SPLIT CASE FIRE PUMPS
AURORA 900 SERIES
®
Split Case Fire Pumps
Horizontal split case pumps are the most common type of fire
pump. These pumps are specifically designed and tested for
fire service applications where reliability of performance is of
vital importance. Split case pumps are characterized by:
•Easy access to all working parts;
•Rugged construction;
•Liberal water passages; and
•Efficient operation.
Split case fire pumps are specified when the source of water
is located above the surface of the ground and provides a
positive suction pressure to the pump at any performance point.
Single-stage or multistage pumps are available dependent upon
discharge pressure requirements.
Aurora split case fire pumps are built per the rigid standards of
NFPA 20 and are listed by Underwriters Laboratories (UL) and
approved by Factory Mutual (FM).
Available in a broad range of operating pressures and flows
from a minimum of 250 GPM, Aurora split case pumps can be
driven by either an electric motor or diesel engine. Aurora’s
UL-Listed, FM-Approved fire pump packages also include the
system controller, with a full range of options and accessories
available to complete the NFPA-compliant fire pump package.
2
In addition to horizontal split case pumps, Aurora also offers
split case performance in a vertical format. Vertical fire pumps
provide distinct advantages over horizontal pump constructions.
•Less floor space is required.
•In-line piping arrangement allows piping in any direction
in most cases.
•Elevated motor protects against potential flooding if the
pump station is in a low area.
•Components are register-fitted to prevent misalignment.
SPLIT CASE FIRE PUMPS
Pump Features
1
7
2
8
3
14
15
16
17
13
9
4
10
5
6
12
11
18
VERTICAL
SPLIT CASE
1.
2.
3.
4.
5.
6.
7.
Computer Machined
8.
Integral Bearing Arms
9.
major components with 360 degree registered
fits to assure concentricity of parts.
eliminate bearing misalignment and
simplify maintenance.
Enclosed Impeller Design
provides high efficiency and performance.
Dynamically Balanced Impeller
is keyed to the shaft and secured by adjustable
shaft sleeves.
Double Suction Impeller
balances hydraulic thrust loads.
Cast Iron Drip Rim Base
12.
directs condensation and any stuffing box
leakage to drain.
Short Bearing Span
holds shaft deflection to .002" at face of
stuffing box at maximum load.
WWW.AURORAPUMP.COM
15.
Stuffing Boxes
16.
are extra deep for proper sealing. Split packing
glands simplify packing maintenance.
ball bearing.
and nonsparking neoprene rotating slingers
protect both bearings during pump operation
and washdown.
selected for 50,000 hour minimum life
at maximum load. Average bearing life
5 x minimum.
prevent corrosion of the shaft. This eliminates
the need for stainless steel shafts.
Case Wearing Rings
and throttle bushings protect the
casing from wear and are easily and
inexpensively replaced.
Bronze Shaft Sleeve
17.
simplifies disassembly. The suction and
discharge piping and shaft alignment are
not disturbed.
O-Ring Sealed Shaft Sleeves
Grease Seals
Bearings
13.
Interwoven, Graphite
Impregnated T.F.E.
Double Row Thrust
11.
14.
diagonally cut packing rings seal
the pump shaft.
10.
Split Case Design
Internal Water Seal Passages
between volute and stuffing box cannot
be damaged.
HORIZONTAL
SPLIT CASE
prevents shaft wear, is slip fit over the shaft,
keylocked, and extends the entire length
of the seal box.
Certified Performance Test
18.
with Positive Suction Pressure
is provided for each fire pump for customer
approval. Pumps are also hydrostatically tested
per NFPA 20 at no less than 250 psi.
3
Fire Pump Feature Selector
Standard
Optional
• Bronze fitted pump construction
• Ductile iron casings (available in selected 481 and 485 models)
• Bronze shaft sleeves
• Some models available in 316 SST, duplex and super duplex
• Bronze case wearing rings
• Right- or left-hand rotation
• Dynamically balanced impellers
• Impeller wearing rings
• Stainless steel impeller key
• Stainless steel shafts
• Carbon steel shaft
• Double row ball bearings on inboard side
• Corrosion-resistant lantern rings*
• Bronze stuffing box bushings
• External bypass line from casing to stuffing boxes
(optional on Model 480s, standard on Model 490s)
• Bronze or stainless steel glands
• Formed steel drip-rim base (horizontal electric driven units only)
• Interwoven graphite-impregnated T.F.E. packing rings
• 15' Suction lift test to verify performance at 150% of rated flow
• Cast integral bearing arms (most models)
• Available accessories include valves, headers, main relief valves,
increasers and reducers, waste cones, and more.
• Regreaseable ball bearings
• Double row thrust bearing (outboard side)
• Upper casing lifting lugs
• Water slingers and grease seals
• Hydrostatic and Certified Performance test**
• Coupling guard
• Suction and discharge gauges with shutoff cocks
• Automatic air release valve
SUCTION
• Casing relief valve (electric driven units only)
STANDARD
RIGHT-HAND ROTATION
(TOP VIEW HORIZONTAL PUMP)
SUCTION
VERTICAL PUMPS PROVIDE
IN-LINE PIPING IN ANY DIRECTION
(ALSO AVAILABLE RIGHT- OR LEFT-HAND)
OPTIONAL
LEFT-HAND ROTATION
(TOP VIEW HORIZONTAL PUMP)
LIC
E
800 AIRPORT ROAD, NORTH AURORA, ILLINOIS 60542 USA
PARALLELWEG 4, 7102 DE, WINTERSWIJK, THE NETHERLANDS
GULF VALVE, HAMRIYA FREE ZONE, PO BOX 41721, SHARJAH, UAE
NO. 10 JIA YE ROAD BIN HU DISTRICT, WUXI CITY, JIANG SU PROVINCE, CHINA 214124
Because we are continuously improving our products and services, Pentair reserves the right to change specifications without prior notice.
AF-02-1033 03/29/16 © 2016 Pentair Ltd. All Rights Reserved.
UT
HY
IT
WWW.AURORAPUMP.COM
ISO 9001
ST
DR
AU
IN
19 17
ST
EGI
ER E D Q U
TY SYSTEM
ALI
R
*Standard on Model 490s; furnished when suction pressure is below 40 psi on Model 480s.
**Test is performed with positive suction pressure.
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertisement