ZoneTight Documentation
Version 11_18_15
Belimo ZoneTight™ Zone Valves
Technical Documentation
Compact
Size
> Learn more
www.zonetight.com
Low Power
Consumption
Zero
Leakage
Table of Contents
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
. 3
. 5
. 7
. 9
.10
.11
.12
.14
.15
.16
.18
.21
.22
.24
.25
.27
Tech.Doc - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
Overview
. . . . . . . . . . . .
QCV Nomenclature. . . . . . . . . .
PIQCV Nomenclature . . . . . . . .
Set-Up
. . . . . . . . . . . .
Accessories . . . . . . . . . . . .
Flow Pattern . . . . . . . . . . . .
Piping
. . . . . . . . . . . .
Field-Set Adjustment . . . . . . . . .
Installation
. . . . . . . . . . . .
Wiring
. . . . . . . . . . . .
Flow Verification . . . . . . . . . . .
Troubleshooting . . . . . . . . . . .
Valve Specification and Dimensions .
Actuator Specification . . . . . . . .
Flow Curves . . . . . . . . . . . .
Terms and Conditions . . . . . . . .
800-543-9038 USA
2
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
Belimo ZoneTight Zone Valves
Overview
Designed for maximum efficiency in tight spaces, Belimo’s ZoneTight valve offering sets new design and performance standards for
both pressure dependent and pressure independent zoning applications.
ZoneTight Zone Valve (QCV)
The ultra-compact QCV leads the way in Belimo’s new generation of room and zone solutions. Equipped with a space-saving 2-way or
3-way ball valve and an electronic rotary actuator, the QCV has an installation height of just 4.33 inches (110 mm) and offers a number
of benefits over conventional pressure dependent control valves, including:
•
Belimo ball valve design with zero leakage eliminates energy loss.
•
Self-cleaning ball valve technology provides superior clog resistance.
•
Low power consumption up to 95% less than conventional zone valves.
•
Field adjustable Cv value to meet your design requirements.
ZoneTight Pressure Independent Zone Valve (PIQCV)
The PIQCV offers all the advantages of a Pressure Independent
Characterized Control Valve (PICCV) but in an ultra compact
configuration. The PIQCV combines a differential pressure regulator
with a 2-way control valve to supply a specific flow for each degree
of ball opening regardless of system pressure fluctuations. The valve
performs the function of a balancing valve and control valve in one unit.
•
Smallest pressure independent characterized ball valve in the market.
•
Actuator runs at 0.3 W saving energy and transformer power.
•
Flow is adjustable at the actuator and always perfectly balanced.
•
Permits PIV installation in tight spaces.
PIQCV
Pressure
Flow
Tech.Doc - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
3
2
1
1
4
9
2
3
ZoneTight Zone Valve
1
11
6
4
7
5
8
1
10
ZoneTight Pressure Independent Zone Valve
Valve body
Control valve (QCV)
Valve body
Control valve (PIQCV)
Regulator
1
2
Stem
1
Body
4
Stem
7
Regulator Cap
3
Ball with profile
2
End Cap
5
Ball with profile
8
Regulator Body
4
Seat
3
PT Ports
6
Seat
9
Diaphragm
Body
800-543-9038 USA
866-805-7089 CANADA
1
10
Regulator Shaft
1
11
Regulator Spring
203-791-8396 LATIN AMERICA / CARIBBEAN
3
Belimo ZoneTight Zone Valves
Features
ZoneTight Features
Compact Design
When faced with limited available mounting space, the Belimo ZoneTight valve’s super-compact design helps
maximize workable space and complements OEM valve compartment optimization.
Ball Valve Technology
Unlike short stroke globe valves with plug and seat design, the self-cleaning ball helps minimize energy losses
caused by clogging (0% A to AB leakage) and eliminates seat leakage. The intuitive configuration also allows
for bi-directional flow (QCV) unlike traditional paddle style zone valves. In addition, equal percentage flow
characteristic provides superior part load coil performance.
Actuator with Patented Brushless DC Motor
The brushless DC motor’s power consumption when running is a mere 0.3 W (0.2 W when holding) saving
energy and transformer power. In addition to significantly reducing energy costs, this helps eliminate failures
due to stalled motors and prolongs actuator life. It also allows for more units to be powered by a single
transformer.
Snap Fitting
The QCV and PIQCV easily connect to the actuator allowing operators and technicians to install valves quickly,
easily, and without the use of tools. This helps simplify commissioning, reduces labor costs and help reduce
inventory.
Field Adjustable Max Cv/Flow
QCVs and PIQCVs can be quickly and easily field adjusted to ensure that necessary design requirements
are met.
Tech.Doc - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
Stem Extension for Insulation
Unlike conventional zone valve actuators, which are normally covered by pipe insulation, the stem extension
on QCVs and PIQCVs allows for easy actuator removal without damaging the surrounding insulation, helping
simplify operation and maintenance activities.
800-543-9038 USA
4
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
Belimo ZoneTight Zone Valves
Nomenclature
QCV Nomenclature
Z2
050
Q
Valve Type Valve Size
Z2 = 2-way
050 = ½”
Z3 = 3-way
075 = ¾”
ZoneTight
Chrome Plated
Brass Ball and
Brass Stem
-J
Cv
Quick
2-way
Connect
J = 5.9
K = 9.8
3-way
E=1
+CQB
24
-SR
Actuator Type Power Supply Control
Non-Spring Return
CQB
Fail-Safe
CQKB
H = 2.7
J = 4.6
-L
Direction of
Rotation
-S = Built-in
24 = 24 VAC/DC -3 = On/Off,
Aux.
Floating
Point
-L
=
Open
(2
VDC)
UP = 110-230 VAC
Switch
-SR = Proportional -R = Close (2 VDC)
2-10 VDC -LL = Normally
Open, Fail Open
-RR = Normally
Close, Fail Close
-LR = Normally
Open, Fail Close
-RL = Normally
Close, Fail Open
Tech.Doc - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
QCV Ordering Example
1
Choose the valve actuator combination.
Z2050Q-J+CQB24-SR
-L
+Tagging (if needed)
3
2
Choose set-up required
Does order
require
tagging?
Set-Up
Proportional Non-Spring Models
L = Normally Open
R = Normally Closed
Tagging:
Valves may be
tagged per customer
specification. ($10.00
charge per tag)
Fail-Safe Models
LL = Normally Open/Fail Open
LR = Normally Open/Fail Closed
Example:
AHU-1
FCU-2
RL = Normally Closed/Fail Open
RR = Normally Closed/Fail Closed
Part number for tagging:
99981-00101
Refers to valve ports from inlet to outlet,
per flow arrow.
4
Complete Ordering Example:
800-543-9038 USA
Z2050Q-J+CQB24-SR-L
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
5
Belimo ZoneTight Zone Valves
QCV Product Range
Suitable Actuators
3-way
NPT
NonSpring
Return
Fail-Safe
Z3050Q-E
CQK Series
Type
CQ Series
Valve Nominal Size
Cv
Inches
DN [mm]
2-way
NPT
5.9*
½
15
Z2050Q-J
9.8*
¾
20
Z2075Q-K
1
½
15
2.7
½
15
Z3050Q-H
4.6
¾
20
Z3075Q-J
QCV
*Maximum flow. Adjustable 0 to max value.
Mode of Operation
The ZoneTight Zone Valve (QCV) is operated by a rotary actuator.
The actuators are controlled by a standard voltage for on/off control,
a proportional signal, or 3-point control system which move the ball
of the valve to the position dictated by the control system.
Product Features
Actuator Specifications
Control type
-3
on/off, floating point
proportional, 2-10 VDC
-SR
use actuator to turn valve stem
Manual override
Electrical connection
3 ft. [1 m] cable with ½” conduit fitting
screw terminals
Power consumption
CQ..
0.3 W running, 0.2 W holding
CQK..
2.5 W running, 0.5 W holding
CQ..UP
1.0 W running, 0.7 W holding
Power supply
24V (110-230 VAC, UP series)
Transformer sizing
CQ..
0.6 VA
CQK..
5 VA
CQ..UP
2 VA
Valve Specifications
Service
Flow characteristic
chilled or hot water, 60% glycol
equal percentage (2-way)
linear (3-way)
75° (2-way), 90° (3-way)
½”, ¾”
NPT female ends
Controllable flow range
Sizes
End fitting
Materials
Body
forged brass
Ball
chrome plated brass
Stem
brass
Seats
Teflon® PTFE
O-rings
EPDM (lubricated)
Media temp. range
36°F to 212°F [2°C to 100°C]
Media temp. limit*
250°F [120°C]
Maximum allowable
operating temperature
212°F [100°C]
Body pressure rating
360 psi
Close-off pressure
75 psi
Maximum differential
pressure (P)
40 psi
Leakage
0%
Teflon® is a registered trademark of DuPont™
*If temperature exceeds 212°F [100°C] operating range due to a
boiler control failure the valve will safely contain the hot water but
manufacturers product warranty becomes invalid.
800-543-9038 USA
6
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
Tech.Doc - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
The equal percentage characteristic of the flow is ensured by
the design of the ball. This characteristic provides linear heating
or cooling output from the coil improving energy efficiency and
comfort.
Belimo ZoneTight Zone Valves
Nomenclature
PIQCV Nomenclature
Z2
050
Valve Type Valve
Size
Z2 = 2-way
ZoneTight
Chrome
Plated Brass
Ball and Brass
Stem
050 = ½”
Q
P
Quick
Connect
Pressure
Independent
-B
24
-SR
Options Flow Rate Actuator Power
Type
Supply
T = PT
Control
Port
+CQB
B = 0.9 GPM
Non-Spring
D = 1.9 GPM
Return
F = 4 GPM
CQB
Fail-Safe
CQKB
-3 = Floating
Point
24 = 24 VAC/DC
UP = 110-230 -SR = Propor
VAC
tional
2-10
VDC
-R
Direction
of
Rotation
-L = Open
(2 VDC)
-R = Close
(2 VDC)
-LL = Normally
Open, Fail Open
-RR =
Normally Close,
Fail Close
-LR =
Normally Open,
Fail Close
-RL =
Normally Close,
Fail Open
-S = Built
-in
Aux.
Switch
Tech.Doc - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
PIQCV Ordering Example
1
Choose the valve actuator combination.
Z2050QP-B+CQB24-SR
-R
+Tagging (if needed)
3
2
Choose set-up required.
Does order
require
tagging?
Set-Up
Proportional Non-Spring Models
L = Normally Open
R = Normally Closed
Tagging:
Valves may be
tagged per customer
specification. ($10.00
charge per tag)
Fail-Safe Models
LL = Normally Open/Fail Open
LR = Normally Open/Fail Closed
Example:
AHU-1
FCU-2
RL = Normally Closed/Fail Open
RR = Normally Closed/Fail Closed
Refers to valve ports from inlet to outlet, per flow arrow.
4
Complete Ordering Example:
800-543-9038 USA
Part number for tagging:
99981-00101
Z2050QP-B+CQB24-SR-R
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
7
Belimo ZoneTight Zone Valves
PIQCV Product Range
Suitable Actuators
2-way
NPT
with PT ports
NonSpring
Return
Fail-Safe
15
Z2050QPT-B
15
Z2050QPT-D
15
Z2050QPT-F
CQK Series
Type
CQ Series
Valve Nominal Size
GPM
Inches
DN [mm]
0.9*
½
1.9*
½
4*
½
2-way
NPT
*Maximum flow. Adjustable 0 to max value.
PIQCV
Mode of Operation
The ZoneTight Pressure Independent Zone Valve (PIQCV) is a
two-way valve which combines the functionality of a control valve
and a pressure regulating valve, creating one precise product which
is unaffected by pressure variations in a system.
Product Features
Actuator Specifications
Control type
-3
on/off, floating point
-SR
proportional, 2-10 VDC (configurable)
use actuator to turn valve stem
Manual override
Electrical connection
3 ft. [1 m] cable with ½” conduit fitting
screw terminals
Power consumption
CQ..
0.3 W running, 0.2 W holding
CQK..
2.5 W running, 0.5 W holding
CQ..UP
1.0 W running, 0.7 W holding
Power supply
24V (110-230 VAC, UP series)
Transformer sizing
CQ..
0.6 VA
CQK..
5 VA
CQ..UP
2 VA
Valve Specifications
Service
Flow characteristic
Controllable flow range
Sizes
End fitting
Materials
Body
Ball
Stem
Stem packing
Seats
O-rings
Seat o-rings
Spring
Media temp. range
Media temp. limit*
Maximum allowable
operating temperature
PT ports
Body pressure rating
Close-off pressure
Differential pressure
(P) range
Leakage
chilled or hot water, 60% glycol
equal percentage
75°
½”
NPT female ends
forged brass
stainless steel
stainless steel
EPDM (lubricated)
Teflon© PTFE
PTFE
EPDM
stainless steel
36°F to 212°F [2°C to 100°C]
250°F [120°C]
212°F [100°C]
optional
360 psi
100 psi
5 to 50 psi
0%
*If temperature exceeds 212°F [100°C] operating range due to a
boiler control failure the valve will safely contain the hot water but
manufacturers product warranty becomes invalid.
800-543-9038 USA
8
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
Tech.Doc - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
Constant flow regardless of pressure variations in the system at set
degrees of ball opening. Maximizes plant T, preventing energizing
additional chiller or boiler due to low T. Simplified valve sizing and
selection, no Cv calculations required.
Belimo ZoneTight Zone Valves
Set-Up
QCV AND PIQCV SET-UP Specify Upon Ordering
Stays in Last Position
NON-SPRING RETURN
2-WAY VALVE
CQBUP-3
Power to brown wire (pin 2 for -T versions) will drive valve
CW. Power to blue wire (pin 3 for -T versions) will drive
valve CCW.
Power to brown wire (pin 2 for -T versions) will drive
valve CW. Power to blue wire (pin 3 for -T versions)
will drive valve CCW.
CQB24-3
Power to red wire (pin 2 for -T versions) will drive valve
CW. Power to white wire (pin 3 for -T versions) will drive
valve CCW.
Power to red wire (pin 2 for -T versions) will drive valve
CW. Power to white wire (pin 3 for -T versions) will
drive valve CCW.
CQB24-SR
CQB24-SR-R: Normally
closed A to AB, valve will
open as voltage increases.
CQB24-SR-L: Normally
open A to AB, valve will
close as voltage increases.
CQKB24
CQKB24-LL, CQKB24-S-LL:
Normally open A to AB,
valve will drive closed.
CQKB24-RR, CQKB24-S-RR:
Normally closed A to AB,
valve will drive open.
Fail-Safe Action: Actuator
will fail open A to AB upon
power loss.
Fail-Safe Action: Actuator
will fail closed A to AB upon
power loss.
CQKB24-SR-RL: Normally
closed A to AB, valve will
open as voltage increases.
CQKB24-SR-RR: Normally
closed A to AB, valve will
open as voltage increases.
Fail-Safe Action: Will fail
open upon power loss.
Fail-Safe Action: Will fail
closed upon power loss.
CQKB24-SR-LL: Normally
open A to AB, valve will
close as voltage increases
CQKB24-SR-LR: Normally
open A to AB, valve will
close as voltage increases
Fail-Safe Action: Will fail
open upon power loss.
Fail-Safe Action: Will fail
closed upon power loss.
CQKB24-S
CQKB24-SR
Tech.Doc - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
FAIL-SAFE
3-WAY VALVE (QCV ONLY)
800-543-9038 USA
866-805-7089 CANADA
One wire control for CW or CCW rotation.
203-791-8396 LATIN AMERICA / CARIBBEAN
9
Belimo ZoneTight Zone Valves
Accessories
VALVES
ACCESSORIES
Z2 (2-WAY)
Z3 (3-WAY)
ZCQB-FL
Flow setter
•
ZPIQCV-M
QCV/PIQCV valve stem extension
•
•
Architectural Cover
(2016 Release)
•
•
FO15010
½” Flow orifice for 1.0 GPM
•
FO15025
½” Flow orifice for 2.5 GPM
•
FO15055
½” Flow orifice for 5.5 GPM
•
FO20100
¾” Flow orifice for 10.0 GPM
•
Tech.Doc - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
FLOW ORIFICE
800-543-9038 USA
10
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
Belimo ZoneTight Zone Valves
Flow Pattern
QCV Flow Pattern
QCV 2-way valves can be piped with flow entering and exiting
either port.
For on/off control of coil flow the QCV 3-way valve can be piped with
the AB port connected to the supply or the return. For changeover
application, AB port can be piped to the coil.
INLET
OUT
OUTLET
TTLET
For a QCV 3-way switching application, pipe hot and cold supply
water to ports A and B and the appropriate seasonal supply water
will exit the AB port for regulation by another 2-way valve; typically
installed in the return pipe.
Port A
Port B
Port AB
Tech.Doc - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
PIQCV Flow Pattern
The PIQCV consists of a differential pressure regulator and a
control valve. The control valve is throttled to match the flow
command of the control signal. The differential pressure regulator
holds the pressure drop across the ball of the valve. As system
pressure changes, the differential pressure regulator moves in
response to keep the flow stable. Pressure (P1) at the inlet PIQCV is
high and pressure (P3) at the outlet is low. The differential pressure
between (P1) and (P3) must be between 5-50 to achieve pressure
independent flow. When differential pressure increases
the regulator opening is decreased. When differential pressure
decreases the regulator opening is increased. This allows for the
constant pressure differential across the ball of the valve.
800-543-9038 USA
P3
866-805-7089 CANADA
P1
P2
P3
203-791-8396 LATIN AMERICA / CARIBBEAN
11
Belimo ZoneTight Zone Valves
Piping
QCV Typical Piping
2-way Valve Piping Diagram
3-way Switching Valve Piping Diagram
3-way Diverting Valve Piping Diagram
PIQCV Typical Piping
BELIMO PIQCV (TYP.)
FLOW
H/C–COIL
P/T PORT
P/T PORT
FLOW
SHUT–OFF
VALVE
AIR VENT
UNION CONNECTION (TYP.)
FLOW
P/T PORT
FLOW
STRAINER
(Optional)
FLOW
SHUT–OFF
VALVE
DRAIN
TYPICAL PARALLEL PIPING IN RELATION
TO THE INPUT AND OUTPUT
800-543-9038 USA
12
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
Tech.Doc - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
PIQCVs are recommended to be installed on the return side of the coil. This diagram represents a typical application. Consult engineering specification and
drawings for project details. PT ports are recommended if not supplied on either side of the valve and the supply side of the heat transfer device to allow for
pressure/flow measurement/calculation.
Belimo ZoneTight Zone Valves
Orientation
QCV/PIQCV Orientation
QCV and PIQCV assemblies can be installed in a vertical or horizontal arrangement, as long as the actuator is positioned to avoid water from
dripping on the actuator.
!
QCV
kg
PIQCV
kg
Tech.Doc - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
>122°F
PIQCV’s should be installed with flow in the direction of the arrow on the valve body. If installed backwards, there could be damage to either the
diaphragm or the regulator. The valve assembly can be installed in a vertical or horizontal arrangement.
360°
90°
90°
90°
90°
800-543-9038 USA
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
13
Belimo ZoneTight Zone Valves
Field-Set Adjustment
QCV/PIQCV Field-Set Flow Capacity Adjustment
Align the clip to the notch scale found on the underside of the actuator to the corresponding flow in the table below. For 3-point floating control
signals adjust the controller runtime parameter to match the runtime of the of the final clip position. For analog 2-10 VDC control signals see
adaption instructions.
For incremental notch settings refer to the flow graphs on page 25 or visit www.zonetight.com and put in your flow requirements to determine
your notch position.
QCV
1
2
1
2
Valve Model
1/2"
3/4"
Clip Position for Cv Adjustment (2-way Valves)
1
2
3
4
5
6
N
No Clip
Z2050Q-J
0.5
0.7
1.2
1.7
2.4
3.4
4.8
5.9
Z2075Q-K
0.5
1.0
1.5
2.3
3.3
4.6
6.6
9.8
30 sec
37 sec
43 sec
49 sec
55 sec
62 sec
68 sec
75 sec
Actuator Runtime
PIQCV
1
2
1
2
Valve Model
(1/2")
Clip Position for Flow Adjustment (GPM)
1
2
3
4
5
6
N
No Clip
0.1
0.2
0.4
0.6
0.8
0.9
0.3
0.4
0.5
0.7
1
1.4
1.9
0.7
1.0
1.4
2.1
2.9
3.7
4.3
37 sec
43 sec
49 sec
55 sec
62 sec
68 sec
75 sec
Z2050QPT-B
Z2050QPT-D
0.2
Z2050QPT-F
Actuator Runtime
30 sec
NPT Installation
ZoneTight valves are provided with ASME NPT female pipe treads for connection to threaded pipe.
800-543-9038 USA
14
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
Tech.Doc - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
Size
Belimo ZoneTight Zone Valves
Installation
Actuator Attachment for QCV/PIQCV
Attach the actuator to the valve body. Align the actuator guide pins to the valve bonnet openings and press down until a click is heard. To remove
the actuator, grasp it with your hand and pull it away from the valve body.
2
click
3
1
Tech.Doc - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
Adaption for Proportional Actuators
For actuators with analog 2-10 VDC signal, after flow capacity adjustment has
been field-set by moving the clip to a desired position, execute the adaption
routine to scale the signal across the available travel. The actuator will travel
first in one direction and stall, then will travel in the opposite direction and
stall. Then it will travel to the commanded position of the control signal. When
the actuator is powered for the first time the adaption routine will execute
automatically. Execute the adaption function any time the clip position is
changed. The adaption routine does not change the actuator speed, which is
75 seconds over 90 degree rotation.
Adaption
For actuators with On/Off or Floating Control input there is no adaption
function or button.
Proportional Actuators: CQB24-SR, CQB24-SR-L, CQB24-SR-R, CQKB24-SR,
CQKB24-SR-LL, CQKB24-SR-RR, CQKB24-SR-LR, CQKB24-SR-RL
On/Off, Floating Point Actuators: CQB24-3, CQBUP-3
On/Off Actuators: CQKB24, CQKB24-S
Proportional Actuator
Insulation
On/Off, Floating Point
Actuator
Insulation should wrap the pipe and valve body but not the actuator. For chilled water applications use the stem extension kit accessory to raise
the actuator above the valve body to provide space for insulation.
kg
>122°F
800-543-9038 USA
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
15
Belimo ZoneTight Zone Valves
Wiring Diagrams
Wiring Diagrams
2
Line
Volts
1
Provide overload protection and disconnect as required.
2
Actuators may be connected in parallel. Power consumption and
input impedance must be observed.
3
Actuators may also be powered by 24 VDC.
5
Only connect common to neg. (-) leg of control circuits.
7
A 500 Ω (ZG-R01) converts the 4 to 20 mA control signal to 2 to 10
VDC.
18
Actuators with plenum rated cable do not have numbers on wires;
use color codes instead.
100
One built-in auxiliary switch (1x SPST), for end position indication,
interlock control, fan startup, etc.
A
Functions
3
18
Blk
Common
Red
+ Hot
A
0%
1
100
100%
S1
S2
NO
On/Off, CQKB24-S-LL
2
Line
Volts
Meets cULus requirements without the need of an electrical
ground connection
Control Signal
VDC/mA
3
5
7
18
Blk
Common
Red
+ Hot
Wht
Y1 Input, 2 to 10V
500
WARNING Live Electrical Components!
2 VDC Close
Open
10 VDC Open
Close
Fail Position
100% Open
2
2
Line
Volts
A
Functions
3
18
Blk
Common
Red
Hot
+
Line
Volts
Control Signal
VDC/mA
A
0%
3
5
7
18
Blk
Common
Red
+ Hot
Wht
Y1 Input, 2 to 10V
500
2 VDC
Open
10 VDC
Close
Fail Position
0%
Close
100%
Proportional, CQKB24-SR-LR
On/Off, CQKB24-RR
2
2
Line
Volts
A
3
Blk
Common
Red
Hot
Line
Volts
5
7
18
Blk
Common
Red
+ Hot
Wht
Y1 Input, 2 to 10V
+
Control Signal
VDC/mA
Functions
3
18
A
0%
500
2 VDC Close
Close
10 VDC Open
Open
Fail Position
100% Open
100%
Proportional, CQKB24-SR-RL
On/Off, CQKB24-LL
2
Line
Volts
A
3
2
18
Blk
Common
Red
+ Hot
Line
Volts
Control Signal
VDC/mA
Functions
3
5
7
18
Blk
Common
Red
+ Hot
Wht
Y1 Input, 2 to 10V
500
A
100%
1
100
0%
S1
2 VDC Close
Close
10 VDC Open
Open
Fail Position
0%
Close
S2
On/Off, CQKB24-S-RR
800-543-9038 USA
16
NO
Proportional, CQKB24-SR-RR
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
Tech.Doc - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
During installation, testing, servicing and troubleshooting of this
product, it may be necessary to work with live electrical components. Have a
qualified licensed electrician or other individual who has been properly
trained in handling live electrical components perform these tasks. Failure to
follow all electrical safety precautions when exposed to live electrical
components could result in death or serious injury.
Belimo ZoneTight Zone Valves
Wiring Diagrams
Wiring Diagrams
2
Actuators may be connected in parallel. Power consumption and
input impedance must be observed.
2
3
Actuators may also be powered by 24 VDC.
5
Only connect common to neg. (-) leg of control circuits.
7
A 500 Ω (ZG-R01) converts the 4 to 20 mA control signal to 2 to 10
VDC.
18
Actuators with plenum rated cable do not have numbers on wires;
use color codes instead.
Meets cULus requirements without the need of an electrical
ground connection
Line
Volts
7
18
Common
Red
+ Hot
Wht
Y1 Input, 2 to 10V
500
Control Signal
VDC/mA
2 VDC
Open
10 VDC
Close
Proportional, CQB24-SR-L
24 VAC Transformer
2
Line
Volts
3
5
7
18
Blk
Common
Red
+ Hot
Wht
Y1 Input, 2 to 10V
500
Control Signal
VDC/mA
2 VDC
Close
10 VDC
Open
Proportional, CQB24-SR-R
24 VAC Transformer
2
Line
Volts
3
18
Blk
Common
Red
+
110 to 230 VAC
2
Line
Volts
A
Wht
Tech.Doc - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
5
Blk
WARNING Live Electrical Components!
During installation, testing, servicing and troubleshooting of this
product, it may be necessary to work with live electrical components. Have a
qualified licensed electrician or other individual who has been properly
trained in handling live electrical components perform these tasks. Failure to
follow all electrical safety precautions when exposed to live electrical
components could result in death or serious injury.
3
Functions
+
18
Blu
Common
Brn
+
Wht
+
A
A
100%
Functions
0%
100%
A
0%
On/Off, CQB24-3
On/Off, CQBUP-3
2
3
18
2
1
Common
A
2
+
B
3
+
Line
Volts
Line
Volts
A
B
Functions
A
0%
18
Blu
Common
Brn
+
Wht
+
B
Functions
A
B
0%
100%
100%
Floating Point, CQB24-3
Floating Point, CQBUP-3
800-543-9038 USA
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
17
Belimo ZoneTight Zone Valves
Flow Verfication
Mechanical PIQCV Pre-Flow
Verification Checklist
After the actuator travel limit clip has been correctly located to position
1-7 (or removed) to match the maximum flow setting of the coil, the
following procedures detail the flow verification and commissioning
procedures for Pressure Independent Valves Quick Compact Valves
(PIQCV). These procedures are not mandatory to ensure proper
operation of PIQCV. PIQCVs are very different from pressure dependent
control valves (standard control valves). Pressure variations in the
system do not affect flow through the PIQCV. Additional flow regulating
devices (e.g. circuit setters and automatic flow limiting devices) should
not be used in conjunction with PIQCVs. This makes the Testing and
Balancing (TAB) or commissioning process much different from
standard control valves. PIQCVs offer numerous maximum design flow
values in each valve body size. It is important to note that the valve will
travel to 90 degrees only when there is no end stop.
External P/T ports allow for independent verification of proper PIQCV
operation. Additionally, these ports allow for future comprehensive
troubleshooting and diagnosis. For proper and accurate flow
verification of the mechanical PIQCV, it is essential that the mechanical
contractor install P/T ports A, B & C as shown in Figure A if the
mechanical PIQCV body is not supplied with integrated ports. If the
PIQCV includes integrated PT ports the mechanical contractor only
needs to install P/T port A.
•
P/T port A and P/T port B (or A and P1) are used for measuring
pressure differential across the coil (used to measure water P to
equate to flow) or to measure water T across the coil.
•
P/T port B and P/T port C (or P1 and P3) are used to measure P
across the PIQCV assembly. PIQCVs must have 5 – 50 psid (11.5
ft. – 115 ft. H2O) (or per manufacturer’s specification) differential
pressure within this range. Do not manually remove the actuator
travel limit clip to fully open the valve to check for design flow
or pressure. Valve shall be commanded to design flow position
via analog or BMS (Building Management System) signal. The
required operating differential pressure range is necessary to
insure pressure independent operation of the PIQCV
•
Verify that system is purged of air and filled to proper pressure.
•
Verify that each PIQCV has the manufacturer’s required operating
differential pressure range across P/T ports B and C (or P1 and P3)
as shown in fig. A.
•
Verify proper pump operation per manufacturer’s specifications.
•
Verify proper supply water temperature is available and is at design
temperature.
•
Proper air filter maintenance has been completed.
•
Fan belts are in proper working order.
•
Heat transfer devices (coils) are clean.
•
Strainers are clean.
•
All manual shutoff valves are open.
•
All bypass valves are closed.
•
No automatic or manual balancing valves exist. If they do exist,
they must be set fully open and locked to not interfere with the
pressure independency function of the PIQCV.
PIQCV Flow Verification and Commissioning
Tech.Doc - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
PIQCV Flow Verification and
Commissioning Overview without Flow
Orifice Device
Note: The flow setter (ZCQB-FL) can be used to adjust the flow if the
BMS is not available during the commissioning process.
BELIMO PIQCV (TYP.)
FLOW
H/C–COIL
P/T PORT
P/T PORT
B
AIR VENT
FLOW
C
P1
SHUT–OFF
VALVE
P3
UNION CONNECTION (TYP.)
FLOW
P/T PORT
800-543-9038 USA
18
FLOW
STRAINER
(Optional)
FLOW
SHUT–OFF
VALVE
A
DRAIN
866-805-7089 CANADA
TYPICAL PARALLEL PIPING IN RELATION
203-791-8396 LATIN AMERICA / CARIBBEAN
Belimo ZoneTight Zone Valves
Flow Verification
Procedures without Flow Orifice Device
Procedure #3 (Terminal Level Verification) – Water Delta Method
Procedure #1 (System Verification) – Total System Flow Method
Verification for PIQCV Cooling/Heating
Verification for PIQCV Cooling/Heating
1. Verify that the system is in proper working order. Depending on the
valves used, check the items listed for PIQCV Pre-Flow Verification
Checklists. Ensure that water is at design temperature.
1. Verify that the system is in proper working order. Depending on the
valves used, check the items listed for PIQCV Pre-Flow Verification
Checklists.
2. If diversity factor = 100%, command open all PIQCV’s via the BMS
system. Systems with less than 100% diversity need to have a
number of valves closed to match design diversity.
3. Ensure that pumps are either manually commanded to sufficient
speed to provide proper differential pressure across all valves OR
if pumps are under DDC pressure control ensure P setpoint is
sufficient to provide the above conditions.
•
Verify total system flow in main return line is at system design flow
rate using one of the following methods: Orifice, Venturi, Electronic
flow meter, System-level Flow Device
1. Decrease the pump speed (or decrease P setpoint if under
control) until a measureable flow decrease occurs.
2. Increase pump speed (or increase P setpoint if under control)
slowly until design flow is reestablished. Make note of the resulting
P. This will be the maximum system P operating setpoint.
Tech.Doc - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
Note: If total flow does not match design flow then troubleshooting
must be done to determine cause. This may involve verifying flows at
the terminal level.
Procedure #2 (Terminal Level Verification) – Air Delta T Method
Verification for PIQCV Cooling/Heating
1. Verify that the system is in proper working order. Depending on the
valves used, check the items listed for PIQCV Pre-Flow Verification
Checklists.
2. Ensure that water is at design temperature.
3. Ensure that terminal airflow is at design airflow rate (cfm).
4. Command open the PIQCV via analog or BMS control signal to
maximum design flow position. (Do not manually open the PIQCV
beyond the actuator travel limit clip position).
2. Ensure that terminal airflow is at design flow rate (cfm) or water
coil airflow is unencumbered.
3. Command open the PIQCV via analog or BMS control signal to
maximum design flow position. (Do not manually open the PIQCV
beyond the actuator travel limit clip position.)
4. Reference approved engineering document containing design
water temperature drop/rise for design conditions.
5. Measure water temperature differential of coil by using P/T ports A
and B (or A and P1) as referenced in Fig. A.
6. Measured temperature differential should be equal to designed
water temperature differential (EWT, LWT) as shown on the
contract documents.
Procedure #4 (Terminal Level Verification) – Coil P (Delta P)
Method
Verification for PIQCV Cooling/Heating
1. Verify that the system is in proper working order. Depending on the
valves used, check the items listed for PIQCV Pre-Flow Verification
Checklists.
2. Command open the PIQCV via analog or BMS control signal to
maximum design flow position. (Do not manually open the PIQCV
beyond the actuator travel limit clip position.)
3. Ensure P across valve assembly between P/T ports B and C (or
P1 and P3) as shown above in Fig. A is within manufacturer’s
operating parameters.
4. Reference approved engineering document containing design coil
water pressure drop (usually expressed in ft. of water) for design
flow conditions. This value will be for the heating/cooling coil
associated with corresponding PIQCV.
5. Reference approved engineering document containing design air
temperature drop/rise for design conditions.
5. Measure coil P by using P/T ports A and B (or A and P1) as
referenced in Fig. A.
6. Measure coil inlet air temperature and coil discharge air
temperature.
6. Formula to calculate flow is: Actual GPM = Design GPM x
7. Difference between coil inlet air reading (EAT) and coil discharge
air reading (LAT) should equal to or exceed design air delta T as
shown on the contract documents.
Note: Measured Coil P and Design Coil P must be expressed in the
same engineering units (feet of water, inches of water, psi, etc.).
800-543-9038 USA
(Measured Coil P/Design Coil P)
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
19
Belimo ZoneTight Zone Valves
Flow Verfication
Flow Verification with Flow Orifice Device
Belimo flow orifice device has two pressure ports for field P measurement with a
manometer gauge.
Connect manometer high pressure line to flow orifice red PT port; connect low pressure line to green
PT port. Follow gauge instructions to verify connections.
TakeP reading in inches of water (w.c.) and transpose to the Flow Orifice line of the Flow Chart.
From that point follow the corresponding chart line to the flow scale and determine the actual flow.
Refer to field-set procedure section on page 14 to adjust flow capacity to meet project requirements.
•
•
•
•
Meter Readings, Water @ 70°F / 21°C
FO15010
1
FO15025
FO15055
FO20100
2
FO15010
FO15055
FO20100
FO15025
Temperature Correction Factor:
155°F / 68°C = 1.01 x GPM
205°F / 96°C = 1.02 x GPM
800-543-9038 USA
20
How to Determine Flow:
1. Enter the chart with the ¨P (differential pressure) reading.
2. Go horizontally across to the size of the valve.
3. Go vertically up or down to read the GPM (flow).
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
Tech.Doc - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
2
FO15010
FO15025
FO15055
FO20100
Belimo ZoneTight Zone Valves
Troubleshooting
Problem
Field Observations
Possible Solution
Actuator will not move.
Actuators wires are connected.
Verify the power supply and control signal are wired and operating correctly.
Remove the actuator from the valve body and use the actuator or a slotted
screwdriver to move the valve stem to verify free rotation.
Valve throttles to a different
position than expected.
For 3-point floating signals the actuator runtime is relative to the travel set by
the clip. The controller runtime parameter may need to be adjusted to match
the runtime of the actuator.
Valve is yielding flow but
cannot be commanded to the
full flow setting
Valve is partially open but will not For analog actuators the adaption function may have previously occurred to
move to a full open position with a a lesser angle of rotation than now exits. Press the adaption button and the
full signal command.
actuator will re-scale to the full travel set by the clip position.
Full flow is lower than
expected.
Clip may be in the wrong position.
The clip may need to be adjusted to a greater angle of rotation to allow
more flow, or removed to obtain maximum flow capacity. Refer to the
flow commissioning instructions (page 18) for adjustment and verification
procedures.
Desired flow cannot be
reached.
Valve is wide open.
Increase the pump differential pressure to resolve low flow problems.
Flow measurements are
not stable.
Air may be in the system.
Remove air from the system to solve the problem.
Tech.Doc - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
Actuator does not modulate
with the control signal as
expected.
800-543-9038 USA
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
21
Belimo ZoneTight Zone Valves
Chrome Plated Brass Ball, NPT Female Ends
Application
The QCV zone valves are suited for large commercial buildings where higher
close-off and the ability to change flow is desired. Common applications
include unit ventilators, fan coil units, VAV reheat coils, fin tube casing,
radiant panels and duct coils. The valve fi ts in space restricted areas and can
be assembled without the use of tools.
Dimensions 2-Way
QCV
D
Valve Specifications
C
chilled or hot water, 60% glycol
equal percentage (2-way), linear (3-way)
75° (2-way), 90° (3-way)
½”, ¾”
NPT female ends
E
B
F
A
forged brass
chrome plated brass
brass
Teflon® PTFE
EPDM (lubricated)
36°F to 212°F [2°C to 100°C]
250°F [120°C]
212°F [100°C]
360 psi
75 psi
Valve
Nominal Size
DN
In.
[mm]
½”
Non-Spring
15
Dimensions (Inches [mm])
A
B
C
D
E
F
4.5”
[114]
2.05”
[52]
3.27”
[83]
2.71”
[69]
1.02”
[26]
1.02”
[26]
20
4.5”
[114]
2.4”
[61]
3.42”
[86.9]
2.77”
[70]
1.2”
[31]
1.2”
[31]
15
4.5”
[114]
2.05”
[52]
3.27”
[83]
2.71”
[69]
1.02”
[26]
1.02”
[26]
20
4.5”
[114]
2.4”
[61]
3.42”
[86.9]
2.77”
[70]
1.2”
[31]
1.2”
[31]
Return
¾”
Non-Spring
Return
½”
Fail-Safe
40 psi
0%
¾”
*If temperature exceeds 212°F [100°C] operating range due to a boiler control failure the
valve will safely contain the hot water but manufacturers product warranty becomes invalid.
Fail-Safe
Dimensions 3-Way
D
C
B
E
F
Valve
Nominal Size
DN
In.
[mm]
½”
Non-Spring
15
B
C
D
E
F
4.5”
[114]
2.05”
[52]
3.69”
[94]
2.56”
[65]
1.02”
[26]
1.02”
[26]
20
4.5”
[114]
2.4”
[61]
3.83”
[97]
2.63”
[67]
1.2”
[31]
1.2”
[31]
15
4.5”
[114]
2.05”
[52]
3.83”
[97]
2.71”
[69]
1.02”
[26]
1.02”
[26]
20
4.5”
[114]
2.4”
[61]
3.98”
[101]
2.77”
[70]
1.2”
[31]
1.2”
[31]
¾”
½”
Fail-Safe
¾”
Fail-Safe
800-543-9038 USA
22
866-805-7089 CANADA
Dimensions (Inches [mm])
A
Return
Non-Spring
Return
A
203-791-8396 LATIN AMERICA / CARIBBEAN
Tech.Doc - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
Service
Flow characteristic
Controllable flow range
Size
Type of end fitting
Materials
Body
Ball
Stem
Seats
O-rings
Media temperature range
Media temperature limit*
Max. allowable operating temp.
Body pressure rating
Close-off pressure
Maximum differential
pressure (P)
Leakage
Belimo ZoneTight Pressure Independent Zone Valves
Stainless Steel Ball, NPT Female Ends
Application
The PIQCV zone valves with its pressure independent technology are suited
for large commercial buildings where higher close-off and dynamic balancing
is required. Common applications include unit ventilators, fan coil units, VAV
reheat coils, fin tube casing, radiant panels and duct coils. The valve fits in
space restricted areas and can be assembled without the use of tools.
Dimensions Z2050QPT-B, Z2050QPT-D
PIQCV
D
Tech.Doc - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
Valve Specifications
Service
Flow characteristic
Controllable flow range
Size
Type of end fitting
Materials
Body
Ball
Stem
Stem packing
Seats
O-rings
Seat o-rings
Spring
Media temperature range
Media temperature limit*
Max. allowable operating temp.
PT ports
Body pressure rating
Close-off pressure
Differential pressure (P) range
Leakage
C
chilled or hot water, 60% glycol
equal percentage
75°
½”
NPT female ends
E
B
F
A
forged brass
stainless steel
stainless steel
EPDM (lubricated)
Teflon® PTFE
PTFE
EPDM
stainless steel
36°F to 212°F [2°C to 100°C]
250°F [120°C]
212°F [100°C]
included
360 psi
100 psi
5 to 50 psi
0%
Valve
Nominal Size
DN
In.
[mm]
½”
Non-Spring
15
Return
½”
15
Fail-Safe
Dimensions (Inches [mm])
A
B
C
D
E
F
4.49”
[114]
3.78”
[96]
4.17”
[106]
3.15”
[80]
1.93”
[44]
1.93”
[49]
4.49”
[114]
3.78”
[96]
4.33”
[110]
3.31”
[84]
1.93”
[44]
1.93”
[49]
Dimensions Z2050QPT-F
*If temperature exceeds 212°F [100°C] operating range due to a boiler control failure the
valve will safely contain the hot water but manufacturers product warranty becomes invalid.
D
C
E
B
F
A
Valve
Nominal Size
DN
In.
[mm]
½”
Non-Spring
15
Return
½”
Fail-Safe
800-543-9038 USA
866-805-7089 CANADA
15
Dimensions (Inches [mm])
A
B
C
D
E
F
4.49”
[114]
4.17”
[106]
4.5”
[114.3]
3.5”
[89]
1.93”
[44]
1.93”
[49]
4.49”
[114]
4.17”
[106]
3.35”
[85]
3.5”
[89]
1.93”
[44]
1.93”
[49]
203-791-8396 LATIN AMERICA / CARIBBEAN
23
Belimo ZoneTight Zone Valves
Non-Spring Return and Fail-Safe Actuator Series
Operation
The ZoneTight Zone Valves (QCV, PIQCV) are operated by rotary actuators.
The actuators are controlled by a standard voltage for on/off control,
proportional signal, or 3-point control system which move the ball of the
valve to the position dictated by the control system.
Non-Spring Return CQ.., CQ..UP
Fail-Safe Actuators CQK..
Manual override
Power consumption
CQ...
CQK...
CQ..UP
Transformer sizing
CQ...
CQK...
CQ..UP
Electrical connection
24V (110-230 VAC, UP series)
use actuator or slotted screwdriver to turn
valve stem
0.3 W running, 0.2 W holding
2.5 W running, 0.5 W holding
1.0 W running, 0.7 W holding
0.6 VA
5 VA
2 VA
3 ft., 18 GA, plenum rated cable
½” conduit connector
Overload protection
Non-Spring Return
Fail-Safe
Operation range Y
electronic throughout 0° to 90° rotation
electronic throughout full stroke
on/off
Angle of Rotation
90°, adjustable with mechanical stop
Position Indication
pointer
Running Time (Motor)
75 seconds
Running Time (Fail-Safe)
60 seconds
Humidity
5 to 95% RH non-condensing
Ambient Temperature Range
+35°F to +104°F [+1.7°C to +40°C]
Storage Temperature Range
-40°F to +176°F [-40°C TO +80°C]
Housing
NEMA 2, IP40, UL enclosure type 2
Housing Material
Noise Level (Motor)
UL94-5VA
cULus acc. to UL60730-1A/-2-14, CAN/CSA
E60730-1:02, CE acc. to 2004/108/EC and
2006/95/EC
<35 dB (A)
Servicing
maintenance free
Quality Standard
ISO 9001
Weight
Non-Spring Return
Fail-Safe
0.44 lb [0.2 kg]
3.6 lbs [1.6 kg]
Agency Listings†
Quality standard
Agency listings
ISO 9001
UL 60730-1/2-14, 2-18, CE according to
2004/108/EC and 2006/95/EC
800-543-9038 USA
24
Tech.Doc - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
Actuator Specifications
Power supply
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
Belimo ZoneTight Zone Valves
Flow Curves
Valve Flow Charts
Two notch positions exist between numbered notches for field-set clip positioning to obtain maximum flow capacity. Refer to charts and set the
clip as needed.
QCV Flow Curves
Actuator Runtime (Seconds)
30 33 35 37 39 41 43 45 47 49 51 53 55 58 60 62 64 66 68
7.0
75
5.9
6.0
5.0
Cv
4.3
4.0
3.0
2.0
1.0 0.5
0.6 0.7
1.2
0.9 1.0
1.3 1.5
1.7
2.4
1.9 2.1
2.6
3.0
3.4
4.8
3.8
0.0
1
2
3
4
5
6
Clip in Notch Position
N
Removed
(Default)
Z2050Q-J Flow Capacity
Tech.Doc - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
Actuator Runtime (Seconds)
30 33 35 37 39 41 43 45 47 49 51 53 55 58 60 62 64 66 68
75
11.0
9.8
10.0
9.0
8.0
6.6
7.0
5.8
5.1
Cv 6.0
4.6
5.0
4.0
3.7
4.0
2.9 3.3
2.5
2.3
3.0
2.0
1.5 1.7
1.3
1.1
2.0
1.0
0.5 0.7 0.8
1.0
0.0
1
2
3
4
5
6
N
Removed
(Default)
Clip in Notch Position
Z2075Q-K Flow Capacity
800-543-9038 USA
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
25
Belimo ZoneTight Zone Valves
Flow Curves
PIQCV Flow Curves
Actuator Runtime (Seconds)
30 33 35 37 39 41 43 45 47 49 51 53 55 58 60 62 64 66 68
1.0
0.9
0.8
0.7
0.6
GPM 0.5
0.4
0.3
0.2
0.1
0.0
75
0.9
0.8
0.7
0.5
0.3
0.6
0.4
0.2
0.1
1
2
3
4
5
6
N
Removed
(Default)
Clip in Notch Position
Z2050QP(T)-B Flow Capacity
Actuator Runtime (Seconds)
30 33 35 37 39 41 43 45 47 49 51 53 55 58 60 62 64 66 68
2.3
75
1.9
2.0
1.8
1.5
GPM
1.3
1.0
0.7
0.3
0.9
1.2
1.3
1.4
0.5 0.6
0.8
0.5
0.8
1.0
0.2
0.3
1
2
0.4
0.0
3
4
5
Clip in Notch Position
6
N
Removed
(Default)
800-543-9038 USA
26
Tech.Doc - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
Z2050QP(T)-D Flow Capacity
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
Belimo ZoneTight Zone Valves
Terms and Conditions of Sale and Warranty
T
Terms
and
d Conditions
C di i
General
1.1. The following Terms and Conditions of Sale (“Terms”) apply
to the sale of products described in this Product Guide
(“Products”). As used herein, “Seller” or “Belimo” refers to
Belimo Aircontrols (USA) Inc. or Belimo Aircontrols (CAN) Inc.,
as applicable, and “Client” refers to the individual or business
entity that purchases the Products from Seller. These Terms
shall apply unless the parties mutually agree to different terms
and memorialize such agreement in writing signed by both
Client and Seller.
II.
Tech.Doc - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
III.
Price
2.1. The Seller’s price for Products (the “Price”) is net, F.O.B.
Point of Origin, and is calculated in US currency for sales made
by Belimo Aircontrols (USA), Inc. and calculated in Canadian
currency for sales made by Belimo Aircontrols (CAN) Inc.
2.2. The Price, unless otherwise agreed upon, does not include
freight and packaging (wooden crates, pallets, etc), the costs of
which will be charged to Client at cost for each shipment and
shall be payable with payment of the Price.
2.3. Orders for Products with a net value of less than US $300
(CAN $300) will be subject to a US $20 (CAN $20) handling fee
(the “Handling Fee”). The Handling Fee will not be charged for
orders of Products with a net value equal to or greater than
US $300 (CAN $300) or for Products ordered through Seller’s
eCommerce ordering system at: www.belimo.com.
2.4. Seller reserves the right to make partial deliveries of orders
of Products, each of which deliveries may be invoiced
separately by Seller.
2.5. The Price does not include charges for wiring diagrams,
installation, and commissioning, which will be charged to Client
separately and will be payable on demand.
Payment
3.1. Invoices are payable in US currency for sales made by
Belimo Aircontrols (USA), Inc. and in Canadian currency for
sales made by Belimo Aircontrols (CAN) Inc. and are due no
later than 30 days from the date of invoice, without any
deductions.
3.2. If Client fails to pay the entire invoice balance within 60 days
from the date of the invoice, Client will be subject to an interest
charge of 2% per month (or the maximum rate permitted by law,
whichever is less) on the outstanding unpaid balance due to
Seller.
3.3. Clients who maintain outstanding balances for 45 days or
more after the date of invoice may be subject to restricted
shipments of Products or may be required to pay for all future
deliveries of Products on a cash-on-delivery basis.
IV.
Title and Risk
4.1. Title to all Products shall remain with Seller and shall not
pass to Client until Seller has received full payment for the
Products.
V.
Damage or Loss in Transit
5.1. Seller assumes no liability for damage or loss of shipment
of Products, which risk shall at all times remain with the carrier.
All shipments must be unpacked and examined by Client
immediately upon receipt. Any external evidence of loss or
damage must be noted on the freight bill accompanying the
shipment of Products or carrier’s receipt and signed by the
carrier’s agent at the time of delivery. Failure to do so will result
in the carrier’s refusal to honor any claim relating to damage of
Products. Client must also notify Seller of such damage by
providing Seller with a copy of the freight bill or damage report
so that Seller can file a claim for loss or damage in transit with
the carrier. If the damage does not become apparent until the
shipment is unpacked, Client must make a request for inspection
800-543-9038 USA
by the carrier’s agent and file with the carrier within 15 days
after receipt of product and notify Seller of the same. Seller is
not liable for consequential damage to Client’s property or a
third-party’s property resulting from the installation of damaged
Products.
VI.
Delivery
6.1. Seller undertakes to make every attempt to adhere to its
stated delivery parameters and to make a timely delivery of the
Products but does not guarantee any delivery specifications.
Each contract entered into for the purchase of Products is not
cancelable nor is Seller liable for any direct or indirect losses
that may arise, for any reason whatsoever, due to Seller’s failure
to meet any stated or assumed delivery schedules.
VII.
Return of Goods
7.1. Products received by Client cannot be returned unless: (i)
Client alerts Seller that it intends to return such Products, (ii)
Seller agrees to accept the return of such Products, (iii) Client
obtains a Return Material Authorization (“RMA”) number from
Seller for the return of such Products, and (iv) Client follows all
return instructions provided by the Seller. The RMA numberr
must be clearly written on the outside of all packaging for any
returned Products. Only Products returned to the properr
location as instructed by Seller and identified with an RMA
A
number will be considered for credit.
7.2. Only Products that are returned in original packaging may
be accepted for return. All returned Products must be shipped
to Seller at Client’s cost. Such returned Products must be
received within 1 yr. from original sale date, in as-new condition,
adequate for resale as new Products to qualify for credit. Client
will be responsible for payment of a restocking charge for all
returned Products in an amount no less than 20% of the invoice
value of the Products (“Restocking Charges”). Product received
damaged or showing evidence of having been installed will be
refused or assessed a higher restocking charge. Custom kits
designed to a Client’s unique specifications are not returnable.
If Client requests product to be returned to them, the Client will
be responsible for return shipping charges. See specific product
literature for exclusions or exceptions.
7.3. Returns that result from Seller errors will be credited in full
and will not be subject to Restocking Charges.
VIII. Warranty
VIII.A 5-year Warranty
8.1. Products that are listed in this Product Guide as carrying a
5-year warranty to a location in the United States or Canada
shall carry a 5-year warranty.
The 5-year warranty is
unconditional for the first two years from the date of production
of the Products. After the first two years from the date of Sale,
the warranty shall be conditional and the warranty coverage
shall not apply to damage to Products caused by ordinary wearr
and tear, negligence or improper use by Client, or other causes
beyond the control of the Seller. Product specific terms off
warranty with regard to warranty period or conditions off
warranty may apply to certain specified Products as stated in
the documentation for those Products.
VIII.B 2-year Conditional warranty
8.2. Products that are listed in this Product Guide as carrying a
2-year warranty to a location in the United States or Canada
shall carry a 2-year warranty. The 2-year warranty is conditional
and the warranty coverage shall not apply to damage to
Products caused by ordinary wear and tear, negligence orr
improper use by Client, or other causes beyond the control off
the Seller. Product specific terms of warranty with regard to
warranty period or conditions of warranty may apply to certain
specified Products as stated in the documentation for those
Products.
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
27
VIII.C General Warranty Terms
8.3. Seller’s warranty may be null and void in the event of any:
(a) modification or unauthorized repairs of Products by Client,
(b) unauthorized incorporation or integration of Products into or
with Client’s equipment, (c) use of Products in an unauthorized
manner, or (d) damage to Products not caused by Seller.
8.4. Client must promptly notify Seller of Products’ alleged
defect and provide Seller with other evidence and documentation reasonably requested by Seller. Before removing Products
from service, Client should contact a Seller-authorized support
technician by calling Belimo customer service. The contact
information for Belimo customer service is listed on the back
page of Belimo’s Product Guide and Price List (“PGPL”) or may
be found at www.belimo.com. Belimo customer service will
work with field technicians to troubleshoot problems. Many
problems can be resolved over the phone.
8.5. If a problem cannot be resolved over the phone, an RMA
number will be issued by Seller for return of the Products. Prior
to returning any Products under a warranty, Client must obtain
an RMA number from Seller, along with shipping instructions for
the return. The RMA number must be clearly written on the
outside of the box containing the returned Products. Only
Products returned to the proper location and identified with an
RMA number will be accepted by the Seller.
8.6. All returned Products should be packaged appropriately to
prevent further damage. Seller reserves the right to refuse any
returned material if improperly packaged or labeled (without an
RMA number). Products returned without proper RMA documentation will void Seller’s warranty.
8.7. Products found to be defective for which a warranty is
applicable will either be replaced or repaired at the Seller’s discretion. Seller is not responsible for charges that Client may
incur as a result of the removal or replacement of Products.
8.8. Repaired or replacement Products are shipped from Seller
via ground shipment. Other shipping methods are available at
the sole expense of the Client.
8.9. Repaired, replaced or exchanged Products will carry a warranty for a period of time equal to the greater of: (i) the remainder of the original 5-year warranty or 2-year warranty that was
applicable to the repaired, replaced or exchanged Products, or
(ii) six months, effective from the date the repaired, exchanged
or replaced Products are shipped by Seller (the “Replacement
Warranty Period”).
8.10. Advanced replacement Products for Products covered
under warranty may be obtained from Seller after the Belimo
customer service troubleshooting process has been completed.
For industrial products (such as butterfly valves), a purchase
order is required. The purchase order will be credited upon the
receipt and verification by Seller of the returned defective
Products. For non-industrial products, an invoice will be issued
and shall be due and payable if the returned Products are not
received by Seller within 60 days from the date that the replacement Products are shipped. Additional charges may apply if the
nature of the problem has been misrepresented by Client.
8.11. Both the conditional and unconditional warranties cover
the Products only, and do NOT cover labor associated with the
troubleshooting, removal or replacement of such Products.
8.12. New Products ordered in an attempt to circumvent the
warranty process may NOT be reimbursed if, upon receipt of
returned Products, it is determined that the defect in the
returned Products is actually field related, or the Products have
been returned for cosmetic reasons only.
8.13. Advanced replacement Products for butterfly valve actuators may not be new, but have been verified by the Seller for
electrical and mechanical operation. Such Products carry the
full warranty for the entire Replacement Warranty Period.
800-543-9038 USA
28
IX
IX.
N
No Warranty
W
for
f Non-HVAC
N
HVAC Application
A li i
9.1. All Seller warranties shall extend only to HVAC use of the
Products. If Products are used in non-HVAC applications (e.g.,
aircraft, industrial processes, etc.), Seller’s warranties shall not
cover such Products. Client will be solely responsible for any
damage to or malfunction of Products or for any damage resulting from such use of Products.
X.
Liability Disclaimer
10.1. These Terms constitute the entire understanding and
agreement between Seller and Client regarding the warranties
that cover Products and supersedes all previous understandings, agreements, communications and representations. Sellerr
shall not be responsible for and Client does not have any right
to make any claim for damage that occurs to any property otherr
than Products. Seller shall in no way be responsible for any
costs incurred by Client in the determination of the causes off
damage to any of Client’s property, for expert opinions, or forr
any punitive or special, incidental or consequential damages off
any kind whatsoever. Seller’s warranty is extended to the Client
only and is non-transferrable.
10.2. Seller shall not be liable for any damage resulting from orr
contributed by Client or third parties acting within the scope off
responsibility of Client or such third party when:
1. Products are used for non-HVAC applications, such as in
aircrafts, industrial processes, etc.;
2. Client uses the Products without complying with applicable
law or institutional regulations or Belimo data and installation
sheets or Client uses the Products without following good
industry practice;
3. Products are used by personnel who have not received
suitable instruction; or
4. Products are modified or repaired without the written
approval of Seller.
When requested to do so, Client shall immediately release Sellerr
in full from any possible third party claims resulting in connection with the circumstances listed above. This also applies to
claims in connection with product liability.
10.3. If Client becomes aware that any third party has made orr
appears likely to make any claim regarding Products (including,
without limitation, regarding Product defects or rights infringed
by Products), then Client shall immediately inform Seller and
afford to Seller all assistance that Seller may require to enforce
its rights and defend such claim.
XI.
Proper Law and Jurisdiction
11.1. All sales of Products under these Terms and the warranties described herein shall be governed by the laws of the State
of Connecticut, and the parties agree to submit to the exclusive
jurisdiction of the Federal and state courts located in the State
of Connecticut with respect to any dispute arising from the subject matter hereof. The parties hereby waive all rights to a jury
trial in connection with any claims relating to the subject matterr
hereof.
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
Tech.Doc - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
Belimo ZoneTight Zone Valves
Terms and Conditions of Sale and Warranty
Was this manual useful for you? yes no