Mitsubishi QJ71C24/-R2 Specifications

Add to my manuals
66 Pages

advertisement

Mitsubishi QJ71C24/-R2 Specifications | Manualzz
Mitsubishi Electric Corporation
Q/QnA Serial
Communication Driver
1
System Configuration....................................................................................................... 3
2
Selection of External Device .......................................................................................... 10
3
Example of Communication Setting ............................................................................... 11
4
Setup Items .................................................................................................................... 32
5
Cable Diagram ............................................................................................................... 39
6
Range of Supported Device Address............................................................................. 60
7
Device Code and Address Code.................................................................................... 64
8
Error Messages.............................................................................................................. 65
1
Q/QnA Serial Communication Driver
Introduction
This manual describes how to connect the Display and the External Device (target PLC).
In this manual, the connection procedure will be described by following the below sections:
1
System Configuration
This section shows the types of External
Devices which can be connected and SIO
type.
)"1 System Configuration" (page 3)
2
Selection of External Device
Select a model (series) of the External
Device to be connected and connection
method.
)"2 Selection of External Device" (page 10)
3
Example of Communication Settings
This section shows setting examples for
communicating between the Display and
the External Device.
)"3 Example of Communication Setting"
4
Setup Items
This section describes communication
setup items on the Display.
Set communication settings of the Display
with GP-Pro EX or in off-line mode.
)"4 Setup Items" (page 32)
5
Cable Diagram
This section shows cables and adapters
for connecting the Display and the
External Device.
)"5 Cable Diagram" (page 39)
Operation
GP-Pro EX Device/PLC Connection Manual
2
(page 11)
Q/QnA Serial Communication Driver
1
System Configuration
The system configuration in the case when the External Device of Mitsubishi Electric Corp. and the Display are
connected is shown.
Series
CPU
Q02CPU
Q02HCPU
Q06HCPU
Q12HCPU
Q25HCPU
Q00JCPU
Q00CPU
Q01CPU
Q02UCPU
Q03UDCPU
Q04UDHCPU
Q06UDHCPU
MELSEC Q
Q00UJCPU
Q00UCPU
Q01UCPU
Q10UDHCPU
Q13UDHCPU
Q20UDHCPU
Q26UDHCPU
Q03UDECPU
Q04UDEHCPU
Q06UDEHCPU
Q10UDEHCPU
Q13UDEHCPU
Q20UDEHCPU
Q26UDEHCPU
Q00CPU
Q01CPU
Q00UJCPU
Q00UCPU
Q01UCPU
Q02UCPU*2
Link I/F
Example of
Communication
Settings
Cable Diagram
RS232C
Setting Example 3
(page 17)
Cable Diagram 1
(page 39)
RS422/485
(4wire)
Setting Example 4
(page 20)
Cable Diagram 2
(page 41)
RS422/485
(4wire)
Multilink
Setting Example 6
(page 26)
Cable Diagram 6
(page 55)
RS232C
Setting Example 3
(page 17)
Cable Diagram 1
(page 39)
RS422/485
(4wire)
Setting Example 4
(page 20)
Cable Diagram 2
(page 41)
RS422/485
(4wire)
Multilink
Setting Example 6
(page 26)
Cable Diagram 6
(page 55)
RS232C
Setting Example 3
(page 17)
Cable Diagram 1
(page 39)
RS422/485
(4wire)
Setting Example 4
(page 20)
Cable Diagram 2
(page 41)
RS422/485
(4wire)
Multilink
Setting Example 6
(page 26)
Cable Diagram 6
(page 55)
RS232C
Setting Example 5
(page 23)
Cable Diagram 3
(page 47)
SIO Type
QJ71C24
QJ71C24-R2
QJ71C24N
QJ71C24N-R2
QJ71C24
QJ71C24N
QJ71C24N-R4
QJ71C24N
QJ71C24N-R2
QJ71C24N
QJ71C24N-R4
QJ71C24N*1
QJ71C24N-R2*1
QJ71C24N*1
QJ71C24N-R4*1
RS232C connector
on CPU
continued to next page
GP-Pro EX Device/PLC Connection Manual
3
Q/QnA Serial Communication Driver
Series
CPU
Q2ASCPU
Q2ASCPU-S1
Q2ASHCPU
Q2ASHCPU-S1
Link I/F
A1SJ71QC24
A1SJ71QC24N
A1SJ71QC24-R2
A1SJ71QC24N-R2
A1SJ71QC24
A1SJ71QC24N
AJ71QC24
AJ71QC24N
AJ71QC24-R2
AJ71QC24N-R2
AJ71QC24
AJ71QC24N
MELSEC QnA
Example of
Communication
Settings
Cable Diagram
RS232C
Setting Example 1
(page 11)
Cable Diagram 1
(page 39)
RS422/485
(4wire)
Setting Example 2
(page 14)
Cable Diagram 2
(page 41)
RS422/485
(4wire)
Multilink
Setting Example 7
(page 29)
Cable Diagram 6
(page 55)
RS232C
Setting Example 1
(page 11)
Cable Diagram 4
(page 48)
RS422/485
(4wire)
Setting Example 2
(page 14)
Cable Diagram 2
(page 41)
RS422/485
(4wire)
Multilink
Setting Example 7
(page 29)
Cable Diagram 6
(page 55)
RS422/485
(4wire)
(when using
CH1)
Setting Example 2
(page 14)
Cable Diagram 5
(page 50)
RS422/485
(4wire)
(when using
CH2)
Setting Example 2
(page 14)
Cable Diagram 2
(page 41)
RS422/485
(4wire)
(when using
CH2)
Multilink
Setting Example 7
(page 29)
Cable Diagram 6
(page 55)
SIO Type
Q2ACPU
Q2ACPU-S1
Q3ACPU
Q4ACPU
Q4ARCPU
AJ71QC24-R4
AJ71QC24N-R4
*1
The unit whose first 5 digits of the serial No. is less than "10042" cannot be connected with the universal model
built-in Ethernet port QCPU.
*2
Available when using the unit whose first 5 digits of the serial No. is "10102" or later, and GX Developer
version 8.76E or later.
GP-Pro EX Device/PLC Connection Manual
4
Q/QnA Serial Communication Driver
„ Connection Configuration
•
1:1 Connection
External Device
Display
•
1:n Connection
Maximum number of connectable units : 16 units
External Device
Display
•
External Device
1:n Connection (when communicating via network)
You can access other stations via MELSECNET/H, MELSECNET/10, Ethernet or Q Series C24 unit. Note that
you can access only the source station when using the RS232C connector on Q00CPU or Q01CPU.
Maximum number of connectable units : 16 units
Display
External Device
(MELSECNET/H, MELSECNET/10
or Ethernet)
External Device
External Device
• In case of communication via network,please set larger value than the response monitoring time of
the relay station for timeout setteings.
GP-Pro EX Device/PLC Connection Manual
5
Q/QnA Serial Communication Driver
Setting examples for access beyond the network are shown below. Check the details of the setup items in
"Setup Item."
)"4 Setup Items" (page 32)
External Device1
Display
(Station No.5)
Network No.1
(MELSECNET/H)
External Device11
External Device12
Network No.2
(MELSECNET/10)
(PC No.6)
External Device22
External Device21
(PC No.8)
Serial Communication
(I/O No.32)
(Station No.15)
External
Device to be
Port No.
Station No.
Network No.
PC No.
Request
Request
destination
destination
module
module
I/O No.
Station No.
Accessed
External
Device 1
1025
5
0
255
1023
0
External
Device 11
1026
5
1
6
1023
0
External
Device 22
1027
5
2
8
32
15
GP-Pro EX Device/PLC Connection Manual
6
Q/QnA Serial Communication Driver
•
n:1 Connection (Multilink connection)
Maximum number of connectable units: 16 units
Display
Display
Display
External Device
• The maximum number of connectable Displays is 16 units. However, keeping performance in
consideration, the number of Displays that can be substantially used is up to 4.
•
n:m Connection (Multilink connection)
Maximum number of connectable units: 16 units
Display
Display
Display
External Device
External Device
Maximum number of connectable units:
16 units per Display
• The maximum number of connectable Displays is 16 units. However, keeping performance in
consideration, the number of Displays that can be substantially used is up to 4.
GP-Pro EX Device/PLC Connection Manual
7
Q/QnA Serial Communication Driver
„ IPC COM Port
When connecting IPC with an External Device, the COM port used depends on the series and SIO type. Please
refer to the IPC manual for details.
Usable port
Usable Port
Series
RS-232C
RS-422/485(4 wire)
RS-422/485(2 wire)
*1
PS-2000B
COM1 , COM2,
COM3*1, COM4
-
-
PS-3450A, PS-3451A,
PS3000-BA, PS3001-BD
COM1, COM2*1*2
COM2*1*2
COM2*1*2
PS-3650A, PS-3651A
COM1*1
-
-
PS-3700A (Pentium®4-M)
PS-3710A
COM1*1, COM2*1,
COM3*2 , COM4
COM3*2
COM3*2
PS-3711A
COM1*1, COM2*2
COM2*2
COM2*2
PL-3000B, PL-3600T,
PL-3600K, PL-3700T,
PL-3700K, PL-3900T
COM1*1*2, COM2*1,
COM3, COM4
COM1*1*2
COM1*1*2
*1
The RI/5V can be switched. Use the IPC’s switch to change if necessary.
*2
Set up the SIO type with the DIP switch. Please set up as follows according to SIO type to be used.
DIP switch setting: RS-232C
DIP switch
1
Setting
*1
OFF
Description
Reserved (always OFF)
2
OFF
3
OFF
4
OFF
Output mode of SD (TXD) data: Always output
5
OFF
Terminal resistance (220Ω) insertion to SD (TXD): None
6
OFF
Terminal resistance (220Ω) insertion to RD (RXD): None
7
OFF
Short-circuit of SDA (TXA) and RDA (RXA): Not available
8
OFF
Short-circuit of SDB (TXB) and RDB (RXB): Not available
9
OFF
10
OFF
SIO type: RS-232C
RS (RTS) Auto control mode: Disabled
*1
When using PS-3450A, PS-3451A, PS3000-BA and PS3001-BD, turn ON the set value.
GP-Pro EX Device/PLC Connection Manual
8
Q/QnA Serial Communication Driver
DIP switch setting: RS-422/485 (4 wire)
DIP switch
Setting
Description
1
OFF
2
ON
3
ON
4
OFF
Output mode of SD (TXD) data: Always output
5
OFF
Terminal resistance (220Ω) insertion to SD (TXD): None
6
OFF
Terminal resistance (220Ω) insertion to RD (RXD): None
7
OFF
Short-circuit of SDA (TXA) and RDA (RXA): Not available
8
OFF
Short-circuit of SDB (TXB) and RDB (RXB): Not available
Reserved (always OFF)
SIO type: RS-422/485
*1
*1
9
OFF
10
OFF*1
RS (RTS) Auto control mode: Disabled
When the connection configuration are the n:1 and n:m connections (both Multilink connections),
turn ON the set value.
DIP switch setting: RS-422/485 (2 wire)
DIP switch
Setting
Description
1
OFF
2
ON
3
ON
4
OFF
Output mode of SD (TXD) data: Always output
5
OFF
Terminal resistance (220Ω) insertion to SD (TXD): None
6
OFF
Terminal resistance (220Ω) insertion to RD (RXD): None
7
ON
Short-circuit of SDA (TXA) and RDA (RXA): Available
8
ON
Short-circuit of SDB (TXB) and RDB (RXB): Available
9
ON
10
ON
Reserved (always OFF)
SIO type: RS-422/485
RS (RTS) Auto control mode: Enabled
GP-Pro EX Device/PLC Connection Manual
9
Q/QnA Serial Communication Driver
2
Selection of External Device
Select the External Device to be connected to the Display.
Setup Items
Setup Description
Number of Devices/
PLCs
Enter an integer from 1 to 4 for the number of series to set.
Manufacturer
Select the manufacturer of the External Device to be connected. Select "Mitsubishi Electric
Corporation".
Series
Select a model (series) of the External Device to be connected and connection method.
Select "Q/QnA Serial Communication".
Check the External Device which can be connected in "Q/QnA Serial Communication" in
system configuration.
"1 System Configuration" (page 3)
)
Port
Select the Display port to be connected to the External Device.
Use System Area
Check this option to synchronize the system data area of the Display and the device
(memory) of the External Device. When synchronized, you can use the ladder program of
the External Device to switch the display or display the window on the Display.
Cf. GP-Pro EX Reference Manual "Appendix 1.4 LS Area (Direct Access
Method)"
This can be also set with GP-Pro EX or in the Display's off-line mode.
Cf. GP-Pro EX Reference Manual "5.17.6 [System Settings] Setting Guide,
[Display Unit] Settings Guide, System Area Settings"
Cf. Maintenance/Troubleshooting Manual "2.15.1 Settings common to all
Display models, [Main Unit Settings] Settings Guide, System Area Settings"
GP-Pro EX Device/PLC Connection Manual
10
Q/QnA Serial Communication Driver
3
Example of Communication Setting
Examples of communication settings of the Display and the External Device, recommended by Pro-face, are
shown.
3.1
Setting Example 1
„ Setting of GP-Pro EX
‹ Communication Settings
To display the setting screen, select [Device/PLC Settings ] from [System setting window] in workspace.
• When using A1SJ71QC24N, A1SJ71QC24N-R2, AJ71QC24N or AJ71QC24N-R2, you can set
the "Speed" up to 115200.
GP-Pro EX Device/PLC Connection Manual
11
Q/QnA Serial Communication Driver
‹ Device Setting
To display the setting screen, click
([Setting]) of External Device you want to set from [Device-Specific
Settings] of [Device/PLC Settings].
When you connect multiple External Device, click
from [Device-Specific Settings] of [Device/PLC
Settings] to add another External Device.
‹ Important Item
When you use 2 types of interface in A1SJ71QC24N, A1SJ71QC24N-R2, AJ71QC24N or AJ71QC24N-R2,
please set the total speed of CH1 and CH2 to 115200 or less.
GP-Pro EX Device/PLC Connection Manual
12
Q/QnA Serial Communication Driver
„ Setting of External Device
Use the front switch of the computer link unit to set the communication settings as below.
DIP
Switch
Settings
SW1
OFF
Operation Setting = Independent
Operation
SW2
ON
Data Length = 8 bits
SW3
ON
With/Without Parity = With
SW4
OFF
Parity = Odd parity
SW5
OFF
Stop Bit = 1 bit
SW6
ON
Sum Check = Enable
SW7
ON
Write during RUN = Enable
SW8
ON
Setting change Enable/Disable =
Enable
SW9
OFF
SW10
ON
SW11
ON
SW12
OFF
Setup Description
Transmission Speed = 19200
• When using A1SJ71QC24N, A1SJ71QC24N-R2, AJ71QC24N or AJ71QC24N-R2, you can set
the "Speed" up to 115200.
•
•
*1
Station Setting Switch
Setting Switch
Settings
x 10
0
x1
0
Mode Setting Switch
Setting Switch
Settings
MODE (CH1)
5*1
MODE (CH2)
5*1
Set the value according to [Format] to be used.
‹ Important Item
When you use 2 types of interface in A1SJ71QC24N, A1SJ71QC24N-R2, AJ71QC24N or AJ71QC24N-R2,
please set the total speed of CH1 and CH2 to 115200 or less.
GP-Pro EX Device/PLC Connection Manual
13
Q/QnA Serial Communication Driver
3.2
Setting Example 2
„ Setting of GP-Pro EX
‹ Communication Settings
To display the setting screen, select [Device/PLC Settings] from [System setting window] in workspace.
• When using A1SJ71QC24N, AJ71QC24N or AJ71QC24N-R4, you can set the "Speed" up to
115200.
GP-Pro EX Device/PLC Connection Manual
14
Q/QnA Serial Communication Driver
‹ Device Setting
To display the setting screen, click
([Setting]) of External Device you want to set from [Device-Specific
Settings] of [Device/PLC Settings].
When you connect multiple External Device, click
from [Device-Specific Settings] of [Device/PLC
Settings] to add another External Device.
‹ Important Item
When you use 2 types of interface in A1SJ71QC24N, AJ71QC24N or AJ71QC24N-R4, please set the total speed
of CH1 and CH2 to 115200 or less.
GP-Pro EX Device/PLC Connection Manual
15
Q/QnA Serial Communication Driver
„ Setting of External Device
Use the front switch of the computer link unit to set the communication settings as below.
DIP
Switch
Settings
SW1
OFF
Operation Setting = Independent
Operation
SW2
ON
Data Length = 8 bits
SW3
ON
With/Without Parity = With
SW4
OFF
Parity = Odd parity
SW5
OFF
Stop Bit = 1 bit
SW6
ON
Sum Check = Enable
SW7
ON
Write during RUN = Enable
SW8
ON
Setting change Enable/Disable =
Enable
SW9
OFF
SW10
ON
SW11
ON
SW12
OFF
Setup Description
Transmission Speed = 19200
• When using A1SJ71QC24N, AJ71QC24N or AJ71QC24N-R4, you can set the "Speed" up to
115200.
•
•
*1
Station Setting Switch
Setting Switch
Settings
x 10
0
x1
0
Mode Setting Switch
Setting Switch
Settings
MODE (CH1)
5*1
MODE (CH2)
5*1
Set the value according to [Format] to be used.
‹ Important Item
When you use 2 types of interface in A1SJ71QC24N, AJ71QC24N or AJ71QC24N-R4, please set the total speed
of CH1 and CH2 to 115200 or less.
GP-Pro EX Device/PLC Connection Manual
16
Q/QnA Serial Communication Driver
3.3
Setting Example 3
„ Setting of GP-Pro EX
‹ Communication Settings
To display the setting screen, select [Device/PLC Settings] from [System setting window] in workspace.
GP-Pro EX Device/PLC Connection Manual
17
Q/QnA Serial Communication Driver
‹ Device Setting
To display the setting screen, click
([Setting]) of External Device you want to set from [Device-Specific
Settings] of [Device/PLC Settings].
When you connect multiple External Device, click
from [Device-Specific Settings] of [Device/PLC
Settings] to add another External Device.
‹ Important Item
When you use 2 types of interface in QJ71C24 or QJ71C24-R2, please set the total speed of CH1 and CH2 to
115200 or less.
GP-Pro EX Device/PLC Connection Manual
18
Q/QnA Serial Communication Driver
„ Setting of External Device
Use the GPP function software by Mitsubishi Electric Corporation to perform the communication settings as
below.
(1) Double-click [PC Parameter] from [Parameter] to select the [I/O Assign Setting] tab.
(2) Click [Type] to select [Intelligent].
(3) Click [Switch Settings] and set as below.
Setting Switch
Setting
Value
Switch 1
07E6
Switch 2
0005*1
Mode = Form 5
Switch 5
0000
Station No. = 0
*1
Setup Description
19200/8/With/Odd/1
Set the value according to [Format] to be used.
• Please refer to the manual of the External Device for more detail on setting description.
‹ Important Item
When you use 2 types of interface in QJ71C24 or QJ71C24-R2, please set the total speed of CH1 and CH2 to
115200 or less.
GP-Pro EX Device/PLC Connection Manual
19
Q/QnA Serial Communication Driver
3.4
Setting Example 4
„ Setting of GP-Pro EX
‹ Communication Settings
To display the setting screen, select [Device/PLC Settings] from [System setting window] in workspace.
GP-Pro EX Device/PLC Connection Manual
20
Q/QnA Serial Communication Driver
‹ Device Setting
To display the setting screen, click
([Setting]) of External Device you want to set from [Device-Specific
Settings] of [Device/PLC Settings].
When you connect multiple External Device, click
from [Device-Specific Settings] of [Device/PLC
Settings] to add another External Device.
‹ Important Item
When you use 2 types of interface in QJ71C24, please set the total speed of CH1 and CH2 to 115200 or less.
GP-Pro EX Device/PLC Connection Manual
21
Q/QnA Serial Communication Driver
„ Setting of External Device
Use the GPP function software by Mitsubishi Electric Corporation to perform the communication settings as
below.
(1) Double-click [PC Parameter] from [Parameter] to select the [I/O Assign Setting] tab.
(2) Click [Type] to select [Intelligent].
(3) Click [Switch Settings] and set as below.
Setting Switch
Setting
Value
Switch 3
07E6
Switch 4
0005*1
Mode = Form 5
Switch 5
0000
Station No. = 0
*1
Setup Description
19200/8/With/Odd/1
Set the value according to [Format] to be used.
• Please refer to the manual of the External Device for more detail on setting description.
‹ Important Item
When you use 2 types of interface in QJ71C24, please set the total speed of CH1 and CH2 to 115200 or less.
GP-Pro EX Device/PLC Connection Manual
22
Q/QnA Serial Communication Driver
3.5
Setting Example 5
„ Setting of GP-Pro EX
‹ Communication Settings
To display the setting screen, select [Device/PLC Settings] from [System setting window] in workspace.
GP-Pro EX Device/PLC Connection Manual
23
Q/QnA Serial Communication Driver
‹ Device Setting
To display the setting screen, click
([Setting]) of External Device you want to set from [Device-Specific
Settings] of [Device/PLC Settings].
When you connect multiple External Device, click
from [Device-Specific Settings] of [Device/PLC
Settings] to add another External Device.
GP-Pro EX Device/PLC Connection Manual
24
Q/QnA Serial Communication Driver
„ Setting of External Device
Use the GPP function software by Mitsubishi Electric Corporation to perform the communication settings as
below.
(1) Double-click [PC Parameter] from [Parameter] to select [Serial Communication Settings].
(2) Set as below.
*1
Setup Items
Settings
Use Serial Communication Function*1
Use
Baud Rate
19.2Kbps
Sum Check
Enable
Transmission Wait Time
No Wait
Write Setting during RUN
Enable
Check the checkbox to make other setting items become available to set.
GP-Pro EX Device/PLC Connection Manual
25
Q/QnA Serial Communication Driver
3.6
Setting Example 6
„ Setting of GP-Pro EX
‹ Communication Settings
To display the setting screen, select [Device/PLC Settings] from [System setting window] in workspace.
• When simultaneously using GP2000 Series during multilink connection, select "QnA Comp. 3C
Frame: Format 4" from the "Format".
GP-Pro EX Device/PLC Connection Manual
26
Q/QnA Serial Communication Driver
‹ Device Setting
To display the setting screen, click
([Setting]) of External Device you want to set from [Device-Specific
Settings] of [Device/PLC Settings].
When you connect multiple External Device, click
from [Device-Specific Settings] of [Device/PLC
Settings] to add another External Device.
‹ Important Item
When you use 2 types of interface in QJ71C24, please set the total speed of CH1 and CH2 to 115200 or less.
GP-Pro EX Device/PLC Connection Manual
27
Q/QnA Serial Communication Driver
„ Setting of External Device
Use the GPP function software by Mitsubishi Electric Corporation to perform the communication settings as
below.
(1) Double-click [PC Parameter] from [Parameter] to select the [I/O Assign Setting] tab.
(2) Click [Type] to select [Intelligent].
(3) Click [Switch Settings] and set as below.
Setting Switch
Setting
Value
Switch 3
07E6
Switch 4
0005*1
Mode = Form 5
Switch 5
0000
Station No. = 0
*1
Setup Description
19200/8/With/Odd/1
Set the value according to [Format] to be used.
• Please refer to the manual of the External Device for more detail on setting description.
‹ Important Item
When you use 2 types of interface in QJ71C24, please set the total speed of CH1 and CH2 to 115200 or less.
GP-Pro EX Device/PLC Connection Manual
28
Q/QnA Serial Communication Driver
3.7
Setting Example 7
„ Setting of GP-Pro EX
‹ Communication Settings
To display the setting screen, select [Device/PLC Settings] from [System setting window] in workspace.
• When using A1SJ71QC24N, AJ71QC24N or AJ71QC24N-R4, you can set the "Speed" up to
115200.
• When simultaneously using GP2000 Series during multilink connection, select "QnA Comp. 3C
Frame: Format 4" from the "Format".
GP-Pro EX Device/PLC Connection Manual
29
Q/QnA Serial Communication Driver
‹ Device Setting
To display the setting screen, click
([Setting]) of External Device you want to set from [Device-Specific
Settings] of [Device/PLC Settings].
When you connect multiple External Device, click
from [Device-Specific Settings] of [Device/PLC
Settings] to add another External Device.
‹ Important Item
When you use 2 types of interface in A1SJ71QC24N, AJ71QC24N or AJ71QC24N-R4, please set the total speed
of CH1 and CH2 to 115200 or less.
GP-Pro EX Device/PLC Connection Manual
30
Q/QnA Serial Communication Driver
„ Setting of External Device
Use the front switch of the computer link unit to set the communication settings as below.
DIP
Switch
Settings
SW1
OFF
Operation Setting = Independent
Operation
SW2
ON
Data Length = 8 bits
SW3
ON
With/Without Parity = With
SW4
OFF
Parity = Odd parity
SW5
OFF
Stop Bit = 1 bit
SW6
ON
Sum Check = Enable
SW7
ON
Write during RUN = Enable
SW8
ON
Setting change Enable/Disable =
Enable
SW9
OFF
SW10
ON
SW11
ON
SW12
OFF
Setup Description
Transmission Speed = 19200
• When using A1SJ71QC24N, AJ71QC24N or AJ71QC24N-R4, you can set the "Speed" up to
115200.
•
•
*1
Station Setting Switch
Setting Switch
Settings
x 10
0
x1
0
Mode Setting Switch
Setting Switch
Settings
MODE (CH1)
5*1
MODE (CH2)
5*1
Set the value according to [Format] to be used.
‹ Important Item
When you use 2 types of interface in A1SJ71QC24N, AJ71QC24N or AJ71QC24N-R4, please set the total speed
of CH1 and CH2 to 115200 or less.
GP-Pro EX Device/PLC Connection Manual
31
Q/QnA Serial Communication Driver
4
Setup Items
Set communication settings of the Display with GP-Pro EX or in off-line mode of the Display.
The setting of each parameter must be identical to that of External Device.
)"3 Example of Communication Setting" (page 11)
4.1
When setting with GP-Pro EX
„ Communication Settings
To display the setting screen, select [Device/PLC Settings] from [System setting window] in workspace.
Setup Items
Setup Description
SIO Type
Select the SIO type to communicate with the External Device.
Speed
Select speed between the External Device and the Display.
Data Length
Select data length.
Parity
Select how to check parity.
Stop Bit
Select stop bit length.
Flow Control
Select the communication control method to prevent overflow of transmission and
reception data.
Use an integer from 1 to 127 to enter the time (s) for which the Display waits for the
response from the External Device.
Timeout
In case of communicating via network,please set larger value than the response monitoring
time of the relay station for timeout settings.
Retry
In case of no response from the External Device, use an integer from 0 to 255 to enter how
many times the Display retransmits the command.
Wait To Send
Use an integer from 0 to 255 to enter standby time (ms) for the Display from receiving
packets to transmitting next commands.
continued to next page
GP-Pro EX Device/PLC Connection Manual
32
Q/QnA Serial Communication Driver
Setup Items
Setup Description
Select the communication frame for the use of MELSEC communication protocol, from
"QnA Comp. 3C Frame: Format 4" or "QnA Comp. 4C Frame: Format 5".
Format
When simultaneously using GP2000 Series during multilink connection, select "QnA
Comp. 3C Frame: Format 4"
RI/VCC
You can switch RI/VCC of the 9th pin when you select RS232C for SIO type.
It is necessary to change RI/5V by changeover switch of IPC when connect with IPC.
Please refer to the manual of the IPC for more detail.
GP-Pro EX Device/PLC Connection Manual
33
Q/QnA Serial Communication Driver
„ Device Setting
To display the setting screen, click
([Setting]) of External Device you want to set from [Device-Specific
Settings] of [Device/PLC Settings].
When [Allowable No. of Device/PLCs] is multiple, click
from [Device-Specific Settings] of [Device/PLC
Settings] to add another External Device.
Setup Items
Setup Description
Station No.
Use an integer from 0 to 31 to enter the station number of the External Device directly
connected to the Display.
Connected to Q Series
C24 I/F Module
Check this checkbox only when the Q Series C24 I/F unit is used.
If this is checked when the Q Series C24 I/F unit is not used, the error may be displayed on
the External Device.
Network No.
Set when you communicate via network. Use an integer from 0 to 239 to enter network No.
of the External Device to communicate. If you do not communicate via network, enter 0.
PC No.
Set when you communicate via network. Use an integer from 0 to 64 or 125 to 126 to enter
PC No. of the External Device to communicate. If you do not communicate via network,
enter 255.
Request destination
module I/O No.
Set when you communicate via network. Use an integer from 0 to 511 to enter I/O No. of
the External Device to communicate. If you do not communicate via network, enter 1023.
Request destination
module Station No.
Set when you communicate via network. Use an integer from 0 to 31 to enter station No. of
the External Device to communicate. If you do not communicate via network, enter 0.
GP-Pro EX Device/PLC Connection Manual
34
Q/QnA Serial Communication Driver
4.2
Communication Settings in Off-line Mode
• Refer to the Maintenance/Troubleshooting manual for information on how to enter off-line mode
or about the operation.
Cf.
Maintenance/Troubleshooting Manual "2.2 Off-line Mode"
• The number of the setup items to be displayed for 1 page in the off-line mode depends on the
Display in use. Please refer to the Reference manual for details.
„ Communication Settings
To display the setting screen, touch [Device/PLC Settings] from [Peripheral Settings] in off-line mode. Touch the
External Device you want to set from the displayed list.
Setup Items
Setup Description
Select the SIO type to communicate with the External Device.
SIO Type
To make the communication settings correctly, confirm the serial interface specifications of
Display unit for [SIO Type].
We cannot guarantee the operation if a communication type that the serial interface does
not support is specified.
For details concerning the serial interface specifications, refer to the manual for Display
unit.
Speed
Select speed between the External Device and the Display.
Data Length
Select data length.
Parity
Select how to check parity.
Stop Bit
Select stop bit length.
Flow Control
Select the communication control method to prevent overflow of transmission and
reception data.
continued to next page
GP-Pro EX Device/PLC Connection Manual
35
Q/QnA Serial Communication Driver
Setup Items
Setup Description
Use an integer from 1 to 127 to enter the time (sec) for which the Display waits for the
response from the External Device.
Timeout
In case of communicating via network,please set larger value than the response monitoring
time of the relay station for timeout settings.
Retry
In case of no response from the External Device, use an integer from 0 to 255 to enter how
many times the Display retransmits the command.
Wait To Send
Use an integer from 0 to 255 to enter standby time (ms) for the Display from receiving
packets to transmitting next commands.
Select the communication frame for the use of MELSEC communication protocol, from
"QnA Comp. 3C Frame: Format 4" or "QnA Comp. 4C Frame: Format 5".
Format
When simultaneously using GP2000 Series during multilink connection, select "QnA
Comp. 3C Frame: Format 4"
GP-Pro EX Device/PLC Connection Manual
36
Q/QnA Serial Communication Driver
„ Device Setting
To display the setting screen, touch [Device/PLC Settings] from [Peripheral Settings]. Touch the External Device
you want to set from the displayed list, and touch [Device].
Setup Items
Setup Description
Device/PLC Name
Select the External Device for device setting. Device name is a title of External Device set
with GP-Pro EX.(Initial value [PLC1])
Station No.
Use an integer from 0 to 31 to enter the station number of the External Device directly
connected to the Display.
Q Series C24 I/F
Select “ON” and “OFF” respectively when the Q Series C24 I/F unit is used and when the
Q Series C24 I/F unit is not used.
If “ON” is selected when the Q Series C24 I/F unit is not used, the error may be displayed
on the External Device.
Network No.
Set when you communicate via network. Use an integer from 0 to 239 to enter network No.
of the External Device to communicate. If you do not communicate via network, enter 0.
PC No.
Set when you communicate via network. Use an integer from 0 to 64 or 125 to 126 to enter
PC No. of the External Device to communicate. If you do not communicate via network,
enter 255.
Request destination
module I/O No.
Set when you communicate via network. Use an integer from 0 to 511 to enter I/O No. of
the External Device to communicate. If you do not communicate via network, enter 1023.
Request destination
module Station No.
Set when you communicate via network. Use an integer from 0 to 31 to enter station No. of
the External Device to communicate. If you do not communicate via network, enter 0.
• Do not set the duplicate device settings in multiple devices. Illegal address may be read.
GP-Pro EX Device/PLC Connection Manual
37
Q/QnA Serial Communication Driver
„ Option
To display the setting screen, touch [Device/PLC Settings] from [Peripheral Settings]. Touch the External Device
you want to set from the displayed list, and touch [Option].
Setup Items
RI/VCC
Setup Description
You can switch RI/VCC of the 9th pin when you select RS232C for SIO type.
It is necessary to change RI/5V by changeover switch of IPC when connect with IPC.
Please refer to the manual of the IPC for more detail.
• GP-4100 series do not have the [Option] setting in the off-line mode.
GP-Pro EX Device/PLC Connection Manual
38
Q/QnA Serial Communication Driver
5
Cable Diagram
The cable diagram shown below may be different from the cable diagram recommended by Mitsubishi Electric
Corp. Please be assured there is no operational problem in applying the cable diagram shown in this manual.
•
The FG pin of the External Device body must be D-class grounded. Please refer to the manual of the External
•
SG and FG are connected inside the Display. When connecting SG to the External Device, design the system
Device for more details.
not to form short-circuit loop.
•
Connect the isolation unit, when communication is not stabilized under the influence of a noise etc..
Cable Diagram 1
Display
(Connection Port)
GP3000 (COM1)
ST (COM1)
IPC*1
PC/AT
GP-4105 (COM1)
*1
Cable
Notes
1A
Mitsubishi Q link cable by Pro-face
CA3-CBLLNKMQ-01
1B
User-created cable
1C
User-created cable
The cable length must be
15m or less.
Only the COM port which can communicate by RS-232C can be used.
„ IPC COM Port (page 8)
)
1A)
CA3-CBLLNKMQ-01
Display
External Device
1B)
Display side
D-sub 9 pin (socket)
Display
Shield
External Device side
D-sub 9 pin (plug)
Pin
Signal name
Pin
Signal name
2
RD(RXD)
3
SD(TXD)
3
SD(TXD)
2
RD(RDX)
4
ER(DTR)
6
DSR(DR)
5
SG
5
SG
7
RS(RTS)
1
CD
8
CS(CTS)
4
DTR(ER)
8
CS(CTS)
Shell
FG
GP-Pro EX Device/PLC Connection Manual
39
Q/QnA Serial Communication Driver
1C)
Display side
Terminal block
Display
Shield
External Device side
D-sub 9 pin (plug)
Signal name
Pin
Signal name
RD(RXD)
3
SD(TXD)
SD(TXD)
2
RD(RDX)
ER(DTR)
6
DSR(DR)
SG
5
SG
RS(RTS)
1
CD
CS(CTS)
4
DTR(ER)
8
CS(CTS)
Shell
FG
GP-Pro EX Device/PLC Connection Manual
40
Q/QnA Serial Communication Driver
Cable Diagram 2
Display
(Connection Port)
GP3000*1 (COM1)
AGP-3302B (COM2)
ST*2 (COM2)
IPC*3
Cable
2A
COM port conversion adapter
by Pro-face
CA3-ADPCOM-01
+
Connector terminal block conversion adapter
by Pro-face
CA3-ADPTRM-01
+
User-created cable
2B
User-created cable
2C
Online adapter by Pro-face
CA4-ADPONL-01
+
Connector terminal block conversion adapter
by Pro-face
CA3-ADPTRM-01
+
User-created cable
2D
Online adapter by Pro-face
CA4-ADPONL-01
+
User-created cable
2E
User-created cable
GP3000*4 (COM2)
GP-4106 (COM1)
*1
All GP3000 models except AGP-3302B
*2
All ST models except AST-3211A and AST-3302B
*3
Only the COM port which can communicate by RS-422/485 (4 wire) can be used.
„ IPC COM Port (page 8)
*4
All GP3000 models except GP-3200 series and AGP-3302B
)
GP-Pro EX Device/PLC Connection Manual
41
Notes
The cable length must be
500m or less.
Q/QnA Serial Communication Driver
2A)
•
1:1 Connection
Sdqlhm`k
aknbj
Chrok`x
B@2,@COBNL,/0
Sdqlhm`shnm
qdrhrs`mbd
22/Ω0.3V
B@2,@COSQL,/0
Dwsdqm`k
Cduhbdrhcd
Rghdkc
Rhfm`k
m`ld
Rhfm`k
m`ld
QC@
RC@
QCA
RCA
RC@
QC@
RCA
QCA
RF
RF
Sdqlhm`shnm
qdrhrs`mbd
22/Ω0.3V
EF
Trdq,bqd`sdcb`akd
•
1:n Connection
Sdqlhm`shnm
qdrhrs`mbd
22/Ω0.3V
Chrok`x
B@2,@COBNL,/0
B@2,@COSQL,/0
Sdqlhm`shnm
qdrhrs`mbd
22/Ω0.3V
Sdqlhm`k
aknbj
Rghdkc
Dwsdqm`k
Cduhbdrhcd
Rghdkc
Dwsdqm`k
Cduhbdrhcd
Rhfm`k
m`ld
Rhfm`k
m`ld
Rhfm`k
m`ld
QC@
RC@
RC@
QCA
RCA
RCA
RC@
QC@
QC@
RCA
QCA
QCA
RF
RF
RF
EF
EF
Trdq,bqd`sdcb`akd
GP-Pro EX Device/PLC Connection Manual
42
Sdqlhm`shnm
qdrhrs`mbd
22/Ω0.3V
Sdqlhm`shnm
qdrhrs`mbd
22/Ω0.3V
Q/QnA Serial Communication Driver
2B)
•
1:1 Connection
Chrok`xrhcd
C,rta8ohm'rnbjds(
Sdqlhm`shnm
qdrhrs`mbd
22/Ω0.3V
Chrok`x
•
Rghdkc
Dwsdqm`k
Cduhbdrhcd
Ohm
Rhfm`k
m`ld
Rhfm`k
m`ld
0
QC@
RC@
1
QCA
RCA
2
RC@
QC@
6
RCA
QCA
4
RF
RF
3
DQ@
EF
7
BR@
8
DQA
5
BRA
Rgdkk
EF
Sdqlhm`shnm
qdrhrs`mbd
22/Ω0.3V
1:n Connection
Chrok`xrhcd
C,rta8ohm'rnbjds(
Sdqlhm`shnm
qdrhrs`mbd
22/Ω0.3V
Chrok`x
Sdqlhm`shnm
qdrhrs`mbd
22/Ω0.3V
Rghdkc
Dwsdqm`k
Cduhbdrhcd
Rghdkc
Dwsdqm`k
Cduhbdrhcd
Ohm
Rhfm`k
m`ld
Rhfm`k
m`ld
0
QC@
RC@
1
QCA
RCA
RCA
2
RC@
QC@
QC@
6
RCA
QCA
QCA
4
RF
RF
RF
3
DQ@
EF
EF
7
BR@
8
DQA
5
BRA
GP-Pro EX Device/PLC Connection Manual
43
Rhfm`k
m`ld
RC@
Sdqlhm`shnm
qdrhrs`mbd
22/Ω0.3V
Sdqlhm`shnm
qdrhrs`mbd
22/Ω0.3V
Q/QnA Serial Communication Driver
2C)
•
1:1 Connection
Sdqlhm`k
aknbj
Sdqlhm`shnm
qdrhrs`mbd
22/Ω0.3V
Chrok`x
B@3,@CONMK,/0
B@2,@COSQL,/0
Rghdkc
Rhfm`k
m`ld
Dwsdqm`k
Cduhbdrhcd
Rhfm`k
m`ld
QC@
RC@
QCA
RCA
RC@
QC@
RCA
QCA
RF
RF
Sdqlhm`shnm
qdrhrs`mbd
22/Ω0.3V
EF
Trdq,bqd`sdcb`akd
•
1:n Connection
Sdqlhm`k
aknbj
Sdqlhm`shnm
qdrhrs`mbd
22/Ω0.3V
Chrok`x
B@3,@CONMK,/0
Sdqlhm`shnm
qdrhrs`mbd
B@2,@COSQL,/0 22/Ω0.3V
Rghdkc
Dwsdqm`k
Cduhbdrhcd
Rghdkc
Dwsdqm`k
Cduhbdrhcd
Rhfm`k
m`ld
Rhfm`k
m`ld
Rhfm`k
m`ld
QC@
RC@
RC@
QCA
RCA
RCA
RC@
QC@
QC@
RCA
QCA
QCA
RF
RF
RF
EF
EF
Trdq,bqd`sdcb`akd
GP-Pro EX Device/PLC Connection Manual
44
Sdqlhm`shnm
qdrhrs`mbd
22/Ω0.3V
Sdqlhm`shnm
qdrhrs`mbd
22/Ω0.3V
Q/QnA Serial Communication Driver
2D)
•
1:1 Connection
C,rta8ohm'oktf(
Sdqlhm`shnm
qdrhrs`mbd
22/Ω0.3V
Dwsdqm`k
Cduhbdrhcd
Ohm
Rhfm`k
m`ld
Rhfm`k
m`ld
1
QC@
RC@
6
QCA
RCA
2
RC@
QC@
7
RCA
QCA
4
RF
RF
Rgdkk
EF
EF
Chrok`x
B@3,@CONMK,/0
Rghdkc
Sdqlhm`shnm
qdrhrs`mbd
22/Ω0.3V
Trdq,bqd`sdcb`akd
•
1:n Connection
C,rta8ohm'oktf(
Sdqlhm`shnm
qdrhrs`mbd
22/Ω0.3V
B@3,@CONMK,/0
Chrok`x
Sdqlhm`shnm
qdrhrs`mbd
22/Ω0.3V
Rghdkc
Dwsdqm`k
Cduhbdrhcd
Rhfm`k
m`ld
RC@
Rghdkc
Dwsdqm`k
Cduhbdrhcd
Ohm
Rhfm`k
m`ld
1
QC@
6
QCA
RCA
RCA
2
RC@
QC@
QC@
7
RCA
QCA
QCA
4
RF
RF
RF
Rgdkk
EF
EF
EF
Trdq,bqd`sdcb`akd
GP-Pro EX Device/PLC Connection Manual
45
Rhfm`k
m`ld
RC@
Sdqlhm`shnm
qdrhrs`mbd
22/Ω0.3V
Sdqlhm`shnm
qdrhrs`mbd
22/Ω0.3V
Q/QnA Serial Communication Driver
2E)
•
1:1 Connection
Display side
Terminal block
Termination
resistance*1
Display
Shield
External
Device side
Signal
name
Signal
name
RDA
SDA
RDB
SDB
SDA
RDA
SDB
RDB
SG
SG
ERA
FG
Termination
resistance
330Ω 1/4W
CSA
ERB
CSB
*1
The resistance in the Display is used as the termination resistance. Set the value of the DIP Switch on the
rear of the Display as shown in the table below.
•
DIP Switch No.
Set Value
1
OFF
2
OFF
3
ON
4
OFF
1:n Connection
Display side
Terminal block
Termination
resistance*2
Display
Termination
resistance*2
Shield
External
Device side
Signal
name
Signal
name
RDA
SDA
Shield
External
Device side
Signal
name
SDA
RDB
SDB
SDB
SDA
RDA
RDA
SDB
RDB
RDB
SG
SG
SG
ERA
FG
FG
Termination
resistance
330Ω 1/4W
Termination
resistance
330Ω 1/4W
CSA
ERB
CSB
*2
The resistance in the Display is used as the termination resistance. Set the value of the DIP Switch on the
rear of the Display as shown in the table below.
DIP Switch No.
Set Value
1
ON
2
OFF
3
ON
4
OFF
GP-Pro EX Device/PLC Connection Manual
46
Q/QnA Serial Communication Driver
Cable Diagram 3
Display
(Connection Port)
Cable
Notes
GP3000 (COM1)
ST (COM1)
IPC*1
PC/AT
3A
Mitsubishi Q connection cable by Pro-face
CA3-CBLQ-01 (5m)
or
RS-232C cable by Mitsubishi Electric Corp.
QC30R2 (3m)
or
RS-232C cable for QCPU connection by Diatrend Corp.
DQCABR2V-H
GP-4105 (COM1)
3B
Mitsubishi PLC Q Series CPU I/F Cable by Pro-face
ZC9CBQ31(3m)
*1
Available to order
the length of
DQCABR2V-H by
Diatrend Corp. up
to 15m.
Only the COM port which can communicate by RS-232C can be used.
„ IPC COM Port (page 8)
)
3A)
CA3-CBLQ-01
or
QC30R2
or
DQCABR2V-H
Display
External Device
3B)
Display side
Terminal block
Signal name Cable color
Display
RD(RXD)
Green
SD(TXD)
Brown
ER(DTR)
Yellow
External Device
SG
ZC9CBQ31
Red
Orange
DR(DSR)
Blue
Blue
CS(CTS)
Blue
GP-Pro EX Device/PLC Connection Manual
47
Q/QnA Serial Communication Driver
Cable Diagram 4
Display
(Connection Port)
GP3000 (COM1)
ST (COM1)
IPC*1
PC/AT
GP-4105 (COM1)
*1
Cable
Notes
4A
RS-232C cable by Pro-face
CA3-CBL232/5M-01 (5m)
4B
User-created cable
4C
User-created cable
The cable length must be
15m or less.
Only the COM port which can communicate by RS-232C can be used.
„ IPC COM Port (page 8)
)
4A)
Display
External Device
CA3-CBL232/5M-01
4B)
Display side
D-sub 9 pin (socket)
Display
External Device side
D-sub 25 pin (plug)
Shield
Pin
Signal name
RD(RXD)
2
SD(TXD)
3
SD(TXD)
3
RD(RXD)
4
ER(DTR)
6
DSR(DR)
5
SG
7
SG
7
RS(RTS)
8
CD
8
CS(CTS)
20
DTR(ER)
5
CS(CTS)
1
FG
Pin
Signal name
2
GP-Pro EX Device/PLC Connection Manual
48
Q/QnA Serial Communication Driver
4C)
External Device side
D-sub 25 pin (plug)
Display side
Terminal block
Display
Shield
Pin
Signal name
RD(RXD)
2
SD(TXD)
SD(TXD)
3
RD(RXD)
ER(DTR)
6
DSR(DR)
SG
7
SG
RS(RTS)
8
CD
CS(CTS)
20
DTR(ER)
5
CS(CTS)
1
FG
Signal name
GP-Pro EX Device/PLC Connection Manual
49
Q/QnA Serial Communication Driver
Cable Diagram 5
Display
(Connection Port)
GP3000*1 (COM1)
AGP-3302B (COM2)
ST*2 (COM2)
IPC*3
Cable
5A
COM port conversion adapter
by Pro-face
CA3-ADPCOM-01
+
Connector terminal block conversion adapter
by Pro-face
CA3-ADPTRM-01
+
User-created cable
5B
User-created cable
5C
Online adapter by Pro-face
CA4-ADPONL-01
+
Connector terminal block conversion adapter
by Pro-face
CA3-ADPTRM-01
+
User-created cable
5D
Online adapter by Pro-face
CA4-ADPONL-01
+
User-created cable
5E
User-created cable
GP3000*4 (COM2)
GP-4106 (COM1)
*1
All GP3000 models except AGP-3302B
*2
All ST models except AST-3211A and AST-3302B
*3
Only the COM port which can communicate by RS-422/485 (4 wire) can be used.
„ IPC COM Port (page 8)
*4
All GP3000 models except GP-3200 series and AGP-3302B
)
GP-Pro EX Device/PLC Connection Manual
50
Notes
The cable length must be
500m or less.
Q/QnA Serial Communication Driver
5A)
Sdqlhm`shnm
qdrhrs`mbd
22/Ω0.3V
Dwsdqm`kCduhbdrhcd
C,rta14ohm'oktf(
Sdqlhm`k
aknbj
Chrok`x
B@2,@COBNL,/0
B@2,@COSQL,/0
Rghdkc
Rhfm`k
m`ld
Ohm
Rhfm`k
m`ld
QC@
2
RC@
QCA
05
RCA
RC@
1
QC@
RCA
04
QCA
RF
6
RF
RF
7
RF
1/
RF
10
RF
3
CRQ@
4
CSQ@
06
CRQA
07
CSQA
0
EF
Trdq,bqd`sdcb`akd
• As the External Device has the termination resistance built-in, you do not need to connect the
termination resistance.
5B)
Chrok`xrhcd
C,rta8ohm'rnbjds(
Sdqlhm`shnm
qdrhrs`mbd
22/Ω0.3V
Chrok`x
Dwsdqm`kCduhbdrhcd
C,rta14ohm'oktf(
Rghdkc
Ohm
Rhfm`k
m`ld
QC@
2
RC@
1
QCA
05
RCA
2
RC@
1
QC@
6
RCA
04
QCA
4
RF
6
RF
3
DQ@
7
RF
7
BR@
1/
RF
8
DQA
10
RF
5
BRA
3
CRQ@
4
CSQ@
06
CRQA
07
CSQA
0
EF
Ohm
Rhfm`k
m`ld
0
• As the External Device has the termination resistance built-in, you do not need to connect the
termination resistance.
GP-Pro EX Device/PLC Connection Manual
51
Q/QnA Serial Communication Driver
5C)
Dwsdqm`kCduhbdrhcd
C,rta14ohm'oktf(
Sdqlhm`k
aknbj
Sdqlhm`shnm
qdrhrs`mbd Rhfm`km`ld
22/Ω0.3V
Rghdkc
Ohm
Rhfm`k
m`ld
QC@
2
RC@
QCA
05
RCA
RC@
1
QC@
RCA
04
QCA
RF
6
RF
RF
7
RF
1/
RF
10
RF
3
CRQ@
4
CSQ@
06
CRQA
07
CSQA
0
EF
Chrok`x
B@3,@COBNL,/0
B@2,@COSQL,/0
Trdq,bqd`sdcb`akd
• As the External Device has the termination resistance built-in, you do not need to connect the
termination resistance.
GP-Pro EX Device/PLC Connection Manual
52
Q/QnA Serial Communication Driver
5D)
External Device
D-sub 25 pin (plug)
Display side
D-sub 9 pin (plug)
Termination
resistance
330Ω 1/4W
Display
CA4-ADPONL-01
Pin
Signl name
2
Shield
Pin
Signl name
RDA
3
SDA
7
RDB
16
SDB
3
SDA
2
RDA
8
SDB
15
RDB
5
SG
7
SG
8
SG
20
SG
21
SG
4
DSRA
5
DTRA
17
DSRB
18
DTRB
1
FG
User-created cable
• As the External Device has the termination resistance built-in, you do not need to connect the
termination resistance.
GP-Pro EX Device/PLC Connection Manual
53
Q/QnA Serial Communication Driver
5E)
External Device side
D-sub 25 pin (plug)
Display side
Terminal block
Termination
resistance*1
Display
Shield
Pin
Signal
name
RDA
3
SDA
RDB
16
SDB
SDA
2
RDA
SDB
15
RDB
SG
7
SG
ERA
8
SG
CSA
20
SG
ERB
21
SG
CSB
4
DSRA
5
DTRA
Signal
name
17
DSRB
18
DTRB
1
FG
• As the External Device has the termination resistance built-in, you do not need to connect the
termination resistance.
*1
The resistance in the Display is used as the termination resistance. Set the value of the DIP Switch on the
rear of the Display as shown in the table below.
DIP Switch No.
Set Value
1
OFF
2
OFF
3
ON
4
OFF
GP-Pro EX Device/PLC Connection Manual
54
Q/QnA Serial Communication Driver
Cable Diagram 6
Display
(Connection Port)
Cable
6A
COM port conversion adapter
by Pro-face
CA3-ADPCOM-01
+
Connector terminal block conversion adapter
by Pro-face
CA3-ADPTRM-01
+
User-created cable
6B
COM port conversion adapter
by Pro-face
CA3-ADPCOM-01
+
Multilink cable by Pro-face
CA3-CBLMLT-01
+
User-created cable
6C
User-created cable
6D
Online adapter by Pro-face
CA4-ADPONL-01
+
Connector terminal block conversion adapter
by Pro-face
CA3-ADPTRM-01
+
User-created cable
6E
Online adapter by Pro-face
CA4-ADPONL-01
+
Multilink cable by Pro-face
CA3-CBLMLT-01
+
User-created cable
6F
Online adapter by Pro-face
CA4-ADPONL-01
+
User-created cable
6G
User-created cable
GP3000*1 (COM1)
AGP-3302B (COM2)
ST*2 (COM2)
IPC*3
GP3000*4 (COM2)
GP-4106 (COM1)
*1
All GP3000 models except AGP-3302B
*2
All ST models except AST-3211A and AST-3302B
*3
Only the COM port which can communicate by RS-422/485 (4 wire) can be used.
„ IPC COM Port (page 8)
*4
All GP3000 models except GP-3200 series and AGP-3302B
)
GP-Pro EX Device/PLC Connection Manual
55
Notes
The cable length must be
1200m or less.
Q/QnA Serial Communication Driver
6A)
Terminal
block
Termination
resistance
330 Ω
1/4W
Termination
resistance
330 Ω
1/4W
Terminal
block
Shield
External Device side
Terminal block
Termination
Signal
resistance
name
330 Ω
SDA
1/4W
Shield
Signal
name
Signal
name
RDA
RDA
RDB
RDB
SDB
SDA
SDA
RDA
SDB
SDB
RDB
SG
SG
SG
TRM
FG
FG
CA3-ADPTRM-01
CA3-ADPTRM-01
CA3-ADPCOM-01
CA3-ADPCOM-01
Display
Termination
resistance
330 Ω
1/4W
Display
User-created cable
6B)
Sdqlhm`k
aknbj
'L2rbqdv(
Sdqlhm`shnm
qdrhrs`mbd
22/ Ω
0.3V
Sdqlhm`shnm
qdrhrs`mbd
22/ Ω
0.3V
Rhfm`k
m`ld
Sdqlhm`k
aknbj
'L2rbqdv(
Rghdkc
Rghdkc
Rhfm`k
m`ld
Dwsdqm`kCduhbdrhcd
Sdqlhm`kaknbj
Sdqlhm`shnm
Rhfm`k
qdrhrs`mbd
m`ld
22/ Ω
RC@
0.3V
QC@
QC@
QCA
QCA
RCA
RC@
RC@
QC@
RCA
RCA
QCA
RF
RF
RF
EF
EF
EF
B@2,BAKLKS,/0
B@2,BAKLKS,/0
B@2,@COBNL,/0
B@2,@COBNL,/0
Chrok`x
Chrok`x
Trdq,bqd`sdcb`akd
GP-Pro EX Device/PLC Connection Manual
56
Sdqlhm`shnm
qdrhrs`mbd
22/ Ω
0.3V
Q/QnA Serial Communication Driver
6C)
Sdqlhm`k
qdrhrs`mbd
22/ Ω
0.3V
Chrok`xrhcd
C,rta8ohm'rnbjds(
Chrok`x
Sdqlhm`k
qdrhrs`mbd
22/ Ω
0.3V
Sdqlhm`kaknbj
'L2rbqdv(
Rghdkc
Rghdkc
Sdqlhm`kaknbj
'L2rbqdv(
Rghdkc
Dwsdqm`kCduhbdrhcd
Sdqlhm`kaknbj
Sdqlhm`k
Ohm
Rhfm`km`ld
Rhfm`km`ld
Rhfm`km`ld
0
QC@
QC@
QC@
1
QCA
QCA
QCA
2
RC@
RC@
RC@
QC@
Rhfm`km`ld qdrhrs`mbd
22/ Ω
RC@
0.3V
RCA
6
RCA
RCA
RCA
QCA
4
RF
RF
RF
RF
3
DQ@
EF
EF
EF
7
BR@
8
DQA
5
BRA
Rgdkk
EF
Chrok`xrhcd
C,rta8ohm'rnbjds(
Chrok`x
Sdqlhm`k
qdrhrs`mbd
22/ Ω
0.3V
Rghdkc
Ohm
Rhfm`km`ld
Rhfm`km`ld
0
QC@
QC@
1
QCA
QCA
2
RC@
RC@
6
RCA
RCA
4
RF
RF
3
DQ@
EF
7
BR@
8
DQA
5
BRA
6D)
Terminal
block
Termination
resistance
330 Ω
1/4W
Termination
resistance
330 Ω
1/4W
Signal
name
Terminal
block
Shield
Shield
Signal
name
External Device side
Terminal block
Termination
Signal
resistance
name
330 Ω
SDA
1/4W
RDA
RDA
RDB
RDB
SDB
SDA
SDA
RDA
SDB
SDB
RDB
SG
SG
SG
TRM
FG
FG
CA3-ADPTRM-01
CA3-ADPTRM-01
CA4-ADPONL-01
CA3-ADPONL-01
Display
Display
User-created cable
GP-Pro EX Device/PLC Connection Manual
57
Termination
resistance
330 Ω
1/4W
Q/QnA Serial Communication Driver
6E)
Sdqlhm`k
aknbj
'L2rbqdv(
Sdqlhm`shnm
qdrhrs`mbd
22/ Ω
0.3V
Sdqlhm`shnm
qdrhrs`mbd
22/ Ω
0.3V
Sdqlhm`k
aknbj
'L2rbqdv(
Rghdkc
Rhfm`k
m`ld
Rghdkc
Rhfm`k
m`ld
Dwsdqm`kCduhbdrhcd
Sdqlhm`kaknbj
Sdqlhm`shnm
Rhfm`k
qdrhrs`mbd
m`ld
22/ Ω
RC@
0.3V
QC@
QC@
QCA
QCA
RCA
RC@
RC@
QC@
RCA
RCA
QCA
RF
RF
RF
EF
EF
EF
B@2,BAKLKS,/0
B@2,BAKLKS,/0
B@3,@CONMK,/0
B@3,@CONMK,/0
Chrok`x
Sdqlhm`shnm
qdrhrs`mbd
22/ Ω
0.3V
Chrok`x
Trdq,bqd`sdcb`akd
6F)
Chrok`x
Sdqlhm`k
qdrhrs`mbd
22/ Ω
0.3V
Sdqlhm`k
B@3,@CONMK,/0 qdrhrs`mbd
22/ Ω
0.3V
C,rta8ohm'oktf(
Sdqlhm`kaknbj
'L2rbqdv(
Rghdkc
Rghdkc
Sdqlhm`kaknbj
'L2rbqdv(
Rghdkc
Dwsdqm`kCduhbdrhcd
Sdqlhm`kaknbj
Sdqlhm`k
Ohm
Rhfm`km`ld
Rhfm`km`ld
Rhfm`km`ld
1
QC@
QC@
QC@
6
QCA
QCA
QCA
2
RC@
RC@
RC@
QC@
Rhfm`km`ld qdrhrs`mbd
22/ Ω
RC@
0.3V
RCA
7
RCA
RCA
RCA
QCA
4
RF
RF
RF
RF
Rgdkk
EF
EF
EF
EF
C,rta8ohm'oktf(
Chrok`x
B@3,@CONMK,/0
Rghdkc
Ohm
Rhfm`km`ld
Rhfm`km`ld
1
QC@
QC@
6
QCA
QCA
2
RC@
RC@
7
RCA
RCA
4
RF
RF
EF
GP-Pro EX Device/PLC Connection Manual
58
Sdqlhm`k
qdrhrs`mbd
22/ Ω
0.3V
Q/QnA Serial Communication Driver
6G)
Display side
Terminal block
Terminal
resistance*1
Terminal
resistance*1
*1
Shield
Display side
Terminal block
Shield
External Device side
Terminal block
Terminal
Signal name
Signal name
RDA
RDA
RDB
RDB
SDA
SDA
RDA
SDB
SDB
RDB
SG
SG
SG
ERA
ERA
FG
CSA
CSA
ERB
ERB
CSB
CSB
Display
Display
Signal name resistance
330 Ω
SDA
1/4W
SDB
Terminal
resistance
330 Ω
1/4W
The resistance in the Display is used as the termination resistance. Set the value of the DIP Switch on the
rear of the Display as shown in the table below.
DIP Switch No.
Set Value
1
ON
2
OFF
3
ON
4
OFF
For the Displays other than that used as the terminal, set the DIP Switch 1-4 on the rear of the Display to
OFF in the n:1 connection.
GP-Pro EX Device/PLC Connection Manual
59
Q/QnA Serial Communication Driver
6
Range of Supported Device Address
Range of supported device address is shown in the table below. Please note that the actually supported range of
the devices varies depending on the External Device to be used. Please check the actual range in the manual of
your External Device.
„ MELSEC Q (High performance model, Basic model) / MELSEC QnA Series
This address can be specified as system data area.
Device
Bit Address
Word Address
Input Relay
X0000-X1FFF
X0000-X1FF0
Output Relay
Y0000-Y1FFF
Y0000-Y1FF0
Internal Relay
M00000-M32767
M00000-M32752
Special Relay
SM0000-SM2047
SM0000-SM2032
Latch Relay
L00000-L32767
L00000-L32752
Annunciator
F00000-F32767
F00000-F32752
Edge Relay
V00000-V32767
V00000-V32752
Step Relay
S0000-S8191
S0000-S8176
Link Relay
B0000-B7FFF
B0000-B7FF0
Special Link Relay
SB000 - SB7FF
SB000 - SB7F0
Timer (Contact)
TS00000-TS23087
-
Timer (Coil)
TC00000-TC23087
-
Retentive Timer (Contact)
SS00000-SS23087
-
Retentive Timer (Coil)
SC00000-SC23087
-
Counter (Contact)
CS00000-CS23087
-
Counter (Coil)
CC00000-CC23087
-
Timer (Current Value)
-
TN00000-TN23087
Retentive Timer (Current
Value)
-
SN00000-SN23087
Counter (Current Value)
-
CN00000-CN23087
Data Register
-
D00000-D25983
Special Register
-
SD0000-SD2047
Link Register
-
W0000-W657F
Special Link Register
-
SW000-SW7FF
File Register (Normal)
-
R00000-R32767
*1
File Register (Block
switching is not necessary)
-
ZR0000000-ZR1042431
*1
GP-Pro EX Device/PLC Connection Manual
60
32bits
Notes
Q/QnA Serial Communication Driver
Device
File Register
(0R - 31R) *2
Bit Address
Word Address
-
0R0000-0R32767
-
1R0000-1R32767
-
2R0000-2R32767
:
:
-
30R0000-30R32767
-
31R0000-31R26623
32bits
Notes
*1
*1
It is different by the memory card which uses the range of file register.
*2
Set the block No. on the head of device name. This is the device name for conversion with GP-Pro/PB III for
Windows. When you newly specify the device, we recommend that you should use the file register (Block
switching is not necessary).
• Please refer to the GP-Pro EX Reference Manual for system data area.
Cf. GP-Pro EX Reference Manual "Appendix 1.4 LS Area (Direct Access Method)"
• Please refer to the precautions on manual notation for icons in the table.
) "Manual Symbols and Terminology"
GP-Pro EX Device/PLC Connection Manual
61
Q/QnA Serial Communication Driver
„ MELSEC Q (Universal model) Series
This address can be specified as system data area.
Device
First 5 digits of the serial No. in
the CPU unit:
Less than 10042
First 5 digits of the serial No. in
the CPU unit:
10042 or later
Bit Address
Word
Address
Bit Address
Word
Address
Input Relay
X0000-X1FFF
X0000-X1FF0
X0000-X1FFF
X0000-X1FF0
Output Relay
Y0000-Y1FFF
Y0000-Y1FF0
Y0000-Y1FFF
Y0000-Y1FF0
Internal Relay
M00000M32767
M00000M32752
M00000M61439
M00000M61424
Special Relay
SM0000SM2047
SM0000SM2032
SM0000SM2047
SM0000SM2032
Latch Relay
L00000L32767
L00000L32752
L00000L32767
L00000L32752
Annunciator
F00000F32767
F00000F32752
F00000F32767
F00000F32752
Edge Relay
V00000V32767
V00000V32752
V00000V32767
V00000V32752
Step Relay
S0000-S8191
S0000-S8176
S0000-S8191
S0000-S8176
Link Relay
B0000-B7FFF
B0000-B7FF0
B0000-BEFFF
B0000-BEFF0
Special Link Relay
SB0000 SB7FFF
SB0000 SB7FF0
SB0000 SB7FFF
SB0000 SB7FF0
Timer (Contact)
TS00000TS25023
-
TS00000TS25471
-
Timer (Coil)
TC00000TC25023
-
TC00000TC25471
-
Retentive Timer
(Contact)
SS00000SS25023
-
SS00000SS25471
-
Retentive Timer
(Coil)
SC00000SC25023
-
SC00000SC25471
-
Counter (Contact)
CS00000CS25023
-
CS00000CS25471
-
Counter (Coil)
CC00000CC25023
-
CC00000CC25471
-
Timer (Current
Value)
-
TN00000TN25023
-
TN00000TN25471
32bits
Notes
continued to next page
GP-Pro EX Device/PLC Connection Manual
62
Q/QnA Serial Communication Driver
First 5 digits of the serial No. in
the CPU unit:
Less than 10042
Device
First 5 digits of the serial No. in
the CPU unit:
10042 or later
32bits
Notes
Bit Address
Word
Address
Bit Address
Word
Address
Retentive Timer
(Current Value)
-
SN00000SN25023
-
SN00000SN25471
Counter (Current
Value)
-
CN00000CN25023
-
CN00000CN25471
Data Register
-
D00000D28159
-
D0000000D0065535
Special Register
-
SD0000SD2047
-
SD0000SD2047
Link Register
-
W0000W6DEF
-
W000000W00FFFF
Special Link
Register
-
SW0000SW6DFF
-
SW0000SW6FFF
File Register
(Normal)
-
R00000R32767
-
R00000R32767
*1
File Register
(Block switching is
not necessary)
-
ZR0000000ZR4184063
-
ZR0000000ZR4184063
*1
-
0R00000R32767
-
0R00000R32767
-
1R00001R32767
-
1R00001R32767
-
2R00002R32767
-
2R00002R32767
:
:
:
:
-
30R000030R32767
-
30R000030R32767
-
31R000031R26623
-
31R000031R26623
File Register
(0R - 31R) *2
*1
*1
It is different by the memory card which uses the range of file register.
*2
Set the block No. on the head of device name. This is the device name for conversion with GP-Pro/PB III for
Windows. When you newly specify the device, we recommend that you should use the file register (Block
switching is not necessary).
• Please refer to the GP-Pro EX Reference Manual for system data area.
Cf. GP-Pro EX Reference Manual "Appendix 1.4 LS Area (Direct Access Method)"
• Please refer to the precautions on manual notation for icons in the table.
) "Manual Symbols and Terminology"
GP-Pro EX Device/PLC Connection Manual
63
Q/QnA Serial Communication Driver
7
Device Code and Address Code
Use device code and address code when you select "Device Type & Address" for the address type in data displays.
Device Name
Device Code
(HEX)
Input Relay
X
0080
Value of word address divided by
0x10
Output Relay
Y
0081
Value of word address divided by
0x10
Internal Relay
M
0082
Value of word address divided by 16
Special Relay
SM
0083
Value of word address divided by 16
Latch Relay
L
0084
Value of word address divided by 16
Annunciator
F
0085
Value of word address divided by 16
Edge Relay
V
0086
Value of word address divided by 16
Step Relay
S
0087
Value of word address divided by 16
Link Relay
B
0088
Value of word address divided by
0x10
Special Link Relay
SB
0089
Value of word address divided by
0x10
Timer (Current Value)
TN
0060
Word Address
Retentive Timer (Current
Value)
SN
0062
Word Address
Counter (Current Value)
CN
0061
Word Address
Data Register
D
0000
Word Address
Special Register
SD
0001
Word Address
Link Register
W
0002
Word Address
Special Link Register
SW
0003
Word Address
File Register (Normal)
R
000F
Word Address
ZR
000E
Word Address
0R
0010
Word Address
1R
0011
Word Address
2R
0012
Word Address
:
:
30R
002E
Word Address
31R
002F
Word Address
Device
File Register (Block switching
is not necessary)
File Register
(0R - 31R)
GP-Pro EX Device/PLC Connection Manual
64
Address Code
:
Q/QnA Serial Communication Driver
8
Error Messages
Error messages are displayed on the Display screen as follows: "No.: Device Name: Error Message (Error
Occurrence Area)". Each description is shown below.
Item
Description
No.
Error No.
Device Name
Name of the External Device where error occurs. Device name is a title of the External
Device set with GP-Pro EX. (Initial value [PLC1])
Error Message
Displays messages related to the error which occurs.
Displays IP address or device address of the External Device where error occurs, or error
codes received from the External Device.
Error Occurrence Area
• IP address is displayed such as "IP address(Decimal): MAC address( Hex)".
• Device address is diplayed such as "Address: Device address".
• Received error codes are displayed such as "Decimal[Hex]".
Display Examples of Error Messages
"RHAA035: PLC1: Error has been responded for device write command (Error Code: 2 [02H])"
• Refer to your External Device manual for details on received error codes.
• Refer to "When an error is displayed (Error Code List)" in "Maintenance/Troubleshooting Manual"
for details on the error messages common to the driver.
GP-Pro EX Device/PLC Connection Manual
65
Q/QnA Serial Communication Driver
GP-Pro EX Device/PLC Connection Manual
66

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals

Download PDF

advertisement