SMC LECSA Series AC Servo Motor Driver Operation Manual

SMC LECSA Series AC Servo Motor Driver Operation Manual
Add to My manuals

Below you will find brief information for AC Servo Motor Driver LECSA Series. The LECSA Series AC Servo Motor Driver is a versatile device, suitable for a variety of applications, featuring various control modes and settings including position control, speed control, torque control and positioning mode, utilizing both pulse input and point table methods. The device offers features such as home position return, automatic tuning, and selectable electronic gears.

advertisement

Assistant Bot

Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.

AC Servo Motor Driver LECSA Series Operation Manual | Manualzz

Doc. no. LEC-OM05607

 

 

 

 

(Simplified Edition)

 

PRODUCT NAME

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AC Servo Motor Driver

(Pulse input type/Positioning type)

MODEL / Series / Product Number

LECSA Series

       

 

Contents

Contents ......................................................................................................1

Introduction.................................................................................................6

Terms ...........................................................................................................6

1.

Configuration.........................................................................................6

2.

Pre-Operation Procedure......................................................................7

2.1

Flow chart ...........................................................................................................7

3.

Wiring .....................................................................................................8

3.1

Power Supply Wiring ......................................................................................... 8

3.2

I/O signal connection example ......................................................................... 9

3.2.1

Position control mode .......................................................................................... 9

3.2.2

Speed control mode............................................................................................12

3.2.3

Torque control mode .......................................................................................... 13

3.2.4

Positioning mode ................................................................................................ 14

3.2.5

Source I/O interfaces .......................................................................................... 15

4.

List of Parameters for each Mode........................................................16

4.1

Parameters common to each mode................................................................ 16

4.2

Position control mode ..................................................................................... 16

4.3

Speed control mode......................................................................................... 16

4.4

Torque control mode ....................................................................................... 17

4.5

Positioning mode ............................................................................................. 17

5.

Parameter Configuration using Setup software (MR Configurator

18

TM

)

5.1

PC Setup software (MR Configurator

TM

) ........................................................ 18

5.1.1

Installation Method ............................................................................................. 18

5.2

Basic driver set-up for Initial Test Drive......................................................... 18

5.2.1

Start up the Setup software (MR Configurator

TM

)............................................. 19

5.2.2

Driver ON LINE Check ........................................................................................ 20

5.2.3

Help Function ...................................................................................................... 20

5.2.4

“System Settings” .............................................................................................. 21

5.2.5

Model Selection................................................................................................... 21

5.2.6

Parameter Upload ............................................................................................... 22

5.3

Parameter Settings .......................................................................................... 23

5.3.1

Settings to Allow Configuration of all Parameters........................................... 23

5.3.2

“Control mode selection”................................................................................... 24

5.3.3

Parameter Configuration Method ...................................................................... 26

5.3.4

Recommended Parameter Values by Actuator Model ..................................... 27

5.3.5

Position control mode (pulse input).................................................................. 32

5.3.6

Electronic Gears ................................................................................................. 34

5.3.7

Automatic Input Signal ON Selection Parameter Configuration..................... 35

5.4

JOG Mode in the Setup Software.................................................................... 37

5.4.1

JOG Mode ............................................................................................................38

5.5

Changing I/O Signal Allocation....................................................................... 39

5.5.1

Initial I/O Signal Allocation ................................................................................. 39

- 1 -

5.5.2

Signal Allocation using Setup Software............................................................ 40

5.5.3

Allocation Examples for Position Control Mode (Pulse Input) ....................... 41

5.5.4

Setting a Maximum of 7 Points using the Point Table in Positioning mode (Point

Table) 43

5.5.5

I/O Signal Allocation Check................................................................................ 47

5.6

Positioning Mode in Setup Software .............................................................. 48

5.6.1

Positioning Mode ................................................................................................ 49

5.6.2

Motorspeed Configuration ................................................................................. 50

5.6.3

Acceleration/deceleration Time Configuation .................................................. 51

5.6.4

Move distance Configuration and Operation< Move distance Configuration>52

5.7

Positioning (Point Table) Operation using the Setup Software ................... 53

5.7.1

Point table List .................................................................................................... 53

5.7.2

Point Table Data .................................................................................................. 53

5.7.3

Point table (Position data) Configuration.......................................................... 54

5.7.4

Point table (Servo Mmotor Speed) Configuration ............................................ 55

5.7.5

Point Table (Acceleration time constant/Deceleration time constant) Configuration

56

5.7.6

Other Settings ..................................................................................................... 56

5.7.7

Single-Step Feed ................................................................................................. 57

5.8

Saving/Loading Parameters............................................................................ 58

5.8.1

Saving Parameters.............................................................................................. 58

5.8.2

To Load saved Parameters................................................................................. 59

6.

Home Position Return Method .............................................................60

6.1

Position Control Mode (Pulse Input) .............................................................. 60

6.2

Positioning mode (point table)........................................................................ 60

6.2.1

Stopper type home position return ................................................................... 61

7.

Diriving Methods for Each Mode .........................................................63

7.1

Position Control Mode (Pulse Input) .............................................................. 63

7.1.1

Position Control Mode Instructions .................................................................. 63

7.2

Speed control mode......................................................................................... 64

7.2.1

Speed Control Mode Operation Instruction ...................................................... 64

7.3

Torque control mode ....................................................................................... 65

7.3.1

Torque Control Mode Operation Instruction..................................................... 65

7.4

Point table method........................................................................................... 66

7.4.1

Operation Instruction of Point Table system .................................................... 66

7.4.2

Setting method.................................................................................................... 68

7.5

Positioning Mode (Programimg Method) ....................................................... 69

7.5.1

Setting method.................................................................................................... 69

7.5.2

Command in the program system ..................................................................... 70

7.5.3

Operation Instruction Method of Program System .......................................... 71

8.

Troubleshooting ....................................................................................72

8.1

Alarms and Warning List ................................................................................. 72

- 2 -

 

LECSA Series / Driver

Safety Instructions

 

These  safety  instructions  are  intended  to  prevent  hazardous  situations  and/or  equipment  damage.  These  instructions  indicate the level of potential hazard with the labels of “Caution,” “Warning” or “Danger”. They are all important notes for  safety and must be followed in addition to International Standards (ISO/IEC), Japan Industrial Standards (JIS) *1.) and other  safety regulations*2.). 

*1) ISO 4414: Pneumatic fluid power -- General rules relating to systems

ISO 4413: Hydraulic fluid power -- General rules relating to systems

IEC 60204-1: Safety of machinery -- Electrical equipment of machines (Part 1: General requirements)

ISO 10218-1992: Manipulating industrial robots -- Safety

JIS B 8370: General rules for pneumatic equipment.

JIS B 8361: General rules for hydraulic equipment.

JIS B 9960-1: Safety of machinery – Electrical equipment for machines. (Part 1: General requirements)

JIS B 8433-1993: Manipulating industrial robots - Safety. etc.

*2) Labor Safety and Sanitation Law, etc.

 

 

 

Caution

Warning

Caution indicates a hazard with a low level of risk which, if not avoided, could result in minor or moderate injury.

Warning indicates a hazard with a medium level of risk which, if not avoided, could result in death or serious injury.

 

 

Danger

Danger indicates a hazard with a high level of risk which, if not avoided, will result in death or serious injury.

Warning

1. The compatibility of the product is the responsibility of the person who designs the equipment or decides its specifications.

Since the product specified here is used under various operating conditions, its compatibility with specific equipment must be decided by the person who designs the equipment or decides its specifications based on necessary analysis and test results.

The expected performance and safety assurance of the equipment will be the responsibility of the person who has determined its compatibility with the product.

This person should also continuously review all specifications of the product referring to its latest catalog information, with a view to giving due consideration to any possibility of equipment failure when configuring the equipment.

2. Only personnel with appropriate training should operate machinery and equipment.

The product specified here may become unsafe if handled incorrectly.

The assembly, operation and maintenance of machines or equipment including our products must be performed by an operator who is appropriately trained and experienced.

3. Do not service or attempt to remove product and machinery/equipment until safety is confirmed.

The inspection and maintenance of machinery/equipment should only be performed after measures to prevent falling or runaway of the driven objects have been confirmed.

When the product is to be removed, confirm that the safety measures as mentioned above are implemented and the power from any appropriate source is cut, and read and understand the specific product precautions of all relevant products carefully.

Before machinery/equipment is restarted, take measures to prevent unexpected operation and malfunction.

4. Contact SMC beforehand and take special consideration of safety measures if the product is to be used in any of the following conditions.

1) Conditions and environments outside of the given specifications, or use outdoors or in a place exposed to direct sunlight.

2) Installation on equipment in conjunction with atomic energy, railways, air navigation, space, shipping, vehicles, military, medical treatment, combustion and recreation, or equipment in contact with food and beverages, emergency stop circuits, clutch and lock circuits in press applications, safety equipment or other applications unsuitable for the standard specifications described in the product catalog.

- 3 -

3) An application which could have negative effects on people, property, or animals requiring special safety analysis.

4) Use in an interlock circuit, which requires the provision of double interlock for possible failure by using a mechanical protective function, and periodical checks to confirm proper operation.

 

Note that the CAUTION level may lead to a serious consequence according to conditions. Please follow the instructions of both levels because they are important to personnel safety.

- 4 -

LECSA Series / Driver

Safety Instructions

Caution

The product is provided for use in manufacturing industries.

The product herein described is basically provided for peaceful use in manufacturing industries.

If considering using the product in other industries; consult SMC beforehand and exchange specifications or a contract if necessary.

If anything is unclear, contact your nearest sales branch.

 

Limited warranty and Disclaimer/Compliance Requirements

The product used is subject to the following “Limited warranty and Disclaimer” and “Compliance

Requirements”.

Read and accept them before using the product.

Limited warranty and Disclaimer

The warranty period of the product is 1 year in service or 1.5 years after the product is delivered.*3.)

Also, the product may have specified durability, running distance or replacement parts. Please consult your nearest sales branch.

For any failure or damage reported within the warranty period which is clearly our responsibility, a replacement product or necessary parts will be provided.

This limited warranty applies only to our product independently, and not to any other damage incurred due to the failure of the product.

Prior to using SMC products, please read and understand the warranty terms and disclaimers noted in the specified catalog for the particular products.

*3.) Vacuum pads are excluded from this 1 year warranty.

A vacuum pad is a consumable part, so it is warranted for a year after it is delivered.

Also, even within the warranty period, the wear of a product due to the use of the vacuum pad or failure due to the deterioration of rubber material are not covered by the limited warranty.

 

 

Compliance Requirements

When the product is exported, strictly follow the laws required by the Ministry of Economy, Trade and

Industry (Foreign Exchange and Foreign Trade Control Law).

- 5 -

 

 

Introduction

It is recommended that the operator read the operation manual for LECSA prior to use. For the handling and details of other equipment, please refer to the operation manual for said equipment.

Check that the main circuit power supply (AC100V/AC200V) and controller circuit power supply (24V) are wired correctly. Please refer to chapter 3.1 of the “LECSA Operation Manual” and chapter 2 of the “LECSA

Operation Manual (Simplified Edition)” for details.

When setup software (MR Configurator) is used, the LECSA□-□ model selection is required. Select '

MR-JN-A ' through “Model Selection" - "System settings" - "Setup" and "Project name".

 

Terms

Position control mode (pulse)

Positioning mode (Point table)

Control the motor rotation speed and direction with pulse train and perform positioning.

Set the positioning data, rotation speed, Acceleration/Deceleration time constant of the drivers point table and execute ON/OFF control of the positioning operation using the I/O signals (a maximum of 7 points can be used for the point table configuration).

 

 

 

 

1. Configuration

Minimum equipment and wiring requirements to get started

Provided by customer

100V AC /200 V AC

7 1

Provided by customer

24 VDC

 

 

 

 

 

 

 

 

Provided by customer

PC

6

2 8

4

 

 

 

 

 

Electric Actuators

Ex) LEF

Provided by customer

 

 

 

 

3

 

 

1 Driver LECSA*-S*

2 Motor cable LE-CSM-***

3 Encoder cable

4 I/O connector

LE-CSE-***

LE-CSNA

I/O cable

5 USB cable

6 Setup software (MR Configurator TM

LEC-CSNA-1

LEC-MR-J3USB

) LEC-MR-SETUP221

7 Main circuit power supply connector CNP1

8 Control circuit power supply connector CNP2 (Accessory)

Note) The lock cable option is not shown on this drawing. Refer to the “LECSA Operation Manual” for details.

- 6 -

2. Pre-Operation Procedure

   

2.1 Flow chart

Power Supply Wiring

See P8 “3. Wiring”

Parameter setting

See P16 “4. List of Parameters for each Mode”

Parameter Settings using the Setup Software (MR

Configurator)

P18 “5. Parameter Settings using the Setup Software (MR

Configurator)”

Signal Assignment Configuration

See P39 “5.5 Changing I/O Signal Allocation”

Home position return Method

See P60 ”6. Home position return”.

Home position return Method

See P60 “6.Home position return”

“Position Control

Mode” Configuration

See P63

“7.1 Position Control

Mode”

Position control using pulse train input

“Speed control mode” Configuration

See P64 “7.2 Speed control mode”

Speed control though specifying the internal set speed using I/O signals

“Torque control mode”

Configuration

See P65

“7.3 Torque control mode”

Thrust control through specifying the internal set torque using I/O signals

“Positioning mode”

Configuration

See P66

“7.4. Positioning mode

(Point table)”

See P69

“7.5. Positioning Mode

(Program)”

Simple positioning mode which is operable using

I/O signals

-Point table method

-Program method

 

- 7 -

 

3. Wiring

   

3.1 Power Supply Wiring

Connect the actuator and driver power supply. This wiring diagram is common for each mode.

(1) LECSA (Incremental encoder)

EX.) Power supply voltage is 200VAC single phase

Trouble

RA

OFF

ON

MC

Forced stop (Note 5) MC

SK

Servo motor

Main circuit power supply

1-phase 200 to 230VAC

NFB

[1]

MC (Note 6) CNP1

L

1

L

2

P

U

V

C

W

Built-in regenerative resistor (Note 1)

(Note 4)

U

V

W

Motor

M

[2]

[3]

Control circuit power supply

24VDC (Note 7)

Circuit protector

CNP2

+24V

0V

CN2

(Note 2)

Encoder cable

Encoder

 

 

[1] Power supply input terminals, L

1

and L

2

: Specify power supply to input terminals L

1

and L

2

.

[2] Connect the motor power supply input terminal (U, V, W) to the driver power terminal (U, V, W).

Connect the motor ground terminal to the driver ground terminal.

Connect the encoder cable.

[3] Connect the 24VDC external power supply to the power supply for control circuit.

 

Refer to “LECSA Operation Manual”, Chapter 3 for further details if the power supply voltage is 100VAC. 

- 8 -

 

3.2 I/O signal connection example

Detail of connection examples for the I/O signals of the driver.

 

 

 

 

 

3.2.1 Position control mode

(1) Connection example

An example of a connection for the position control mode is shown below. Connect wires as necessary.

This is a wiring example using the Mitsubishi Electric (FX3U-□□MT/ES) PLC for position control.

(Connection example of the open collector system) See“LECSA Operation Manual” and the technical data disclosed the PLC and positioning unit operation manuals.

Programmable logic

controller

FX

3U

MT/ES (Note 13)

2m max. (Note 8)

S/S

24V

0V

L

PLC power supply

N

24VDC

(Note 4, 10) DICOM

OPC

DOCOM

(Note 7)

CN1

1

2

13

PP 23

(Note 7)

CN1

9

12

ALM

MBR

(Note 2)

RA1

RA2

Trouble (Note 6)

Electromagnetic brake interlock

(Note 10, 12)

(Note 14)

Y000

COM1

Y010

COM3

NP 25

10m max.

(Note 15)

Y004

COM2

X

X

X

CR 5

INP 10

RD

OP

LG

SD

11

21

14

Plate

15 LA

16 LAR

17 LB

18 LBR

19 LZ

20 LZR

14 LG

Plate SD

Encoder A-phase pulse

(differential line driver)

Encoder B-phase pulse

(differential line driver)

Encoder Z-phase pulse

(differential line driver)

Control common

(Note 10, 11)

(Note 3, 5) Forced stop

Servo-on

(Note 5)

Reset

Forward rotation stroke end

Reverse rotation stroke end

10m max.

EM1

(Note 7)

CN1

8

SON 4

RES

LSP

LSN

3

6

7

(Note 9)

MR Configurator

Personal computer

USB cable

(option)

CN3

CNP1

(Note 1)

 

 

When connecting the CN1-23 pin and CN1-25 pin, supply the + 24V to OPC.

Refer to“LECSA Operation Manual”,section 3.2 for wiring details.

Refer to “LECSA Operation Manual (Simplified Edition)”,section 3.2.1 (2) and (3) for input/output signal details.

- 9 -

 

(2) Input signal

Position control mode: P, Speed control mode: S, Torque control mode: T, Point table method: CP,

Program method: CL

● : Automatic ON can be set, ○ : Initial setting, □ : Assignment is available with parameter,-: Assignment is not available 

Symbol Device name

Automatic

ON

P S T

CP/

CL

Function

PP

NP

PG

Forward rotation pulse train

Reverse rotation pulse train

Differential forward rotation pulse train

‐ 

‐ 

‐ 

○ 

○ 

○ 

‐ 

‐ 

‐ 

‐ 

‐ 

‐ 

‐ 

‐ 

‐ 

In the open collector system

(max. input frequency 200kpps)

Forward rotation pulse train across PP-DOCOM

Reverse rotation pulse train across NP-DOCOM

In the differential receiver system

NG

Differential reverse rotation pulse train

‐  ○  ‐  ‐  ‐ 

(max. input frequency 1Mpps)

Forward rotation pulse train across PG-PP

Reverse rotation pulse train across NG-NP

SON Servo-on ● 

RES Reset

‐ 

○ 

○ 

○ 

○ 

○ 

○ 

○ 

□ 

Operation is available when SON is turned ON.

LSP

LSN

Forward rotation stroke end

Reverse rotation stroke end

● 

● 

‐ 

○ 

○ 

□ 

□ 

□ 

□ 

‐ 

‐ 

□ 

□ 

□ 

□ 

Alarm can be reset.

Turn this signal on before operation. When this signal turns off, the product is stopped suddenly and servo lock is enabled.

Turn this signal on before operation. When this signal turns off, the product is stopped suddenly and servo lock is enabled.

When this signal turns on, the torque will be lower than the set parameter torque.

TL1

ST1

ST2

RS1

RS2

Internal torque limit selection

Forward rotation start

Reverse rotation start

Forward rotation selection

Reverse rotation selection

SP1 Speed selection 1

SP2 Speed selection 2

SP3 Speed selection 3

‐ 

‐ 

‐ 

‐ 

‐ 

‐ 

‐ 

‐ 

‐ 

‐ 

‐ 

‐ 

‐ 

‐ 

○ 

○ 

‐ 

‐ 

○ 

□ 

□ 

‐ 

‐ 

○ 

○ 

○ 

□ 

□ 

○ 

○ 

‐ 

‐ 

‐ 

‐ 

‐ 

Start the servo motor.

Start the servo motor.

Servo motor torque generating direction is selected.

Servo motor torque generating direction is selected.

The command rotation speed during operation is selected.

EM1 Forced

CR Clear

● 

‐ 

○ 

○ 

○ 

‐ 

○ 

‐ 

○ 

‐ 

When this signal turns on, forced stop can be released.

When CR is turned on, the droop pulses of the position control counter are cleared on its leading edge.

DI0

DI1

DI2

Point table No/

Program No. selection 1

Point table No/

Program No selection 2

Point table No/

Program No selection 3

● 

● 

● 

‐ 

‐ 

‐ 

‐ 

‐ 

‐ 

‐ 

‐ 

‐ 

○ 

○ 

□ 

Select point table, program and return to home position mode with DI0 to DI2.

MD0

Automatic/manual selection

●  ‐  ‐  ‐  ○ 

When this signal turns on, automatic operation mode is activated. When this signal turns off, manual operation mode is activated.

- 10 -

(3) Output signal

Position control mode: P, Speed control mode: S, Torque control mode: T, Point table method: CP,

Program method: CL

: Initial setting,

: Assignment is available with parameter,-: Assignment is not available 

Symbol Device name P S T

CP/

CL

Function

ALM Trouble ○  ○  ○  ○ 

This signal turns off while alarm is generated.

ZSP Zero

MBR

Electromagnetic brake interlock

‐ 

‐ 

□ 

□ 

○ 

○ 

‐ 

○ 

‐ 

□ 

□ 

○ 

○ 

‐ 

‐ 

□ 

‐ 

□ 

○ 

○ 

○ 

‐ 

‐ 

□ 

□ 

○ 

When servo-on turns on and operation is available, this signal turns on.

This signal turns on when the droop pulse is within the setting range.

When the servo motor rotation speed reaches the set speed, this signal turns on.

This signal turns on when reaching the speed restricted by parameter.

This signal turns on when reaching the torque set by parameter while torque is generated. .

When the servo motor rotation speed is lower than the speed set by parameter, this signal turns on.

This signal turns off in case of servo off or when alarm is generated.

- 11 -

 

3.2.2 Speed control mode

(1) Connection example

An example of a connection for the speed control mode is shown below. Connect wires as necessary.

(Note 9,

10, 12)

(Note 8)

(Note 3, 5) Forced stop

Servo-on

Reset

Speed selection 1

Forward rotation start

Reverse rotation start

MR Configurator

Personal computer

24VDC (Note 4, 9)

10m max.

USB cable

(option)

DICOM

(Note 7)

CN1

1

(Note 7)

CN1

9

DOCOM

EM1

SON

13

8

4

10

11

ALM

SA

RD

RES

SP1

ST1

ST2

6

7

3

5

12 MBR

CN3

19

20

15

17

18

LZ

LZR

LA

16 LAR

LB

LBR

(Note 2)

14 LG

21 OP

Plate SD

2m max.

RA1

RA2

RA3

RA4

Trouble (Note 6)

Speed reached

Ready

Electromagnetic brake interlock

(Note 9, 11)

10m max.

Encoder Z-phase pulse

(differential line driver)

Encoder A-phase pulse

(differential line driver)

Encoder B-phase pulse

(differential line driver)

Control common

Control common

Encoder Z-phase pulse

(open collector)

CNP1 (Note 1)

 

 

Refer to“LECSA Operation Manual”,section 3.2 for wiring details.

Refer to “LECSA Operation Manual (Simplified Edition)”,section 3.2.1 (2) and (3) for input/output signal details. 

- 12 -

 

3.2.3 Torque control mode

(1) Wiring example

An example of a connection for the torque control mode is shown below. Connect wires as necessary.

 

(Note 8, 9)

(Note 3) Forced stop

Servo-on

Reset

(Note 7)

MR Configurator

Speed selection 1

Forward rotation selection

Reverse rotation selection

Personal computer

24VDC (Note 4, 8)

10m max.

USB cable

(option)

DICOM

DOCOM

EM1

(Note 6)

CN1

(Note 6)

CN1

1

9 ALM

13

8

11 RD

SON

RES

SP1

4

3

5

12 MBR

RS1

RS2

7

6

CN3

19

20

15

16

17

18

LZ

LZR

LA

LAR

LB

LBR

(Note 2)

14 LG

21 OP

Plate SD

2m max.

RA1

RA2

RA3

Trouble (Note 5)

Ready

Electromagnetic brake interlock

(Note 8, 10)

10m max.

Encoder Z-phase pulse

(differential line driver)

Encoder A-phase pulse

(differential line driver)

Encoder B-phase pulse

(differential line driver)

Control common

Control common

Encoder Z-phase pulse

(open collector)

CNP1 (Note 1)

 

 

Refer to“LECSA Operation Manual”,section 3.2 for wiring details.

Refer to “LECSA Operation Manual (Simplified Edition)”,section 3.2.1 (2) and (3) for input/output signal details.

- 13 -

 

3.2.4 Positioning mode

(1) Connection example

An example of a connection for the position control mode is shown below. Connect wires as necessary. 

(Note 9,

10, 12)

(Note 3, 5) Forced stop

Servo-on

Automatic/manual selection

Proximity dog

Point table No./Program No. selection 1

Point table No./Program No. selection 2

Forward rotation start

Reverse rotation start

(Note 8)

MR Configurator

+

Personal computer

24VDC (Note 4, 9)

10m max.

USB cable

(option)

OPC

DICOM

DOCOM

(Note 7)

CN1

(Note 7)

CN1

2

9 ALM

1

13

10 MEND

EM1

SON

8

4

11 RD

12 MBR

MD0

DOG

3

25

DI0

DI1

ST1

ST2

5

23

6

7

CN3

(Note 2)

RA1

RA2

RA3

RA4

Trouble (Note 6)

Travel completion

(Note 13)

Ready

Electromagnetic brake interlock

(Note 9, 11)

19

20

15

LZ

LZR

LA

16 LAR

17 LB

18 LBR

14 LG

21 OP

Plate SD

CNP1

2m max.

(Note 1)

10m max.

Encoder Z-phase pulse

(differential line driver)

Encoder A-phase pulse

(differential line driver)

Encoder B-phase pulse

(differential line driver)

Control common

Control common

Encoder Z-phase pulse

(open collector)

 

When connecting the CN1-23 pin and CN1-25 pin, supply the + 24V to OPC.

Refer to“LECSA Operation Manual”,section 3.2 for wiring details. 

Refer to “LECSA Operation Manual (Simplified Edition)”,section 3.2.1 (2) and (3) for input/output signal details.

- 14 -

3.2.5 Source I/O interfaces

Source type I/O interfaces can be used with this driver. If used, all DI-1 input signals and DO-1 output signals are source type signals. Complete wiring according to the following interfaces.

 

(1) Digital input interface DI-1

SON, etc.

Approx. 5.6k

Approx. 5mA

V

CES

1.0V

I

CEO

100 A

Switch

24VDC 10%

200mA

DICOM

(2) Digital output interface DO-1

A maximum voltage drop of 2.6V may occur in the driver.

 

ALM, etc.

Load

DOCOM

(Note) 24VDC 10%

200mA

If polarity of diode is reversed, servo amplifier will fail.

 

ORIGINAL IMAGE REQUIRED

Note. If the voltage drop (2.6V max) interferes with the relay operation, apply high voltage (up to 26.4V) from external source.

- 15 -

 

 

4. List of Parameters for each Mode

 

These parameters require configuration in each control mode. Please configure parameters as required.

Refer to “LECSA Operation Manual (Simplified Edition)”,section 5.3 and “LECSA Operation Manual”,chapter

4 for details.

Refer to “LECSA Operation Manual”,chapter 4 for parameters which are not disclosed in this document.

4.1 Parameters common to each mode

(1) [Basic settings parameters (No.PA□□)]

No. Symbol Name Unit

000h

 

(2) [I/O setting parameters (No. PD □□)]

These parameters are set when changing the input/output signal assignment and switching the input signal automatic on. See “LECSA Operation Manual (Simplified Edition)”,section 5.5 and “LECSA

Operation Manual” section 4.4 for details.

4.2 Position control mode

(1) [Basic settings parameters (No.PA□□)]

No. Symbol Description Unit

PA05 FBP Number of command input pulses per revolution

100 ×100 pulse/rev

1

PA08

PA09

ATU

RSP

Electronic gear denominator

(Command input pulse multiplying factor denominator)

Auto tuning mode

Auto tuning response

1

001h

6

100 pulse

000h

0 PA14 POL Rotation direction selection

 

4.3 Speed control mode

(1) [Basic settings parameters (No.PA□□)]

No. Symbol Name

PA08

PA09

ATU

RSP

Auto tuning mode

Auto tuning response

 

(2) [Extension setting parameters (No. PC□□)]

No. Symbol Name

[Applied]

[Applied]

[Applied]

[Applied]

Unit

001h

6

Unit

0 ms

0 ms

0 r/min

100 r/min

500 r/min

1000 r/min

200 r/min

300 r/min

500 r/min

800 r/min

- 16 -

4.4 Torque control mode

(1) [Extension setting parameters (No. PC□□)]

No. Symbol Name

[Applied]

[Applied]

[Applied]

[Applied]

0 ms

0 ms

0 r/min

100 r/min

500 r/min

1000 r/min

200 r/min

300 r/min

500 r/min

800 r/min

 

4.5 Positioning mode

(1) [Basic settings parameters (No.PA□□)]

No. Symbol

PA05 FBP

Name

Number of command input pulses per revolution

Unit

100 ×100 pulse/rev

1

1

PA08

PA09

ATU

RSP

Auto tuning mode

Auto tuning response

001h

6

100 pulse

000h

0 PA14 POL Rotation direction selection

 

  (2) [Positioning setting parameters (No. PE□□)]

No. Symbol Name Unit

0000h

0000h

0010h

500 r/min

0 μm

100 ms

0 ×10 STM μm

100 r/min

0 ×10 STM μm

0 ×10 STM μm

 

(3) [I/O setting parameters (No. PD□□)]

These parameters are set when changing the assignment of the input/output signal and using the point table at a maximum of 7 points.

See “LECSA Operation Manual (Simplified Edition)”,section 5.5 and “LECSA Operation Manual”,section 4.4 for details.

- 17 -

 

5. Parameter Configuration using Setup software (MR Configurator

TM

)

This section describes the configuration procedure for main parameters using the setup software (MR

Configurator TM : LEC-MR-SETUP221E). See chapter 4 of the “LECSA Operation Manual” for parameter details.

 

 

5.1 PC Setup software (MR Configurator

TM

)

 

 

*1 Setup software version C5 or above is required.

*2 The setup software (MR Configurator

TM

: LEC-MR-SETUP221E)must be purchased as an additional item.

*3 The USB cable (LEC-MR-J3USB) must be purchased as an additional item.

 

5.1.1 Installation Method

Perform installation according to the “MR Configurator

TM on the setup software (MR Configurator

TM

instruction manual” (Manual/ib0300079*.pdf) contained

) CD ROM. The “SETUP221” software will be added to the PC.

 

5.2 Basic driver set-up for Initial Test Drive

Switch on the 24 VDC and 230 VAC power supply to the LECSA driver and wait until the driver display flashes as shown below.

     

- 18 -

5.2.1 Start up the Setup software (MR Configurator

TM

① Connect the PC and LECSA using the USB cable. 

)

 

② Turn on the power of the LECSA. 

③  Start application “SETUP221E”. 

 

 

 

Once the application starts, the screen below will be displayed.

 

- 19 -

5.2.2 Driver ON LINE Check

Check that the driver is enabled (ON LINE).

 

If the driver is not enabled, check the wiring and power supply voltage.

5.2.3 Help Function

By selecting “MR Configurator Help” in “Help” from any window of the setup software, a “HELP” screen will be shown as shown below.

   

- 20 -

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5.2.4 “System Settings”

① From “Setup” menu select “System Settings”, the “System Settings” window will be displayed.

5.2.5 Model Selection

① The Mitsubishi Electric Corporation series will be displayed in the model selection list.

② Please select MR-JN-A if using the LECSA.

③ Please select “servo amplifier connection USB” as the communication device.

④ Select “Online” in the connection selection menu.

⑤ Click OK.

⑥ Click OK.

 

- 21 -

 

5.2.6 Parameter Upload

Upload the current parameters from the driver to the software.

① From the “Parameters” menu select “Parameter list” the “parameter setting” window will open.

② Click the “Read All” button.

③ If a Servo-alarm occurs, click “OK”.

 

The parameters PA, PB, PC, PD and PE can be set using the following tabs.

PA** : Basic settings/Basic settings (list)

PB** : Gain/Filter

PC** : Extension setting

PD** : I/O setting

PE** : Positioning setting

 

- 22 -

 

 

5.3 Parameter Settings

 

5.3.1 Settings to Allow Configuration of all Parameters

To enable settings for all parameters for this driver PA19 needs to be set to 00E.

 

①  Select “Basic settings (list)” tab and change “PA19” Value to “00E”.

②  Select “Write All”. 

③  Cycle the poweroff, then on for parameters for this driver to be enabled. 

 

- 23 -

 

5.3.2 “Control mode selection”

When using Position control mode (pulse input)

Change the “control mode” from “Position control mode (pulse input)” to “Positioning (Point table)”. 

① From the “Basic settings” tab and “Parameter Setting” window from the drop down selection “Control mode selection” select “Positioning (Point table)

 

 

When using Position control mode (pulse input)

② Parameter PA01 will change to 000 under the “Basic settings (list)” tab.

Positioning mode (point table)

② Parameter PA01 will change to 006 under the “Basic settings (list)” tab.

③ Click “Write All”.

④ Click “OK”.

⑤ Click “OK” (Parameters will be enabled after cycling the power OFF→ON). 

 

- 24 -

 

 

 

 

 

 

 

 

 

 

 

Please be aware of the following when changing parameters.

・ For each parameter type, all have the feature that “parameters are enabled after the power supply is cycled after configuration” (Driver data will not come into effect until the power supply has been turned off).

・ The parameter writing range to the driver differs between “Write” and “Write All”.

①  “Write”: The parameter for the applicable frame will be written to the driver. 

②  “Write All”: All parameters will be written to the driver. 

 

Details of each parameter will be displayed in the help window when the parameter is double clicked.

(See screenshot below.)

 

   

- 25 -

 

 

 

 

 

5.3.3 Parameter Configuration Method

Set the parameters for applicable actuator.

Refer to “LECSA Operation Manual (Simplified Edition)”,section 5.4.3 for recommended parameter values for

SMC supplied actuators.

However, when using position control mode (pulse input), do not alter parameters PE02/PE03/PE04/PE07/PE08/

PE10/PE11 from their initial values (Only change these parameters for Positioning mode (point table/program method)).

 

PA05/PA06/PA07 Configuration Examples

① Parameters PA05/PA06/PA07 are configured under the “Basic settings (list)” tab.

② Select “Write All”.

Cycle the power off to on. The parameters will now be active.

- 26 -

5.3.4 Recommended Parameter Values by Actuator Model

Please change the parameter values according to the customer application. See section 4 of the “LECSA

Operation Manual” for details.

 

Recommended Parameter Values [LEF]

LEFS25 LEFS32 LEFS40

Series Lead symbol H A B H A B H A B

Parameter

Para

No

Initial value

Recommended Value

Number of command input pulses per revolution *3.

Electronic gear numerator *3.

Electronic gear denominator *3.

Feel length multiplication (STM)

(Multiplier)

Home position return type

Home position return direction

Home position return Speed

(rpm)

Home position return/JOG operation

Accelerationeration/Deceleration time constants (msec)

Home position return position data (μm)

Stopper type home position return stopper time (msec)

Stopper type home position return torque limit value (%)

Regenerative option

Rotation direction selection *4

Adaptive tuning mode

★ Load to motor inertia moment ratio

Machine resonance suppression filter 1

PA05 100

PA06

PA07

PE02 0000

PE03 0010

PE03 0010

PE04 500 90

PE07 100 1000

PE08 0

PE10 100

PE11 15

PA02

PA14

PB01

1

1

000

0

000

PB06 7

PB13 4500

20 12

150

600

6

□□□

□□

3 (Stopper type)

1

(Motor side)

1 (+Counter motors side)

000

50

4500

8 30

0000 ((<1000 stroke)/0001 (>1000 stroke)

300

300

100 (Positioning mode: 10)

24

75

1200

100

16

113

800

-2000 (<1000 stroke)/-200 (>1000 stroke)

200

30

225

400

60

1500

000 (Non)/002 (LEC-MR-RB-032)

20

90

1000

10

180

500

Notch shape selection 1 PB14 000 000

★ Parameter setting required. 

Differs to initial value

*1. Parameter is set to the recommended value. Please set parameter according to customer application.

*2. Mechanical resonance may occur depending on the shape or mounting orientation of the work piece. Please change this parameter during initial configuration.

(Parameter initial configuration ⇒ Set the recommended parameter value ⇒ Operation start)

*3. Other than positioning mode: Actuator travel distance at 10 [μm/pulse] per pulse.

Positioning Mode: Minimum actuator travel distance of 1[μm].

*4. When the motor mounting position is right side parallel (LEFS*R) or left side parallel (LEFS*L), the rotation direction selection is 0(+: Counter motors side).

- 27 -

 

Series

Parameter

Lead symbol

LEFB25 LEFB25U LEFB32 LEFB32U LEFB40

S

LEFB40U

Para

No

Lead 54

Initial value

Recommended value

Number of command input pulses per revolution *3.

Electronic gear numerator *3.

Electronic gear denominator *3.

PA05 100

PA06 1

PA07 1

Feel length multiplication

(STM) (Multiplier)

PE02 0000

Home position return type PE03 0010

Home position return direction

Home position return

Speed (rpm)

Home position return/JOG operation

Accelerationeration/Decel eration time constants

(msec)

Home position return position data (μm)

Stopper type home position return stopper time (msec)

Stopper type home position return torque limit value (%)

Regenerative option

PE03 0010

PE04 500

PE07 100

PE08 0

PE10 100

PE11 15

Rotation direction selection

★ Adaptive tuning mode

★ Load to motor inertia moment ratio

□□ 1 □ (Motor side)

PA02

PB01

000

000

1 (+

PA14 0

Counter motors side)

002

0 (+:

Counter motors side)

000 (Non)/002 (LEC-MR-RB-032)

1 (+

Counter motors side)

0 (+:

Counter motors side)

1 (+

Counter motors side)

000

PB06 7

100 (Positioning mode: 10)

0000 (<1000 stroke)/0001 (>1000 stroke)

□□□

100

54

3 (Stopper type)

66

2700

-3000 (<1000 stroke)/-300 (>1000 stroke)

200

30

50

0 (+:

Counter motors side)

★ Machine resonance suppression filter 1

★ Notch shape selection

1

PB13 4500

PB14 000

400

030

4500

000

★ Parameter setting required.

Differs to initial value

*1. Parameter is set to the recommended value. Please set parameter according to customer application.

*2. Mechanical resonance may occur depending on the shape or mounting orientation of the work piece. Please change this parameter during initial configuration.

(Parameter initial configuration ⇒ Set the recommended parameter value ⇒ Operation start)

*3. Other than positioning mode: Actuator travel distance at 10 [μm/pulse] per pulse.

Positioning Mode: Minimum actuator travel distance of 1[μm].

- 28 -

Recommended Parameter Values [LEJ]

Series

Parameter

Para.

No

Lead

Initial value

LEJS40 LEJS63

T

24 16 8 30 20 10 27 42

Recommended value

Number of command input pulses per revolution *3.

Electronic gear numerator

*3.

Electronic gear denominator *3.

Feel length multiplication

(STM) (Multiplier)

Home position return type

Home position return direction

Home position return

Speed (rpm)

Home position return/JOG operation

Accelerationeration/Decel eration time constants

(msec)

Home position return position data (μm)

Stopper type home position return stopper time (msec)

Stopper type home position return torque limit value (%)

Regenerative option

PA05 100

PA06 1

PA07 1 24

PE02 0000

PE03 0010

PE03 0010

PE04 500 75

PE07 100 1200

PE08 0

PE10 100

PE11 15

16

113

800

8

225

400

100

100 (Positioning mode: 10)

30

□□□

□□

60

1500

1 □

20

90

1000

200

30

10

3 (Stopper type)

(Motor side)

180

500

27

0000 (<1000 stroke)/0001 (>1000 stroke)

133

1350

-2000 (<1000 stroke)/-200 (>1000 stroke)

42

86

2100

PA02

Rotation direction selection PA14

000

0

000 (Non)/002 (LEC-MR-RB-032)/003 (LEC-MR-RB-12)

1

(+Counter motors side)

0

(+:Counter motors side)

000 002 000 ★ Adaptive tuning mode

★ Load to motor inertia moment ratio

PB01 000

PB06 7 7 50

★ Machine resonance suppression filter 1

PB13 4500

★ Notch shape selection 1 PB14 000

4500

000

400

4500

030 000

★ Parameter setting required.

Differs to initial value

*1. Parameter is set to the recommended value. Please set parameter according to customer application.

*2. Mechanical resonance may occur depending on the shape or mounting orientation of the work piece. Please change this parameter during initial configuration.

(Parameter initial configuration ⇒ Set the recommended parameter value ⇒ Operation start)

*3. Other than positioning mode: Actuator travel distance at 10 [μm/pulse] per pulse.

Positioning Mode: Minimum actuator travel distance of 1[μm].

- 29 -

Recommended value

Recommended Parameter Values [LEY]

Series

Parameter

Lead

Para. No

Initial value

LEY25/LEYG25 LEY25D/LEYG25D

12 6 3 12 6 3 20

LEY32/LEYG32 LEY32D/LEYG32D

10 5 16 8 4

Number of command input pulses per revolution *3.

Electronic gear numerator *3.

Electronic gear denominator *3.

Feel length multiplication (STM)

(Multiplier)

Home position return type

Home position return direction

Home position return

Speed (rpm)

Home position return/JOG operation

Accelerationeration/De celeration time constants (msec)

Home position return position data (μm)

Stopper type home position return stopper time (msec)

Stopper type home position return torque limit value (%)

Regenerative option

PA05

PA06

PA07

PE02

PE03

PE03

PE04

PE07

PE08

PE10

PE11

100

1

1

0000

0010

0010

500

100

0

100

15

12 6 3 12

□□□

□□ 1 □

100

100 (Positioning mode: 10)

6 3 20

0000 (<1000 stroke)/0001 (>1000 stroke)

3 (Stopper type)

(Motor side)

50 100 200 50 100 200 30

200

30

10 5 16

-2000 (<1000 stroke)/-200 (>1000 stroke)

8 4

60 120 38 75 150

600 300 150 600 300 150 1000 500 250 800 400 200

Rotation direction selection

PA02 000

PA14 0

0

(+:Counter motors side)

000 (Non)/002 (LEC-MR-RB-032)

1

(+Counter motors side )

0

(+:Counter motors side)

000

1

(+Counter motors side )

Adaptive tuning mode PB01

Load to motor inertia moment ratio

Machine resonance suppression filter 1

Notch shape selection

1

PB06

PB13

PB14

000

7

4500

000

7

4500

000

Differs to initial value

*1. Parameter is set to the recommended value. Please set parameter according to customer application.

*2. Mechanical resonance may occur depending on the shape or mounting orientation of the work piece. Please change this parameter during initial configuration.

(Parameter initial configuration ⇒ Set the recommended parameter value ⇒ Operation start)

*3. Other than positioning mode: Actuator travel distance at 10 [μm/pulse] per pulse.

Positioning Mode: Minimum actuator travel distance of 1[μm].

- 30 -

Series

 

Lead symbol A B

LEY63

C L A

LEY63D

B C

Parameter

Para. No

Initial value

Recommended value

Number of command input pulses per revolution *3.

Electronic gear numerator *3.

Electronic gear denominator *3.

Feel length multiplication (STM)

(Multiplier)

Home position return type

Home position return direction

Home position return

Speed (rpm)

Home position return/JOG operation

Accelerationeration/D eceleration time constants (msec)

Home position return position data (μm)

Stopper type home position return stopper time (msec)

Stopper type home position return torque limit value (%)

Regenerative option

Rotation direction selection

Adaptive tuning mode

Load to motor inertia moment ratio

Machine resonance suppression filter 1

Notch shape selection 1

PA05

PA06

PA07

PE02

PE03

PE03

PE04

PE07

PE08

PE10

PE11

PA02

PB01

PB06

PB13

PB14

100

1

1

0000

0010

0010

500

100

0

100

15

000

PA14 0

000

7

4500

000

20

30

1000

100

(10)

10

60

500

5

□□□

120

250

□□ 1 □

100

35

(7)

1

(2)

210

143

200

30

000 (Non)/002 (LEC-MR-RB-032)/003 (LEC-MR-RB-12)

0

1

(+:Counter motors side) (+Counter motors side )

000

7

4500

000

20

3 (Stopper type)

(Motor side)

30

1000

100

(10)

10

0000 (<1000 stroke)/0001 (>1000 stroke)

60

500

-4000 (<1000 stroke)/-400 (>1000 stroke)

5

120

250

Differs to initial value

*1. Parameter is set to the recommended value. Please set parameter according to customer application.

*2. Mechanical resonance may occur depending on the shape or mounting orientation of the work piece. Please change this parameter during initial configuration.

(Parameter initial configuration ⇒ Set the recommended parameter value ⇒ Operation start)

*3. Other than positioning mode: Actuator travel distance at 10 [μm/pulse] per pulse.

Positioning Mode: Minimum actuator travel distance of 1[μm].

- 31 -

5.3.5 Position control mode (pulse input)

It is required to set the command input pulse form dependent on the upper unit pulse train when using the Position control mode (pulse input).

・ Input form (3 types)

① Forward rotaion pulse train/Reverse rotaion pulse train

② Pulse train/ Directionphase pulse train/B-phase pulse train

③ A-phase pulse train/ B-phase pulse train

 

・ Logic (2 types)

 

・ Input form (3 pulse types) × positive/negative logic (2 types) = 6 selectable types

In the upper level device (positioning module), there is a parameter which sets the output pulse form (mode). The form of the upper level device (positioning module) must be made “compatable” with the LECSA. If the forms are not compatable, the operation work correctly. Please be aware that depending on the upper level device

(positioning module), the “command input pulse forms” above may not be available.

Parameter No. PA13

Selection of command input pulse form

Setting Pulse train form Forward rotation command Reverse rotation command

00

Forward rotation pulse train

Reverse rotation pulse train

PP

NP

01

Signed pulse train

PP

NP

H

L

02

10

11

12

A-phase pulse train

B-phase pulse train

PP

NP

Forward rotation pulse train

Reverse rotation pulse train

PP

NP

PP

Signed pulse train

NP

A-phase pulse train

B-phase pulse train

PP

NP

Pulse train input filter selection

Setting

0

1

2

Command pulse frequency

1Mpps or less

500kpps or less

200kpps or less

L

H

 

Ex.) Setting of Command input Pulse form, when:

(1) The command pulse frequency is 200kpps or less and

(2) The pulse train form is set to positive logic, with the NP signal high and low

[PA13] = 201

- 32 -

 

 

 

 

 

 

 

 

 

 

 

 

 

  ①

 

 

 

 

 

 

 

 

 

 

① Change PA13 in the Basic settings list tab to 201.

 

② Click “Write All”.

Cycle the power off, then on for the Parameters to be activated.

   

- 33 -

5.3.6 Electronic Gears

It is necessary to adjust the electric gear to convert from the command pulse sent from position unit to the travel amount of electrical actuator.

 

See “LECSA Operation Manual (Simplified Edition)”,section 5.3.4 for the recommended values for electronic gears for each actuator model.

Please configure the electronic gear values according to the customer application.

(1) LECSA Parameter Configuration: [PA05], [PA06] and [PA07]

No. Symbol

Parameter

Name

Initial value

Setting range Unit

Position

Control mode

Internal speed

Internal torque

Positioning

PA05 *FBP Number of command input pulses per revolution 100

0 100 to

500

100 pulse/rev

Electronic gear numerator

(Command pulse multiplying factor numerator)

Electronic gear denominator

(Command pulse multiplying factor denominator)

1

1

1 to 65535

1 to 65535

 

 

 

 

 

(1) Complete configuration as shown below.

 

*[PA05] = 100 (Initial value)

 

 

* [PA06] = [PA05]×100×P×

1

1000

* [PA07] = Actuator lead (L) [mm]

P: Travel amount per 1 command pulse [μm]*

 

Ex.)

Travel amount per 1 command pulse (P=10μm)

Actuator lead (L = 6mm)

[PA05] = 100 (Initial value)

[PA06]=100×100×10×

=100×100×0.01

=100

1

1000

[PA07]=6 (Actuator lead (L) [mm])

*In case position control mode, "Travel amount per 1 command pulse"P = 10[um]

*In case positioning mode, "Travel amount per 1 command pulse"P = 1[um] 

- 34 -

5.3.7 Automatic Input Signal ON Selection Parameter Configuration

Configure the input signal automatic ON selection parameter.

The parameter “PD01:Input signal automatic ON selection” settings, defines which input signals will turn ON automatically when the control circuit power supplyis turned on., doing this allows additional I/O signal selection range.

Please allocate it according to your system specification.

Configure the automatic ON selection in parameter [PD01], or configure the I/O signal layout. If I/O signal wiring layout is altered, do not configure PD01:Input signal automatic ON selection.

*If all I/O signals are controlled, please set PD01 to 0000.

Please configure PD01:Input signal automatic ON selection in Hexadecimal (HEX).

 

During Actuator Operation: <Signals which must be ON during actuator operation>

 

    Set PD01 as 0C24. The following signals will automatically turn on when power supply turns on.

SON Servo-on

OFFServo-off

LSP

LSN

Forward rotaion Stroke end

(normally closed contact)

Reverse rotaion Stroke end

(normally closed contact)

ON Servo-on (operational)

OFF Forward rotaion Stroke end

ON Forward rotaion Stroke end off (operational)

OFFReverse rotaion Stroke end

ON Reverse rotaion Stroke end off (operational)

(normally closed contact)

OFFForced stop

ON Forced stop off (operational)

 

In positioning mode (point table), congifure the operation mode using automatic/manual selection MD0.

The MD0 off selection will allow Jog operation and it will require an input reserved for MD0.

For Automatic MD0 please set PD01 as 0C25. Will also include MD0 automatic ON.

ON: Automatic Operation Mode

Home position return/positioning mode operation available.

 

- 35 -

 

 

 

 

 

 

 

 

 

 

 

* Enabling “Stroke end” (LSP, LSN) , “Forced stop” (EM1) and “Servo-on” (SON) Signals

① Set to PD01 to 0C24 in the I/O setting tab.

② Select “Write All”.

Cycle the power off, then for thechanged Parameters to be enabled.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

* In this configuration, the stroke end (LSP, LSN), forced stop (EM1) and servo-on (SON) signals will be ON automatically when the power is turned ON.

- 36 -

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5.4 JOG Mode in the Setup Software

 

① The “JOG Mode” window can be displayed by selecting “Jog” from the “Test” menu in the setup software.

② Click “OK”.

(When using this function, all external input signal operation will be diabled. If controlling using a PLC or other upper device, please turn off the power and reset the device before use.)

- 37 -

 

5.4.1 JOG Mode

① In order to prevent accidental impact at the end of the stroke, test actuator operation at low speed.

See “LECSA Operation Manual (Simplified Edition)”,section 5.6.2 for motor speed configuration.

See “LECSA Operation Manual (Simplified Edition)”,section 5.6.3 for Acceleration/deceleration time.

② Check actuator JOG operation using [Forward (CCW)] and [Reverse (CW)] in JOG mode. (if operation is not correct, please check wiring and parameters).

When performing JOG operation in the setup software, the rotation direction of the actuator does not change if you change the setting of parameter PA14

(Rotation direction selection).

The actuator moves in the direction of [Forward (CCW)] button and

[Reverse (CW)] button.

③ If the selection “LSP and LSN are automatically turned ON” is not checked, an alarm will occur (if checked, the stroke end signals (LSP & LSN) will be automatically turned ON when this window is open).

 

Motorspeed 0 ~ allowable actuator speed

Acceleration/de celeration time

0 ~ 50000

  r/min ms

Description

Set the command speed of the servo motor for execution of positioning

(motor rotations/minute).

Set the time until the servo motor reaches/stops to the rated speed (3000 r/min).

- 38 -

 

5.5 Changing I/O Signal Allocation

Input/output signal assignment can be changed as appropriate from initial settings. There may be cases when changes to the Input/output signal assignment are required for actuator operation.

Please be aware that any changes will alter signals entered as initial settings.

Please allocate it according to your system specification.

*When configuring PD**, please set parameter write inhibit [PA19] to 00E.

See “LECSA Operation Manual”,section 4.4 for details.

Set parameters related to I/O: [PD02] to [PD18]

PD02 to PD14 Input signal assignment (CN1-23, CN1-25, CN1-3 to CN1-8)

PD15 to PD18 Output signal assignment (CN1-9 to CN1-12)

 

5.5.1 Initial I/O Signal Allocation

(1) Position control mode (pulse input):

The initial (Default) allocation of I/O signals is shown below.

Input signal points (6): (position control mode) and initial assignment Output signal points (4) (position control mode) and initial assignment

 

 

See “LECSA Operation Manual”,section 3.5 and “LECSA Operation Manual”,section 3.6 for details regarding signals.

See “LECSA Operation Manual”,section 4.4.2 for parameter configuration values.

※ Pins CN1-23 and CN1-25 are pulse input terminals. These cannot be allocated as any other input signals.

※ Pins CN1-3 - CN1-8 (input signals) and CN1-9 - CN1-12 (output signals) can be allocated as current SYNC (NPN) interface and current SOURCE (PNP) interface wiring and I/O signal allocation.

(2) Positioning mode:

The initial allocation of the I/O signals is shown below.

Input signal points (8): (positioning mode) and initial assignment Output signal points (4): (positioning mode) and initial assignment

 

 

See “LECSA Operation Manual”,section 13.2.3 for details regarding signals.

See “LECSA Operation Manual”,section 4.4.2 for details on parameter setting values.

※ Pins CN1-23 and CN1-25 can be allocated in current SYNC (NPN) interface interface wiring and I/O signal allocation only.

※ Pins CN1-3 and CN1-8 (input signals) and CN1-9 ~ CN1-12 (output signals) can be allocated in currect SYNC (NPN) interface and current SOURCE (PNP) interface wiring and I/O signal allocation.

- 39 -

 

 

 

 

 

 

 

 

 

 

 

 

5.5.2 Signal Allocation using Setup Software

① The “Parameter Setting” window will be displayed when “parameter list” is selected from the “parameters” menu in the setup software.

② Click the I/O setting tab.

③ When changing the allocation of signals, parameters for “PD02” - “PD18” can be altered.

 

 

 

- 40 -

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5.5.3 Allocation Examples for Position Control Mode (Pulse Input)

(1) Example of Gain switch (CDP) Settings

When changing pin CN1-4 from Servo-on (SON) to Gain switch (CDP).

Changing PD05 from 0202 to 0211

1 1

- 41 -

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(2) Symbol allocation using the setup software:

Changing pins CN1 – 4 from servo-on (SON) to gain switch (CDP):

① Change PD05 from 0202 to 0211 in the I/O settings tab.

② Select “Write All”.

Cycle the power off, then on for the parametersto be enabled..

   

※ Please allocate pins CN1-4 separately.

※ See “LECSA Operation Manual”,section 4.4.2 for details on allocation of input signals to pins CN1-3

- CN1-8.

※ See “LECSA Operation Manual”,section 4.4.2 for details on allocation of Output signals to pins

CN1-9 - CN1-12.

- 42 -

5.5.4 Setting a Maximum of 7 Points using the Point Table in Positioning mode (Point

 

 

 

Table)

The point table can reach a maximum of 7 points using input signals DI0, DI1 and DI2.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The default allocation, allocates signals DI0 to (CN1-5) and DI1 to (CN1-23).

Note – CN1-23 can only be used if the input is configured as current sink NPN

4 points can be specified , however 1 point is reserved for the home position return, 3 points can be specified in the point table.

When using a maximum of 7 point tables, wiring and input signal allocation of the DI2 must be

implemented.

 

- 43 -

 

 

 

 

 

 

(1) Example of Allocation of a Maximum of 7 Points in current SYNC (NPN) Interface

Changing pin CN1-7 from Reverse rotation start (ST2) to point table no./program no. selection 3 (DI2):

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

  ① Change PD12 from 0808 to 2E08.

 

2E

- 44 -

 

 

(1) Example of Allocation of a Maximum of 7 Points in current Source (PNP) Interface

① Changing pins CN1-3 from Automatic/manual selection (MD0) to point table no./program no. selection 3

(DI2):

② Changing pins CN1-7 from Reverse rotation start (ST2) to point table no./program no. selection 2 (DI1):

     

①  

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

① Change PD04 from 2003 to 2E03.

 

 

 

 

 

 

 

 

 

2E

 

②  Change PD12 from 0808 to 2D08.  

2D

- 45 -

Note

One example of signal allocation will be shown using the Setup Software. It is expected that the user will follow similar method applicable to the relevant signals that need reallocation.

(1) Example of Signal Allocation using the setup software

When changing pins CN1-7 from Reverse rotation start (ST2) to point table no./program no. selection 3 (DI2):

① Change PD12 from 0808 to 2E08 in the I/O settings tab.

② Click “Write All”

Cycle the power off, and then on for the parameters to be enabled.

0808 →2 E08

 

 

* Complete pin CN1-7 allocation separately.

* See “LECSA Operation Manual”,section 4.4.2 for details on allocation of input signals to pins CN1-3 - CN1-8

* See “LECSA Operation Manual”,section 4.4.2 for details on allocation of input signals to pins CN1-23 and

CN1-25

* See “LECSA Operation Manual”,section 4.4.2 for details on allocation of output signals to pins CN1-9 and

CN1-12

Schematics showing typical 3 point positioning

- 46 -

 

 

 

 

 

 

 

 

 

 

5.5.5 I/O Signal Allocation Check

The ON/OFF state (including layout check) and signal names allocated to CN1 can be checked. When parameters for PD02 - PD18 have been changed, It is necessary to confirm these are correctly assigned.

 

 

 

 

 

 

 

 

① From the Monitor menu of the Setup Software select Input/Output I/F Display. The Input/Output I/F

Display window opens and displays the inputs and outputs that are applicable. The window also displays the applicable MODE. The highlighted background implies the signals are active.

Positioning mode (point table)

- 47 -

 

 

 

 

 

 

 

 

 

 

 

 

 

5.6 Positioning Mode in Setup Software

① Using the Setup Software menu Test select Positioning. The positioning Mode window opens and

Test-mode window opensin the.

② Click OK. In the Test-mode

(When using this function, external input signal operation will be disabled. When controlling from a PLC or upper device, the power must be turned off and then on.)

- 48 -

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5.6.1 Positioning Mode

① In order to prevent accidental impact at the end of the stroke, operate the actuator at a low speed initially. When changing speed or movement, increase the values whilst checking operation

(Change motorspeed, acceleration/deceleration time, movement distance values if required).

See “LECSA Operation Manual (Simplified Edition)”,section 5.6.2 for motorspeed configuration.

See “LECSA Operation Manual (Simplified Edition)”,section 5.6.3 for acceleration/deceleration time configuration.

See “LECSA Operation Manual (Simplified Edition)”,section 5.6.4 for move distance configuration.

② Actuator positioning operates using [Forward (CCW)] and [Reverse (CW)].

(Check wiring and parameters if operation cannot be performed correctly).

When performing positioning operation in the setup software, the rotation direction of the actuator does not change if you change the setting of parameter PA14 (Rotation direction selection).

The actuator moves in the direction of [Forward (CCW)] button and [Reverse (CW)] button.

③ Check the command impulse unit (electronic gear enabled).

The electronic gear duty set to PA05/PA06/PA07 will be enabled.

See “LECSA Operation Manual (Simplified Edition)”,section 5.3.4 – “Parameter Values by Actuator

Model” for PA05/PA06/PA07 settings for each actuator.

If PA05/PA06/PA07 are set to the values in “LECSA Operation Manual (Simplified Edition)”,section

5.3.4– Parameter Values by Actuator Model, the travel distance of the actuator per 1 pulse will be calculated as follows.

Position control mode (pulse input)

・ travel distance of the actuator per 1 pulse = 10[μm] ( 0.01[mm])

Positioning mode

・ travel distance of the actuator per 1 pulse = 1[μm] ( 0.001[mm])

④ If the “Stroke-end” (LSP, LSN) signal is not configured as ON, an alarm may occur. (When checked, the “stroke-end” (LSP, LSN) will be automatically turned ON only when this window is open.)

Motorspeed

0 ~ Allowed Speed for each actuator

Acceleration/de celeration time

0 ~ 50000

Move distance 0 ~ 99999999 r/min ms pulse

Description

Set the command speed of the servo motor for execution of positioning

(Motor rotations/min).

Set the time until the servo motor reaches/stops to the rated speed (3000 r/min)

Sets movement distance.

- 49 -

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5.6.2 Motorspeed Configuration

<Rotation Speed Configuration>

① Motorspeed (r/min) configuration.

*R/min (rpm): Indicated motor rotation speed (motor rotations/min)

Rotation speed must be between 0 and the allowable speed limit for each actuator. Please be aware that the actuator will not operate if this is set to 0.

If the rotation speed is too low, this may cause vibration; check the actuator while changing settings.

Movement speed (mm/s) must be converted into rotation speed (r/min).

See below for the conversion formula.

 

Calculating motor speed conversion example using an actuator with a 20mm lead and 500 [mm/sec] speed. 

Rotations per Second

Distance of movement per second

÷

Distance of movement per rotation

Rotation Speed (rpm) = Speed (mm/s) ÷ Lead (mm) }×60 (S)

= {500 (mm/s) ÷20 (mm) }×60 (s) =1500 (rpm)

 

- 50 -

5.6.3 Acceleration/deceleration Time Configuation

< Acceleration/deceleration Time Configuration>

 

 

 

① Acceleration/deceleration time (ms) configuration:

The acceleration/deceleration time sets the amount of time (ms) in which a prescribed number of rotations

(3000[r/min]) is reached.

The acceleration/deceleration time must be set to a value between 0 and the allowable acceleration/deceleration speed for each actuator.

The acceleration/deceleration time must be converted from the acceleration/deceleration speed. See below for the conversion formula.

   

 

Calculating Acceleration/deceleration conversion example using an actuator with a 8 [mm] lead

with an acceleration of 3000[mm/sec 2 ].

Speed at a rated motor rotation of 3000rpm

 

Accel/decel time (ms) = {Rated Rotation Speed (r/min) ÷60 (S) }× Screw Lead (mm) × 1000

 

  Acceleration/deceleration speed (mm/s 2 )

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Acceleration/deceleration time (ms) = {3000 (r/min) ÷60 (S) } × 8 (mm) × 1000

3000 (mm/s 2 )

                                        =  133 (ms) 

- 51 -

5.6.4 Move distance Configuration and Operation < Move distance Configuration>

① Set the move distance [pulse]. Select a value within the stroke range.

② Actuator position will operate using [Forward (CCW)], [Reverse (CW)].

The position at which power is turned ON will be set as the home position, and the actuator will travel the amount set as move distance (check wiring and parameters If operation is not performed correctly).

When performing positioning operation in the setup software, the rotation direction of the actuator does not change if you change the setting of parameter PA14 (Rotation direction selection).

The actuator moves in the direction of [Forward (CCW)] button and [Reverse (CW)] button.

③ Check command input pulse units (electronic gear enabled).

The electronic gear duty configured in PA05/PA06/PA07 will be enabled. See “LECSA Operation Manual

(Simplified Edition)”,section 5.3.4 for setting values for PA05/PA06/PA07 in each actuator. If parameters

PA05/PA06/PA07 are set according to“LECSA Operation Manual (Simplified Edition)”,section 5.3.4, the travel distance of the actuator per 1 pulse will be as follows.

 

Position control mode (pulse input)

・ travel distance of the actuator per 1 pulse = 10[μm] ( 0.01[mm])

Positioning mode

・ travel distance of the actuator per 1 pulse = 1[μm] ( 0.001[mm])

 

 

 

 

 

 

Travel distance (mm) must be converted to tavel distance (pulse).

See below for the conversion formula. As an example, for a travel of 100m;

Position control mode (pulse input

Travel distance of the actuator per 1 pulse = 0.01 (mm)

*1

100 (mm)/0.01 (mm) = 10000 (pulse)

Positioning mode

Travel distance of the actuator per 1 pulse = 0.001 (mm)

*1

100 (mm)/0.001 (mm) = 100000 (pulse)

*1 The travel distance of the actuator per 1 pulse is set according to the electronic gears (PA05/PA06/PA07) outlined in 5.3.4 “Recommended

Parameter Values by Actuator Model”.

   

 

 

 

 

 

 

 

④ If the stroke end signals (LSP, LSN) are not turned ON, an alarm may occur (If checked, the stroke end

(LSP, LSN) signals will be turned ON automatically only when this window is open).

* Ensure that the [Forward (CCW)] and [Reverse (CW)] driving directions are checked. If the driving direction is unclear, operate the actuator slowly with a small move distance while checking the driving direction.

   

- 52 -

 

5.7 Positioning (Point Table) Operation using the Setup Software

This feature is only available in positioning (point table) mode.

When positioning using the positioning (point table) mode, the point table (position data, speed data, acceleration time, deceleration time etc.) must be configured.

5.7.1 Point table List

① Using the “Positioning Data” menu in the setup software.The “Point table list” can be opened by selecting

“Point Table”

② “Read All”: point table data will be read from the LECSA and displayed.

③ “Write All”: point table data will be written to the LECSA.

② ③

 

5.7.2 Point Table Data

Position data

Servo motor speed

- 999.999

~ 999.999

×10STM mm

Description

(1) When using this point table as absolute value command system, set the target address (absolute value).

(2) When using this point table as incremental value command system, set the travel distance. A "-" sign indicates a reverse rotation command.

Number of decimal places changes according to STM (Feel length multiplication)

0 ~ allowable actuator speed r/min Sets the command rotation speed (Motor rotations/min) when positioning is executed.

Acceleration time constant

Deceleration time constant

0 ~ 20000

0 ~ 20000 ms ms

Set the time until the servo motor reaches to the rated speed. (3000 r/min)

Set the time until the servo motor stops from the rated speed. (3000 r/min

When dwell is set and the set dwell has passed after the position command of the

Auxiliary function 0 ~ 3

Set "1" in the auxiliary function and 0 in the dwell to perform varied speed operation.

(1) When using this point table in the absolute value command system

0: Automatic operation is performed in accordance with a single point table chosen.

1: Operation is performed in accordance with consecutive point tables without a stop.

(2) When using this point table in the incremental value command system

2: Automatic operation is performed in accordance with a single point table chosen.

3: Operation is performed in accordance with consecutive point tables without a stop.

When a different rotation direction is set, smoothing zero (command output) is confirmed and the rotation direction is then reversed.

Setting "1" in point table No. 7 results in an error.

 

Manuf .1

Manuf .2

Do not change.

- 53 -

5.7.3 Point table (Position data) Configuration

< Position data Configuration>

For actuators with a stroke less than 1000mm, set parameter PE02 (Feel length multiplication (STM)

(Multiplier) ) to 0000 and the STM value to x1.

For actuators with a stroke more than 1000mm, set parameter PE02 (Feel length multiplication (STM)

(Multiplier) ) to 0001 and the STM value to x10.

② Configure position data (mm). Set to a value within the stroke range.

 

 

* If electronic gear parameters (PA05/PA06/PA07) are set according to“LECSA Operation Manual (Simplified

Edition)”,section 5.3.4 in positioning mode:

The smallest unit for actuator movement is 1[μm] (0.001[mm]).

- 54 -

 

 

 

5.7.4 Point table (Servo Mmotor Speed) Configuration

<Rotation Speed Configuration>

① Rotation speed configuration:

*R/min (rpm): motor command rotation speed (motor rotations/min)

Travel speed (mm/s) must be converted into rotation speed (r/min).

See below for the conversion formula.

Example using a 20[mm] Lead Actuator with target travel speed of 500[mm/sec]

Rotations per second

Travel distance per second

÷

Travel distance per rotation

Rotation Speed (rpm) = {Speed (mm/s) ÷ Lead (mm) }×60 (S)

= {500 (mm/s) ÷20 (mm) }×60 (s) =1500 (rpm)

 

 

The rotation speed must be a value between 0 and the allowable actuator speed. The actuator will not operate if set to 0.

Too low rotation speed (r/min), may cause vibration (resonance);

 

- 55 -

5.7.5 Point Table (Acceleration time constant/Deceleration time constant)

Configuration

< Acceleration time constant/Deceleration time constant Configuration>

① Acceleration time constant (ms)/Deceleration time constant (ms) configuration:

Acceleration/deceleration (mm/s

2

) must be converted to the acceleration time constant/deceleration time constant

(ms). See below for the conversion formula.

 

 

Conversion example for a 8[mm] lead actuator driven at an acceleration of 3000 [mm/sec 2 ]

 

Rated Motor Rotation Speed (mm/s)

 

 

 

 

 

 

                                    Acceleration/deceleration speed (mm/s

2

)   

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Acceleration/Deceleration time constant (ms) = {3000 (r/min) ÷60 (S) } × 8 (mm) × 1000

= 133 (ms)

The acceleration time constant/deceleration time constant defines the time in (ms) when the motor rotations of (3000[r/min]) are met.

The acceleration time constant/deceleration time constant must be a number between 0 and the allowable acceleration/deceleration speed range for each actuator.

5.7.6 Other Settings

The dwell and auxiliary functions are set to 0 as default.

Do not change Manuf .1 (0) or Manuf .2 (0.00) from the initial values.

- 56 -

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5.7.7 Single-Step Feed

In Test mode a single step within point table can be executed.

① From the “Test” menu in the setup software select “Single-step Feed”which opens a window for

“Single-step feed”. (When using this function, external input signal operation will be disabled. If controlling using a PLC or other upper device, ensure the power is turned off and then on before operation.)

② Select point table number. 

③    Press “Start”. 

The actuator will set the position at which the power was turned on as the home position (0), and move towards the defined point table position.

 

* Check parameters PA05/PA06/PA07 parameters (electronic gear duty) if an unexpected move was observed.

Note

* Home position return cannot be performed in test mode.

In Test mode the default position of the actuator is set as the home position when the power was turned on.It is therefore possible to drive the actuator past the stroke ends. Please pay particular attention to the position of the actuator on power up.

 

- 57 -

 

 

 

 

 

 

 

 

 

 

 

 

 

5.8 Saving/Loading Parameters

5.8.1 Saving Parameters

 

① From the “Project” menu in the setup software select “Save As Project” opens a window “Save As Project”.

② Enter a project name.

③ Click “Save”.

Files will be saved to the default folder “C:/Melservo/setup221/*project name*

(If the path is changed then, the files will be saved to the new path /*project name*)

Files Saved   device.prd paramet.prm project.prj point.ptbn

I/O signal device selection parameters setting file

Settings files for parameters PA, PB, PC, PD and PE

Project information file

Point table data file.

(Files will not be created in position control mode (pulse input))

 

* Note Always upload current parameters from the driver to the software before saving.

(See“LECSA Operation Manual (Simplified Edition)”,section 5.2.6 for uploading.)

- 58 -

 

 

 

 

 

 

 

 

 

 

 

5.8.2 To Load saved Parameters

① “Open Project” from the “Project” menu using the setup software The “Open Project” window will open.

② Select the drive/bus/*project name* of the saved parameters.

③ Click “Open”.

Parameters will be loaded.

* If the “project.prj” file name differs to that selected in ②, parameters may not be able to be loaded. Please move all project files to drive/bus/*project name* “project.prj”.

 

 

- 59 -

 

 

 

 

 

6.

Home Position Return Method

6.1 Position Control Mode (Pulse Input)

When using the home position return in position control mode (pulse input), use the home position return function in the positioning module of the upper PLC.

Please see product operation manuals for positioning module layouts, parameter configuration, home position return method etc.

6.2 Positioning mode (point table)

In positioning mode (point table) a home position return function is available. There are 6 types of home position return as shown below. See“LECSA Operation Manual”,section 13.6 for details.

 

Type Home position return method Features

Dog type

Count type

Data set type

Stopper type

With Deceleration started at the detection of front edge of a proximity dog switch signal, the position where the first Z-phase signal is given past the rear edgeof the dog signal or a motion has been made over the home position shift distance starting from the Z-phase signal is defined as a home position. (Note)

With Deceleration started at the detection of front edge of a proximity dog switch signal, the position where the first Z-phase signal is given after advancement over the preset moving distance after the proximity dog switch signal or a motion has been made over the home position shift distance starting from the Z-phase signal is defined as a home position.

An arbitrary position defined as a home position.

The position where the actuator stops when its slider is pressed against a machine stop is defined as a home position.

General home position return method using a proximity dog.

Good repeat accuracy of home position return

Decreases product load.

Used when the width of the proximity dog can be set greater than the deceleration distance of the servo motor.

Home position return method using a proximity dog.

Used when it is minimisation of the proximity dog length is required.

No proximity dog required.

Since the machine part collides with the machine be fully lowered.

The machine and stopper strength must be increased.

Home position ignorance

(Servo-on position as home position)

The position where servo is switched on is defined as a home position.

Dog type rear end reference

Count type front end reference

Dog cradle type

The position where the axis, which had started dcceleration of the front edge of a proximity dog switch signal, has moved the after-proximity dog moving distance and home position shift distance after it has passed the rear edge of proximity dog switch signal is defined as a home position.

The position where the axis, which had started dcceleration at the front edge of a proximity dog switch signal, has moved the after-proximity dog moving distance and home position shift distance is defined as a home position.

The position where the first Z-phase signal is detected after detection of the proximity dog front edge signal is defined as a home position.

Z-phase signal not required.

Z-phase signal not required.

Note. The Z-phase signal is a signal recognised in the driver once per servo motor revolution. This cannot be used as an output signal.

Set parameter PE03 (Home position return type) for home position return. The parameter recommended in “LECSA

Operation Manual (Simplified Edition)”,section 5.3.4 is the stopper type (PE03:0003). Please select the home position return as appropriate to the customer application.

 

- 60 -

6.2.1 Stopper type home position return

In stopper type home position return, a machine part is pressed against a stopper using JOG operation to make a

  home position return and that position is defined as the home position.

(1) Devices and Pparameters

Configure the input devices and parameters as shown below.

Description

Manual home position return mode selection

Automatic/manual selection (MD0) Turn MD0 ON.

Point table No./Program No. selection 1 to 3 (DI0 to DI2)

Point table: Select the home position return mode by turning OFF

DI0, DI1 and DI2.

Program: Select a program that has the home position return "ZRT" command.

Stopper type home position return

Home position return direction

Home position return speed

Stopper time

Parameter No. PE03

Parameter No. PE03

Parameter No. PE04

Parameter No. PE10

Stopper type home position return torque limit value

Home position return

Acceleration time constant

Home position return position data

Parameter No. PE11

Parameter No. PE07

Parameter No. PE08

 

Note

* To set [PE**], set parameter write inhibit [PA19] to "00E".

3: Stopper type home position return is selected.

Select the home position return direction.

Set the speed till contact with the stopper.

Time from when the part makes contact with the stopper to when home position return data is obtained to output home position return completion (ZP).

Set the servo motor torque limit value for execution of stopper type home position return.

Set the Acceleration time constant during a home position return.

Set the current position at home position return completion.

- 61 -

 

(2) Timing chart

Automatic/manual selection (MD0)

ON

OFF

DI0, DI1, and DI2

Forward rotation start

(ST1)

ON

OFF

Reverse rotation start

(ST2)

ON

OFF

(Note 1)

6ms or more 6ms or more

(Note 4)

Torque limit value Parameter No. PC14 (Note 3) Parameter No. PE 11 Parameter No. PC14

Servo motor speed

Forward rotation

0r/min

Acceleration time constant parameter

No. PE07

Home position return speed parameter No. PE04

Home position address parameter

No. PE08

3ms or less

Stopper time parameter No. PE10

Stopper

Limiting torque (TLC)

ON

OFF

Rough match (CPO)

ON

OFF

Travel completion

(MEND)

ON

OFF

Home position return completion (ZP)

ON

OFF

(Note 2)

 

Forward rotation

ON

OFF

ON

OFF

 

Forced stop (EM1)

ON

OFF

 

Note 1. External input signal detection is delayed by the input filter setting time of parameter No. PD19. Implement a sequence that changes DI0, DI1 and DI2 ahead of time by considering delays in output signal sequence from the PC or PLC and variations of a signal change due to hardware.

2. TLC turns ON when the torque reaches the value set in forward torque limit (parameter No. PA11),reverse torque limit (parameter

No. PA12) or internal torque limit (parameter No. PC14).

3. The torque limit that is enabled at this point is as follows.

(Note)

Input device

TL1

Limit value status Validated torque limit values

1

Parameter No. PC14 >

Parameter No. PC14 <

Parameter No. PE11

Parameter No. PE11

Parameter No. PE11

Parameter No. PC14

Note. 0: off

1: on

4. Point table method: Select the home position return mode by turning OFF DI0, DI1 and DI2.

Program method: Select the program that has the home position return "ZRT" command.

The set value in parameter No. PE08 (home position return position data) is applied as position address at the time of the home position return being completed.

- 62 -

 

7. Diriving Methods for Each Mode

7.1 Position Control Mode (Pulse Input)

The motor rotation speed and direction is controlled using the pulse train and executes positioning operation.

 

7.1.1 Position Control Mode Instructions

The command pulse sent as input to the driver from the positioning unit and the driver operates the actuator in accordance with the command pulse. The command pulse and driver operation examples are shown below.

Command pulse Droop pulses

Droop pulses [pulses] 0

CDL

CDL

 

 

After-changing gain  

Servo motor speed 0 r/min

(95ms)

ON

OFF

Electromagnetic brake interlock

(MBR)

(Note 1) ON

OFF

Servo-on (SON)

ON

OFF

(95ms)

Position command

(Note 4) brake

0 r/min

Release

Activate

 

 

 

 

 

 

 

 

Forward rotation stroke end

(LSP)

Reverse rotation stroke end

(LSN)

Forced stop

(EM1) OFF

ON

OFF

ON

OFF

ON

(Note 3)

Release delay time and external relay (Note 2)

Coasting

Tb

Electromagnetic brake sequence output

(parameter No. PC09)

 

- 63 -

 

7.2 Speed control mode

This mode allows for accurate, smooth control of the rotation speed and direction of the servo motor.

* To set [PC**], set parameter write restriction [PA19] to "00E".

7.2.1 Speed Control Mode Operation Instruction

The servo motor will rotate when signal ST1 and ST2 turn on. An operation example of the speed control mode is shown below.

 

Internal speed command settings

Speed command and speed

The servo motor operates at the speed set in parameters.

Up to 8 speeds can be set to the internal speed command.

The following table indicates the rotation direction according to forward rotation start (ST1) and reverse rotation start (ST2) combination.

  (Note 1) Input device 

  (Note 2) Rotation direction 

ST2  ST1 

0  0  Stop    (Servo lock)   

Forward rotation (CCW)

Forward rotation (CCW)   

Reverse rotation (CW)   

1  1  Stop    (Servo lock)   

Note 1. 0: off

1: on

2. If the torque limit is canceled during servo lock, the servo motor may suddenly rotate according to position deviation in respect to the command position.

Reverse rotation (CW)  

Connect the wirings as follows when operating in forward or reverse rotation with the internal speed command set to the eighth speed.

Note that the inputs are configured as Current sink NPN Type

Forward rotation start

Peverse rotation start

Speed selection 1

Speed selection 3

ST1

ST2

SP1

SP2

SP3

DOCOM

(Note 2)

Assignment of signals in the initial setting

- LECSA: SP1

Assign signals "speed selection 2 (SP2) and speed selection 3 (SP3) "when the driver is used to [Internal speed command 7].

DICOM

 

 

24VDC

 

 

Refer to “LECSA Operation Manual (Simplified Edition)”,section 5.5 for signal assignment.

LECSA Speed Command Parameter Setting

SP3 

  (Note) Input device 

SP2  SP1 

Speed command value 

Internal speed command 0 (parameter No. PC05)   

Internal speed command 1 (parameter No. PC06)   

Internal speed command 2 (parameter No. PC07)   

Internal speed command 3 (parameter No. PC08)   

Internal speed command 4 (parameter No. PC31)   

Internal speed command 5 (parameter No. PC32)   

Internal speed command 6 (parameter No. PC33)   

Internal speed command 7 (parameter No. PC34)   

Note. 0:OFF

1:ON

8 patterns of speed configurations are available for LECSA,.

Initial  phase 

- 64 -

 

7.3 Torque control mode

Servo motor output torque is controlled. Speed control function is also available.

* To set [PC**], set parameter write restriction [PA19] to "00E".

7.3.1 Torque Control Mode Operation Instruction

The servo motor will rotate when signal RS1 and RS2 turn on. An operation example of the torque control mode is shown below. Internal torque command settings:

Torque is controlled by the internal torque command set in parameter No. PC12.

If the internal torque command is small, the torque may vary when the actual speed reaches the speed limit value.

In such case, increase the speed limit value.

The following table indicates the torque generation directions determined by the forward rotation selection (RS1) and the reverse rotation selection (RS2) when the internal torque command (parameter No. PC12) is used.

(Note) Input device Rotation direction

0 0

0.1 to 100.0%

Torque is not generated.

CCW (reverse rotation in driving

0.0% regenerative mode)

CW (forward rotation in driving

Torque is not generated.

Forward rotation (CCW)

1 1 regenerative mode)

Torque is not generated.

Note. 0: off

1: on

Generally, make connection as shown below.

Note that the inputs are configured as Current sink NPN Type

Reverse rotation (CW)

Forward rotation start

Peverse rotation start

Speed selection 1

Speed selection 3

24VDC

RS1

RS2

SP1

SP2

SP3

DOCOM

DICOM

(Note 2)

Assignment of signals in the initial setting

- LECSA: SP1

Assign signals "speed selection 2

(SP2) and speed selection 3 (SP3)

"when the driver is used to up to

[Internal speed command 7].

 

 

 

Refer to “LECSA Operation Manual (Simplified Edition)”,section 5.5 for assignment of signal.

LECSA speed restricted parameter setting

(Note) Input device

Speed command value

SP3 SP2 SP1

Initial phase

Note. 0:OFF

1:ON

For LECSA, 8 patterns of speed setting are available.

- 65 -

 

7.4 Point table method

Positioning operation can be executed by setting the position data, rotation speed, acceleration time constant, deceleration time constant to the point table data. (The maximum points that can be set in point table is 7.)

 

7.4.1 Operation Instruction of Point Table system

Select the point table No. represented by the values of DI0, DI1 and DI2. Start the operation by selecting ST1 or ST2.

Functions/Applications

I/O division

Positioning mode

CP CL

Point table No.

/Program No. selection 1

DI0 DI-1

Point table No.

/Program No. selection 2

Point table No.

/Program No. selection 3

Program input 1

DI1

DI2

PI1

CN1-5 <In point table method>

The point table No. and the home position return mode are selected by DI0 to DI2.

<In program method>

The program No. is selected by DI0 to DI2.

Device

CN1-23 DI2 DI1 DI0

0

0

0

0

1

0

0

1

1

0

1

1

1

0

1

1

0

1

0

1

0

1

0

1

Point table method

Home position return mode

Point table No. 1

Point table No. 2

Point table No. 3

Point table No. 4

Point table No. 5

Point table No. 6

Point table No. 7

Note. 0: off

1: on

Turn PI1 on to resume the step stopped by the

SYNC (1) command in the program.

DI-1

DI-1

DI-1

Point table No.

Position data

[×10 STM μm]

Servo motor speed [r/min]

Acceleration time constant

[ms]

Deceleration time constant

[ms]

Dwell

[ms]

Auxiliary function

 

Note. Always set "0" or "2" to the auxiliary function in the last point table among the consecutive point tables.

0: When point table is used in absolute value command system

2: When point table is used in incremental value command system

- 66 -

Automatic/manual selection (MD0)

Servo-on (SON)

Forward rotation start

(ST1)

ON

OFF

ON

OFF

ON

OFF

Point table No.

Servo motor speed

In-position (INP)

Rough match (CPO)

(Note 2)

Travel completion

(MEND)

Point table No. output

(PT0 to PT2)

Ready (RD)

Forward rotation

0r/min

Reverse rotation

ON

OFF

ON

OFF

ON

OFF

Trouble (ALM)

ON

OFF

ON

OFF

ON

Forward rotation stroke end

(LSP)

OFF

ON

Reverse rotation stroke end

(LSN)

OFF

ON

Forced stop

(EM1) OFF

(Note 1)

6ms or more 6ms or more

3ms or less

1

Point table

No.1

 

Point table

No.2

Point table

No.3

1

 

- 67 -

7.4.2 Setting method

 

 

  (1) Setting with the button on the front of the driver

Ex.) When the servo motor rotation speed of point table No.3 is changed from 2500 (r/min) to 1000 (r/min) .

Driver operation display

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

  a. When the "MODE" button on the driver operation is pressed, the display will be shifted as shown below.

Select "P-1". b. When the "UP" and "DOWN" buttons on the driver operation are pressed, the display will be shifted as shown below, Select

"P-3" and press the "SET" button. c. The "UP" and "DOWN" buttons on the driver operation are pressed to Select "Spd", thenpress the "SET" button.

Point table No.1

500 

No.2 No.3 No.4 No.5

・・・

No.6 No.7

is displayed. The lower 3 digits of the set value are displayed. The operation procedure is described below.

When the "MODE" button is pressed, the upper 3 digits are displayed. Change the set value as shown below.

U P

D O W N

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Position data

Upper 3 digits

Servo Motor speed

Acceleration constant

Deceleration constant

Set value before change

(r/min) 

2     5 0 0  a. The set screen can be selected from the upper 3 digits and lower 3 digits with "MODE" button. b. Press the "SET"button.

The set value will start flashing.

Dwell

(Stop time)

 

 

 

 

 

 

 

 

  c. Press the "UP"and "DOWN"buttons to change the set value. d. Press the "SET"button.

The set value will light up.

* When the set value is flashing, it is not registered.

Set value after change

 

 

 

 

1 0 0 0

(r/min)

 

Refer to “LECSA Operation Manual”,chapter 13 for details.

Auxiliary functions

Lower 3 digits b. Press the "SET"button.

The set value will start flashing. c. Press the "UP"and "DOWN"buttons to change the set value. d. Press the "SET"button.

The set value will light up.

* When the set value is flashing, it is not registered.

- 68 -

 

7.5 Positioning Mode (Programimg Method)

To perform the positioning operation, create a program using position data, rotation speed, acceleration constant and deceleration constant (The maximum number of programs is 8 for which a total of 120 steps can be created per program). Install the set up software,MR Configurator TM :LEC-MR-SETUP221E which is required for setting the program data with the program system.

*1. Software version C5 or higher is required.

*2. Setup software should be prepared by the user.

*3. USB cable (LEC-MR-J3USB) is required for software installation.

See “LECSA Operation Manual”,section 13.4 for details regarding the positioning mode (programming method).

See “LECSA Operation Manual”,section 13.9 for details regarding programming methods.

7.5.1 Setting method a. Launch the setup software and select [Program (P)] of [Positioning data]. b. Select [Edit] on the program window to open the program edition window.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

[OK]. e. Program data is written to the driver with [Write All] on the program window.

e b

C a d

- 69 -

7.5.2 Command in the program system

An example of the program commands is shown below.

The maximum number of program steps is 120. Though up to 8 programs can be created, the total number of each program steps is up to 120.

The set program can be selected using point table no./program no. selection 1 (DI0) to point table no./program no. selection 3 (DI2).

 

(1) Command list

Indirect

Description

SPN

STA

STB

Speed (Motor speed)

Acceleration time constant

SPN

(Setting value)

0 to instantaneous permissible speed

STA

(Setting value)

0 to 20000

Deceleration time constant

STB

(Setting value)

0 to 20000 r/min ms ms

Used to set the command speed of the servo motor for positioning.

The set value should be equal to or less than the instantaneous permissible speed of the servo motor.

Used to set the Acceleration time constant.

The set value is the time in which the servo motor reaches the rated speed from a stop.

It cannot be changed during command output.

Used to set the Deceleration time constant.

The set value is the time in which the servo motor stops from the rated speed.

It cannot be changed during command output.

- 70 -

 

 

 

 

7.5.3 Operation Instruction Method of Program System

Select the program No. represented by the values of DI0, DI1 and DI2 and start the operation by selecting

ST1.

Functions/Applications

I/O division

Positioning mode

CP CL

Point table No.

/Program No. selection 1

Point table No.

/Program No. selection 2

Point table No.

/Program No. selection 3

Program input 1

DI0 CN1-5 <In point table method>

The point table No. and the home position return mode are selected by DI0 to DI2.

<In program method>

The program No. is selected by DI0 to DI2.

DI-1

Device

DI1 CN1-23 DI2 DI1 DI0 Program DI-1

0

0

0

0

1

DI2 1

1

0

0

1

1

1

0

0

0

1

0

0

1

0

1

1

PI1

1

Note. 0: off

1

1: on

Turn PI1 on to resume the step stopped by the SYNC (1) command in the program.

DI-1

Program Description

SPN (1000)

STA (200)

STB (300)

MOV (1000)

TIM (100)

MOV (2000)

STOP

Speed (Motor speed)

Acceleration time constant

Deceleration time constant

Absolute move command

Dwell command time

Absolute move command

Program end

1000[r/min]

200[ms]

300[ms]

1000[×10 STM μm]

100[ms]

2000[×10 STM μm] a) b) c) d) e) f) b) Acceleration

time constant

(200ms) c) Deceleration

time constant

(300ms) b) Acceleration

time constant

(200ms) c) Deceleration

time constant

(300ms)

Forward rotation

Servo motor speed

0r/min a) Servo motor

speed

(1000r/min) a) Servo motor

speed

(1000r/min) d) Absolute

move command

(1000 10 STM m) e) Dwell command

time (100ms) f) Absolute

move command

(2000 10 STM m)

 

- 71 -

 

8. Troubleshooting

8.1 Alarms and Warning List

POINT

As soon as an alarm occurs, turn off servo-on (SON) and the main circuit power supply.

When a fault occurs during operation, the corresponding alarm or warning is displayed. If an alarm or warning occurrs, refer to“LECSA Operation Manual”,section 8.2 or“LECSA Operation Manual”,section 8.3 and take the appropriate action. When an alarm occurs, ALM turns off.

After removing the cause of the alarm, the alarm can be deactivated in any of the methods marked in the alarm deactivation column. The warning is automatically canceled after removing the cause of occurrence.

No.

LED display

Name Power

OFF ON

Alarm deactivation

Press "SET" on current alarm screen.

Alarm reset

(RES)

A.10

A.12

A.13

A.15

A.16

A.17

A.19

A.1A

A.1C

A.1E

A.1F

A.20

A.21

A.24

A.30

A.31

A.32

A.33

A.35

A.37

A.45

A.46

A.50

A.51

A.52

A.8E

888

Undervoltage

Memory error 1 (RAM)

Clock error

Memory error 2 (EEP-ROM)

Encoder initial communication error1

Board error

Memory error 3 (Flash-ROM)

Motor combination error

Software combination error

Encoder initial communication error 2

Encoder initial communication error 3

Encoder normal communication error 1

Encoder normal communication error 2

Main circuit error

Regenerative error

Overspeed

Overcurrent

Overvoltage

Command frequency error

Parameter error

Main circuit device overheat

Servo motor overheat

Overload 1

Overload 2

Error excessive

USB communication error

Watchdog

(Note 1)

(Note 1)

(Note 1)

(Note 1)

(Note 1)

(Note 1) (Note

(Note 1) (Note

(Note 1) (Note

(Note 1) (Note

(Note 1) (Note

- 72 -

 

 

3-digit,

LED display

Name

The servo motor stops

/does not stop.

A.90

A.91

A.96

A.97

A.98

A.99

A.E0

A.E1

A.E6

A.E9

A.EC

A.ED

A.F0

Home positioning incomplete warning

Driver overheat warning

Home position setting error

Program operation disabled

Software limit warning

Stroke limit warning

Excessive regeneration warning

Overload warning 1

Servo forced stop warning

Main circuit off warning

Overload warning 2

Output watt excess warning

Tough drive warning

Stops

Does not stop

Stops

Does not stop

Stops (Note 2)

Stops (Note 2)

Does not stop

Does not stop

Stops

Stops

Does not stop

Does not stop

Does not stop

Note 1. Deactivate the alarm about 30 minutes of cooling time after removing the cause of occurrence.

2. Operation to the direction which cancels the warning can be performed.

- 73 -

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Revision history 

No.LEC‐OM05601 

  Dec./2012 1st printing 

No.LEC‐OM05602 

  Dec./2013 2nd printing 

No.LEC‐OM05603 

  Jun./2014 3rd printing 

No.LEC‐OM05604 

  Aug./2014 4th printing 

No.LEC‐OM05605 

  Oct./2014 5th printing 

No.LEC‐OM05606 

  Oct./2014 6th printing 

No.LEC‐OM05607 

  Dec./2014 7th printing 

 

 

4-14-1, Sotokanda, Chiyoda-ku, Tokyo 101-0021 JAPAN

Tel: + 81 3 5207 8249 Fax: +81 3 5298 5362

URL http://www.smcworld.com

Note: Specifications are subject to change without prior notice and any obligation on the part of the manufacturer.

© 2014 SMC Corporation All Rights Reserved

- 74 -

advertisement

Key Features

  • Pulse input type/Positioning type
  • Position control mode
  • Speed control mode
  • Torque control mode
  • Positioning mode
  • Home position return
  • Automatic tuning
  • Electronic gear
  • Setup software (MR Configurator)

Frequently Answers and Questions

What are the different control modes available on the LECSA Series AC Servo Motor Driver?
The LECSA Series AC Servo Motor Driver provides four control modes: Position control mode, Speed control mode, Torque control mode and Positioning mode.
How do I configure parameters for the LECSA Series AC Servo Motor Driver?
The parameters for the LECSA Series AC Servo Motor Driver can be configured using the setup software (MR Configurator).
What is the home position return method for the LECSA Series AC Servo Motor Driver?
The home position return method for the LECSA Series AC Servo Motor Driver is achieved by setting parameters PE03 and PE04.
How do I use the setup software (MR Configurator) to configure the LECSA Series AC Servo Motor Driver?
You can connect the driver to your PC using the USB cable and start the MR Configurator software. Then, select the correct model, upload current parameters, and configure the desired settings.
What is the maximum number of points that can be used in the Point Table method for the LECSA Series AC Servo Motor Driver?
The LECSA Series AC Servo Motor Driver allows for a maximum of 7 points in the point table method.

Related manuals

Download PDF

advertisement

Table of contents