90-NET UPS spec sheet

Add to my manuals
2 Pages

advertisement

90-NET UPS spec sheet | Manualzz

Secure Power Always

Chloride 90-NET UPS (180 - 750 kVA)

Secure, scalable power for today’s and tomorrow’s data center requirements.

Chloride 90-NET UPS

The Chloride 90-NET UPS Series is designed to meet the changing priorities and requirements of modern data centers in configurations of up to eight modules.

The series is optimized for high density applications ranging from conventional servers and communications gear to advanced blade servers—without derating or modification. Solid design and technology, paralleling capability, and dual inputs assure the highest levels of system availability while setting new standards for efficiency, cost-effectiveness, flexibility, and quiet operation.

Dependable technology

• True on-line operation

• High efficiency

• Blade server (leading power factor) ready

• 0.9 leading to 0.9 lagging output power factor

• Vector-control IGBT inverter

• Advanced battery management

• Low input THDi

• LIFE.net for real-time monitoring of UPS status from the Chloride Service Center

Versatile options

• External maintenance bypass

• Space-saving internal maintenance bypass

• ManageUPS CIO web based management software

• ManageUPS Net Adapter +B Modbus

• MopUPS ® PR parallel/redundant management/shutdown software

• Extended warranties and service plans

• Preventative maintenance packages

• Multiple bus synchronization module

Convenient features

• Parallelable, up to 8 modules

• User friendly display and operator controls

• 180-500 kVA models include ManageUPS ®

Adapter - SNMP/Web for UPSs*

• Quiet operation

• Dual input capability

• Power walk-in capability (selectable)

• Generator mode (selectable)

• Easy installation and maintenance

• Internal maintenance bypass standard on 180-500 kVA models, optional on

750 kVA models

* 750 kVA models include ManageUPS Adapter +E (with envoronmental sensors)

Reliable service

• 24-hour technical support

• Nationwide network of local, experienced factory trained technicians

Assured safety & quality

• Listed to UL 1778, CSA 22.2 No. 107.3

• ISO 9001 & ISO 14001

R

Three-Phase On-line UPS

Chloride 90-NET UPS (180 - 750 kVA)

90-NET UPS model 180 kVA

Model 225

225 kVA 300 kVA

Model 400

400 kVA

Model 500 Model 750

500 kVA 750 kVA

Base unit part number 90NET/225/180-44 90NET/225/225-44 90NET/400/300-44 90NET/400/400-44 90NET500/500-44 90NET/750/750-44

Power rating @ 0.9 power factor (kVA/kW) 180/162 225/202 300/270 400/360 500/450 750/675

Input voltage single input (VAC) 480, 480/277 (if neutral is used) 480, 480/277 (if neutral is used)

480, 480/277

(if neutral is used)

480, 480/277

(if neutral is used)

Input voltage dual input (VAC) 480 rectifier, 480/277 bypass (if neutral is used) 480 rectifier, 480/277 bypass (if neutral is used)

480 rectifier, 480/277 bypass (if neutral used)

480 rectifier, 480/277 bypass (if neutral is used)

Input voltage tolerance

Input frequency (Hz)

Input power factor

+ 15% / -15%

60 ±5%

>0.9

+ 15% / -15%

60 ±5%

>0.9

+ 15% / -15%

60 ±5%

>0.9

+ 15% / -15%

60 ±5%

>0.9

Input current (nominal/maximum) (A)

Input THDi

Output voltage (VAC)

Output voltage regulation

Nominal output current (A)

Voltage THD

Load power factor (without derating)

Output frequency (Hz)

System efficiency

Full load heat rejection (BTU/hr)

Runtimes

UPS dimensions HxWxD - in (cm)

225/295

217

285/355

≤ 7%

480/277

271

< 3% for 100% linear loads

0.9 leading - 0.9 lagging

60 Hz ± 0.75% (selectable) up to 93.4%

39,059 up to 93.5%

48,033 call factory

386/466 513/625

≤ 7%

641/780

≤ 7%

480/277 480/277

±1% with balanced load; ±3% with 100% unbalanced load

361 601

77.3 x 56 x 33.6 (196.4 x 142.2 x 85.4)

481

< 3% for 100% linear loads

0.9 leading - 0.9 lagging

60 Hz ± 0.75% (selectable) up to 93.6%

63,100 up to 93.8%

81,300 call factory

903

< 3% for 100% linear loads

0.9 leading - 0.9 lagging

60 Hz ± 0.75% (selectable) up to 93.8% up to 93%

101,500 call factory

77.3 x 56 x 33.6 (196.4 x 142.2 x 85.4)

962/1173

≤ 5%

480/277

173,402 call factory

77.3 x 131.3 x 33.6

(196.4 x 333.5 x 85.4)

UPS net weight - lbs (kg)

UPS ship weight - lbs (kg)

Overload capacity

Inverter technology

Maximum acoustical

Connectivity

Temperature

Relative humidity

Altitude

2,867 (1,300)

3,067 (1,391)

4,515 (2,048)

4,715 (2,138)

4,975 (2,257)

5,175 (2,347)

9,371 (4,250)

9,820 (4,454)

150% for 1 minute; 125% for 10 minutes

IGBT with vector control system—

DSP technology for real time response to overloads and power disturbances

65 dBA @ 1 meter 65 dBA @ 1 meter 70 dBA @ 1 meter 70 dBA @ 1 meter 72 dBA @ 1 meter 75 dBA @ 1 meter

SNMP, dry contact, RS-232 (standard) operating: +32°F - +104°F (0°C - +40°C)

≤ 95%, non-condensing

5000 feet (1500 m) asl without derating

This company has a policy of continuous product development and improvement, and we therefore reserve the right to vary any information or specification without prior notice.

This publication is issued to provide outline information only and is not deemed to form any part of any offer and contract.

ManageUPS and MopUPS are registered trademarks of ONEAC. All other trademarks, product and corporate names are the property of their respective owners.

© 2008 Chloride Group PLC

Chloride North America

27944 North Bradley Road

Libertyville, IL 60048

USA

T 800 327 8801, 847 816 6000

F 847 680 5124 www.chloridepower.com/usa