Premoulded screened separable connectors
Type SOC 400
WWW.CABLEJOINTS.CO.UK
THORNE & DERRICK UK
TEL 0044 191 490 1547 FAX 0044 477 5371
TEL 0044 117 977 4647 FAX 0044 977 5582
WWW.THORNEANDDERRICK.CO.UK
Kabeldon Cable Accessories 12-24 kV
Kabeldon premoulded screened Separable Connectors, 400 A
1
6
7
2
4
5
3
8
9
10
Routine test
All connectors are routinely tested with respect to
Pd < 5 pC at 22 kV
AC
Visual inspection
45 kV for one minute
1. Insulating plug
Made of epoxy with embedded brass parts.
The outer brass plate comes into contact with the conductive layer for a fully screened connection.
Also available with insulation in between and a separate contact spring for capacitive testing.
2. Pin contact
See opposite page.
3. Bail restrain
A stainless steel frame holds the connector on the place by means of a pressure plate and a bolt.
4. Cable lug
Bolted type, tested and approved in accordance with IEC 61238-1. The cable lug is made of aluminium alloy and is tin-plated. Can be installed on aluminium as well as copper conductors, as the connection is encapsulated inside the connector and is not subjected to humid conditions.
5. Inner conductive layer
Creates a Faraday cage around the connector.
This ensures a stable electrical potential and eliminates the need for fi lling material in cavities and between the conductor and cable lug.
6. Insulating layer
High electrical strength, a thickness of min 10 mm and the elasticity of the material ensures the function with active pressure on all interfaces.
Premoulded together with the inner and outer conduictive layer. Electrical properties are ensured by routine test.
7. Outer conductive layer
UV-, ozone- and tracking-resistant. UV-resistance tested for 3000 h in a Xenon radiator. Thickness
2 mm on it’s thinnest part. When connected to the cable screen, the connector meets international requirements for a fully screened system.
8. Adapter
Made of fl exible insulating rubber with an integrated resistive stress control part.
9. Earth connection
The conductive layer is connected to the cable screen via a stainless steel band strip. The band strip can temporarily be removed from the cable screen, which makes it possible to perform cable sheath tests without disconnecting the connector from the bushing.
10. Designed for polymeric insulated cables
SOC screened connectors can be installed on XLPE as well as EPR (fl exible rubber) insulated cables.
Technical data
Lightning impulse withstand
Interface standard for bushing
Current-carrying capacity
Cable conductor size
Cable insulation diameter
125 kV
EN 50180 & EN 50181
400 A
50 - 300 mm²
15.0 - 34,9 mm
All dimensions in mm
Type test according to CENELEC HD 628.1 and 629.1 test sequence D1 and D2
The screened separable connectors have been tested and approved in accordance with this international standard.
Pin contact SOC 400
The pin contact is made of copper and is silver-plated. An expansion ring installed with a torque wrench keeps the pin in contact with the cable lug. The whole connector is secured to the bushing by means of a bail restrain.
Test sequence D1
1. DC voltage withstand test at 76 kV negative polarity for 15 min
2. AC voltage withstand test at 57 kV for 5 minutes
3. Pd measurement at ambient temperature at 24 kV
4. Lightning impulse voltage test at 95°C with peak values 125 kV, 10 positive and 10 negative impulses
5. Load cycling in air 3 x 8 h at 32 kV
6. Pd measurement at elevated and ambient temperature at 24 kV
7. Load cycling in air 60 x 8 h at 32 kV
8. Load cycling under 1 m water 63 x 8 h at 32 kV
9. Disconnection / connection 5 complete operations
10. Pd measurement at elevated and ambient temperature at 24 kV
11. Lightning impulse voltage test at ambient temperature with peak values 125 kV, 10 positive and 10 negative impulses
12. AC voltage withstand test at 32 kV for 15 minutes
Bushings as per
EN 50181 & EN 50181
R3
R3
40
R3
11
5, 5
90
Bail holde r
400 series, 400 A
Contact type: sliding Ø14
Interface type: B
Requirements
No breakdown or fl ashover
No breakdown or fl ashover
Discharge level <10 pC
No breakdown or fl ashover
No breakdown or fl ashover
Discharge level <10 pC
No breakdown or fl ashover
No breakdown or fl ashover
No visible damage to contacts
Discharge level <10 pC
No breakdown or fl ashover
No breakdown or fl ashover
Test sequence D2 Requirements
13. Thermal short circuit test for 1 sec to reach a conductor temperature of 250°C No visible signs of damage
14. Lightning impulse voltage test at ambient temperature with peak values 125 kV, 10 positive and 10 negative impulses
15. AC voltage withstand test at 32 kV for 15 minutes
No breakdown or fl ashover
No breakdown or fl ashover
For information only 16. Examination
Tests Nos. 17 - 19 are carried out on separate test objects
17. Screen resistance measurement before and after ageing
18. Leakage current measurement
19. Screen fault current initiation
Resistance <5000
Leakage current <0.5 mA at 24 kV
Fault current should fl ow continuously
210
SOC 400
Type test according to Class A in IEC 61238-1: Compression and mechanical connectors for power cables with copper or aluminium conductors
Screw cable lugs included in SOC 400 have been tested and approved according to this international standard.
Electrical test. The current cycling test was performed with a 300 mm² aluminium conductor.
Test sequence Requirements
1. The fi rst and second cycle are used to determine the reference conductor temperature and the heat cycle duration used on the test loop for all subsequent heat cycles.
Reference conductor 122.1°C, total cycle time 1 h 30 min.
2. 200 heat cycles performed
3. Six short-circuits to reach a conductor temperature of 250 - 270°C with cooling to a temperature 35°C after each short circuit.
Short circuit current 25 kA for 2.4 seconds.
4. Another 800 heat cycles are performed, 1000 cycles in total
Test result for the electrical test with resistance measurement
A Initial scatter, prior to heat cycling
B Mean scatter, over the last 11 resistance measurement intervals
C Change in resistance factor D, for each of the six connectors
D Resistance factor ratio, for each of the six connectors
0.3
0.3
0.15
1.5
Reference conductor (122.1°C)
Mechanical test
Tensile force during 1 min. Requirement aluminium 40 N x A and copper 60 N x A. Maximum force 20 kN.
A = Nominal conductor cross-section in mm². Test performed with the following conductor sizes:
Aluminium 150 mm²
Aluminium 185 mm²
Aluminium 300 mm²
Copper 150 mm²
6 kN
7.4 kN
12 kN
9 kN
ABB Kabeldon
ABB Automation Technologies AB
Box 531
SE-441 15 Alingsås, Sweden
Tel: +46 322 770 00
Fax: +46 322 770 01 www.abb.se/kabeldon
WWW.CABLEJOINTS.CO.UK
THORNE & DERRICK UK
TEL 0044 191 490 1547 FAX 0044 477 5371
TEL 0044 117 977 4647 FAX 0044 977 5582
WWW.THORNEANDDERRICK.CO.UK
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement