9202A
Pulse isolator
9202A
– Interface for NAMUR sensors and switches
– Extended self-diagnostics and detection of cable fault
– 1 or 2 channels
– Can be supplied separately or installed on power rail, PR type 9400
– SIL 2-certified via Full Assessment
Advanced features
• Configuration and monitoring by way of detachable display
front (PR 4511/4501).
• Selection of direct or inverted function for each channel via
PR 4511/4501.
• Advanced monitoring of internal communication and stored
data.
• Optional redundant supply via power rail and/ or separate
supply.
• SIL 2 functionality is optional and must be activated in a menu
point.
Connections
Application
• The device can be mounted in and receive signals from nonclassified area and zone 2.
• Pulse isolator for transmission of signals from NAMUR
sensors and mechanical switches.
• Monitoring of error events and cable breakage via the
individual status relay and/or a collective electronic signal via
the power rail.
• The 9202A has been designed, developed and certified for
use in SIL 2 applications according to the requirements of IEC
61508.
Technical characteristics
• 1 green and 2 yellow/red front LEDs indicate operation status
and malfunction.
• 2.6 kVAC galvanic isolation between input, output and supply.
Mounting
• The devices can be mounted vertically or horizontally without
distance between neighbouring units.
This page is automatically generated on the basis of information provided on www.prelectronics.com and affiliated websites. It is provided to you as a service and for information
purpose only. While we have attempted to maintain the information as accurately as possible, the page may contain errors or omissions for which we disclaim any and all liability
Environmental Conditions
Specifications range.......................................
Storage temperature......................................
Calibration temperature.................................
Relative humidity............................................
Protection degree...........................................
Installation in..................................................
Output specifications
-20°C to +60°C
-20°C to +85°C
20...28°C
< 95% RH (non-cond.)
IP20
Pollution degree 2 &
measurement / overvoltage
cat. II
Mechanical specifications
Dimensions (HxWxD).....................................
Dimensions (HxWxD) w/ 4501
/ 4511.............................................................
Weight approx................................................
Weight incl. 4501 / 4511 (approx.).................
DIN rail type...................................................
Wire size........................................................
Screw terminal torque....................................
Vibration.........................................................
Vibration: 2...13.2 Hz.....................................
Vibration: 13.2...100 Hz.................................
109 x 23.5 x 104 mm
109 x 23.5 x 116 / 131 mm
170 g
185 g / 270 g
DIN EN 60715/35 mm
0.13...2.08 mm2 AWG 26...14
stranded wire
0.5 Nm
IEC 60068-2-6 : 2007
±1 mm
±0.7 g
Common specifications
Supply
Supply voltage............................................... 19.2...31.2 VDC
Isolation voltage
Test /working: Input to any............................. 2.6 kVAC / 300 VAC
reinforced isolation
Analog output to supply................................. 2.6 kVAC / 300 VAC
reinforced isolation
Output 1 to output 2....................................... 1.5 kVAC / 150 VAC
reinforced isolation
Status relay to supply..................................... 1.5 kVAC / 150 VAC
reinforced isolation
Relay output
Max. switching frequency...............................
Max. voltage...................................................
Max. current...................................................
Max. AC power..............................................
20 Hz
250 VAC / 30 VDC
2 AAC / 2 ADC
500 VA / 60 W
Status relay
Max. voltage................................................... 110 VDC / 125 VAC
Max. current................................................... 0.3 ADC / 0.5 AAC
Max. AC power.............................................. 62.5 VA / 32 W
NPN outputs
Max. switching frequency...............................
Min. pulse length............................................
Max. load, current / voltage............................
Voltage drop at 80 mA...................................
5 kHz
> 0.1 ms
80 mA / 30 VDC
< 2.5 VDC
Observed authority requirements
EMC............................................................... 2004/108/EC
LVD................................................................ 2006/95/EC
Approvals
UL................................................................... UL 61010-1
EAC................................................................ TR-CU 020/2011
DNV Marine.................................................... Stand. f. Certific. No. 2.4
SIL.................................................................. SIL 2 certified & fully assessed
acc. to IEC 61508
Auxiliary supplies
NAMUR supply.............................................. 8 VDC / 8 mA
Fuse............................................................... 400 mA SB / 250 VAC
Max. power consumption............................... ≤ 3 W (2 channels)
Communications interface............................. Communication enabler 4511
/ Programming front 4501
Response time for cable fault........................ < 200 ms
Input specifications
Sensor types.................................................. NAMUR according to EN
60947-5-6 / mechanical
contact
Frequency range............................................ 0...5 kHz
Min. pulse length............................................ > 0.1 ms
Input resistance.............................................. Nom. 1 kΩ
Trig level, signal............................................. < 1.2 mA, > 2.1 mA
Trig level, cable fault...................................... < 0.1 mA, > 6.5 mA
9202A-030115
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project