Reznor UEAS Instructions
Add to my manuals8 Pages
Reznor UEAS is a gas-fired unit heater designed to provide warmth in various indoor spaces. It features a built-in DSI Control Module that manages ignition and flame control, ensuring efficient and reliable operation. With its compact design, the UEAS heater can be easily installed in tight spaces, making it suitable for garages, workshops, warehouses, and other commercial or industrial environments. It offers adjustable heat output to meet specific heating requirements and includes safety features such as a flame sensor and limit controls to prevent overheating.
advertisement
Description and
Application
Installation
Instructions
Doc No 303109(2-16)
Ignition Conversion Kit Instructions
Applies: All UEAS Models Built Prior to March, 2013
Prior to March, 2013 all UEAS models were built at the factory with a separate Time Delay Relay (reference P/N 221388) and utilized DSI Control
Module circuit board P/N 195265.
All UEAS models built at the factory after March, 2013 do not use a separate Time
Delay Relay and utilizes a different DSI Control Module circuit board (reference P/N
269867). This circuit board has the time delay “built in” so as to eliminate the need for a separate time delay relay.
This set of instructions provide the steps required to convert models built prior to
March, 2013 to current ignition control specifications.
Qty
1
1
1
Ignition Conversion Kit P/N 1006137
P/N Description
269867 Ignition Control
221211 Wiring Diagram Label
D303109 Instruction Form
WARNING
This ignition conversion kit is to be installed by a qualified agency in accordance with these instructions and in compliance with all codes and requirements of authorities having jurisdiction.
Failure to follow instructions could result in death, series injury and or property damage. The qualified agency performing this work assumes responsibility for this installation.
1. Turn off the gas supply at the shutoff valve upstream of the combination valve and turn off the electrical supply powering the unit.
2. Locate “Right Side” of unit and remove the two retaining screws as shown in the sketch below.
Right Side View
Front
View
Retaining Screw
Low Side Cover
Note: Model 260 or 310 shown above.
(Models 130 & 180 have a single access cover)
The “Low Side Cover” can now be tilted out at the bottom and removed to access ignition system components.
3. Now the ignition system components can be seen, as shown in the sketch below.
Gas Valve
Control Panel Assembly
Doc No D303109 (2-16), page 1
Installation
Instructions
(cont’d)
4. Looking at the DSI Control Module (circuit board), notice the that the
Time Delay Relay is a separate component located in the upper right side next to the circuit board as shown in the sketch below.
5. Notice that the time delay relay has two electrical terminals with a blue wire attached to each therminal as shown below.
Time Delay Relay
Doc No D303109 (2-16), page 2
6. Remove and discard the one center hold down screw that retains the relay to the unit.
Now remove the time delay relay and set it (with its two blue wires still attached to the time delay relay electrical terminals) in front of the circuit board as shown in the photo on the right.
Next remove and discard the one blue wire that is attached to the time delay relay electrical terminal (see arrow) and the other end of this same wire that is attached to the gas valve terminal (see arrow).
7. Remove the remaining blue wire that is attached to the other electrical terminal on the time delay relay as indicated with arrow in picture shown below on the left and connect it to the gas valve electrical terminal (reference arrow) as shown below in the picture on the right.
8. Remove all wires & plugs attached to the DSI Control Module (circuit board). Then “squeeze” the tops of the four white bayonet style posts
(shown in ellipses) to release the circuit board. Now remove and discard the board. Reference photo shown below.
4
3
1 2
9. Install the new DSI Control Module (circuit board) P/N 269867 that was included in this kit onto the four white bayonet style posts.
10. Change the wiring diagram label on the heater. Place the label that was included in this kit, P/N 221211 over top of the existing one. It is a shelf adhesive label.
11. Using the wiring diagram shown on page 4, reconnect all plugs and wire connections. ( Note, the old wiring diagram is shown on page 5.
Use it for reference ONLY!)
12. Turn on the electric and gas. Relight the unit following the instructions on the lighting instruction plate.
13. Power up unit and using the units Installation manual, verify proper operation.
Doc No D303109 (2-16), page 3
Current Wiring Diagram
G
W1
G
FACTORY WIRING
FIELD WIRING
OPTIONAL FACTORY
WIRING
WIRE CONNECTOR
SYSTEM TRANSFORMER
Y
R
115/1/60
G
W2
W1
RC
R
R
WIRING CODE
BLACK - BK
BROWN - BR
RED - R
ORANGE - O
YELLOW - Y
GREEN - G
BLUE - BL
PURPLE - PR
WHITE - W
P3-1
BR
SEC COM
BK
L1 NEUTRAL NEUTRAL L1
GRD
SCREW
G
G
Y
G NEUTRAL
W
PR
P3-2
G
EAC/BLO
BK
FAN MOTOR
BK W
W1 Y P3-3 G
W
W
R
R
W2
DOOR INTERLOCK
R R
LIMIT CONTROL
R R
R R
FLUE LIMIT CONTROL
P1-3
Y
PRESSURE SWITCH
Y Y
P1-6
P1-5
GAS VALVE
BL BR
P3-4
P3-5
P1-8
BL
P1-4
P1-2
FLAME
ELECTRODE
R
P1-7
BR
P1-9
FLAME
GROUND
OPERATING SEQUENCE
1. SET THERMOSTAT AT LOWEST SETTING;
FAN SWITCH AT "AUTO" POSITION.
2. TURN ON MANUAL GAS VALVE.
3. TURN ON POWER TO UNIT.
4. SET THERMOSTAT AT DESIRED SETTING.
5. THERMOSTAT CALLS FOR HEAT, ENERGIZING THE VENTER MOTOR.
6. VENTER PRESSURE SWITCH CLOSES, FIRING UNIT AT FULL RATE.
7. BURNER FLAME IS SENSED, AND IN 30 SECONDS THE BLOWER
MOTOR IS ENERGIZED.
8. IF THE FLAME IS EXTINGUISHED DURING MAIN BURNER OPERATION,
THE INTEGRATED CONTROL SYSTEM CLOSES THE MAIN VALVE AND
MUST BE RESET BY INTERRUPTING POWER TO THE CONTROL CIRCUIT
(SEE LIGHTING INSTRUCTIONS).
9. SET FAN SWITCH AT "ON" POSITION FOR CONTINUOUS BLOWER OPERATION.
UEAS SERIES: AG1
WD# 230300 REV. #3
Doc No D303109 (2-16), page 4
R
C LED FLASH CODES
GREEN LED
STEADY ON
FAST FLASH
1 FLASH
NORMAL OPERATION NO CALL FOR HEAT
NORMAL OPERATION CALL FOR HEAT
IN LOCKOUT FROM FAILED IGNITIONS OR FLAME LOSSES
2 FLASH
3 FLASH
4 FLASH
STEADY OFF
PRESSURE SWITCH DOES NOT CLOSE WITHIN 30 SECONDS
OF VENTER ENERGIZED
LIMIT SWITCH OR FLUE LIMIT CONTROL OPEN
PRESSURE SWITCH IS CLOSED BEFORE VENTER IS ENERGIZED
INTERNAL CONTROL FAULT OR NO POWER
YELLOW LED
FLAME SENSED STEADY ON
SLOW FLASH WEAK FLAME
FAST FLASH UNDESIRED FLAME (VALVE OPEN & NO CALL FOR HEAT)
IND BK
FLAME
LED
Y
OK
LED
G
NEUTRAL
W
CAPACITOR
(SEE NOTE #7)
W
VENTER
MOTOR
BK
G
DSI CONTROL
SPARK
TRANSFORMER CAPACITOR
(SEE NOTE #7)
SPARK GAP
TOTAL WIRE
LENGTH
150'
250'
350'
FIELD CONTROL WIRING
DISTANCE FROM
UNIT TO CONTROL
75'
125'
175'
MIN. RECOMMENDED
WIRE GUAGE
#18 GA. WIRE
#16 GA. WIRE
#14 GA. WIRE
NOTES
1. THE FOLLOWING CONTROLS ARE FIELD INSTALLED OPTIONS: THERMOSTAT
2. DOTTED WIRING INSTALLED BY OTHERS.
3. CAUTION: IF ANY OF THE ORIGINAL WIRING AS SUPPLIED WITH THE
APPLIANCE MUST BE REPLACED, IT MUST BE REPLACED WITH WIRING MATERIAL
HAVING A TEMPERATURE RATING OF AT LEAST 105° C. EXCEPT FOR SENSOR
LEAD WIRE, FLUE LIMIT CONTROL AND LIMIT WIRING WHICH MUST BE 150° C.
4. LINE AND FAN MOTOR BRANCH WIRE SIZES SHOULD BE OF A SIZE TO PREVENT
VOLTAGE DROPS BEYOND 5% OF SUPPLY LINE VOLTAGE.
5. USE #14 GA. WIRE FOR LINE WIRING ON THE UNIT.
6. USE #18 GA. WIRE FOR CONTROL WIRING ON THE UNIT.
7. CAPACITOR IS REMOTE MOUNTED.
8. VERIFY JUMPER ON CL22 THERMOSTAT TERMINALS R TO RC.
9. FAN SWITCH OR LOW STAGE OF CL22 THERMOSTAT ENERGIZES THE BLOWER MOTOR.
10. HIGH STAGE OF CL22 THERMOSTAT INITIATES A CALL FOR HEAT.
Old Wiring Diagram - REFERENCE ONLY
Doc No D303109 (2-16), page 5
Additional
References
The following form was shipped with your unit from factory or additional copies can be obtained from your factory representative:
• Installation/Operation/Maintenance manual - Form I-UEAS (P/N 221232)
The following forms can be obtained from your factory representative:
• Replacement Parts - Form P-UEAS (P/N 269865)
• Replacement Valves & Ignition Controls by Serial No. Code - Form P-VALVES (P/N 263995)
Doc No D303109 (2-16), page 6
NOTES:
Doc No D303109 (2-16), page 7
Doc No D303109 (2-16), page 8
Specifications & illustrations subject to change without notice and without incurring obligations.
© Nortek Global HVAC, LLC 2016. All rights reserved.
All marks are the property of their respective organizations.
O’Fallon, MO I Printed in U.S.A. (1/16)
Doc No D303108 (2-16)
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project