Description and

Application

Installation

Instructions

Doc No 303109(2-16)

Ignition Conversion Kit Instructions

Applies: All UEAS Models Built Prior to March, 2013

Prior to March, 2013 all UEAS models were built at the factory with a separate Time Delay Relay (reference P/N 221388) and utilized DSI Control

Module circuit board P/N 195265.

All UEAS models built at the factory after March, 2013 do not use a separate Time

Delay Relay and utilizes a different DSI Control Module circuit board (reference P/N

269867). This circuit board has the time delay “built in” so as to eliminate the need for a separate time delay relay.

This set of instructions provide the steps required to convert models built prior to

March, 2013 to current ignition control specifications.

Qty

1

1

1

Ignition Conversion Kit P/N 1006137

P/N Description

269867 Ignition Control

221211 Wiring Diagram Label

D303109 Instruction Form

WARNING

This ignition conversion kit is to be installed by a qualified agency in accordance with these instructions and in compliance with all codes and requirements of authorities having jurisdiction.

Failure to follow instructions could result in death, series injury and or property damage. The qualified agency performing this work assumes responsibility for this installation.

1. Turn off the gas supply at the shutoff valve upstream of the combination valve and turn off the electrical supply powering the unit.

2. Locate “Right Side” of unit and remove the two retaining screws as shown in the sketch below.

Right Side View

Front

View

Retaining Screw

Low Side Cover

Note: Model 260 or 310 shown above.

(Models 130 & 180 have a single access cover)

The “Low Side Cover” can now be tilted out at the bottom and removed to access ignition system components.

3. Now the ignition system components can be seen, as shown in the sketch below.

Gas Valve

Control Panel Assembly

Doc No D303109 (2-16), page 1

Installation

Instructions

(cont’d)

4. Looking at the DSI Control Module (circuit board), notice the that the

Time Delay Relay is a separate component located in the upper right side next to the circuit board as shown in the sketch below.

5. Notice that the time delay relay has two electrical terminals with a blue wire attached to each therminal as shown below.

Time Delay Relay

Doc No D303109 (2-16), page 2

6. Remove and discard the one center hold down screw that retains the relay to the unit.

Now remove the time delay relay and set it (with its two blue wires still attached to the time delay relay electrical terminals) in front of the circuit board as shown in the photo on the right.

Next remove and discard the one blue wire that is attached to the time delay relay electrical terminal (see arrow) and the other end of this same wire that is attached to the gas valve terminal (see arrow).

7. Remove the remaining blue wire that is attached to the other electrical terminal on the time delay relay as indicated with arrow in picture shown below on the left and connect it to the gas valve electrical terminal (reference arrow) as shown below in the picture on the right.

8. Remove all wires & plugs attached to the DSI Control Module (circuit board). Then “squeeze” the tops of the four white bayonet style posts

(shown in ellipses) to release the circuit board. Now remove and discard the board. Reference photo shown below.

4

3

1 2

9. Install the new DSI Control Module (circuit board) P/N 269867 that was included in this kit onto the four white bayonet style posts.

10. Change the wiring diagram label on the heater. Place the label that was included in this kit, P/N 221211 over top of the existing one. It is a shelf adhesive label.

11. Using the wiring diagram shown on page 4, reconnect all plugs and wire connections. ( Note, the old wiring diagram is shown on page 5.

Use it for reference ONLY!)

12. Turn on the electric and gas. Relight the unit following the instructions on the lighting instruction plate.

13. Power up unit and using the units Installation manual, verify proper operation.

Doc No D303109 (2-16), page 3

Current Wiring Diagram

G

W1

G

FACTORY WIRING

FIELD WIRING

OPTIONAL FACTORY

WIRING

WIRE CONNECTOR

SYSTEM TRANSFORMER

Y

R

115/1/60

G

W2

W1

RC

R

R

WIRING CODE

BLACK - BK

BROWN - BR

RED - R

ORANGE - O

YELLOW - Y

GREEN - G

BLUE - BL

PURPLE - PR

WHITE - W

P3-1

BR

SEC COM

BK

L1 NEUTRAL NEUTRAL L1

GRD

SCREW

G

G

Y

G NEUTRAL

W

PR

P3-2

G

EAC/BLO

BK

FAN MOTOR

BK W

W1 Y P3-3 G

W

W

R

R

W2

DOOR INTERLOCK

R R

LIMIT CONTROL

R R

R R

FLUE LIMIT CONTROL

P1-3

Y

PRESSURE SWITCH

Y Y

P1-6

P1-5

GAS VALVE

BL BR

P3-4

P3-5

P1-8

BL

P1-4

P1-2

FLAME

ELECTRODE

R

P1-7

BR

P1-9

FLAME

GROUND

OPERATING SEQUENCE

1. SET THERMOSTAT AT LOWEST SETTING;

FAN SWITCH AT "AUTO" POSITION.

2. TURN ON MANUAL GAS VALVE.

3. TURN ON POWER TO UNIT.

4. SET THERMOSTAT AT DESIRED SETTING.

5. THERMOSTAT CALLS FOR HEAT, ENERGIZING THE VENTER MOTOR.

6. VENTER PRESSURE SWITCH CLOSES, FIRING UNIT AT FULL RATE.

7. BURNER FLAME IS SENSED, AND IN 30 SECONDS THE BLOWER

MOTOR IS ENERGIZED.

8. IF THE FLAME IS EXTINGUISHED DURING MAIN BURNER OPERATION,

THE INTEGRATED CONTROL SYSTEM CLOSES THE MAIN VALVE AND

MUST BE RESET BY INTERRUPTING POWER TO THE CONTROL CIRCUIT

(SEE LIGHTING INSTRUCTIONS).

9. SET FAN SWITCH AT "ON" POSITION FOR CONTINUOUS BLOWER OPERATION.

UEAS SERIES: AG1

WD# 230300 REV. #3

Doc No D303109 (2-16), page 4

R

C LED FLASH CODES

GREEN LED

STEADY ON

FAST FLASH

1 FLASH

NORMAL OPERATION NO CALL FOR HEAT

NORMAL OPERATION CALL FOR HEAT

IN LOCKOUT FROM FAILED IGNITIONS OR FLAME LOSSES

2 FLASH

3 FLASH

4 FLASH

STEADY OFF

PRESSURE SWITCH DOES NOT CLOSE WITHIN 30 SECONDS

OF VENTER ENERGIZED

LIMIT SWITCH OR FLUE LIMIT CONTROL OPEN

PRESSURE SWITCH IS CLOSED BEFORE VENTER IS ENERGIZED

INTERNAL CONTROL FAULT OR NO POWER

YELLOW LED

FLAME SENSED STEADY ON

SLOW FLASH WEAK FLAME

FAST FLASH UNDESIRED FLAME (VALVE OPEN & NO CALL FOR HEAT)

IND BK

FLAME

LED

Y

OK

LED

G

NEUTRAL

W

CAPACITOR

(SEE NOTE #7)

W

VENTER

MOTOR

BK

G

DSI CONTROL

SPARK

TRANSFORMER CAPACITOR

(SEE NOTE #7)

SPARK GAP

TOTAL WIRE

LENGTH

150'

250'

350'

FIELD CONTROL WIRING

DISTANCE FROM

UNIT TO CONTROL

75'

125'

175'

MIN. RECOMMENDED

WIRE GUAGE

#18 GA. WIRE

#16 GA. WIRE

#14 GA. WIRE

NOTES

1. THE FOLLOWING CONTROLS ARE FIELD INSTALLED OPTIONS: THERMOSTAT

2. DOTTED WIRING INSTALLED BY OTHERS.

3. CAUTION: IF ANY OF THE ORIGINAL WIRING AS SUPPLIED WITH THE

APPLIANCE MUST BE REPLACED, IT MUST BE REPLACED WITH WIRING MATERIAL

HAVING A TEMPERATURE RATING OF AT LEAST 105° C. EXCEPT FOR SENSOR

LEAD WIRE, FLUE LIMIT CONTROL AND LIMIT WIRING WHICH MUST BE 150° C.

4. LINE AND FAN MOTOR BRANCH WIRE SIZES SHOULD BE OF A SIZE TO PREVENT

VOLTAGE DROPS BEYOND 5% OF SUPPLY LINE VOLTAGE.

5. USE #14 GA. WIRE FOR LINE WIRING ON THE UNIT.

6. USE #18 GA. WIRE FOR CONTROL WIRING ON THE UNIT.

7. CAPACITOR IS REMOTE MOUNTED.

8. VERIFY JUMPER ON CL22 THERMOSTAT TERMINALS R TO RC.

9. FAN SWITCH OR LOW STAGE OF CL22 THERMOSTAT ENERGIZES THE BLOWER MOTOR.

10. HIGH STAGE OF CL22 THERMOSTAT INITIATES A CALL FOR HEAT.

Old Wiring Diagram - REFERENCE ONLY

Doc No D303109 (2-16), page 5

Additional

References

The following form was shipped with your unit from factory or additional copies can be obtained from your factory representative:

• Installation/Operation/Maintenance manual - Form I-UEAS (P/N 221232)

The following forms can be obtained from your factory representative:

• Replacement Parts - Form P-UEAS (P/N 269865)

• Replacement Valves & Ignition Controls by Serial No. Code - Form P-VALVES (P/N 263995)

Doc No D303109 (2-16), page 6

NOTES:

Doc No D303109 (2-16), page 7

Doc No D303109 (2-16), page 8

Specifications & illustrations subject to change without notice and without incurring obligations.

© Nortek Global HVAC, LLC 2016. All rights reserved.

All marks are the property of their respective organizations.

O’Fallon, MO I Printed in U.S.A. (1/16)

Doc No D303108 (2-16)

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals

Download PDF

advertisement