Castle Care-Tech EURO mini Security access control system Installation Manual

Castle Care-Tech EURO mini Security access control system Installation Manual

CASTLE EURO is a versatile and reliable security system designed to protect your premises from intruders, fire, and other hazards. It features 10 fully programmable inputs, each of which can be configured as unused, fire, hold up, 24-hour, intruder, final exit, entry route, ER (FX in part), FX (ER in part), keyswitch latched, or keyswitch pulsed. The system also includes 4 programmable outputs that can be programmed as PGM, bell, strobe, or outputs on inputs 7, 8, 9, and 10.

advertisement

Assistant Bot

Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.

EURO mini Installation Manual | Manualzz

I n s t a l l a t i o n M a n u a l

2 x 2 x

EN50131-1

Grade 2 Compliance

EN50131-1

Grade 2 Compliance

C

ontents Page

System Overview

Technical Specification

Overview

The Control Panel

The Printed Circuit Board

The Tamper Spring and Connections

Connections

Transformer / Battery Connection

Keypad Connection

Reader Connection

Double Pole - Alarm Connections

Double Pole - Tamper Connections

DEOL: 4K7 Alarm, 2K2 Tamper

DEOL: 4K7 Alarm, 4K7 Tamper

Siren Connection

Speaker Connection

Output Connection/Example

Compliance Statement and Warranty

Compliance Statement

Warranty

Input Table Appendix

6

8

9

6

7

4

5

12

13

13

14

9

10

11

12

14

15

16

16

16

17

Castle Care-Tech Page:3

S

ystem Overview

10 fully programmable inputs Inputs on main control panel

Input configuration Double end of line (4K7 Alarm, 2K2 Tamper)

Double end of line (4K7 Alarm, 4K7 Tamper)

Double Pole

Input Types

Programmable

Outputs

Output Types

Unused, Fire, Hold Up, 24 Hour, Intruder, Final

Exit, Entry Route, ER (FX in part), FX (ER in part),

Keyswitch Latched, Keyswitch Pulsed

PGM, Bell, Strobe + 4 Outputs on Inputs 7,8,9 and 10

(programmed either as an input or output)

Not Used, Fire, Hold Up Any, Intruder Any, Tamper Any,

Set Fail, Entry Deviation, Siren Any, Strobe Any, Exit

Starts Any, Final Set Any, Strobe Set Fail, Keyswitch

Unset, Entry/Exit, Lights, Restore 1, Restore 2, PIR

Latch 1, PIR Latch 2, Mains Good, Detr Indn Enable,

Follow Test, Off During Test, Detr Walk Test, Mains Fail,

Battery Fault, Low Volts, Global Fault 1, Global Fault 2,

Engineer Access

Keypad Contemporary LCD Keypad 32 Character

Number of Keypads 4

Arming Options

User Codes

Timed, Final Door, Timed/Final

30 user codes, 1 Master Manager, 1 Engineer

Logs

Fuses

Tampers

500 Mandatory, 200 Optional

AUX, Bell, RS485 Bus, Battery

Case Tamper and Siren Tamper

Page:4 Castle Care-Tech

T

echnical Specification

Electrical Specification

Supply Voltage (A.C.) 18VAC Nominal (+-20%), 50Hz (+-10%)

Supply Voltage (D.C.) 12VDC Nominal (10-15 Volt DC Range)

Power Supply 1A Regulated

Supply Current <80mA Quiescent (DC supply, no active outputs)

Battery supply protection Reverse polarity protected

Battery final disconnect

voltage 10.5V

PGM/SAB outputs Switched negative 1Ah (max)

Shared PGM outputs Switched negative 50mA (max)

SAB/AUX supply fuses 800mA quick-blow

Battery reverse

protection fuse 1.6A slow-blow

Mains Fuse Mains Fuse - Anti-Surge 315mA

Physical/Mechanical Specification

Dimensions 250 x 297 x 82mm

Weight 3.07 kilos

Environmental Specification

Operational temperature

range -20°C to +60°C

Storage temperature

range -20°C to +60°C

Electrical Rating: 1A. EN50131-6:1997 rating: 875mA when used in Grade 1 system, 465mA when used in Grade 2 system

Battery recommend 3Ah or 7Ah (Max)

Castle Care-Tech Page:5

O verview

Control Panel

The EURO mini is already fully assembled in a metal case. The diagram below shows a basic overview of the different components.

The Control Panel

Wall Fixing

Holes

BELL

BUS

AUX

Remove for DP

BATTERY

Z1 GND Z2 GND +12V Z3 GND Z4 Z5 GND Z6 GND +12V Z7 GND Z8 Z9 GND Z10 D1- D2+ D3 D4 - BAT + GND

Cable

Entry Holes

Mains

Transformer

Battery

Holder

3Ah or 7Ah Battery

Fuse carrier handle

Mains Fuse

Anti-Surge: 315mA

Live

Earth

Neutral

To Mains Supply

Main Cable

Entry Hole

Page:6 Castle Care-Tech

O

verview

The EURO mini printed circuit board is as follows:

The Printed Circuit Board

Power LED

(flashes) Fuses

Printed Circuit Board

BELL

BUS

Remove for DP

AUX

BATTERY

Z1 COM Z2 COM +12V Z3 COM Z4 Z5 COM Z6 COM +12V Z7 COM Z8 Z9 COM Z10 D1- D2+ D3 D4 - BAT + GND

Double Pole

Link

The Z1 and Z2 GND terminal cannot be used as 0V

PGM Output 1

AUX+ +12V Supply

SPK Speaker Output

STB Output 2

BELL Output 3

TR

B-

Siren Tamper Return

0V

B+

Z1

+12V Supply

Input 1

COM Common Only

Z2 Input 2

COM 0V/Common

+12V +12V Supply

Z3 Input 3

COM 0V/Common

Z4

Z5

Input 4

Input 5

COM 0V/Common

Z6

COM 0V/Common

+12V +12V Supply

Z7

COM 0V/Common

Z8

Z9

D3

D4

~

Input 6

Input 7 / Output 4

Input 8 / Output 5

Input 9 / Output 6

COM 0V/Common

Z10 Input 10 / Output 7

D1-

D2+

RS485 Bus: 0V

RS485 Bus: +12V

RS485 Bus: Data A

RS485 Bus: Data B

-BAT Battery Negative

BAT+ Battery Positive

GND Earth

~ 17V Input

17V Input

Fuses

Castle Care-Tech Page:7

O

verview

Tamper Connections

The EURO mini printed circuit board is protected by a metal casing. The lid is tampered by a spring that is connected to the printed circuit board.

To disable the tamper spring, simply link out the tamper connections shown below.

The Tamper Spring and Connections

Tamper

Connection

Tamper

Spring

BELL

BUS

Remove for DP

AUX

BATTERY

Z1 COM Z2 COM +12V Z3 COM Z4 Z5 COM Z6 COM +12V Z7 COM Z8 Z9 COM Z10 D1- D2+ D3 D4 - BAT + GND

Page:8 Castle Care-Tech

C onnections

Transformer

Battery

The transformer will be factory fitted to the connections shown below on the

EURO mini.

It is recommended that a 3Ah or 7Ah battery should be used on the EURO mini.

This connects to the Battery positive and negative terminals.

Transformer / Battery Connection

BELL

BUS

AUX

Remove for DP

BATTERY

Z1 COM Z2 COM +12V Z3 COM Z4 Z5 COM Z6 COM +12V Z7 COM Z8 Z9 COM Z10 D1- D2+ D3 D4 - BAT + GND

Battery 12V

Transformer

To Earth terminal of mains block

Castle Care-Tech Page:9

C onnections

Contemporary

Keypad

A maximum of 4 keypads may be installed to the EURO mini. Each keypad

(EUR-068 or EUR-069) connects to the RS485 terminal: D1-, D2+, D3 and D4.

Each keypad must be individually addressed, starting with 00. To do this, press and hold the ‘D’ key, until ‘KEYPAD CODE’ is displayed. Enter ‘2000’ and select the appropriate address. Press the ‘YES’ key to change any other required options, and the ‘A’ key to save the data.

Keypad Connection

BELL

BUS

AUX

Remove for DP

BATTERY

Z1 COM Z2 COM +12V Z3 COM Z4 Z5 COM Z6 COM +12V Z7 COM Z8 Z9 COM Z10 D1- D2+ D3 D4 - BAT + GND

4

7

0

470ohm Resistor connected to the control panel and to the device which is furthest away

4

7

0

D1- D2+ D3 D4

Page:10 Castle Care-Tech

C onnections

Internal Tag

Reader

A maximum of 3 readers may be installed to the EURO mini if the EUR-068 is installed. Each connect to the RS485 terminal: D1-, D2+, D3 and D4.

Each reader must be individually addressed, starting with 01. To do this, there are dip switches on the back of the reader.

Address

2

1

8

4

32

16

To address the reader as 02 for example, dip switch “2” must be selected to the right (towards the address number)

To address the reader as 01 for example, dip switch “1” must be selected to the right (towards the address number)

Reader Connection

BELL

BUS

AUX

Remove for DP

BATTERY

Z1 COM Z2 COM +12V Z3 COM Z4 Z5 COM Z6 COM +12V Z7 COM Z8 Z9 COM Z10 D1- D2+ D3 D4 - BAT + GND

4

7

0

470ohm Resistor connected to the control panel and to the device which is furthest away

4

7

0

D1- D2+ D3 D4

Castle Care-Tech Page:11

C onnections

BELL

BUS

Double Pole

Input Wiring

If double pole is used, the link above input 1 (shown below) needs to be open.

Double pole requires no resistors, but it requires a dedicated tamper circuit

(When a clean start 2002 is performed, input 1 is defaulted as tamper).

The first diagram below shows the connection of door contacts/detectors to the

Z1 COM Z2 COM +12V Z3 COM Z4 Z5 COM Z6 COM +12V Z7 COM Z8 Z9 COM Z10 D1- D2+ D3 D4 - BAT + GND

EURO mini, the second diagram shows how the tamper circuits of each detector should be connected. The diagrams are split for clearer wiring connections.

Please note that any ‘terminal blocks’ used should be located inside the control panel.

BELL

+12V GND +12V GND

BUS

+12V GND

Example cable

wiring

R = Red

B = Black

Y = Yellow

G = Green

Y G

Remove for DP

B Y G R B Y G R B Y G

BATTERY

Spare N/C Contact

+AUXALARM TAMPER +AUXALARM TAMPER +AUXALARM TAMPER

This link

Z1 COM Z2 COM +12V Z3 COM Z4 Z5 COM Z6 COM +12V Z7 COM Z8 Z9 COM Z10 D1- D2+ D3 D4 - BAT + GND

Input 2 should be OFF

Y G

Input 3

Detector

+12V GND

R B Y G

Input 4

Detector

+12V GND

R B Y G

Input 5

Detector

+12V GND

R B Y G

Example cable

wiring

R = Red

B = Black

Y = Yellow

G = Green

Spare N/C Contact

+AUXALARM TAMPER +AUXALARM TAMPER

Input 2

Door Contact

BELL

Input 3

Detector

Double Pole - Tamper Connections

AUX

Remove for DP

Input 4

Detector

BUS

+AUXALARM TAMPER

Input 5

Detector

BATTERY

Z1 COM Z2 COM +12V Z3 COM Z4 Z5 COM Z6 COM +12V Z7 COM Z8 Z9 COM Z10 D1- D2+ D3 D4 - BAT + GND

BELL

Example cable wiring

W = White

Blu = Blue

Terminal Block (inside control panel)

Terminal Block (inside control panel)

This link should be OFF AUX

Remove for DP

W Blu W Blu

+AUXALARM TAMPER +AUXALARM TAMPER +AUXALARM TAMPER

Z1 COM Z2 COM +12V Z3 COM Z4 Z5 COM Z6 COM +12V Z7 COM Z8 Z9 COM Z10 D1- D2+ D3 D4 - BAT + GND

Input 3

Detector

Input 4

Detector

Input 5

Detector

Example cable wiring

W = White

Blu = Blue

Terminal Block (inside control panel)

Terminal Block (inside control panel)

This link

Page:12 Castle Care-Tech

+AUXALARM TAMPER

Input 3

Detector

+AUXALARM TAMPER

Input 4

Detector

+AUXALARM TAMPER

Input 5

Detector

BELL

BUS

BATTERY

AUX

Remove for DP

This link should be ON

Z1 COM Z2 COM +12V Z3 COM Z4 Z5 COM Z6 COM +12V Z7 COM Z8 Z9 COM Z10 D1- D2+ D3 D4 - BAT + GND

4

K

7

4

K

7

+12V GND

4

K

7

4

K

7

Spare N/C Contact

Input 1

Door Contact

+AUXALARM TAMPER

Input 2

Detector

C onnections

Resistor

Input Wiring

If double end of line is used, the link above input 1 (shown below) needs to be closed, and specific resistors need to be used depending on which mode is selected (see Choose Mode in the programming manual). There are 2 choices:

BUS

DEOL: 4K7 Alarm, 2K2 Tamper

AUX

Remove for DP

BATTERY

This link should be ON

Z1 COM Z2 COM +12V Z3 COM Z4 Z5 COM Z6 COM +12V Z7 COM Z8 Z9 COM Z10 D1- D2+ D3 D4 - BAT + GND

4

K

7

2

K

2

+12V GND

4

K

7

2

K

2

Spare N/C Contact +AUXALARM TAMPER

Input 1

Door Contact

BELL

Input 2

Detector

DEOL: 4K7 Alarm, 4K7 Tamper

AUX

Remove for DP

BUS

BATTERY

This link should be ON

Z1 COM Z2 COM +12V Z3 COM Z4 Z5 COM Z6 COM +12V Z7 COM Z8 Z9 COM Z10 D1- D2+ D3 D4 - BAT + GND

4

K

7

4

K

7

+12V GND

4

K

7

4

K

7

Spare N/C Contact

Input 1

Door Contact

+AUXALARM TAMPER

Input 2

Detector

Castle Care-Tech Page:13

BELL

BUS

AUX

Remove for DP

BATTERY

This link should be ON

Z1 COM Z2 COM +12V Z3 COM Z4 Z5 COM Z6 COM +12V Z7 COM Z8 Z9 COM Z10 D1- D2+ D3 D4 - BAT + GND

4

K

7

2

K

2

+12V GND

4

K

7

2

K

2

Spare N/C Contact

Input 1

Door Contact

+AUXALARM TAMPER

Input 2

Detector

C onnections

Siren Connection

Speaker Connection

The connections for a +12V Siren are described below, at default all outputs are negative applied and this cannot be altered.

There is also a connection for 1 or 2 16ohm speakers, which will follow the keypad sounds.

Siren Connection

BELL

BUS

AUX

Remove for DP

BELL

BATTERY

BUS

Z1 COM Z2 COM +12V Z3 COM Z4 Z5 COM Z6 COM +12V Z7 COM Z8 Z9 COM Z10 D1- D2+ D3 D4 - BAT + GND

AUX

Remove for DP

BATTERY

+12V Supply

0V

Siren

Bell Trigger

0V

Bell Tamper

Bell Trigger

Strobe Trigger

Siren

Speaker Connection

BELL

BUS

AUX

Remove for DP

BELL

BATTERY

BUS

Z1 COM Z2 COM +12V Z3 COM Z4 Z5 COM Z6 COM +12V Z7 COM Z8 Z9 COM Z10 D1- D2+ D3 D4 - BAT + GND

AUX

Remove for DP

BATTERY

1 or 2 16ohm speakers may be wired in parallel

1 or 2 16ohm speakers may

Page:14 Castle Care-Tech parallel

C onnections

Output

Connections

The EURO mini supports up to 7 outputs. 4 of the outputs are shared with inputs on the system, therefore if the outputs are used (see Change Outputs in the programming manual), inputs 7 to 10 become disabled. All outputs on the system are negative applied and cannot be altered.

The example below shows how to connect a typical 12V dialler.

Output Connection/Example

BELL

BUS

AUX

Remove for DP

BATTERY

Z1 COM Z2 COM +12V Z3 COM Z4 Z5 COM Z6 COM +12V Z7 COM Z8 Z9 COM Z10 D1- D2+ D3 D4 - BAT + GND

All outputs are negative applied

GND +12V

In this example the inputs are programmed as outputs

See ‘Change Outputs’ section in the Programming manual.

1 2 3 4 5 0v +12V

Inputs Auxillary

Example

Auto Dialler

Castle Care-Tech Page:15

C ompliance Statement and Warranty

Compliance Statement

The EURO mini complies with the requirements of the EMC Directive (2004/108/

EC) and the Low Voltage Directive (2006/95/EC).

The EURO mini complies with TS50131-3:2003

Suitable for use in systems installed to PD6662 (AMD2) at security grade 1 or 2X and environmental class 2.

2 x

TS50131-3:2003

EN50131-1

PD6662:2004

Security Grade 2x

Environmental Class 2

Warranty

EN50131-1

Grade 2 Compliance

This product is sold subject to our standard warranty conditions and is warranted against defects in workmanship for a period of 18 months. In the interest of continuing improvement of quality, customer care and design, Castle Care Tech

Ltd reserves the right to amend specifications without giving prior notice.

Page:16 Castle Care-Tech

I

nput Table Appendix

Input Type Input

Number

Input Areas

4

5

6

1

2

3

9

10

7

8

Description

Castle Care-Tech Page:17

Page:18 Castle Care-Tech

Castle Care-Tech Page:19

Contact Details

Castle Care-Tech Ltd

First Floor

6 Bracknell Beeches

Old Bracknell Lane West

Bracknell

Berkshire

RG12 7BW

Helpdesk:

01344 469499

Opening Hours:

7.00am - 7.30pm

Monday to Friday

E-mail:

[email protected]

Website:

www.castle-caretech.com

advertisement

Key Features

  • Fully programmable
  • Supports up to 10 inputs and 7 outputs
  • Contemporary LCD Keypad
  • Tamper-proof case
  • Battery backup

Frequently Answers and Questions

How many keypads can I install with the EURO mini?
You can install up to 4 keypads with the EURO mini.
What type of battery should I use with the EURO mini?
A 3Ah or 7Ah battery is recommended for use with the EURO mini.
What is the maximum number of readers that can be installed?
You can install a maximum of 3 readers with the EURO mini if the EUR-068 is installed.