ENG-Manual-TU-RS485-ETH-V3

TU-RS485-ETH IO DL
TU-RS485-ETH ANL
Intelligent Converter RS485/Ethernet, Datalog and Web Server unit
0003
CD Automation S.r.l.
Via Picasso 34/36 - 20025 – Legnano (MI) – ITALY
Tel +39 0331 577479 – Fax +39 0331 579479
E-Mail: info@cdautomation.com - WEB:
www.cdautomation.com
TU RS485/ETH serie
CD Automation srl
1 Sommario
2
PRODUCT CODE ........................................................................................................ 4
3
HARDWARE INSTALLATION....................................................................................... 4
4
Software Configurator................................................................................................... 5
4.1
SOFTWARE INSTALLATION ....................................................................................................................5
4.1.1
MINIMUM SYSTEM REQUIREMENTS .................................................................................................5
4.1.2
PROCEDURE .......................................................................................................................................5
4.2
DevTU WINDOW....................................................................................................................................6
4.3
TERMINOLOGY.......................................................................................................................................7
4.4
PROJECT MANAGMENT.........................................................................................................................8
4.4.1
START A NEW PROJECT ......................................................................................................................8
4.4.2
SAVE AND LOAD A PROJECT...............................................................................................................8
4.4.3
CLOSE A PROJECT...............................................................................................................................8
4.5
WORK WITH THE FUNCTION BLOCKS....................................................................................................9
4.5.1
INSERT A FUNCTION BLOCK ...............................................................................................................9
4.5.2
REMOVE A FUNCTION BLOCK ............................................................................................................9
4.5.3
MODIFY A FUNCTION BLOCK .............................................................................................................9
4.5.4
MOVE A FUNCTION BLOCK ................................................................................................................9
4.5.5
ZOOM.................................................................................................................................................9
4.5.6
STRUCTURE OF A FUNCTION BLOCK............................................................................................... 10
4.5.7
COPY A FUNCTION BLOCK............................................................................................................... 10
4.6
COMPILE AND ERROR CHECK ............................................................................................................. 10
4.7
INTERNAL REGISTERS.......................................................................................................................... 11
4.8
TYPE OF DATA FORMAT...................................................................................................................... 11
4.9
MAPPING Register.............................................................................................................................. 12
4.10
TU-RS485/ETH IO DL and TU-RS485/ETH ANL ................................................................................ 13
4.10.1
SYSTEM REGISTERS OVERVIEW ................................................................................................... 13
4.10.1.1
FIRMWARE............................................................................................................................... 13
4.10.1.2
NAME....................................................................................................................................... 13
4.10.1.3
PORT 1 Baud Rate .................................................................................................................... 13
4.10.1.4
NODE ID ................................................................................................................................... 13
4.10.1.5
PORT 1 Timeout RX.................................................................................................................. 13
4.10.1.6
DIGITAL INPUTS........................................................................................................................ 13
4.10.1.7
DIGITAL OUTPUTS .................................................................................................................... 13
4.10.1.8
SYSTEM FLAGS ......................................................................................................................... 14
4.10.1.9
PC (Program Counter).............................................................................................................. 14
4.10.1.10 STATUS..................................................................................................................................... 14
1
TU RS485/ETH serie
CD Automation srl
4.10.1.11 COM ERRORS........................................................................................................................... 14
4.10.1.12 GATEWAY MASK ...................................................................................................................... 14
4.10.1.13 PORT 0 Settings ....................................................................................................................... 14
4.10.1.14 TIMERS Enable......................................................................................................................... 15
4.10.1.15 RTC (Real Time Clock/Calendar) .............................................................................................. 15
4.11
5
TU-RS485/ETH ANL only .................................................................................................................... 16
4.11.1.1
Analogue Input measure ......................................................................................................... 16
4.11.1.2
Analogue output values........................................................................................................... 16
4.11.1.3
FREQ [x] ................................................................................................................................... 16
4.11.1.4
COUNTER [x] ............................................................................................................................ 16
4.11.1.5
Input type programming (%R34) ............................................................................................. 17
4.12
FUNCTION LIST ................................................................................................................................... 18
4.13
INSERTION OF TABLES ........................................................................................................................ 28
4.14
SEARCHING OF THE DEVICES CONNECTED......................................................................................... 29
4.15
CONNECTING TO THE CONTROLLER................................................................................................... 29
4.16
DOWNLOAD THE PROGRAM .............................................................................................................. 30
4.17
DEBUG MODE ..................................................................................................................................... 30
4.18
RELEASE MODE................................................................................................................................... 31
4.19
INIT MODE .......................................................................................................................................... 31
4.20
SCHEDULER (Data Logger) .................................................................................................................. 32
4.21
INSERTION OF VARIABLES .................................................................................................................. 33
WEBSEVER ................................................................................................................34
5.1
Operating environment...................................................................................................................... 34
5.2
User Management and security ......................................................................................................... 34
5.3
Log-in .................................................................................................................................................. 35
5.4
Navigation........................................................................................................................................... 35
5.5
Maintenance....................................................................................................................................... 36
5.5.1
5.5.1.1
Network ................................................................................................................................... 37
5.5.1.2
E-Mail....................................................................................................................................... 38
5.5.1.3
DDNS........................................................................................................................................ 40
5.5.1.4
Advanced ................................................................................................................................. 41
5.5.2
5.6
6
Information ..................................................................................................................................... 37
Users ............................................................................................................................................... 41
Download ........................................................................................................................................... 42
TROUBLERSHOOTING..............................................................................................44
6.1
ERROR MESSAGES IN THE LOG WINDOW AND IN THE STATUS BAR ................................................. 44
6.2
ERROR MESSAGES INSIDE THE POP-UP WINDOWS ........................................................................... 45
6.3
POSSIBLE CAUSES OF FAULT............................................................................................................... 46
2
TU RS485/ETH serie
6.4
CD Automation srl
Warranty condition ............................................................................................................................ 47
3
TU RS485/ETH serie
CD Automation srl
2 PRODUCT CODE
Model: TU-RS485-ETH IO DL

1 serial interface RS-485 Modbus RTU Master

1 serial interface RS-485 Modbus RTU Slave

1 slot for USB Memory

Interface Ethernet 10Base-T, Modbus TCP

N.4 Digital Inputs

N.2 SPDT Relays

Galvanic Isolation on all the ways
Model: TU-RS485-ETH ANL

1 serial interface RS-485 Modbus RTU Master

1 serial interface RS-485 Modbus RTU Slave

1 slot for USB Memory

Interface Ethernet 10Base-T, Modbus TCP

Galvanic Isolation on all the ways

1 Universal Analogue input

1 Voltage/current Input

2 Passive Analogue output

2 Digital Inputs

N.2 SPDT Relays

Transmitter Power Supply
3 HARDWARE INSTALLATION
The TU-RS485/ETH series is suitable for fitting to DIN rails in the vertical position.
For optimum operation and long life follow these instructions:
When the devices are installed side by side it may be necessary to separate them by at least 5 mm in
the following case:
If panel temperature exceeds 45°C and high power supply value( > 27Vdc).
Make sure that sufficient air flow is provided for the device avoiding to place raceways or other objects which
could obstruct the ventilation slits. Moreover it is suggested to avoid that devices are mounted above appliances
generating heat; their ideal place should be in the lower part of the panel.
Install the device in a place without vibrations.
Moreover it is suggested to avoid routing conductors near power signal cables (motors, induction ovens,
inverters, etc...) and to use shielded cable for connecting signals.
4
TU RS485/ETH serie
CD Automation srl
4 Software Configurator
DevTU is an Integrated Development Environment running under the Windows® Operative System that allows
to design and debug the applications based on the TU-RS485-ETH series control devices.
With DevTU it is possible to set the TU-RS485-ETH series controllers to execute I/O read and write operations
(TU-E3000 series), mathematical and logic operations and timers.
Moreover it is possible to read and write in real time the Internal Registers of the Controller or connect it directly
to the slave devices connected to its Modbus Master Port.
4.1
SOFTWARE INSTALLATION
4.1.1
MINIMUM SYSTEM REQUIREMENTS
Operative System
Available Hard Disk memory
Windows® 2000 / NT / ME / XP/ Vista / Win 7
2 MB
4.1.2 PROCEDURE

Close eventual active or background applications.

Insert the CD-ROM of installation in the driver.

Wait for the Autorun window opening.

If the Autorun function is disabled, open the CD-ROM and execute the installation file at the path:

<CD Driver>:/doc/download.html

Click on the Tools button.

Click on the “download” button in the TU-RS485-ETH section.

Follow the Installation Wizard.
5
TU RS485/ETH serie
4.2
CD Automation srl
DevTU WINDOW
In the Main Window of DevTU the following components are shown:

The Menu bar, the Tool bar and the Status bar (Fig.1.1-A)

The Log window (Fig.1.1-B)

The Main Program window (Fig.1.1-C)

The Registers Table (Fig.1.1-D)
A
B
C
D
Fig. 1
6
TU RS485/ETH serie
4.3
CD Automation srl
TERMINOLOGY
Description of terms and abbreviations used in DevTU and in this manual.
Controller
Integrated Development Environment
IDE
Program
Device of the TU-RS485-ETH series.
Instructions set to create, to debug and to test the Program.
Variable
List of functions executed from the Controller.
Each block constituting the Main Program. Each Function Block can
contain a function.
Logical, mathematical or flow operation executed from the Controller.
Each parameter contained in a function
Register
Position of a variable in the volatile memory of Controller.
Retentive Register
Position of a variable in the non-volatile memory of Controller.
String of characters used to identify the name of an object (Function
Block, Register, Table,...)
Function Block FB
Function
Label
7
TU RS485/ETH serie
4.4
CD Automation srl
PROJECT MANAGMENT
4.4.1 START A NEW PROJECT
A
B
C
Click on the “New Project” button (Fig.2.1-A) or select “ Project -> New ” in
the Menu bar.
The following windows will appear:
Fig. 2.1
Log
: empty window that will contain the operation
performed
(Fig.1.1-B).
Program
: in this window it is possible to insert the Function
Blocks to generate the Program.
For a new Project this window contains a blank
Function Block. (Fig.1.1-C).
Registers Table
:contains the list of Controller's Registers (Fig.1.1-D).
4.4.2 SAVE AND LOAD A PROJECT
To save the Project click on the “Save Project” button (Fig.2.1-C) or select
“ Project -> Save ” or “ Project -> Save As... ” in the Menu bar.
When a Project is saved for the first time, DevTU requires the file name
that will be used as name for the Project.
It will be created a main file with (.prj) extension and the system files
necessary for the correct working of the device.
To load a Project previously saved click on the “Open Project” button
(Fig.2.1-B) or select “ Project -> Open ” in the Menu bar. It will be loaded
the Program, the name and the types of the Registers and the eventual
tables, display windows and the scheduler objects .
4.4.3 CLOSE A PROJECT
To close an existing Project, select “ Project -> Close in the Menu bar.
When DevTU closes a project, it ask if the user want to save the changes
eventually done.
To close the software DevTU,select “ Project -> Exit in the Menu bar. It
asks if the user want to save the changes eventually done.
8
TU RS485/ETH serie
4.5
CD Automation srl
WORK WITH THE FUNCTION BLOCKS
4.5.1 INSERT A FUNCTION BLOCK
To set a Function Block it is necessary to activate it, clicking inside the
block: the block is active when its border is highlighted in red .
Fig. 2.2
It is possible to insert a new Function Block before or after the
highlighted block (Fig.2.3-A).
Click on the “Insert Before” button (Fig.2.2-A) to insert a new block
between the highlighted block and the previous .
A
B
C
D
E F
G H
Click on the “Insert After” button (Fig.2.2-B) to insert a new block
between the highlighted block and the successive.
B
The new block inserted will be automatically highlighted.
4.5.2 REMOVE A FUNCTION BLOCK
To remove a Function Block, click on the block to select it and then click
on the “Delete” button (Fig.2.2-H).
4.5.3 MODIFY A FUNCTION BLOCK
A
To modify a Function Block, click two times on the block or click on the
block to select it and then click on the “Modify” button (Fig.2.2-G).
The operations described above are also accessible from the menu that
appears clicking the right button of the mouse inside the highlighted
Function block.
4.5.4
MOVE A FUNCTION BLOCK
Fig. 2.3
Click on the “Move Up” button (Fig.2.2-C) to change the position of the
active block and that one that precedes it.
Click on the “Move Down” button (Fig.2.2-D) to change the position of the
active block and that one that follows it.
4.5.5
ZOOM
The “Zoom” button (Fig.2.3-B) allows to change the scale of visualization
of the Main Program window reducing the dimensions of the Function
Blocks ( Zoom - ) or turn back to the standard visualization ( Zoom + ).
9
TU RS485/ETH serie
CD Automation srl
4.5.6 STRUCTURE OF A FUNCTION BLOCK
When the user modifies a Function Block, the “Function Block” window
(Fig.2.4) will be visualized; this allows to set the variables relative to the
Function selected.
The Functions are gathered in specific functional groups: to visualize
them, click on the button relative to a functional group (Fig.2.4-A) in
order to visualize its specific functions (Fig.2.4-B).
Clicking on the button relative to the function to be inserted; it will appear
a menu where it is possible to set the Label and the Variables (Fig.2.4-C)
proper of the selected function.
A
C
B
To define particular variables like Masks or Tables, it is possible to use
the “Set” button to open a window of guided insertion of the value.
D
At the end, click on the “OK” button (Fig.2.4-D) to insert the function
inside the Main Program window.
In the Main Program window, the following parameters will be visualized:
B
Fig. 2.4
C
A
Index (Fig.2.5-A): unique number that identifies the position of the block
inside the Program.
Label (Fig.2.5-B): unique label that identifies the Function Block inside
the Program (used for the functions of the “Flow” functional group, refer
to section “Function description”).
Fig. 2.5
D
Symbol (Fig.2.5-C): icon relative to the function to be inserted.
Variable (Fig.2.5-D): parameter of the Function Block.
Refer to the section “Function description” to know how to insert the
functions.
4.5.7
A
B
Fig. 2.6
COPY A FUNCTION BLOCK
To copy a Function Block, select the Function Block to copy clicking on it,
click on the button “Copy” (Fig.2.6-A), create a new Function Block in the
desired point of the Project and than click on the button “Paste” (Fig.2.6-B)
Fig. 2.7
A
It will be created a Block with the same properties of the original.
B
4.6
COMPILE AND ERROR CHECK
When the insertion of the Function Blocks is complete, it is possible to
compile the Program clicking on the “Compile ” button (Fig.2.7).
It will be created a report in the Log window (Fig.2.7) containing the
eventual errors and/or anomalies encountered during the error checking
procedure(Fig.2.8-A).
If the compiling process has a successful conclusion, the Log window
will show the memory resources in use by the Program (Fig.2.8-B).
10
Fig. 2.8
NOTE:
It is possible to insert up to 255 function blocks and up to the available
memory capacity (Program Memory).
TU RS485/ETH serie
4.7
CD Automation srl
INTERNAL REGISTERS
The Internal Memory of the Controller is composed of a 16 bit Register series divided as follows:
System Registers: contain the information about the status
Controller.
General Purpose Registers: can be used in the Program to
move the data or to execute calculation functions
Retentive General Purpose Registers: can be used from the
Program to move the data or to execute calculation functions.
These Registers are saved in Eprom each time their values
change and they are uploaded when the Controller is powered-on.
%S
%R
%R
Fig. 3.1
Fig. 3.2
B
Click on the “Watch” button (Fig.3.1) to visualize the Registers Table (Fig.3.2).
To update the Register's value, click on the “Read” button (Fig.3.2-A).
For each Register it is visualized:
The Register address (Fig.3.2-B)
The Register name (Fig.3.2-C)
The value contained into the Register (Fig.3.2-D)
The Register data format (Fig.3.2-E)
To modify the name or the value of a Register, click two times on the row
of table regarding the Register.
Inside the “Set” window (Fig.3.3) it is possible to set the name (Label) of the
Register (only for the General Purpose Register), to force the value contained in the Register (only if the Controller is connected) and to set the
type of data format of the Register.
.
4.8
TYPE OF DATA FORMAT
Each General Purpose Register can be read or written using one of the
following data format :
Uint
Int
Ulong
Long
Float
Hex
ASCII
Bin
K_Flt
K_Long
16 bit Unsigned Integer (0 ÷ 65535)
16 bit Signed Integer (-32768 ÷ +32767)
32 bit Unsigned Long (0 ÷ 4,294,967,295)
32 bit Signed Long (-2,147,483,648 ÷ +2,147,483,647)
32 bit Floating Point
16 bit Unsigned Integer visualized as Hexadecimal
characters (0000 ÷ FFFF)
16 bit Unsigned Integer visualized as ASCII characters
16 bit Unsigned Integer visualized as binary code
Floating Point Constant (as decimal)
Long Constant (as binary code)
NOTE: the 32 bit Registers request the position of 2 Registers.
11
Fig. 3.3
C
D
E
A
TU RS485/ETH serie
4.9
CD Automation srl
MAPPING Register
Mapping modules TU-RS485-ETH IO DL
Mapping modules TU-RS485-ETH ANL
Register
Description
Access
Register
Description
Access
%S0
--Reserved--
R/W
%S0
--Reserved--
R/W
%S1
Firmware [0]
R
%S1
Firmware [0]
R
%S2
Firmware [1]
R
%S2
Firmware [1]
R
%S3
Name [0]
R/W
%S3
Name [0]
R/W
%S4
Name [1]
R/W
%S4
Name [1]
R/W
%S5
Port 1 [BaudRate]
R/W
%S5
Port 1 [BaudRate]
R/W
%S6
Node ID
R/W
%S6
Node ID
R/W
%S7
Port 1 [Timeout RX]
R/W
%S7
Port 1 [Timeout RX]
R/W
%S8
Digital Inputs
R/W
%S8
Digital Inputs
R/W
%S9
Digital Outputs
R/W
%S9
Digital Outputs
R/W
%S10
System Flags
R/W
%S10
System Flags
R/W
%S11
--Reserved--
-
%S11
--Reserved--
-
%S12
--Reserved--
-
%S12
--Reserved--
-
%S13
PC
R
%S13
PC
R
%S14
Status [0]
R
%S14
Status [0]
R
%S15
Status [1]
R
%S15
Status [1]
R
%S16
COM Errors
R/W
%S16
COM Errors
R/W
%S17
Gateway Mask [L-H]
R/W
%S17
Gateway Mask [L-H]
R/W
%S18
Port 0 [Settings]
R/W
%S18
Port 0 [Settings]
R/W
%S19
Port 2 [Settings]
R/W
%S19
Port 2 [Settings]
R/W
%S20
Timers Enable
R/W
%S20
Timers enabled
R/W
%S21
--Reserved--
-
%S21
--Reserved---
-
%R22
--RTC(0)
R/W
%R22
--RTC(0)
R/W
%R23
--RTC(1)
R/W
%R23
--RTC(1)
R/W
%R24
--RTC(2)
R/W
%R24
--RTC(2)
R/W
%R25
--RTC(3)
General
Purpose
Registers
R/W
%R25
--RTC(3)
R/W
%R26
Analogue Input ch. 0
R
%R27
Analogue Input ch. 1
R
%R28-%R31
--Reserved--
-
%R32
Analogue output 0
R/W
R
%R33
R/W
-
%R34
%R928
Analogue output 1
Program. sensor ch. 0 &
1
“General Purpose” registers
Digital Input 0 Frequency
%R929
Digital Input 1 Frequency
R
%R930-%R931
--Reserved--
-
%R932-933
Digital Input 0 Counter
R/W
%R934-935
Digital Input 1 Counter
R/W
%R936-%R941
--Reserved-“General Purpose” registers
Memory registers
-
%R26
…
%R959
%R928
R/W
R
%R932-933
Digital Input 0 Frequency
Digital Input 1 Frequency
Digital Input 2 Frequency
Digital Input 3 Frequency
Digital Input 0 Counter
%R934-935
Digital Input 1 Counter
R/W
%R929
%R930
%R931
%R35-%R927
R/W
%R936-937
Digital Input 2 Counter
R/W
%R938-939
%R960
…
%R1023
Digital Input 3 Counter
Memory
Registers
R/W
R/W
%R942-%R959
%R960%R1023
12
R/W
R/W
R
R/W
R/W
TU RS485/ETH serie
CD Automation srl
4.10 TU-RS485/ETH IO DL and TU-RS485/ETH ANL
Function of all models
4.10.1
SYSTEM REGISTERS OVERVIEW
This paragraph describes the working of the System Registers. Refer to the Registers Mapping relative to the
device in use to find out the position and the type of access to the Register.
4.10.1.1 FIRMWARE
Field of 2 read only Registers: contains the identifier firmware code provided from the manufacturer.
4.10.1.2 NAME
Field of 2 read/write Registers (4 bytes or 4 ASCII characters) at the user disposal: it can contain the name of
Controller or a unique code that identifies its function in the plant. Each one of the byte can contain any value
from 0 up to 255, the ASCII characters are included.
The default value of this field contains the identifier of the device in ASCII characters.
4.10.1.3 PORT 1 Baud Rate
Field of 1 read/write Register used to select the baud rate of the PORT 1 Modbus Master serial port. Set the
value in function of the following table
BaudRate(Baud)
1200
2400
4800
9600
Value
0
1
2
3
BaudRate(Baud)
19200
38400
57600
115200
Value
4
5
6
7
4.10.1.4 NODE ID
Field of 1 read/write Register: contains the Modbus node address of the device; the addresses allowed are
from 1 up to 247.
Each device connected to the same net must have an unique address.
4.10.1.5 PORT 1 Timeout RX
Field of 1 read/write Register: contains the value of the delay time successive to the reception of the response
on the PORT1 Modbus Master; the value is expressed as milliseconds.
4.10.1.6 DIGITAL INPUTS
Field of 1 read/write Register: contains the status of the Digital Inputs (0 = OFF , 1 = ON).
Bit
15
14
13
12
11
10
-
-
-
-
#3
#2
Descr.
Channel
09
08
07
06
05
04
03
02
01
00
#0
-
-
-
-
-
-
-
-
Input
#1
4.10.1.7 DIGITAL OUTPUTS
Field of 1 read/write Register: contains the status of the Digital Outputs and allows to drive directly the Output
relays (0 = OFF , 1 = ON) .
Bit
15
14
13
12
11
10
08
07
06
05
04
03
02
01
00
-
-
-
-
-
-
-
-
Output
Descr.
Channel
09
-
-
-
-
-
-
#1
#0
13
TU RS485/ETH serie
4.10.1.8
CD Automation srl
SYSTEM FLAGS
Field of 1 read/write Register: contains the following system flags:
- PowerUp Event : this bit is forced to 1 at each Controller power-on. It is possible to set the value as 0 to
monitor eventual Controller reset events .
4.10.1.9
PC (Program Counter)
Field of 1 read only Register: shows the position of the instruction (Function Block) executed in the Main
Program . The value 0 is the first instruction (Function Block 1).
4.10.1.10
STATUS
Field of 2 read only Registers reserved for diagnostic operations.
4.10.1.11
COM ERRORS
Field of 1 read\write Register: is a counter of communication errors on the PORT1 Modbus Master. The value of
this Register is incremented each time that a query is sent on the Master Port and there is not response. This
value can be reset.
4.10.1.12
GATEWAY MASK
Field of 1 read/write Register: contains the range of Modbus addresses which the Controller can send to queries
on the PORT1 Master Port. If is requested to the Controller to send queries to an address out of this range, the
command won't be executed.
Bit
15
Descr.
14
13
12
11
10
09
08
07
First address of the Mask
4.10.1.13
06
05
04
03
02
01
00
Last address of the Mask
PORT 0 Settings
Field of 2 read/write Registers: contain the parameters “Baud-rate” and “delay time” (expressed as milliseconds)
of the serial PORT0 Slave Port. Set the value of the first Register in function of the following table:
Bit
Descr.
15
14
13
12
11
10
09
08
07
06
05
Baud Rate
04
03
02
Delay (0÷255)
BaudRate
1200
2400
4800
9600
19200
38400
57600
115200
Value
0
1
2
3
4
5
6
7
14
01
00
TU RS485/ETH serie
4.10.1.14
CD Automation srl
TIMERS Enable
Field of 1 read/write Register. Each bit of this Register is associated to an internal Timer. The Timer starts to
count when the associated bit is set as 0; when the parameter “ time” of the Timer Function Block set for the
Timer has passed, the Timer stops to count and the associated bit is automatically forced to 1.
15
Bit
14
13
12
11
10
09
Descr.
Channel
08
07
06
05
04
03
02
01
00
Timers
T7 T6 T5 T4 T3 T2 T1 T0 T15 T14 T13 T12 T11 T10 T9 T8
4.10.1.15
RTC (Real Time Clock/Calendar)
Field of 4 read/write Registers: contain the value of the internal clock.
The following information are available:

Seconds
00 ÷ 59

Minutes
00 ÷ 59

Hours
00 ÷ 23

Day of week
01 ÷ 07 (01=Sunday, 02=Monday, .... 07=Saturday)

Date
01 ÷ 31 (it depends on the month)

Month
01 ÷ 12 (01=January, 02=February, .... 12=December)

Year
00 ÷ 99 (00=2000, 99=2099)
NOTE: all of the values are expressed as hexadecimal characters .
NOTICE! Writing these Registers will imply the variation of the clock and calendar settings.
Bit
15
14
13
12
11
10
RTC[0]
RTC[1]
RTC[2]
09
08
07
06
05
04
03
02
Seconds [0÷59]
Minutes [0÷59]
Hours [0÷23]
Day of week [1÷7]
Date [1÷31]
Month [1÷12]
Year [0÷99]
RTC[3]
15
01
00
TU RS485/ETH serie
CD Automation srl
4.11 TU-RS485/ETH ANL only
Function only in TU-RS485/ETH ANL model
4.11.1.1 Analogue Input measure
Contains the measures of the inputs programmed in the register %R34.
Description
Register
channel 0
%R26
channel 1
%R27
4.11.1.2 Analogue output values
Contain the value to set in Integer format for the two output currents.
Number for 4 mA: 4000; number for 20 mA = 20000
Description
Register
channel 0
%R32
channel 1
%R33
4.11.1.3 FREQ [x]
Contains the measure of each digital input's frequency.
The resolution is 0.01Hz.
Description
Register
channel 0
%R928
channel 1
%R929
4.11.1.4 COUNTER [x]
Contains the pulse counter (32 bit) each digital input.
Each counter is automatically incremented at each rise front of the relative digital input.
Description
Register
channel 0
%R932 + %R933
channel 1
%R934 + %R935
16
TU RS485/ETH serie
CD Automation srl
4.11.1.5 Input type programming (%R34)
Contain the programming of the two analogue input channels.
Bit 0-7: programming input channel 0 (universal input).
Bit 8-15: programming input channel 1(Volt – mA input).
INPUT TYPE PROGRAMMING TABLE
Input type
----------100 mV
Dec. value
Input type
Bin. value
Input type
Hex. value
Input type
0
00000000
0x00
YES
Channel 0 Channel 1
YES
1
00000001
0x01
YES
NO
10 V
2
00000010
0x02
YES
YES
20 mA
3
00000011
0x03
YES
YES
Tc J
4
00000100
0x04
Tc K
5
0x05
YES
YES
NO
Tc R
6
00000101
00000110
0x06
YES
NO
Tc S
7
00000111
0x07
YES
NO
Tc T
8
00001000
0x08
YES
NO
Tc B
9
00001001
0x09
YES
NO
NO
Tc E
10
00001010
0x0A
YES
NO
Tc N
11
00001011
0x0B
YES
NO
12
00001100
0x0C
YES
NO
13
00001101
0x0D
YES
NO
Pt1000
14
00001110
0x0E
YES
NO
Ni100
15
16
00001111
0x0F
YES
NO
00010000
0x10
YES
NO
17
18
00010001
0x11
0x12
YES
NO
YES
NO
Res 600 Ω
Pt100
Ni1000
Potentiometer
Res 2000 Ω
00010010
17
TU RS485/ETH serie
CD Automation srl
4.12 FUNCTION LIST
Functions selection tree, divided per functional group
COMM
“Communication” functions
Read
Holding
MOVE
Read
Input
Modbus function “Read Input Registers” (3xxxx , command 0x04)
Write
Modbus function “Write Holding Registers” (4xxxx , command 0x16)
Read
TU-E 3000
Read values from the TU-E 3000 series
Write
TU-E 3000
Write values to the TU-E 3000 series
“Move” functions
Move
Bitwise
Modbus function “Read Holding Registers” (4xxxx , command 0x03)
Moves the value of an Internal Register or kostant in a new Register without to change the original
value.
“Logical operations” functions
AND (bit)
OR (bit)
XOR (bit)
AND between two bits.
OR between two bits.
XOR between two bits.
AND (word) AND between two words (Registers).
OR (word)
OR between two words (Registers).
XOR (word) XOR between two words (Registers).
NOT
SHIFT
Inversion of one or more bits.
Bit Set
Forces to 1 one or more bits.
Bit Reset
Forces to 0 one or more bits.
“Logical operations” functions
Shift R
“Shift to Right” a word (Register) .
Shift L
“Shift to Left” a word (Register).
Rotate R
“Rotate to Right” a word (Register).
Rotate L
“Rotate to Left” a word (Register).
18
TU RS485/ETH serie
MATH
CD Automation srl
“Math” functions
Add
Add two values.
Sub
Subtract two values.
Mult
Multiply two values.
Div
Divide two values.
Scale
SQRT
Average
Proportional scale adaption.
Square Root Extraction.
Calculation of the Arithmetic Mean of two or more values.
Linearization Linearization function of a Register's value following a linearization table.
ABS
Calculation of the absolute value.
e^(x)
Exponential function.
x^y
COMP
Raise X to the Y power.
“Comparison” function
Trip
FLOW
“Flow” functions
GOTO
If (bit) goto
Call
Return
Timers
“Timing” function
Timer
Activation of an Internal Timer
19
TU RS485/ETH serie
CD Automation srl
Read Holding Read the Holding Registers from a Modbus slave device
Reads the values of N holding Registers (Modbus function 0x03, Registers 4xxxx ) from a Modbus slave
device and writes the values in the selected Internal Registers. In case of missing response or wrong
response by the slave device, the Registers of destination are not updated and the value of the System
Register “COM Errors” is increased.
Variables:
Address
Register
Num
Dest
Delay
Modbus address of the slave device (1÷247)
Address of the first Register to read (the mapping Registers starts from 0)
Numbers of Registers to read (1÷16)
Address of the first Internal Register wherein the read values are written to.
Delay time between the reception of the response and the execution of the next instruction
Read Input
Read the Input Registers from a Modbus slave device
Reads the values of N input Registers (Modbus function 0x04, Registers 3xxxx ) from a Modbus slave device
and writes the values in the Internal Registers. In case of missing response or wrong response by the slave
device, the Registers of destination are not updated and the value of the System Register “COM Errors” is
increased.
Variables:
Address
Register
Num
Dest
Delay
Modbus address of the slave device (1÷247)
Address of the first Register to read (the mapping Registers starts from 0)
Numbers of Registers to read (1÷16)
Address of the first Internal Register wherein the read values are written to.
Delay time between the reception of the response and the execution of the next instruction.
Write
Write the Holding Registers of a Modbus slave device
Writes the values of N Internal Registers in N Holding Registers of a Modbus slave device (Modbus function
0x16, Registers 4xxxx ). In case of missing response or wrong response by the slave device, the Registers of
destination are not updated and the value of the System Register “COM Errors” is increased.
Variables:
Address
Register
Num
Source
Delay
Modbus address of the slave device (1÷247)
Address of the first Register to write (the mapping Registers starts from 0)
Numbers of Registers to write (1÷16)
Address of the first Internal Register from which the values to write are withdraw from.
Delay time between the reception of the response and the execution of the next instruction.
Read3000
Read the I/O Registers from a Modbus slave TU-E3000 series device
Reads the I/O values from a Modbus slave TU-E3000 series device and writes the values in the Internal
Registers. The function will generate the proper Modbus command and will process the response.
In case of missing response or wrong response by the slave device, the Registers of destination are not
updated and the value of the System Register “COM Errors” is increased.
Refer to the technical documentation of the TU-E3000 series device for the complete description of the I/O
Registers.
Variables:
Device
Address
Resource
From
To
Dest
Delay
Selection of the TU-E3000 series slave device.
Modbus address of the slave device (1÷247).
Type of data to read (analog inputs, digital inputs , etc...)
First Resource to read.
Last Resource to read.
Address of the first Internal Register wherein the read values are written to.
Delay time between the reception of the response and the execution of the next instruction.
20
TU RS485/ETH serie
Write3000
CD Automation srl
Write the I/O Registers of a Modbus slave TU-E3000 series device
Writes the values of N Internal Registers in the I/O Register of a Modbus slave TU-E3000 series device. The
function will generate the proper Modbus command and will process the response. In case of missing
response or wrong response by the slave device, the Registers of destination are not updated and the value of
the System Register “COM Errors” is increased.
Refer to the technical documentation of the TU-E3000 series device for the complete description of the I/O
Registers.
Variables:
Device
Address
Resource
From
To
Source
Delay
Selection of the TU-E3000 series device.
Modbus address of the slave device (1÷247)
Type of data to write (analogue outputs, digital outputs, etc...)
First Resource to write.
Last Resource to write.
Address of the first Internal Register from which the values to write are withdraw from.
Delay time between the reception of the response and the execution of the next instruction.
Move
Move the value of an Internal Register or Constant in a new Register without to change the original value.
Writes in an Internal Register the value of a Constant (pre-set) or the value of another Register (copy). The
value will be converted to the format selected for the Register of destination. The address of the source
Register and the address of the Register of destination can be the same (modify the format of the Register).
Variables:
Source
Dest
And (word)
Constant or Internal Register from which the value is read.
Internal Register wherein the value is written.
Executes the logical operation “AND” between two values.
Executes the logical operation “AND” between a Register and a constant (mask) or between two Registers.
The value will be converted to the format selected for the Register of destination. The address of the source
Register and the address of the Register of destination can be the same (modify the format of the Register).
After the execution of the logical operation, only the bits set as 1 in the mask will be forced; the bits set as 0
won't be modified. In case of a 32 bit source Register or constant (long) and a 16 bit Register of destination
(integer), the most significant bits will be ignored. It is possible to use this function to force one or more bits of
a Register as 0 ( in the mask set as 0 the bits to force, set as 1 the other bits ).
Variables:
Source A
Source B
Mask Out
Dest
Constant or Internal Register relative to the first operator.
Constant or Internal Register relative to the second operator.
Mask applied to the result.
Internal Register wherein the result is written.
Or (word)
Executes the logical operation ”OR” between two values.
Executes the logical operation “OR” between a Register and a Constant (mask) or between two Registers.
The value will be converted to the format selected for the destination Register. The address of the source
Register and the address of the Register of destination can be the same (modify the format of the Register).
After the execution of the logical operation only the bits set as 1 in the mask will be forced; the bits set as 0
won't be modified. In case of a 32 bit source Register or constant (long) and a 16 bit Register of destination
(integer), the most significant bits will be ignored. It is possible to use this function to force one or more bits of
a Register as 1 ( in the mask set as 1 the bits to force, set as 0 the other bits ).
Variables:
Source A
Source B
Mask
Dest
Constant or Internal Register relative to the first operator.
Constant or Internal Register relative to the second operator.
Mask applied to the result.
Internal Register wherein the result is written.
21
TU RS485/ETH serie
Xor (word)
CD Automation srl
Executes the logical operation “XOR” (Exclusive Or) between two values.
Executes the logical operation “XOR” between a Register and a constant (mask) or between two Registers.
The value will be converted to the format selected for the Register of destination. The address of the source
Register and the address of the Register of destination can be the same (modify the format of the Register).
After the execution of the logical operation only the bits set as 1 in the mask will be forced ; the bits set as 0
won't be modified. In case of a 32 bit source Register or constant (long) and a 16 bit Register of destination
(integer), the most significant bits will be ignored. It is possible to use this function to invert (NOT) one or more
bits of a Register ( in the mask set as 1 the bits to invert, set as 0 the other bits ).
Variables:
Source A
Source B
Mask Out
Dest
Constant or Internal Register relative to the first operator.
Constant or Internal Register relative to the second operator.
Mask applied to the result.
Internal Register wherein the result is written.
And (bit)
Executes the logical operation “AND” between two bits.
Executes the logical operation “AND” (bit to bit) between a Register and a Constant (mask) or between two
Registers. The value will be converted to the format selected for the Register of destination. The address of
the source Register and the address of the Register of destination can be the same (modify the format of the
Register). After the execution of the logical operation only the bits set as 1 in the mask will be forced ; the bits
set as 0 won't be modified. In case of a 32 bit source Register or Constant (long) and a 16 bit Register of
destination (integer), the most significant bits will be ignored.
Variables:
Source A
Mask A
Source B
Mask A
Dest
Mask Out
Constant or Internal Register relative to the first operator.
Bits of the first operator
Constant or Internal Register relative to the second operator.
Bits of the second operator
Internal Register wherein the result is written.
Mask applied to the Register of destination.
Or (bit)
Executes the logical operation “OR” between two bits.
Executes the logical operation “OR” (bit to bit) between a Register and a constant (mask) or between two
Registers. The value will be converted to the format selected for the Register of destination. The address of
the source Register and the address of the Register of destination can be the same (modify the format of the
Register). After the execution of the logical operation only the bits set as 1 in the mask will be forced; the bits
set as 0 won't be modified. In case of a 32 bit source Register or constant (long) and a 16 bit Register of
destination (integer), the most significant bits will be ignored.
Variables:
Source A
Mask A
Source B
Mask A
Dest
Mask Out
Constant or Internal Register relative to the first operator.
Bits of the first operator
Constant or Internal Register relative to the second operator.
Bits of the second operator
Internal Register wherein the result is written.
Mask applied to the Register of destination.
22
TU RS485/ETH serie
XOr (bit)
CD Automation srl
Executes the logical operation “XOR” (Exclusive Or) between two bits.
Executes the logical operation “XOR” (bit to bit) between a Register and a constant (mask) or between two
Registers. The value will be converted to the format selected for the Register of destination. The address of
the source Register and the address of the Register of destination can be the same (modify the format of the
Register). After the execution of the logical operation only the bits set as 1 in the mask will be forced ; the bits
set as 0 won't be modified. In case of a 32 bit source Register or constant (long) and a 16 bit Register of
destination (integer), the most significant bits will be ignored.
Variables:
Source A
Mask A
Source B
Mask A
Dest
Mask Out
Constant or Internal Register relative to the first operator.
Bits of the first operator
Constant or Internal Register relative to the second operator.
Bits of the second operator
Internal Register wherein the result is written.
Mask applied to the Register of destination .
NOT
Executes the inversion of one or more bits of a Register.
Executes the inversion of one or more bit of a Register. After the execution of the logical operation will be
forced only the bits set as 1 in the mask; the bits set as 0 won't be modified.
Variables:
Source
Dest
Mask Out
Internal Register containing the value.
Internal Register wherein the result is written.
Mask applied to the Register of destination.
Shift R
Shift to right the bits of a Register .
Executes the shift of a Register to right: all of the bits are shifted of N positions to right. The most significant
bits will be forced to 0.
Variables:
Source
N
Dest
Internal Register containing the value.
Number of shift to execute.
Internal Register wherein the result is written.
Shift L
Shift to left the bits of a Register.
Executes the shift of a Register to left: all of the bits are shifted of N positions to left. The least significant bits
will be forced to 0.
Variables:
Source
N
Dest
Internal Register containing the value.
Number of shift to execute.
Internal Register wherein the result is written.
23
TU RS485/ETH serie
Rotate R
CD Automation srl
Rotates to right the bits of a Register.
Executes the rotation of a Register to right: all of the bits are shifted of N positions to right. At each shift the
most significant bit receives the value of the least significant bit.
Variables:
Source
N
Dest
Internal Register containing the value.
Number of shift to execute.
Internal Register wherein the result is written.
Rotate L
Rotates to left the bits of a Register.
Executes the rotation of a Register to left: all of the bits are shifted of N positions to left. At each shift the least
significant bit receives the value of the most significant bit.
Variables:
Source
N
Dest
Add
Internal Register containing the value
Number of shift to execute.
Internal Register wherein the result is written.
Calculates the sum of two values
Calculates the sum between an Internal Register and a constant or between two Internal Registers.
Variables:
Source A
Source B
Dest
Constant or Internal Register relative to the first operator.
Constant or Internal Register relative to the second operator.
Internal Register wherein the result is written.
Sub
Calculates the difference of two values
Calculates the difference between an Internal Register and a constant or between two Internal Registers.
Variables:
Source A
Source B
Dest
Constant or Internal Register relative to the first operator.
Constant or Internal Register relative to the second operator.
Internal Register wherein the result is written.
Mult
Calculates the multiplication of two values
Calculates the multiplication between an Internal Register and a constant or between two Internal Registers.
Variables:
Source A
Source B
Dest
Constant or Internal Register relative to the first operator.
constant or Internal Register relative to the second operator.
Internal Register wherein the result is written.
24
TU RS485/ETH serie
Div
CD Automation srl
Calculates the division between two values.
Calculates the division between an Internal Register and a constant or between two Internal Registers.
Variables:
Source A
Source B
Dest
Constant or Internal Register relative to the first operator.
Constant or Internal Register relative to the second operator.
Internal Register wherein the result is written.
Scale
Executes the proportional scaling of a value
Executes the proportional scaling between the input range values and the output range values, referring to the
value of an Internal Register.
Variables:
Source
Span In
Zero In
Dest
Span Out
Zero Out
Internal Register containing the value to scale.
Maximum value of the input range
Minimum value of the input range
Internal Register wherein the result is written.
Maximum value of the output range
Minimum value of the output range
SQRT
Calculates the Square Root of a value
Calculates the Square Root of a value contained in an Internal Register.
Variables:
Source
Dest
Internal Register containing the value
Internal Register wherein the result is written.
Average
Calculates the Arithmetic mean of N values.
Calculates the Arithmetic mean of N Internal Registers values. (sum of the values / N).
Variables:
Source
N
Dest
Address of the Internal Register containing the first value.
Number of Internal Register of which calculate the mean.
Internal Register wherein the result is written.
Linearization Calculates a value in function of a linearization table.
Calculates the Linearization of a value in function of the linearization table selected. Refer to the section
“Table” for more information.
Variables:
Source
Function
Dest
Internal Register containing the value to linearize.
Name of the Linearization table to be followed.
Internal Register wherein the result is written.
25
TU RS485/ETH serie
Trip
CD Automation srl
Control of a Trip Alarm
Controls a Trip Alarm with setting of the Trip level, hysteresis and delay time for ON and OFF condition. If the
input value is higher than the high trip level (MAX) for a time longer than Ton, the bits selected in the output
mask will be forced to 1. If the input value is lower than the low trip level (MIN) for a time longer than Toff, the
bits selected in the output mask will be forced to 0.
It is possible to use this Function Block to execute the operation “A>B”: set the trip levels with the same value
and the delay times Ton and Toff = 0.
NOTE: the output status is updated at each execution of the Function after the end of the delay time: it is
suggested to insert this Function Block in a zone of the Program continuously executed.
The graph (Fig.4.1) shows the working of a Trip alarm that goes on if the input signal is higher than 100°C for at
least 2 seconds and goes off if the input signal is lower than 90°C for at least 5 seconds.
100
Max
90
Min
Input
Output
(dest. bit)
Toff
Ton
(5 sec.)
(2 sec.)
Variables:
Input
Max
Min
Dest
Mask
Use Timer
Timer On
Timer Off
Internal Register containing the value to compare
High Trip level
Low Trip level
Internal Register wherein the result is written.
Mask applied to the result.
Number of Internal Timer to use (0÷15)
Delay time for Trip Alarm activation (ms)
Delay time for Trip Alarm de-activation (ms)
26
Fig. 4.1
TU RS485/ETH serie
Goto
CD Automation srl
Unconditioned jump to a Function Block.
Executes an unconditioned jump to a Function Block. The Function Block recalled must have a unique Label.
It is possible to select the Label of the Function Block which jump to, sorting out it between those available in
the list box “Func.Block”. The list is automatically updated each time that the user identifies a new Block; in the
case of the list is empty the value 0 appears.
Variables:
Func.Block
Pointer to the Function Block which jump to.
If (bit)
Conditioned jump to a Function Block.
Executes a conditioned jump to the Function Block indicated in the variable “Goto if true” if the status of the bit
selected is 1, while if the status of the bit is 0 jumps to the Function Block indicated in the variable “Goto if
false”. All of the Function Blocks called must have a unique Label. It is possible to select the Label of the
Function Block which jump to, sorting out it between those available in the list box “Goto if true” and “Goto if
false” . The lists are automatically updated each time that the user identifies a new Block; in the case of the list
is empty the value 0 appears.
Variables:
Source
Bit
Goto if True
Goto if False
Internal Register used as reference
Number of the bit to control (0÷15)
Pointer to the Function Block which jump to (if Bit=1)
Pointer to the Function Block which jump to (if Bit=0)
Call
Recall a Subroutine
Executes a jump to the first Function Block of a Subroutine; at the end of the Subroutine (command “Return”),
the Function Block successive to the block “Call” will be executed. The Function Block recalled must have a
unique Label. It is possible to select the Label of the Function Block which jump to, sorting out it between
those available in the list box “Func.Block”. The list is automatically updated each time that the user identifies
a new Block; in the case of the list is empty the value 0 appears.
NOTE: for each block “Call” must correspond a block “Return”, otherwise it is possible to occur in a “Stack
Overflow” error (refer to the section Troubleshooting).
Variables:
Func.Block
Pointer to the Function Block which jump to
Return
Return from a Subroutine
Indicates the end of a Subroutine. The Program will return to the Block following the Function Block “Call”.
NOTE: for each block “Return” must correspond a block “Call”, otherwise it is possible to occur in a “Stack
Overflow” error (refer to the section Troubleshooting).
Timers
Activation of an Internal Timer
Sets an Internal Timer and starts to count. During the count, the bit relative to the Timer selected
in the System Register “Timers Enable”, will be forced to 0. At the end of the count, the bit will be
forced to 1.
It is possible to check the status of the bit to determine the end of the time set.
Variables:
Timer
msec
Reg
Number of the Internal Timer to enable
Timer Pre-set (milliseconds)
If Timer = 0 is the value of time in msec.
27
TU RS485/ETH serie
CD Automation srl
4.13 INSERTION OF TABLES
To insert the linearization tables, it is necessary to open the proper window selecting “Tools -> Tables” in the Menu bar (Fig.5.1) .
To upload the points of a table from a file, click on the “Load from File”
button (Fig.5.1-A); the parameters relative to the table like the name, the
number of points and the input and output values for each point will be
loaded.
Each table must be associated to a unique name that identifies the table
inside the Program when the user recall it: to modify the name, click on
the text box “Name” (Fig.5.1-B) and write the new name or select one between those existing.
The number of points (32 max.) defines the steps of linearization applied
to a variable.
To modify it click on the text box “N points” (Fig.5.1-C) and write the new
value: the window will be automatically updated.
Each point is defined by the input and output values. The input values
must be inserted in increasing order, while the output values can be inserted both in increasing and decreasing order.
The example (Fig.5.1-D) shows how to create an 8 points table to linearize a RTD temperature sensor and to obtain the conversion Ohm/°C
(Fig.5.2) .
Example of table
provided from the
manufacturer of the
sensor :
°C
A E
F
G
B
C
D
Ohm / °C characteristic
70
°C
Ohm
60
0
1000
50
15
1145.6
20
1367.3
25
1532.7
30
1673.4
20
40
1904.5
10
50
1966.3
60
2000
Fig. 5.1
40
30
0
800
1000
1200
1400
1600
1800
2000
2200
Ohm
Fig. 5.2
When the insertion of points is complete, it is possible to save the table in a
file, clicking on the “Save to File” button (Fig.5.1-E); by this command the name of the table, the number of points
and the input and output values per each points will be saved.
To insert the table inside the Program, click on the “>>” button (Fig.5.1-F). The “Table List” will be updated with the
name of the table just inserted and shows the tables available for the Program. To turn back to the Function
Block window, click on the “OK” button.
Select the Internal Register which the linearization curve will be associated to and click on the “OK” button to
turn back to the Main Program window.
When the Function Block is recalled by the Program, the Controller executes a control between the value
contained into the Internal Register and the points of the selected table and calculates by interpolation the
output value.
In the example (Fig.5.1-D) for an input value of 1789 Ohm, will be calculated an output of 35 °C.
28
TU RS485/ETH serie
CD Automation srl
4.14 SEARCHING OF THE DEVICES CONNECTED
Connect the Controller to the Ethernet network and power-on it (refer to
the data-sheet).
Open the window “Search” (Fig.6.1) selecting “Tools -> Search” in the Menu
bar. In this window it is possible to select the type of Controller to search
(Fig.6.1-A) and to set the receiving Time-out (time over which the device is
intended as not connected )- Fig.6.1-B. To search eventual devices
connected to the serial Modbus-master port of the Controller (Sub-Nodes),
the user must indicate the range of addresses to control (Fig.6.1-C); to use
this function it is necessary that the Controller is set in “Debug” modality
and in “Stop” condition.
When a Controller compatible with the type selected is recognized, it is
visualized in the Ethernet list (Fig.6.1-E), wherein it is possible to read the IP
address , the MAC address and the Modbus node of the device.
D
A
When the options have been selected, click on the “Search” button (Fig.6.1D) to start the search. If necessary it is possible to interrupt the search
clicking on the “Stop” button.
E
B
C
F
Afterwards, if required, the Modbus slave devices connected to the
Controller will be searched. The recognized devices will be visualized in
the Subnet list (Fig.6.1-F), wherein it will be possible to read the Modbus
slave node address and, in case of the TU-E3000 series devices, the
Firmware code. At the end of the search, it is possible to select one of the
Controllers detected clicking on its name and set it as default Controller,
clicking on the name by the right button of the mouse and selecting the
“Set as Controller” option; after this operation,the connection to the
Controller will be automatically executed. Refer to the next paragraph to
set the Controller manually.
Fig. 6.1
4.15 CONNECTING TO THE CONTROLLER
Open the window “Settings” (Fig.6.2) selecting “Settings -> Controller” in the
Menu bar.
Set the following parameters:
Node ID
:Modbus node address (1 ÷ 247)
Channel
:Communication Interface (Ethernet or serial port)
IP Address
:Controller IP address
Port
:Modbus/TCP socket reserver port (502 for direct
connection)
Timeout
:Receiving Timeout for TCP commands
Fig. 6.2
A
C
To confirm, click on the “OK” button.
Click on the “Connect” button (Fig.6.3-A): if the connection ends correctly,
the message “Connected” will be visualized in the Status bar Fig.6.3-B) and
in the Log window (Fig.6.4); in case of error, refer to the section
“Troubleshooting” to solve the problem.
From this moment all of the reading, writing, Programming and debugging
operations will be sent only to the selected Controller.
If the user have to change the Controller, it is necessary to disconnect the
Controller in use, click on the “Disconnect” button (Fig.6.3-C), modify the
parameters in the “Settings” window and then click on the “Connect” button
to communicate with the new Controller.
29
Fig. 6.3
B
Fig. 6.4
TU RS485/ETH serie
CD Automation srl
4.16 DOWNLOAD THE PROGRAM
When the Program is complete and if the compiling ends correctly it is
possible to download it in the RAM memory of Controller. To do it, open
the “Download” window (Fig.6.6). clicking on the “Download” button
(Fig.6.5-A).
A
A
Fig. 6.5
The Download operations are allowed only in “Debug” modality (refer to
the section “Debug Modality”).
C
Inside the “Download” window it is possible to set one or more options:
D
“Download Program” (Fig.6.6-A) – Starts to download the Program in the
RAM memory of Controller.
E
B
Fig. 6.6
“Verify” (Fig.6.6-B) – Compares the Program contained in the RAM
memory with the compiled Program.
“Save in Flash” (Fig.6.6-C) – Transfers the Program loaded in the RAM
memory to the Internal Flash Memory of the Controller.
“Clear Register Memory” (Fig.6.6-D) – Resets the value of the
Controller's General Purpose Internal Registers .
“Run After Download” (Fig.6.6-E) – At the end of the download, sets the
Controller in “Run” modality (execution of the Program).
A
C
D
E
F
G
4.17 DEBUG MODE
By this modality it is possible to follow the Program flow and to monitor
in real time the Controller's status and the value of the Internal Registers.
B
Fig. 6.7
When the Program is interrupted the Register Table is updated to the
last reading.
During the development of the Program, if the Controller is connected,
click on the “Debug” button (Fig.6.7-A) to activate the “Debug” modality.
In the Status bar the message “Debug Mode” (Fig.6.7-B) will be visualized
and in the Tool bar will be activated the commands to execute the
following debug operations:
Run (Fig.6.7-C)
A
:Executes the Program continuously.
Run To Break (Fig.6.7-D): Executes the Program up to the Break point .
Pause (Fig.6.7-E)
:Interrupts the execution of the Program ( “Run”
condition) / executes the Program step by
step (“Stop” condition)
Animate (Fig.6.7-F)
Simulates the evolution of the Program flow
executing it step by step.
Stop (Fig.6.7-G)
:Blocks the Program and reset it to the first
Function Block.
The Function Block in execution is identified by the Index parameter
coloured in red and is updated the PC (”Program Counter”) value
(Fig.6.8-A).
Open the “Settings” window (Fig.6.9), selecting “Settings -> Workspace”
to set the following options for the Debug modality:
“Run-Time Register Update” (Fig.6.9-A) – If active, in “Run” condition the
table Register will be automatically updated (1 read per second)
“Animate Time” (Fig.6.9-B) – Setting of the playing time between one
step and the successive in the “Animate” condition.
30
Fig. 6.8
TU RS485/ETH serie
CD Automation srl
4.18 RELEASE MODE
After the phases of development and Debug it is possible to proceed with
the “Release” modality, clicking on the “Release” button (Fig.6.10-A).
In the Status bar the message “Release Mode” (Fig.6.10 -B) will be
visualized and in the Tool bar the commands relative to the operations of
Debug and Download will be disabled.
In the “Release” Modality, at the power-on, the Controller will be
automatically set in “Run” condition, loading in the RAM memory the
Program saved in the Internal Flash memory.
In this modality it is possible to read and write the Internal Registers.
A
B
4.19 INIT MODE
Fig. 6.9
The “INIT” modality can be used in case of fortuitous loss of configuration
to set the Controller in the default condition in order to recover the desired
configuration. In this modality the value of the following parameters of the
controller will be automatically set independently of the configuration saved
in Eprom.
IP Address
Value assigned automatically from the network by
a DHCP server
Modbus Node
0x0Ah (10)
PORT 0 (Slave)
Baud-rate = 9600 bps
In this modality is not possible to execute the Program (Run) and the
Debug functions are disabled but it is allowed to download the Program, to
read and write the Internal Registers and the Gateway function is enabled.
IMPORTANT:
In “Debug” modality, at the power-on the Controller will be automatically set in “Stop” condition without load and execute the Program. For
such reason, at the end of the Debug operations, set the Controller in “Release” modality.
In “INIT” modality is not possible to execute the Program (Run) and
the Debug functions are disabled but it is allowed to download the Program, to read and write the Internal Registers and the Gateway function is
enabled.
31
A
B
Fig. 6.10
TU RS485/ETH serie
CD Automation srl
4.20 SCHEDULER (Data Logger)
The scheduler allows to manage up to 8 tasks of recording at the same
time (data-logger).
Fig. 6.13
The data will be saved on the USB memory in .CSV format; it is possible
to get access to all of the files contained in the memory card by a page of
Web Server.
Open the “Scheduler” window (Fig.6.14), selecting “Tools -> Scheduler”
(Fig.6.13) to insert the tasks relative to the data-logger.
Fig. 6.14
To insert the “Logger” object, click on the “Logger” button (Fig.6.15A) and
then click on the “Insert Object” button (Fig.6.15B) . The “Logger” text will
appear inside the “Task List” (Fig.6.15C) .
For each task it is possible to set:
Lifetime (Fig.6.16A): indicate the period of validity of the task, that is active
only in the period of time included in these parameters.
Directory of destination (Fig.6.16B): indicates the directory inside which
the files of the current task will be created. If the
directory doesn't exist, it will be automatically created.
File generation options (Fig.6.16C): the current file will be closed and a
new file will be created in function of the parameter of
time selected (hour, day, month and year). To the new
file generated will be assigned a name in function of
the date and time when it has been created (ex: a file
created the day May 8th 2010 at the 14.00 will be
Fig. 6.15
A
B
C
named as “08051014.csv”).
Recording Time (Fig.6.16D): if the “Time” option is set, a record of data
will be saved at regular intervals each time that the
selected period is expired.
Recording Trigger (Fig.6.16E): if the “Trigger” option is set, a record of
data will be saved at the variation (rising or falling
edge) of the bit indicated.
Fig. 6.16
A
Record format (Fig.6.16F): the indicated values will be used to create the
fields that compose the record of data.
B
It is possible to insert the following parameters:
- Event type : identifier number for the event that enabled the
saving of the record of data (2 = trigger (rising edge of bit) ;
C
4 = trigger (falling edge of bit) ; 128= recording time.
F
D
- dd/mm/yy : date;
E
- hh:mm:ss : time;
- Var[n] : value of the variable n (register).
H
To modify the format of the variables click on the “Set Formats” button
(Fig.6.16G) (refer to the section “Insertion of Variables”.
G
Fig. 6.17
I
J
To confirm the task settings, click on the “Apply” button (Fig.6.16H).
E
A
B
C
D
F
32
G
H
TU RS485/ETH serie
CD Automation srl
4.21 INSERTION OF VARIABLES
By this window (Fig.6.17) it is possible to indicate which registers will be
available for the data-logger functions. For each register must be
specified the number of the register (Fig.6.17A), the format type of the
register (Fig.6.17B), the numeric format (Fig.6.17C) and an eventual label of
description (Fig.6.17D).
To confirm the modifies of the register properties click on the “Set”
button (Fig.6.17E).
To scroll up or down the register list click on the “Up” or “Down” buttons
(Fig.6.17J).
To add or remove a register click on the “+” or “-” buttons (Fig.6.17I).
When all the registers have been inserted, click on the “Write” button
(Fig.6.17G) to save the data inside the Controller.
To modify the values it will be possible to reload the project or read them
directly from the Controller clicking on “Update” button (Fig.6.17F) .
To close this window click on the “OK” button (Fig.6.17H) .
IMPORTANT:
The device doesn't execute automatically the change to the Daylight Saving Time (DST).
33
Fig. 6.17
I
J
E
A
B
C
D
F
G
H
TU RS485/ETH serie
CD Automation srl
5 WEBSEVER
With Webserver extension is possible configure the network and services and download the data
stored in USB memory
The TU RS485/ETH have a factory IP Address 192.168.100.110, to change it use DevTU tool or enter
in Network web page in maintenance section
5.1
Operating environment
Supported browser:
5.2

IE9

FireFox

Goole Crome
User Management and security
User Type
Description
Download log
Maintenance Network
Maintenance  Mail
Maintenance  DDNS service
Maintenance  Users
The system have different user for different function explained below
User 1
End User 1
X
-
-
-
X
System User
System User
X
X
X
X
X
34
TU RS485/ETH serie
5.3
CD Automation srl
Log-in
Initial page that appear after a remote connection
Initial user and password are
Level
User
Password
Normal User
user1
user1_
Administrator
admin
admin_
The data on screen are :

User Name
: User name for log-in

Password
: Password for the user
to identify the right user (see User Management and security)
5.4
Navigation
On the top of the page there are buttons for web navigation



Download
: used for download data logged in .csv file
Maintenance : enter in installation/maintenance utility, the functions enabled depend of user log-in
Logout
: come back in log-in page
35
TU RS485/ETH serie
5.5
CD Automation srl
Maintenance
In this section is possible set all the service and function.
Every user have different responsabilty and can do different thing
User 1 ,
Admin System
36
TU RS485/ETH serie
CD Automation srl
5.5.1 Information
In this section It’s possible set Network setting and system information
5.5.1.1 Network
CAUTION this setting will reboot the RCU and be shure that MCB is in off condition

Dynamic IP (DHCP) : Used to get automatically IP configuration for a network DHCP
server

IP Address
: Network Static IP address for this unit

Gateway
: Network Gateway address IP Address
(necessary for go out local LAN)

Subnet Mask
: Enter Subnet Mask

Primary DNS
: Enter primary DNS server IP Address

Secondary DNS
: Enter primary DNS server IP Address

Update BUTTON
: Confirm and save IP setting

Return BUTTON
: Come back previous page without save data
CAUTION: This configurations mast be confirmed by local LAN System administrator people
After configuration you can open a browser (es Internet explorer, Firefox,…) an type on url the IP address
setting (ex: http://192.168.100.113 )
37
TU RS485/ETH serie
CD Automation srl
5.5.1.2 E-Mail
Mail service is a very powerful and flexible service.
With this service, TU RS485/ETH can send an email with a preformatting text up to 5 different email address
after a trigger signal occurs
Trigger signal can be:

After a scheduled timer

Changing a bit status in the project
38
TU RS485/ETH serie
CD Automation srl
Mail Address

From
: is an email addres tha rappresent the sender

To
:Is the main address to be sended the alarm information

Cc
:Is like “sen in copy” so send the same email sendend to main address
Message
Is the section to compose the message

Subject : is subject of email

Body
:Is the body of the email, here will be the real dynamic message
An example of body text is
Place: #037
Country: #038
Model: #035
S/N: #036
-Alarm Status1)#041
2)#042
3)#043
4)#047
5)#048
6)#049
7)#050
The body can be filled with static text and variable text
Ex “Place:” is a static text and “#037” is a variable text
The text in variable are defined in the internal project
The maximum number of variable in a project are 96 and the maximum number of fixed string are 128
39
TU RS485/ETH serie
CD Automation srl
5.5.1.3 DDNS

Status
: if checked DDNS function is enabled

DDNS Service
: fixed to www.dyndns.com

Remote server
: DDNS server for service

User
: user for DDNS service (created on www.dyndns.com website)

Password
: Password for DDNS service

Test
: Give a status after a DDNS request
40
TU RS485/ETH serie
CD Automation srl
5.5.1.4 Advanced
This section there is system information and special parameter
Admin System User
Advanced Information

Web Version
: Revision of Web Page

Firmware Ver.
: Revision of Firmware

MAC Address
: MAC Address of Ethernet board

Host Name
: Host (NETBios) name in the network

Socket Time Out
: Maximum time for the Remote connection
5.5.2 Users
Is possible modify the user name and password of every user.
User1 Level
Admin System User and Factory User Level
41
TU RS485/ETH serie
5.6
CD Automation srl
Download
In download section is possible download data-log files
Filter

From
: start data for search filter

To
: end data for search filter

Refresh
: button for execute search filter
To change the value of Month and year click on
buttons
Container
is the actual container of data
42
TU RS485/ETH serie
CD Automation srl
File list
is the list of sub container or file logs (.csv)

To download Files: click on

To delette Files: click on
Button
Button
43
TU RS485/ETH serie
CD Automation srl
6 TROUBLESHOOTING
6.1
ERROR MESSAGES IN THE LOG WINDOW AND IN THE STATUS BAR
EVENT
POSSIBLE CAUSES
POSSIBLE SOLUTIONS
“Not Connected”.
-The Controller is not connected.
-The communication channel selected
has not been enabled.
-Verify in the “Settings” menù :
for Ethernet port:
-IP address
-Port number reserved to the Modbus
TCP socket (Port)
-Time out value.
-Modbus node ID of the device.
for serial port (COM):
-COM port number.
-Baud rate.
-Modbus node ID of the device.
“Com Error”.
-Wrong setting of the Ethernet port's
communication parameters.
-Wrong setting of the Slave port's
communication parameters.
-Wrong command addressing on the
Master port.
-Verify in the “Settings” menù :
for Ethernet port:
-IP address
-Port number reserved to the Modbus
TCP socket (Port)
-Time out value.
-Modbus node ID of the device.
for serial port (COM):
-COM port number.
-Baud rate.
-Modbus node ID of the device.
-Verify in the “Config” menù :
-Modbus node ID of the device.
-Baud rate.
- Delay of receiving (Slave port)
If the parameters have been correctly set
check the connection of the device
“Com Timeout”.
-With communication channel configured,
indicates a missing reception of the
response by the device.
-Wrong communication parameters.
“Label error”.
-One or more errors occur inside a
Function Block when the Program is
compiled,downloaded or verified.
44
-Verify in the “Settings” menù :
for Ethernet port:
-IP address
-Port number reserved to the Modbus
TCP socket (Port)
-Time out value.
-Modbus node ID of the device.
for serial port (COM):
-COM port number.
-Baud rate.
-Modbus node ID of the device.
-Check the parameters of the Function
Block identified by the index number
visualized inside the log window. (refer to
the sections 2.3 and 4.2).
TU RS485/ETH serie
6.2
CD Automation srl
ERROR MESSAGES INSIDE THE POP-UP WINDOWS
EVENT
“Controller not connected”.
“Timeout”.
POSSIBLE CAUSES
-The Controller is not connected.
-The communication channel selected
has not been enabled.
-The response provided by the Controller
is not correct and the communication has
been interrupted.
POSSIBLE SOLUTIONS
-Verify in the “Settings” menù :
for Ethernet port:
-IP address
-Port number reserved to the Modbus
TCP socket (Port)
-Time out value.
-Modbus node ID of the device.
for serial port (COM):
-COM port number.
-Baud rate.
-Modbus node ID of the device.
-Verify in the “Settings” menù :
for Ethernet port:
-IP address
-Port number reserved to the Modbus
TCP socket (Port)
-Time out value.
-Modbus node ID of the device.
for serial port (COM):
-COM port number.
-Baud rate.
-Modbus node ID of the device.
-Verify in the “Config” menù :
-Modbus node ID of the device.
-Baud rate.
- Delay of receiving (Slave port)
If the parameters have been correctly set
check the connection of the device
“Wrong response (function)”.
“Check values”.
- The Modbus slave device asked by the
Controller doesn't provide a correct
response.
-Verify in the “Config” menù :
-Modbus node ID of the device.
-Baud rate set for the Slave device.
- Delay of receiving (Slave port)
- Stop bit, Parity type.
- Number of the registers read or written.
-Modbus function code transmitted.
- Delay of receiving (Master port)
- One or more parameters of a Function
Block are not correct; this error occur
when the user clicks on the “OK” at the
moment to insert the Function Block in
the Program.
-Check the parameters of the Function
Block: for the functions of external
reading and writing, refer to the User
Guide of the Slave device in use.
45
TU RS485/ETH serie
6.3
CD Automation srl
POSSIBLE CAUSES OF FAULT
EVENT
POSSIBLE CAUSES
POSSIBLE SOLUTIONS
Is not possible to power-on the
Controller.
-The Controller is not correctly powered.
-The value of the power supply value is
lower than the specifications limits.
-Refer to the data-sheet of the Controller
in use and verify the relative Technical
Specifications.
There is not communication between
the Host PC and the Controller.
-Ethernet port not correctly connected.
-Modbus Slave port not correctly
connected.
-Eventual interface between PC and
Controller not correctly connected.
-Wrong communication parameters.
-Refer to the section 7.1
-Refer to the data-sheets of the Controller
and the Interface device in use.
-Refer to the section 8.1 .
There is not communication between
the Controller and one or more
Modbus slave devices.
-Modbus Master port not correctly
-Refer to the section 8.1
connected.
-Refer to the data-sheets of the Controller
-The slave device is not correctly powered. and the Slave devices in use.
-The slave device is not correctly
-Slave device in INIT condition and Baudconnected on the RS-485 serial line.
rate of communication different of 9600
-Wrong communication parameters.
bps.
-The Modbus addresses of the slave
-Verify the values of Gateway Mask.
devices connected are not included in the
range set in the System Register %S17
(Gateway Mask) .
The Program is not correctly executed -Wrong communication parameters.
-The Controller is in “Debug” modality and
or it is impossible to execute the
in Halt, Stop or Break Point condition.
Program.
-Wrong data-format of the Registers.
-Wrong parameters of the Function Block.
-Controller in Stack Overflow condition.
-Parameters of the eventual Slave
devices connected not correctly inserted.
-The Program has not been downloaded
-Controller in INIT modality.
The configuration of the Controller is
unknown.
-
-Refer to the section 8.1
-Set the Controller in “Debug” modality
and in “Run” condition or in “Release”
modality.
-Remove eventual Break Points.
-Set the correct data-format of Registers.
-Verify the parameters of Function Block
(data-format, masks, tables, etc..).
-Control, in the Program, the correspondence between Call and Return.
-Control the configuration of the Slave
devices ( type of input and output, etc..)
-Download the Program.
-Control if the INIT modality is active.
-Set the Controllore in “INIT” modality; the
parameters of configuration of the
Controller will be forced to the default
values listed in section 6.6 .
-Controller not correctly connected.
The Controller is connected in “INIT”
-Wrong port Baud Rate.
modality but is not executed (where
foresee the LED “STS” doesn't blink)
or there is not communication between
the Host PC and the Controller.
-Connect the terminal INIT to GND.
-Switch-off and than power-on the
Controller after the connection of the
terminal INIT to GND.
-Set the Baud-rate of the Slave Port as
9600 bps.
-Change or insert the battery.
-Control the parameters of the System
Registers (refer to the sections 3.3
and 3.4).
The functions Clock and Calendar
(where foresee) don't work correctly.
-Battery low or absent.
-Clock and Calendar parameters not
correctly set in the proper Registers.
The function “Search” doesn't find
any Controller.
-There are not Controllers connected.
-Refer to the data-sheet of the Controller
-Controllers not correctly connected.
in use and verify the relative Technical
-The Controllers connected by Ethernet
Specifications.
port has been set with communication
-Verify the parameters of the Ethernet
parameters not compatible with the
interface of the Host PC.
Ethernet interface of the Host PC in use. -Call the System Administrator in order to
-On the network are active Firewall or
connect the controller to the network.
Routers that block the access to the
Controller.
46
TU RS485/ETH serie
EVENT
CD Automation srl
POSSIBLE CAUSES
POSSIBLE SOLUTIONS
The function “Search” doesn't find any -There are not slave devices connected .
-The slave devices are not correctly
Slave device.
connected.
-The Controller which the slave devices
are connected to has not been selected.
-The Modbus addresses of the slave
devices connected are not included in the
range set in the System Register %S17
(Gateway Mask) or in the range set in the
menu “Search”.
- The baud-rate of the Slave devices
connected is not the same of that set for
the Master port of the Controller.
- The Timeout values are not correct.
-Refer to the data-sheets of the slave
devices in use and verify the relative
Technical Specifications.
-Verify that the Controller selected is the
same which the slave devices are
connected to.
- Verify the correspondence between
settings and Modbus addresses of the
slave devices.
-Verify the values of Gateway Mask.
-Control the baud-rate and delay time of
the slave devices connected.
The Web Pages haven't been loaded.
-Verify the IP address written in the
address bar.
-Verify the parameters of the Ethernet
interface of the Host PC.
-Call the System Administrator in order to
connect the controller to the network.
-The IP address written in the address bar
of the Internet browser is not the same of
Controller's IP address.
-The Controllers connected by Ethernet
port has been set with communication
parameters not compatible with the
Ethernet interface of the Host PC in use.
-On the network are active Firewall or
Routers that block the access to the
Controller.
-The data have been saved in General
The data saved as Kostant in the
Register table, are not saved when the Purpose Registers instead Retentive
Registers .
Controller is switched off.
6.4
-Save the kostant values in Retentive
Registers.
Warranty condition
CD Automation gives a 12 months warranty to its products.
The warranty is limited to repairing and parts substitution in our factory and
does exclude products not properly used and fuses.
Warranty does not include products with serial numbers deleted. The faulty
product should be shipped to CD Automation at customer’s cost and our Service will evaluate if product is under warranty terms.
Substituted parts remain of CD Automation property.
47
TU RS485/ETH serie
CD Automation srl
CD Automation s.r.l. reserves its rights to modify its products totally or in part without notice at any time.
48