

EOL

EN 54‑13 (BOSEC certificate TCC 2 - 977)

Each zone must be completed with a terminal element.

You can either use a 3.9 kΩ ± 1% resistor or EOL modules for an

EN 54-13 (BOSEC certificate TCC 2 - 977) compliant termination.

Unused zones must also be terminated with a terminal element.

Mixing different terminal elements is not allowed.

Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980

22 en | Installation Conventional Fire Panel

Notice!

Note that the maximum line resistance for conventional zones is

22.5 Ohm.

The voltage of the zones is 20 VDC ±1 V.

The maximum current of the zones is 100 mA ±5 mA.

Notice!

Observe local regulations for the maximum number of detectors in a zone.

When using the FLM-320-EOL4W Module, use the battery calculator included on the CD.

Notice!

The last zone of the fire panel supports the use of 4-wire detectors.

The fire panel does not support dual-detector dependency with

4-wire detectors.

Please use permissible external power supply units depending on power consumption.

Notice!

Activating a manual call point in a zone programmed as "No

Delay" triggers an immediate alarm.

Notice!

Only use manual call points in zones which are programmed as

No Delay.

2014.06 | 7.0 | F.01U.172.980

Bosch Sicherheitssysteme GmbH

Conventional Fire Panel Installation | en 23

3.3.3

Aux power

Non-EN54-13

3,9kΩ b+ a-

+

4W

-

EOL b+ a-

+

-

4W

FLM-320-EOL4W

EN54-13 (BOSEC certificate TCC 2 - 977)

The fire panel allows you to use 4-wire (4W) elements on the last zone. These must be supplied with power by the auxiliary power supply or an external power source. Both the zone and the auxiliary power must be terminated by a terminal element.

For EN 54-13 (BOSEC certificate TCC 2 - 977) compliant connection of 4‑wire elements, the AUX and zone lines must be routed in separate cables.

You can either use a 3.9 kΩ ±1% resistor or EOL modules for

EN 54-13 (BOSEC certificate TCC 2 - 977) compliant termination.

Program the reset behavior of the auxiliary power as described

in Aux Power, page 37.

Notice!

Note that the maximum line resistance for the auxiliary power is

22.5 Ohm.

Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980

24 en | Installation

3.3.4

Notification Appliances

Conventional Fire Panel

A- B+ A- B+

OUT IN

NAC1

A- B+ A- B+

OUT IN

NAC2

Notice!

Each notification appliance output provides connected notification appliances with a maximum current of 500 mA at

24 VDC. The permissible voltage range of the output is 21–

29 VDC.

Notice!

Note that the maximum line resistance for notification appliances is 22.5 Ohm.

The fire panel offers you two notification appliance circuit lines that can be used to activate the audible notification appliances and visual notification appliances. When there is a fire alarm, the notification appliance circuit lines are activated depending on programming.

2014.06 | 7.0 | F.01U.172.980

Bosch Sicherheitssysteme GmbH

Conventional Fire Panel Installation | en 25

Notice!

Connect the notification appliances to the terminals NAC1 and/or NAC2. This connection is EN 54‑13 (BOSEC certificate

TCC 2 - 977) compliant.

3.3.5

Relay Outputs

NO C NC

ALARM

NO C NC

FAULT

Notice!

The fault relay is activated in a normal state. It is opened in the event of a fault.

The fire panel has two relay outputs. The relays work as potential-free change-over contacts.

The alarm relay is activated by every fire alarm.

Notice!

A transmission device must be installed in the immediate vicinity (without a space) of the FPC‑500‑x.

The connecting line between the fire panel and the transmission device must not be exposed, as it is not monitored.

Notice!

Both relay outputs "ALARM" and "FAULT" can switch a maximum of 1 A @ 30 VDC each.

Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980

26 en | Installation Conventional Fire Panel

Notice!

Note that the maximum line resistance for the relay outputs is

22.5 Ohm.

3.3.6

Extensions

The extension modules offer four connections activated by transistors or relay.

Notice!

The relay outputs can switch a maximum of 1 A @ 30 VDC each.

The transistor outputs switch a maximum of 20 mA @ 24 VDC each. Inductive loads are not permitted.

3.3.7

External power supply

You can use the FPP-5000 as an external power source for the

FPC-500 Fire Panel.

Notice!

Note that the FPP‑5000 housing must be installed in the direct vicinity (without a space) of the FPC‑500‑x. The connecting line between the FPP-5000 and the transmission device must not be exposed, as it is not monitored.

FPC‑500‑2 and FPC‑500‑4

Wire the FPP-5000 as shown in FPC‑500‑2 and FPC‑500‑4, page

26.

Program input 1 to Ext PS Fault (see Input 1, page 48). The

relay is not included in the scope of delivery.

2014.06 | 7.0 | F.01U.172.980

Bosch Sicherheitssysteme GmbH

Conventional Fire Panel

Relais

24VDC/1A

NC C NO

3k9

1 2

MAIN POWER

MAIN POWER

TROUBLE

BATTERY 1

TROUBLE

BATTERY 2

TROUBLE

MAIN BAT1 BAT2 FAULT

Installation | en 27

12 V 12 V FPP--5000

FPC‑500‑8

Wire the FPP-5000 as shown in FPC‑500‑8, page 27.

Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980

28 en | Installation Conventional Fire Panel

Program input 1 to Ext PS Fault and input 2 to Ext Batt Fault

(see Input 1, page 48). The relays are not included in the scope

of delivery.

+ - + -

24V 24V

1 2

MAIN POWER

MAIN POWER

TROUBLE

BATTERY 1

TROUBLE

BATTERY 2

TROUBLE

MAIN BAT1 BAT2 FAULT

Relais

24VDC/1A

Relais

24VDC/1A

NC C NO NC C NO

3k9 3k9

12 V 12 V FPP--5000

2014.06 | 7.0 | F.01U.172.980

Bosch Sicherheitssysteme GmbH

Conventional Fire Panel Installation | en 29

3.4

3.4.1

Initial Start-Up

As soon as the fire panel is connected to the power for the first time, an LED and buzzer test begins. This is completed the first time a key is pressed.

In the initial start-up, you must make the following basic settings:

– Set the language

– Set the time and date

Setting the Language

To set the language, proceed as follows:

Use the arrow keys to set the desired language.

i

3.4.2

ACK

Confirm your selection in the menu with the ACK key.

Setting the Time and Date

Set the current time and date. The current time and date are important for functions such as

– Event memory and

– Automatic switching to night mode.

Use the arrow keys to set the current day.

i

ACK

Confirm your selection in the menu with the ACK key.

Repeat this procedure to set the correct values for the month, year and time.

Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980

30 en | Installation Conventional Fire Panel

Notice!

Summer and winter time settings are not made automatically.

Make these settings manually.

If there is a total power failure, you must make the settings for the date and time again.

2014.06 | 7.0 | F.01U.172.980

Bosch Sicherheitssysteme GmbH

Conventional Fire Panel System Configuration | en 31

4 System Configuration

To be able to perform the actions in operating level 3, you will need a code you can enter with the zone keys.

Notice!

The following codes are programmed in delivery status:

Operating level 2: 1234

Operating level 3: 3333

The basic settings can be found in Default Settings, page 74.

Calling up operating level 3

Press the "Code input" key.

You will be prompted to enter a code.

C O D E /

Enter the code with zone keys 1 to 8.

!

You are in the programming menu of the system.

Caution!

In operating level 3, the fire panel is not operational. None of the inputs and outputs are monitored.

Automatic exit of level 3

If you are in level 3 and no key has been pressed for 10 minutes, the system will exit level 3 automatically.

One minute before exiting level 3, a pulse tone of the internal buzzer indicates the time. The time up to the automatic exit of level 3 is displayed in the LCD display.

Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980

32 en | System Configuration Conventional Fire Panel

Exiting operating level 3

Notice!

When you exit operating level 3, the fire panel automatically switches to night mode.

If you are in operating level 3, proceed as follows.

RESET

ACK RESET

Press the RESET key.

You exit operating level 3 when you are at the top level of the menu. The configuration is stored and the inputs and outputs are activated.

– Press the ACK key to exit operating level 3.

– If you do not want to exit operating level 3, press the RESET key.

Menu

Operating level 3 of the fire panel offers you the following setting options:

– 1-System Config

– 2-Delay Config

– 3-Zone Config

– 4-Input Config

– 5-Output Config

– 6-View Config

– 7-Output Control

– 8-Config Reset

Notice!

The structure and description of menus of operating levels 1 and 2 can be found in the operating instructions.

2014.06 | 7.0 | F.01U.172.980

Bosch Sicherheitssysteme GmbH

Conventional Fire Panel System Configuration | en 33

Notice!

The menus are described in these instructions as follows:

A hyphen between the number and the menu description "-" shows you that it is a menu item with a submenu.

An equals sign between the number and the menu description

"=" represents a set value.

A space between the number and the menu description " " is a value that can be set.

Preset values are always shown in bold.

Operation

You have different options for navigating in the menu of the fire panel.

Using autoscrolling

ACK

The menus scroll automatically every 2.5 seconds to the next menu item. If you would like to select the menu item currently shown, simply confirm with the

ACK key.

Navigating with the zone keys

1

...

8

In the menu, each menu item has a number from 1 to 8 preceding it. Use the zone keys to select the desired menu item in the menu. The desired menu item does not have to be shown in the display.

Navigating with the arrow keys i

Use the arrow keys to navigate in the menu.

Using the arrow keys stops autoscrolling in the menus.

ACK

Confirm your selection in the menu with the ACK key.

Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980

34 en | System Configuration Conventional Fire Panel

4.1

4.1.1

4.1.2

Exiting submenus

RESET

ESC In the menu and in the submenus, you can jump to a higher level or cancel the setting using the RESET

(ESC) key.

Hold the RESET (ESC) key down for 2 seconds to jump to the uppermost level.

System Configuration

In the System Config menu, you can specify basic settings for your fire panel.

Setting the Date/Time

1

Press zone key 1. This takes you to the System

Config menu.

1

Press zone key 1.

You can now set the date and time.

ACK

To save the currently displayed value, press the ACK key.

Repeat the steps to set the month, year, hour, and minute.

Buzzer Beep

1

Press zone key 1. This takes you to the System

Config menu.

2

1

...

2

Press zone key 2.

This takes you to the Keypad Tone submenu.

Press zone keys 1 or 2:

– 1=On (default setting)

– 2 Off

2014.06 | 7.0 | F.01U.172.980

Bosch Sicherheitssysteme GmbH

Conventional Fire Panel System Configuration | en 35

4.1.3

4.1.4

EOL Elements

You can use EOL Devices to specify whether you want to use resistors or EOL modules for zone termination.

1

Press zone key 1. This takes you to the System

Config menu.

3

1

...

3

Press zone key 3.

This takes you to the EOL Devices submenu.

Press zone keys 1 to 3:

– 1=Resistor (default setting, not EN 54‑13 compliant)

– 2 Only 2W Module

– 3 With 4W Module

1 2 3 4 5 6 7 8

CS TH: mA

If you select With 4W Module, you must specify the threshold for the creeping short-circuit.

You can calculate this using the battery calculator included on the CD.

Resetting Zones

In this menu, you can specify the delay times for resetting zones. You can specify how long the zones can be disconnected from the power and how long the stabilization time of the detector should last. This setting is used for the zone test, restarting the fire panel and intermediate alarm storage.

Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980

36 en | System Configuration Conventional Fire Panel

Cut For

1

Press zone key 1. This takes you to the System

Config menu.

4

1

Press zone key 4.

This takes you to the Zone Reset submenu.

Press zone key 1.

This takes you to the Cut For submenu.

1

...

5

Press zone keys 1 to 5.

– 1 1s

– 2=5s (default setting)

– 3 10s

– 4 15s

– 5 20s

Stabilize for

1

Press zone key 1. This takes you to the System

Config menu.

4

2

1

...

5

Press zone key 4.

This takes you to the Zone Reset submenu.

Press zone key 2.

This takes you to the Stabilize For submenu.

Press zone keys 1 to 5.

– 1 1s

– 2=5s (default setting)

– 3 10s

– 4 15s

– 5 20s

2014.06 | 7.0 | F.01U.172.980

Bosch Sicherheitssysteme GmbH

Conventional Fire Panel System Configuration | en 37

4.1.5

4.1.6

Aux Power

The With Zone setting relates to the last zone of the fire panel.

If the last zone is reset after a pre-alarm or alarm, the AUX power supply is reset simultaneously.

The With Panel setting also resets the power supply each time the fire panel is reset.

If you select Never, the auxiliary power supply is never reset.

1

Press zone key 1. This takes you to the System

Config menu.

5

1

...

3

Press zone key 5.

This takes you to the Aux Power submenu.

Press zone keys 1 to 3.

– 1=With Zone (default setting)

– 2 With Panel

– 3 Never

Faults

The Faults setting specifies whether faults on the fire panel are to be displayed until the fire panel is manually reset.

Notice!

This setting does not apply to system faults.

System faults can only be reset manually.

Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980

38 en | System Configuration Conventional Fire Panel

4.1.7

1

Press zone key 1. This takes you to the System

Config menu.

6

1

...

2

Press zone key 6.

This takes you to the Faults submenu.

Press zone key 1 or 2.

– 1=Latching (default setting)

– 2 Non Latching

Level Code

In the Level Code menu, you can specify new codes for operating levels 2 and 3. The new code must be 4 characters long and is displayed during entry.

Notice!

The following codes are programmed in delivery status:

Operating level 2: 1234

Operating level 3: 3333

1

Press zone key 1. This takes you to the System

Config menu.

7

1

...

2

Press zone key 7.

This takes you to the Code submenu.

– 1- Level 2 Code

– 2- Level 3 Code

1 2 3 4 5 6 7 8

Level 2 Code

Set to: ____

You are prompted to enter the new code.

2014.06 | 7.0 | F.01U.172.980

Bosch Sicherheitssysteme GmbH

Conventional Fire Panel System Configuration | en 39

1 2 3 4 5 6 7 8

Level 2 Code

Confirm: ____

You then have to confirm the new code by entering it again.

The procedure for changing the code for operating level 3 is exactly the same.

Notice!

If you have forgotten your code, contact your Bosch partner.

4.1.8

4.2

Test Log

You can decide whether or not the fire panel creates a Test

History.

1

Press zone key 1. This takes you to the System

Config menu.

8

1

...

2

Press zone key 8.

This takes you to the Test History submenu.

Use zone keys 1 or 2.

– 1=Log Enabled (default setting)

– 2 Log Disabled

Configuring Delays

In the Delay Config menu, you can program different delay times for different zone programs, outputs and fault types.

2

Press zone key 2. This takes you to the Delay Config menu.

Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980

40 en | System Configuration Conventional Fire Panel

4.2.1

Deactivating Day Mode

Specify whether you want day mode (zones with alarm verification start a verification time in the event of an alarm) to be exited manually by the user or automatically at a defined time. You can program the time in this submenu.

Notice!

Day mode must always be started manually; it is not possible to configure an automatic start.

2

Press zone key 2. This takes you to the Delay Config menu.

1

Press zone key 1.

This takes you to the Day Mode Off submenu.

1

...

2

Use zone keys 1 or 2.

– 1=Manual (default setting)

– 2 Automatic

If you set Day Mode Off to Automatic, you must program the changeover time from day to night mode.

1 2 3 4 5 6 7 8

Off Time: :17:00

Confirm with

Set the time with the arrow keys and confirm using the ACK key.

Alarm Verification 4.2.2

Notice!

This setting only applies to zones that are programmed as alarm verification.

Note that the delay settings are only effective in day mode. In night mode, the alarm is triggered immediately.

2014.06 | 7.0 | F.01U.172.980

Bosch Sicherheitssysteme GmbH

Conventional Fire Panel System Configuration | en 41

In the Alarm Verific menu, you set the times within which the user must confirm a triggered alarm (ACK Within). The Invest

Time submenu specifies the time available to the user to enter the alarm triggering area before the notification appliance is activated. You can also use NAC 1 to specify whether:

Alert switches NAC 1 on immediately in the event of an alarm. NAC 1 is then switched off during the verification time and switched on again after the verification time.

– With Evacuate, NAC 1 is switched off during the delay time and only activated during the actual alarm.

Time setting for alarm acknowledgement

2

Press zone key 2. This takes you to the Delay Config menu.

2

1

Press zone key 2.

This takes you to the Alarm Verific submenu.

Press zone key 1.

This takes you to the ACK Within submenu.

1

...

4

Use the zone keys to set the respective delay.

– 1 30 s

2= 60 s (default setting)

– 3 90 s

– 4 120s

Time setting for verification time

2

Press zone key 2. This takes you to the Delay Config menu.

2

Press zone key 2.

This takes you to the Alarm Verific submenu.

Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980

42 en | System Configuration Conventional Fire Panel

4.2.3

2

1

...

8

Press zone key 2.

This takes you to the Invest Time submenu.

Use the zone keys to set the respective delay.

1 1 min (default setting)

– 2 2 min

– 3 3 min

– 4 4 min

– 5 5 min

– 6 6 min

– 7 7 min

– 8 8 min

Notification appliance 1

2

Press zone key 2. This takes you to the Delay Config menu.

2

3

1

...

2

Press zone key 2.

This takes you to the Alarm Verific submenu.

Press zone key 3.

This takes you to the NAC 1 submenu.

Press zone key 1 or 2.

– 1 Alert

– 2=Evacuate (default setting)

Intermediate Alarm Storage

Intermediate alarm storage is an automatic procedure designed to rule out false alarms as far as possible. The entire procedure lasts up to 60 seconds:

– Ten seconds after a fire is detected, the zone is reset

(setting Reset After).

The zone is reset for x seconds (setting Cut For, Cut For ,

page 36).

2014.06 | 7.0 | F.01U.172.980

Bosch Sicherheitssysteme GmbH

Conventional Fire Panel System Configuration | en 43

!

– There is an x second stabilization phase for the elements in

the zone (setting Stabilize For, Stabilize for, page 36).

Caution!

Detectors of the FCP-320 series must not be used with intermediate alarm storage because the detector calculates a new standby value after the reset. This can generate an increased alarm threshold. If there is a fire, this can thus delay the trigger of an alarm.

Before using automatic fire detectors, find out from the manufacturer whether they can be used for intermediate alarm storage.

In this menu you can change the pre-set time values indicated above.

Reset after

2

Press zone key 2. This takes you to the Delay Config menu.

3

1

1

...

4

Press zone key 3.

This takes you to the Int Alarm Stor submenu.

Press zone key 1.

This takes you to the Reset After submenu.

Use the zone keys to set the respective delay.

– 1 1 s

– 2 5 s

3= 10 s (default setting)

– 4 15s

– 5 20 s

Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980

44 en | System Configuration Conventional Fire Panel

4.2.4

4.3

Display total delay

2

Press zone key 2. This takes you to the Delay Config menu.

3

Press zone key 3.

This takes you to the Int Alarm Stor submenu.

2

Press zone key 2.

This takes you to the Total Delay submenu.

The total delay is displayed.

Delay for Mains Fault

The Power Fault menu option enables you to specify the delay after which an error message indicating a power supply failure

(mains or battery) is to be displayed. If the fault is resolved before the time set here, it is no longer displayed.

2

Press zone key 2. This takes you to the Delay Config menu.

4

1

...

5

Press zone key 4.

This takes you to the Power Fault submenu.

Use the zone keys to set the respective delay.

– 1=No Delay (default setting)

– 2 1 min

– 3 5 min

– 4 10 min

– 5 15 min

Zone Configuration

In the Zone Config menu, you can program the individual zones of the fire panel. Depending on the panel, you can set 2, 4 or 8 zones. The following zone types are available:

2014.06 | 7.0 | F.01U.172.980

Bosch Sicherheitssysteme GmbH

Conventional Fire Panel System Configuration | en 45

No delay (No Delay)

A zone programmed as No Delay triggers an alarm immediately.

If you are using manual call points, they must be set as No

Delay.

Notice!

Only use manual call points in zones which are programmed as

No Delay.

Int Alarm StorIntermediate alarm storage

A zone triggers an alarm. This is evaluated by the fire panel as a pre-alarm and is not displayed. The zone is reset automatically.

If it triggers an alarm again, the panel switches immediately to alarm. If a second alarm is not triggered, the fire panel reverts to its normal state after 10 minutes.

Alarm verification (Alarm Verific)

Notice!

Note that the delay is only effective in day mode. In night mode, the alarm is triggered immediately.

Notice!

If the fire panel automatically switches to night mode during an ongoing verification time, an alarm is triggered immediately.

Notice!

If during the verification time in one zone an alarm is triggered in another zone, which is programmed as alarm verification, an alarm is triggered immediately.

If a zone programmed as alarm verification detects an alarm, it triggers an alarm, which is delayed.

Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980

46 en | System Configuration Conventional Fire Panel

!

The LCD display prompts you to verify the alarm. You must confirm the alarm within a pre-defined time using the ACK key.

After this pre-defined time the verification time begins. Within this time you must investigate the alarm triggering area and, if necessary, trigger an alarm.

During the verification time, the panel can be reset without triggering an alarm. After the verification time has expired, the panel goes into the alarm state.

Dual-detector dependency (2-Det Depend)

Caution!

Detectors with connected remote displays must not be used with the dual-detector dependency.

Dual-detector dependency only works with detectors that use an alarm resistance of 820 ohm +/- 5% or 910 ohm +/- 5%.

Otherwise, in the event of a fire, proper functioning of the fire panel cannot be guaranteed.

Notice!

The fire panel does not support dual-detector dependency with

4-wire detectors.

The zone must contain more than one detector. If one of the detectors in the zone triggers, this is evaluated as a pre-alarm. If an additional detector in the same zone is activated, an alarm is triggered. The panel automatically attempts to reset the prealarm every 10 minutes. However, this is not possible if a detector remains active. This procedure is repeated until no more detectors are active and the panel returns to its normal state, or until a second detector becomes active, thus elevating the pre-alarm to an alarm.

Dual-zone dependency (2-Zone Depend)

Applies to adjacent zones, for example zones 1 and 2.

If a zone detects an alarm, this is evaluated as a pre-alarm. An alarm is only triggered when the second zone detects an alarm.

2014.06 | 7.0 | F.01U.172.980

Bosch Sicherheitssysteme GmbH

Conventional Fire Panel

4.4

System Configuration | en 47

Possible zone dependencies:

– FPC‑500-2: 1&2

– FPC‑500‑4: 1&2, 3&4

– FPC‑500‑8: 1&2, 3&4, 5&6, 7&8

If you set a zone to dual-zone dependency, the other associated zone is also changed automatically.

Zones 1 to 8

3

Press zone key 3. This takes you to the Zone Config menu.

1

Press zone key 1.

This takes you to the zone 1 submenu.

1

...

6

Use the zone keys to program the zone.

– 1=No Delay (default setting)

– 2 Int Alarm Stor

– 3 Alarm Verific

– 4 2-Det Depend

– 5 2-Zone Depend

Zones 2 to 8 are pre-programmed in the same way as zone 1.

You can change the settings as with zone 1.

Notice!

Zones 3 and 4 are only available on the FPC‑500‑4 and

FPC‑500‑8 panels. Zones 5–8 are only available on the

FPC‑500‑8.

Configuring Inputs

In the Input Config menu, you can program the behavior of the inputs.

Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980

48 en | System Configuration Conventional Fire Panel

Notice!

Only use buttons (no locking element) if you have programmed inputs as Drill/Evacuate, Silence, or Reset Panel.

Access levels as per EN 54‑2 must be observed.

Notice!

Depending on the panel, there is one input on the FPC‑500‑2 and FPC‑500‑4, and two inputs on the FPC‑500‑8.

4.4.1

4

Press zone key 4.

This takes you to the Input Config menu.

Input 1

4

Press zone key 4.

This takes you to the Input Config menu.

1

1

...

7

Press zone key 1.

This takes you to the Input 1 submenu.

Use the zone keys to set the programming for input

1.

– 1= Not Used (default setting)

– 2 Drill/Evacuate

– 3 Silence

– 4 Level 2

– 5 Reset Panel

– 6 Ext PS Fault

– 7 Ext Batt Fault

Notice!

You do not have to confirm the input functions on the panel.

Thus use a key switch if possible to activate inputs.

2014.06 | 7.0 | F.01U.172.980

Bosch Sicherheitssysteme GmbH

Conventional Fire Panel System Configuration | en 49

4.4.2

4.5

4.5.1

!

Input 2 (FPC-500‑8 only)

4

Press zone key 4.

This takes you to the Input Config menu.

2

Press zone key 2.

This takes you to the Input 2 submenu.

Additional settings correspond to those for Input 1.

Configuring Outputs

In the Output Config menu, you can program the behavior of the individual fire panel outputs.

Notification Appliances

In the NAC submenu, you specify the behavior of the notification appliances. You can use NAC Zones to assign the notification appliances to particular zones. Reactive NAC specifies whether silenced notification appliances are reactivated by a new alarm in another zone. You can use NAC in test to specify whether the notification appliances are activated for 15 seconds when a zone test is performed.

Caution!

When assigning the zones to notification appliances, make sure that each zone of the fire panel is assigned to at least one notification appliance.

Zones not assigned do not trigger any alarm signaling via the notification appliance if there is a fire.

Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980

50 en | System Configuration Conventional Fire Panel

Notification appliance 1 zone assignment

5

Press zone key 5.

This takes you to the Output Config menu.

1

1

1

...

8

Press zone key 1.

This takes you to the NAC submenu.

Press zone key 1.

This takes you to the NAC Zones submenu.

Use the zone keys to select the corresponding zones whose alarm you want to activate notification appliance 1.

You can select multiple zones. If you press the zone key again, the selection is cancelled.

Confirm your selection.

ACK

Notification appliance 2 zone assignment

See "Notification appliance 1 zone assignment", Notification

appliance 1 zone assignment, page 50.

Reactivating notification appliances

5

Press zone key 5.

This takes you to the Output Config menu.

1

3

1

...

2

Press zone key 1.

This takes you to the NAC submenu.

Press zone key 3.

This takes you to the Reactive NAC submenu.

Press zone keys 1 or 2.

1=By Other Zone (default setting)

2 No Reactivate

2014.06 | 7.0 | F.01U.172.980

Bosch Sicherheitssysteme GmbH

Conventional Fire Panel System Configuration | en 51

4.5.2

Notification appliance behavior in zone test

5

Press zone key 5.

This takes you to the Output Config menu.

1

4

1

...

2

Press zone key 1.

This takes you to the NAC submenu.

Press zone key 4.

This takes you to the NAC in test submenu.

Press zone keys 1 or 2.

1 Activation

2=No Activation (default setting)

Alarm Relay

In the Alarm Relay submenu, you can specify the properties of the alarm relay. These include the Silencable and Drillable settings. You can use Silencable to specify whether the relay can be silenced manually. Drillable specifies whether the alarm relay is also activated during a manual alarm (Drill/Evac).

Alarm relay can be muted

5

Press zone key 5.

This takes you to the Output Config menu.

2

1

1

...

2

Press zone key 2.

This takes you to the Alarm Relay submenu.

Press zone key 1.

This takes you to the Silencable submenu.

Press zone keys 1 or 2.

1 Silencable

2=Not Silencable (default setting)

Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980

52 en | System Configuration Conventional Fire Panel

4.5.3

Alarm relay follows manual alarm

5

Press zone key 5.

This takes you to the Output Config menu.

2

2

1

...

2

Press zone key 2.

This takes you to the Alarm Relay submenu.

Press zone key 2.

This takes you to the Drillable submenu.

Press zone keys 1 or 2.

1 Drillable

2= Not Drillable (default setting)

OC/Relay Extensions

In the OC/Relay Ext menu, you can individually set the properties of all OC/Relay outputs. The possible settings for the

OC/Relay outputs 2 to 8 correspond to those for the first OC/

Relay . The following settings are possible:

Zone = Alarm: The output is activated if the zone triggers an alarm. Here zone 1 is assigned to output 1, etc.

Zone Normal: If the zone is not in a normal state, the output is activated. Assignment: zone 1 to output 1 etc.

Sum Alarm: When the fire panel is in an alarm state, this output is activated regardless of the zone.

Sum PreAlarm: When the fire panel is in a pre-alarm state, this output is activated regardless of the zone.

Sum Fault: This output is activated if there is a fault.

Sum Disable: If a fire panel element is disabled, this output is activated (zones, notification appliances, relays).

Sum Test: This output is activated if a zone in the fire panel is in test mode.

Not Used: The output is not used.

2014.06 | 7.0 | F.01U.172.980

Bosch Sicherheitssysteme GmbH

Conventional Fire Panel

4.6

System Configuration | en 53

5

Press zone key 5.

This takes you to the Output Config menu.

3

Press zone key 3.

This takes you to the OC/Relay Ext submenu.

Press zone key 1 to choose Open Collector 1.

1

1

...

8

Use the zone keys to make the corresponding setting.

– 1=Zone = Alarm (default setting)

– 2 Zone Normal

– 3 Sum Alarm

– 4 Sum PreAlarm

– 5 Sum Fault

– 6 Sum Disable

– 7 Sum Test

– 8 Not Used

The procedure for OC/Relay 2 to 8 is the same.

Displaying the Configuration

In the View Config menu, you can display the programming of the fire panel.

6

Press zone key 6.

This takes you to the View Config menu.

i

Use arrow keys to scroll more quickly through the displayed programming.

Hold the arrow key down to scroll through the menu in increments of 10 steps.

To exit the display, press the ESC key.

RESET

Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980

54 en | System Configuration Conventional Fire Panel

4.7

4.7.1

4.7.2

Controlling Outputs

In the Output Control menu you can activate and deactivate the individual outputs for test purposes. When you exit operating level 3, all activations of the outputs are reset to the normal state again.

Notification appliance 1

7

Press zone key 7.

This takes you to the Output Control menu.

1

ACK RESET

Press zone key 1.

This takes you to the NAC 1 submenu.

– Press the ACK key.

Notification appliance 1 is activated.

– Press the RESET key.

Notification appliance 1 is deactivated.

Notification appliance 2

7

Press zone key 7.

This takes you to the Output Control menu.

2

ACK RESET

Press zone key 2.

This takes you to the NAC 2 submenu.

– Press the ACK key.

Notification appliance 2 is activated.

– Press the RESET key.

Notification appliance 2 is deactivated.

2014.06 | 7.0 | F.01U.172.980

Bosch Sicherheitssysteme GmbH

Conventional Fire Panel System Configuration | en 55

4.7.3

4.7.4

4.7.5

Alarm Relay

7

Press zone key 7.

This takes you to the Output Control menu.

3

ACK RESET

Press zone key 3.

This takes you to the Alarm Relay submenu.

– Press the ACK key.

The alarm relay is activated.

– Press the RESET key.

The alarm relay is deactivated.

Fault Relay

7

Press zone key 7.

This takes you to the Output Control menu.

4

ACK RESET

Press zone key 4.

This takes you to the Fault Relay submenu.

– Press the ACK key.

The fault relay is activated.

– Press the RESET key.

The fault relay is deactivated.

OC/Relay Extension

7

Press zone key 7.

This takes you to the Output Control menu.

5

Press zone key 5.

This takes you to the OC/Relay Ext submenu.

Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980

56 en | System Configuration Conventional Fire Panel

4.7.6

4.8

1

Press zone key 1.

This takes you to the OC/Relay 1 submenu.

ACK

RESET

– Press the ACK key.

The OC/Relay 1 output is activated.

– Press the RESET key.

The OC/Relay 1 output is deactivated.

Continue in the same way for the Open Collector outputs 2 to 8.

Control all outputs

7

Press zone key 7.

This takes you to the Output Control menu.

6

ACK RESET

Press zone key 6.

This takes you to the All submenu.

– Press the ACK key.

All outputs are activated.

– Press the RESET key.

All outputs are deactivated.

Resetting To Delivery State

You can use Config Reset to reset the programming of the fire panel to the default values set when delivered.

Notice!

Resetting the fire panel deletes all of your changes to the programming. The panel is reset to the default programming,

see Default Settings, page 74.

2014.06 | 7.0 | F.01U.172.980

Bosch Sicherheitssysteme GmbH

Conventional Fire Panel System Configuration | en 57

8

Press zone key 8.

This takes you to the Config Reset menu.

ACK RESET

– Press the ACK key.

The fire panel is reset to the delivery state.

– Press the RESET key.

You exit the menu without making changes.

Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980

58 en | Fault Diagnosis

5 Fault Diagnosis

Conventional Fire Panel

Thermal fuse, power supply unit monitoring

The integrated power supply unit is equipped with a thermal fuse. If there is an overload this will switch off the power supply.

After the fuse cools off, it will switch the power on again.

There is a green LED on the power supply unit. This flashes when there is an error in the power supply unit.

Thermal fuse, battery monitoring

There is a thermal fuse on the motherboard that monitors the battery current and protects against reverse polarity.

When the fuse cools off, the battery current is switched on again.

Updating the panel software (firmware) via USB

You can update the panel software using the USB port on the lower left side of the main board. To do this, connect the USB port to your computer and install the programming software supplied on the CD. Follow the on-screen instructions.

2014.06 | 7.0 | F.01U.172.980

Bosch Sicherheitssysteme GmbH

Conventional Fire Panel Technical Data | en 59

6

6.1

Technical Data

Zones

Max. number of detectors in accordance with EN 54‑2

Max. number of detectors per zone in accordance with

EN 54‑2

Max. number of extensions

Prog. inputs

AUX output

Alarm device output

Relay

Electrical Data

Power supply voltage

Current consumption

AC power consumption

Operating voltage

I min

I max, a

I max, b

FPC-500

‑2

FPC-500

‑4

FPC-500

-8

2

64

4

128

8

256

0

1

32

1

1

2

2

2

2

FPC-500

‑2

FPC-500

‑4

FPC-500

-8

230 VAC +10%/-15%, 50–

60 Hz

275 mA 312 mA 375 mA

80 W

21.4 VDC to 29 VDC

70 mA

0.7 A

2.3 A

Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980

60 en | Technical Data Conventional Fire Panel

Zones

AUX

Voltage

Max. output current

Max. line resistance

– Voltage

– Max. output current

Max. line resistance

Fuse

Notification appliance outputs

– Voltage

– Max. output current

– Max. line resistance

– Fuse

Relay outputs

– Breaking capacity

– Max. line resistance

Transistor outputs

– Breaking capacity

– Max. line resistance

Recommended cable type

Batteries

– Max. inner resistance

– Max. current consumption

– Fuse

End-point voltage

FPC-500

‑2

FPC-500

‑4

FPC-500

-8

20 VDC ±1VDC

100 mA ±5 mA

22.5 Ohm

21 VDC to 29 VDC

500 mA ±10%

22.5 Ohm

0.75 A @ 60 V

21 VDC to 29 VDC

500 mA ±10% per output

22.5 Ohm

0.75 A @ 60 V

1 A @ 30 VDC

22.5 Ohm

No inductive loads

20 mA @ 24 VDC

22.5 Ohm

Unshielded cable, 0.8-mm cable diameter, cable cross section up to 1.5 mm 2

800 mOhm

2.3 A

5 A @ 60 V

21.4 V

2014.06 | 7.0 | F.01U.172.980

Bosch Sicherheitssysteme GmbH

Conventional Fire Panel Technical Data | en 61

6.1.1

Communication parameters

Notification appliances

Standby

– A-

– B+

Alarm state

– A-

– B+

Inputs

FPC-500

‑2

FPC-500

‑4

FPC-500

-8

10 V to 15 V

0 V to 0.5 V

0 V to 1 V

21 V to 29 V

– Alarm resistor 820 ohm ±5%

– EOL Resistor 3900 ohm ±1%

Zones (with resistance combination)

– Alarm resistor

– EOL Resistor

Zones (with EOL modules)

820 ohm ±5%

910 ohm ±5%

No 2-Det Depend: 680 ohm

±5%

3900 ohm ±1%

– Alarm resistor 820 ohm ±5%

910 ohm ±5%

No 2-Det Depend: 680 ohm

±5%

Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980

62 en | Technical Data Conventional Fire Panel

6.2

6.3

Mechanical

Dimensions (H x W x D)

Weight

Housing material

– Front

– Back

Housing color

– Front

– Back

FPC-500

‑2

FPC-500

‑4

FPC-500

-8

351 x 351 x 90 mm

2200 g, without batteries

ABS+PC

ABS-FR

RAL 9003 (Signal White)

PANTONE 10 C (Cool Grey)

Environmental Conditions

FPC-500

‑2

IP 30

FPC-500

‑4

FPC-500

-8

Protection category according to EN 60529

Protection class as per

EN 60950

EMC interference immunity, emissions

EMC interference immunity

Vibrations

Permitted operating temperature

II

EN 61000-6-3

EN 50130-4

EN 60068-2-6

0 °C to +40 °C

Permitted storage temperature -10 °C to +55 °C (14 °F to 131

°F)

Relative humidity Max. 95% non-condensing

2014.06 | 7.0 | F.01U.172.980

Bosch Sicherheitssysteme GmbH

Conventional Fire Panel Technical Data | en 63

6.4

Information as per EN 54‑4, chapter 7.1

a) This is a power supply unit that is installed in the FPC‑500

Fire Panel. It provides power to the device and the connected peripherals and is used to charge the two connectable batteries.

b) Technical data

61 W 1) Recommended power output

2) Power supply

Operating voltage

3) Communication parameters

4) Fuse values

5) Batteries

230 VAC +10%/-15%, 50–60 Hz

26 VDC to 29 VDC

None

3.15 A/250 V

2 x 7.0–7.2 Ah (max.) lead gel battery

2.3 A 6) Max. current consumption

7) Max. battery inner resistance

8) I min

I max, a

I max, b

9) Cable parameters

Battery

Board power supply

230-V power supply

800 mOhm

70 mA

0.7 A

2.3 A

Cable enclosed

Wired ex works

1.5-mm 2 standard cable

Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980

64 en | Technical Data

6.5

Conventional Fire Panel c) The power supply unit is a component of the FPC‑500 Fire

Panel and is supplied preinstalled. No additional installation instructions are necessary.

1) Please refer to the information on environmental conditions in this document.

2) The power supply unit is supplied preinstalled – assembly instructions are not required.

3) For connection instructions, please refer to the FPC‑500 installation instructions.

d) The power supply unit is a component of the FPC‑500 Fire

Panel – there are no additional operating instructions.e) The power supply unit is a component of the FPC‑500 Fire Panel – no operation is required.f) Have maintenance and installation work carried out regularly by trained, qualified personnel. Bosch

Sicherheitssysteme GmbH recommends carrying out a functional and visual check at least once a year. Replace the batteries on a regular basis. Please observe the appropriate requirements stipulated by the local authorities etc.

Options with requirements as per EN

54‑2:1997/A1:2006

The FPC‑500 provides the following options with requirements under EN 54‑2:1997/A1:2006

– Alarm counter

– Test status

– Output for activation of fire alarm devices

– Transmission delay

– Dependency of fire detection status on more than one alarm signal

– Type A dependency

– Type B dependency

2014.06 | 7.0 | F.01U.172.980

Bosch Sicherheitssysteme GmbH

Conventional Fire Panel

7

7.1

Appendix

Appendix | en 65

Brief Overview, Operating Level 1 and 2

Submenu

1 2

Menu operating level 1 and 2 i

1 Current

Events

1 Faults

2 Disablements

3 Test

4 PreAlarm

1 Event History 2 History

2 Test History

3 Alarm Counter -

4 System Info 1 SW Release

-

-

-

3

-

-

-

-

-

-

-

-

2 Operation Days -

Menu operating level 2 – code required i

5 View Config -

6 System Config 1 Date/Time

2 Keypad Tone

-

1 On

2 Off

3 Language 1 1-A - L

2 2-M - Z

Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980

66 en | Appendix Conventional Fire Panel

7.2

Test menu

Submenu

1

Test menu

1 Test MMI

2 Test Zones

2 3

3 Dis/Enable

2014.06 | 7.0 | F.01U.172.980

-

1 Zone 1

2 Zone 2

3 Zone 3

4 Zone 4

5 Zone 5

6 Zone 6

7 Zone 7

8 Zone 8

1 Zones

2 NAC

3 Relays

4 All

- -

- -

- -

- -

- -

- -

- -

- -

- -

1 Zone 1

2 Zone 2

3 Zone 3

4 Zone 4

5 Zone 5

6 Zone 6

7 Zone 7

8 Zone 8

ACK =YES ESC=No

ACK =YES ESC=No

ACK =YES ESC=No

Bosch Sicherheitssysteme GmbH

Conventional Fire Panel Appendix | en 67

7.3

Brief Overview, Operating Level 3

Submenu

1

1 - System Config

1 1 Date/Time

2 Keypad Tone

2 3

3 EOL Devices

4 Zone Reset

5 Aux Power

6 Faults

1 On

2 Off

1 Resistor

- -

- -

- -

2 Only 2W Module - -

3 With 4W Module - -

1 Cut For 1 1 s

2 5 s

2 Stabilize For

3 10 s

4 15 s

5 20 s

1 1 s

2 5 s

3 10 s

1 With Zone

2 With Panel

3 Never

1 Latching

- -

- -

- -

4 15 s

5 20 s

- -

Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980

68 en | Appendix Conventional Fire Panel

Submenu

1

7 Code

8 Test History

2

2 Non Latching

1 Level Code 2

2 Level Code 3

1 Log Enabled

2 Log Disabled

Submenu

1

2 - Delay Config

2

2 1 Day Mode Off 1 Manual

2 Automatic

2 Alarm Verific 1 ACK Within

2014.06 | 7.0 | F.01U.172.980

2 Invest Time

3

3

- -

- -

- -

- -

- -

- -

Off Time: : 17:00

1 30 s

2 60 s

3 90 s

4 120 s

1 1 min Delay

2 2 min Delay

3 3 min Delay

4 4 min Delay

5 5 min Delay

6 6 min Delay

7 7 min Delay

8 8 min Delay

Bosch Sicherheitssysteme GmbH

Conventional Fire Panel Appendix | en 69

Submenu

1

3 Int Alarm Stor

2 Zone 2

Bosch Sicherheitssysteme GmbH

2

3 NAC 1

1 Reset After

4 Power Fault

2 Total Delay

1 No Delay

2 1 min Delay

3 5 min Delay

4 10 min Delay

5 15 min Delay

Submenu

1

3 - Zone Config

3 1 Zone 1

2

- -

- -

- -

3

1 Alert

2 Evacuate

1 1 s

2 5 s

3 10 s

4 15 s

5 20 s

- -

- -

- -

3

1 No Delay

2 Int Alarm Stor

3 Alarm Verific

4 2-Det Depend

5 2-Zone Depend - -

1 No Delay - -

- -

- -

- -

- -

2014.06 | 7.0 | F.01U.172.980

70 en | Appendix Conventional Fire Panel

Submenu

1

3 Zone 3

4 Zone 4

5 Zone 5

6 Zone 6

7 Zone 7

8 Zone 8

4 - Input Config

4 1 Input 1

2 3

No Delay (FPC‑500‑4 /-8)

No Delay (FPC‑500‑4 /-8)

No Delay (FPC‑500‑8)

No Delay (FPC‑500‑8)

No Delay (FPC‑500‑8)

No Delay (FPC‑500‑8)

2 Input 2

Submenu

1

5 - Output Config

5 1 NAC

2

2014.06 | 7.0 | F.01U.172.980

1 Not Used

2 Drill/Evacuate

3 Silence

4 Level 2

5 Reset Panel

6 Ext PS Fault

7 Ext Batt Fault - -

See Input 1 (FPC‑500‑8)

- -

- -

- -

- -

- -

- -

3

1 NAC Zones 1

2 NAC Zones 2

3 Reactive NAC

- -

- -

1 By Other Zone

2 No Reactivate

Bosch Sicherheitssysteme GmbH

Conventional Fire Panel

Submenu

1 2

4 NAC in test

2 Alarm Relay 1 Silencable

2 Drillable

3 OC/Relay Ext 1 OC/Relay 1

2 OC/Relay

3 OC/Relay

4 OC/Relay

5 OC/Relay

6 OC/Relay

7 OC/Relay

8 OC/Relay

Appendix | en 71

3

1 Activation

2 No Activation

1 Silencable

2 Not Silencable

1 Drillable

2 Not Drillable

1 Zone = Alarm

2 Zone Normal

3 Sum Alarm

4 Sum PreAlarm

5 Sum Fault

6 Sum Disable

7 Sum Test

8 Not Used

See OC/Relay 1

See OC/Relay 1

See OC/Relay 1

See OC/Relay 1

See OC/Relay 1

See OC/Relay 1

See OC/Relay 1

6 - View Config

Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980

72 en | Appendix Conventional Fire Panel

Submenu

1

7 - Output Control

7 1 NAC 1

2 NAC 2

3 Alarm Relay

4 Fault Relay

5 OC/Relay Ext

2

3 OC/Relay 3

4 OC/Relay 4

5 OC/Relay 5

6 OC/Relay 6

7 OC/Relay 7

3

ACK =On ESC=Off - -

ACK =On ESC=Off - -

ACK =On ESC=Off - -

ACK =On ESC=Off - -

1 OC/Relay 1 ACK =On ESC=Off

2 OC/Relay 2 ACK =On ESC=Off

ACK =On ESC=Off

ACK =On ESC=Off

ACK =On ESC=Off

ACK =On ESC=Off

ACK =On ESC=Off

6 All

8 - Config Reset

Navigation in the menu

8 OC/Relay 8 ACK =On ESC=Off

ACK =On ESC=Off - -

Press the arrow key to scroll up in the menu.

i

Press the arrow key to scroll down in the menu.

Press the ACK key to confirm your selection.

ACK

2014.06 | 7.0 | F.01U.172.980

Bosch Sicherheitssysteme GmbH

Conventional Fire Panel Appendix | en 73

RESET

RESET

ESC

ESC

1

...

8

Press the ESC key to exit the selection without making a change or to jump up a menu level.

Hold the ESC key down for 2 seconds to jump to the uppermost menu level.

In the menu, each menu item has a number from 1 to 8 preceding it. Use the zone keys to select the desired menu item in the menu.

Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980

74 en | Appendix Conventional Fire Panel

7.4

Default Settings

Menu item

1 System Config

2 Keypad Tone

3 EOL Devices

4 Zone Reset

1 Cut For

2 Stabilize For

5 Aux Power

6 Faults

8 Test History

2 Delay Config

1 Day Mode Off

2 Alarm Verific

1 ACK Within

2 Invest Time

3 NAC 1

3 Int Alarm Stor

3 Zone Config

1 Reset After

4 Power Fault

1 Zone 1

...

4 Input Config

2014.06 | 7.0 | F.01U.172.980

1 min

Evacuate

10 s

No Delay

No Delay

Default setting

On

Resistor

5 s

5 s

With Zone

Latching

Log Enabled

Manual

60 s

Bosch Sicherheitssysteme GmbH

Conventional Fire Panel Appendix | en 75

Menu item

1 Input 1

...

5 Output Config

1 NAC

1 NAC Zones

2 NAC Zones

Default setting

Not Used

All zones

3 Reactive NAC By Other Zone

4 NAC in test

2 Alarm Relay

1 Silencable

2 Drillable

3 OC/Relay Ext

1 OC/Relay 1

All zones

No Activation

Not Silencable

Not Drillable

Zone = Alarm

Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980

76 en | Appendix Conventional Fire Panel

7.5

Event Memory

Message Meaning

Drill/Evacuate A manual alarm has been triggered on the panel.

Zone Alarm Zone # has triggered an alarm.

Zone PreAlarm Zone # has triggered a pre-alarm.

Zone Open

Zone Short

Zone # is interrupted.

Zone # has a short-circuit.

Zone Normal Zone # is in the normal state. (Fault or alarm eliminated)

Zone Disabled Zone # was enabled.

Zone Enabled

Input Open

Input Short

Input Normal

Aux Power

Short

Aux Power

Normal

NAC Open

NAC Short

NAC Normal

NAC Enabled

NAC Disabled

Zone # was enabled.

Input # interrupted.

Input # short-circuit.

Input # normal.

Short-circuit in the AUX power supply

Error in the AUX power supply eliminated.

Notification appliance #, line interrupted

Notification appliance #, short-circuit on line.

Notification appliance # normal. (Fault was eliminated)

Notification appliances re-enabled.

Notification appliances disabled.

2014.06 | 7.0 | F.01U.172.980

Bosch Sicherheitssysteme GmbH

Conventional Fire Panel Appendix | en 77

Message Meaning

Relays Enabled Relays re-enabled.

Relays Disabled Relays disabled.

Battery Fault Fault in the battery power supply.

Battery Restore Battery power supply was restored.

Mains Fault Fault in the 230 V power supply.

Mains Restore 230 V power supply was restored.

Ext PS Fault Fault in external power supply unit.

Ext PS Normal Fault in external power supply unit resolved.

Ext BATT Fault Fault in external battery.

Ext BATT

Normal

Fault in external battery resolved.

Sys Load Fault Current consumption of panel and all connected peripherals is above 3.5 A.

Sys Load

Normal

Current consumption is back in permitted range.

System Fault

Panel boot-up

Reset Panel

Night Mode

Day Mode

Earth Fault

Earth Normal

Level Enter

Level Exit

System fault

Panel has been restarted.

Panel has been reset.

Panel has switched to night mode.

Panel has switched to day mode.

Grounding fault.

Fault in grounding resolved.

Operating level # entered.

Operating level # exited.

Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980

78 en | Appendix

7.6

Conventional Fire Panel

Message

Silenced

Unsilenced

Meaning

An alarm has been silenced.

A silenced alarm has been reactivated.

Test Memory Messages

Message

Zone Start

Zone Test

Zone End

Meaning

Zone # set to test mode.

Zone # successfully tested.

Zone # test mode exited.

2014.06 | 7.0 | F.01U.172.980

Bosch Sicherheitssysteme GmbH

Conventional Fire Panel

Index

A

Access model, 12

Alarm relay

Programming, 51

AUX;Reset settings, 37

B

Buzzer beep

Setting, 34

C

Cable entries, 13

Code

Change;Password:Change, 38

Code;Password, 31

Confirmation time

Setting, 41

D

Date/Time

Setting, 34

Default settings, 74

Delay

Power supply fault;Power

supply:Fault delay, 44

Delay settings, 39

E

Emergency power

supply;Batteries, 17

Extensions, 18

F

Fault handling;Store faults, 37

Index | en 79

H

Housing

Installing, 15

Open, 14

I

Input, 20

Programming a function, 48

Installation location, 13

Intermediate alarm storage

Setting, 42

Invest time

Setting, 41

M

Mains supply, 16

N

Navigating

Arrow keys, 33

Navigation, 72

Zone keys, 33, 73

Notification appliance, 24

Assignment to zones, 50

Behavior in zone test, 51

Specifying reactivation, 50

Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980

80 en | Index

O

Operating level 3

Automatic exit, 31

Calling up, 31

Exiting, 32

Operation, 33

Outputs

Activation for testing, 54

Programming, 49

Programming;Transistor outputs:Programming;Relay

outputs:Programming, 52

P

Programming

Resetting to delivery state, 56

R

Relay outputs;Alarm relay;Fault

relay, 25

S

Screw terminals, 19

Submenus

Exiting, 34

T

Terminal resistance;Terminal element;EOL module;End-Of-

Line module, 20, 21

Test log

Setting, 39

Conventional Fire Panel

Z

Zone reset

Disconnection duration, 36

Setting times, 35

Stabilization time, 36

Zone termination

Setting, 35

Zone types, 44

dual-detector dependency;dual-detector

dependency, 46

Dual-zone dependency;dual-

zone dependency, 46

Intermediate alarm storage;Intermediate alarm

storage, 45

Manual alarm verification;Manual alarm

verification, 45

No delay;No delay, 45

Zones

Specify zone type, 47

2014.06 | 7.0 | F.01U.172.980

Bosch Sicherheitssysteme GmbH

Bosch Sicherheitssysteme GmbH

Robert-Bosch-Ring 5

85630 Grasbrunn

Germany www.boschsecurity.com

© Bosch Sicherheitssysteme GmbH,

2014

advertisement

Key Features

  • Up to 8 monitored detector zones
  • Two monitored notification appliance outputs
  • Alarm verification
  • Intermediate alarm storage
  • EN 54-13 compliant (BOSEC certificate TCC 2 - 977),
  • Three operating levels
  • Emergency power supply using batteries

Frequently Answers and Questions

How many zones can I monitor with the FPC-500-2?
The FPC-500-2 can monitor up to 2 zones.
What is the maximum current of the notification appliance outputs?
Each notification appliance output provides connected notification appliances with a maximum current of 500 mA at 24 VDC.
How do I set the language on the fire panel?
In the initial start-up, you must set the language using the arrow keys and confirm your selection with the ACK key.

Related manuals

Download PDF

advertisement

Table of contents