FSTF24 US
On/Off, Spring Return Fail-Safe, 24 VAC
Technical Data
Power Supply
285459
24 VAC ± 20%, 24 VDC -10% + 20%
Power Consumption Running 2 W, 3 VA
Power Consumption Holding 1.5 W, 2 VA
Transformer Sizing
Shaft Diameter
Electrical Connection
Overload Protection
Electrical Protection
Angle of Rotation
Torque
5 VA (class 2 power source)
1/4” to 1/2” round, centers on 1/2”
3 ft., 18 GA appliance cable, 1/2” conduit connector electronic throughout 0° to 95° rotation actuators are double insulated
95°
18 in-lbs [2 Nm] minimum
Direction of Rotation
Position Indication can be selected by CCW/CW mounting visual indicator, 0° to 95° (0° is full spring return position)
No Manual Override
Running Time (Motor)
Running Time (Fail-Safe)
<75 seconds @ 250°F [121°C]
< 25 seconds @ 32°F to 122°F [0°C to 50°C]
Humidity 5 to 95% RH non-condensing
Ambient Temperature Range 32°F to +122°F [0°C to +50°C]
Storage Temperature Range -40°F to +176°F [-40°C to +80°C]
Housing NEMA 2, IP42, UL enclosure type 2
Housing Material
Agency Listings†
Noise Level (Motor)
Noise Level (Fail-Safe)
Servicing
UL94-5VA cULus acc. to UL60730-1A/-2-14, CAN/CSA
E60730-1:02, Listed to UL 2043 - suitable for use in air plenums per Section 300.22(C) of the
NEC and Section 602 of the IMC
<45 dB (A)
<62 dB (A) maintenance free
Quality Standard
Weight
ISO 9001
1.26 lbs. (0.57 kg.)
Part no. Clamp side spring return
FSTF120 US CW
FSTF120.1 US CW (bulk pack)
FSTF120.1 CCW CCW (bulk pack)
FSTF120-S US CW CW
FSTF120-S.1 US CW (bulk pack)
FSTF120-S.1 CCW CCW (bulk pack)
† UL File XAPX.E108966
Torque 18 in-lb, 250°F for 30 min, for fire and smoke dampers
Application
The type FSTF spring-return actuator is intended for the operation of smoke and combination fire and smoke dampers in ventilation and air-conditioning systems. The actuator will meet requirements of UL555 and UL555S when tested as an assembly with the damper. Square footage of damper operated will depend on make and model per damper manufacturer UL testing.
Operation
Mounting of the actuator to the damper axle shaft or jackshaft is via a coldweld clamp. Teeth in the clamp and V-bolt dig into the metal of both solid and hollow shafts maintaining a perfect connection. The specially designed clamp will not crush hollow shafts. The bottom end of the actuator is held by an antirotation strap or by a stud provided by the damper manufacturer. The actuator is mounted in its fail safe position with the damper blade(s) typically closed.
Upon applying power, the actuator drives the damper to the open position. The internal spring is tensioned at the same time. If the power supply is interrupted, the spring moves the damper back to its fail-safe position.
Dimensions (Inches[mm])
0.68" [16.7]
Standard:
1/4" to 1/2"
1/4" to 5/16"
0.77" [19.5]
6.28" [159.5]
0.2" [5.2]
0.43" [11]
4.5" [114]
Safety Notes
Screw a conduit fitting into the actuator’s bushing. Jacket the actuator’s input and output wiring with suitable flexible conduit. Properly terminate the conduit in a suitable junction box.
Retrofit Safety Note
Use of the FSTF for replacement of other makes of actuators is limited in damper area. The FSLF is preferred for direct coupled applications. The FSTF may be applied for linkage applications on dampers 1.5 sq.ft. and smaller at velocities under 2000 fpm.
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN
Accessories
KH-TF US Crankarm for Shafts to 1/2”
KH-TF-1 US Crankarm for Shafts with 1/4” slot
KH-TF-1.1 US Crankarm for Shafts with 1/4” slot
TF-P
TOOL-06
Anti-Rotation Bracket
8 mm and 10 mm Wrench
ZDB-TF
ZG-TF2
ZG-TF3
ZG-TF112
ZS-100
ZS-150
BAE165 US
Angle of Rotation Limiter for TF
Crankarm Adaptor Kit (includes mounting hardware)
TF mounting tubes and hardware kit
Crankarm Adaptor Kit (includes ZG-113 and KH-TF)
Weather Shield - Galvaneal
Weather Shield - Polycarbonate
165°F electric thermal sensor. SPST, NC
Typical Specification
All smoke and combination fire and smoke dampers shall be provided with Belimo FSTF, FSLF, FSNF, or FSAF actuators. All substitutions must be approved before submission of bid. Damper and actuator shall have UL 555S
Listing for 250°F &/or 350°F. Actuator shall have been tested to UL 2043 per requirements of IMC 602.2 and NEC 300.22 (c). Where position indication is required -S models with auxiliary switches or damper blade switches will be provided per code requirements.
Wiring Diagrams
Provide overload protection and disconnect as required.
45
75
Actuators may also be powered by 24 VDC.
Actuators may be powered in parallel. Power consumption must be observed.
Ground present on some models.
Meets cULus requirements without the need of an electrical ground connection.
FSTF24 US
On/Off, Spring Return Fail-Safe, 24 VAC
C (Blk)
H (Red)
3 1
1 Common
2 Hot
24 VAC/DC
Detector or relay
F&S Damper
HOT 2 1
Fusible link F&S or smoke damper
Actuator
To alarm system
Typical smoke or fusible link damper wiringi
Detector or relay F&S Damper
165°F
HOT 2 1
45
N, L2, or COM
N, L2, or COM
Manual reset
Actuator
To alarm system
Typical containment damper control wiring
1
N, L2, Com
Hot
45
Parallel Actuator Wiring
1
2
75
1
2
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN
FSTF24-S US
On/Off, Spring Return, 24 VAC, Auxiliary Switch
Technical Data
Power Supply
285460
24 VAC ± 20%, 24 VDC -10% + 20%
Power Consumption Running 2 W, 3 VA
Power Consumption Holding 1.5 W, 2 VA
Transformer Sizing
Shaft Diameter
Electrical Connection
Overload Protection
Electrical Protection
Angle of Rotation
Torque
5 VA (class 2 power source)
1/4” to 1/2” round, centers on 1/2”
(2) 3 ft, 18 GA appliance cables with 1/2” conduit connectors electronic throughout 0° to 95° rotation actuators are double insulated
95°
18 in-lbs [2 Nm] minimum
Direction of Rotation
Position Indication can be selected by CCW/CW mounting visual indicator, 0° to 95° (0° is full spring return position)
No Manual Override
Running Time (Motor)
Running Time (Fail-Safe)
<75 seconds @ 250°F [121°C]
< 25 seconds @ 32°F to 122°F [0°C to 50°C]
Humidity 5 to 95% RH non-condensing
Ambient Temperature Range 32°F to +122°F [0°C to +50°C]
Storage Temperature Range -40°F to +176°F [-40°C to +80°C]
Housing NEMA 2, IP42, UL enclosure type 2
Housing Material
Agency Listings†
Noise Level (Motor)
Noise Level (Fail-Safe)
Servicing
UL94-5VA cULus acc. to UL60730-1A/-2-14, CAN/CSA
E60730-1:02, Listed to UL 2043 - suitable for use in air plenums per Section 300.22(C) of the
NEC and Section 602 of the IMC
<45 dB (A)
<62 dB (A) maintenance free
Quality Standard
Weight
Auxiliary Switch
ISO 9001
1.5 lbs. (0.68 kg.)
2 x SPST 3A resistive (0.5A inductive) @ 120
VAC, one fixed at 10º and one fixed at 80º
Part no. Clamp side spring return
FSTF120 US CW
FSTF120.1 US CW (bulk pack)
FSTF120.1 CCW CCW (bulk pack)
FSTF120-S US CW CW
FSTF120-S.1 US CW (bulk pack)
FSTF120-S.1 CCW CCW (bulk pack)
† UL File XAPX.E108966
Torque 18 in-lb, 250°F for 30 min, for fire and smoke dampers
Application
The type FSTF spring-return actuator is intended for the operation of smoke and combination fire and smoke dampers in ventilation and air-conditioning systems. The actuator will meet requirements of UL555 and UL555S when tested as an assembly with the damper. Square footage of damper operated will depend on make and model per damper manufacturer UL testing.
Operation
Mounting of the actuator to the damper axle shaft or jackshaft is via a coldweld clamp. Teeth in the clamp and V-bolt dig into the metal of both solid and hollow shafts maintaining a perfect connection. The specially designed clamp will not crush hollow shafts. The bottom end of the actuator is held by an antirotation strap or by a stud provided by the damper manufacturer. The actuator is mounted in its fail safe position with the damper blade(s) typically closed.
Upon applying power, the actuator drives the damper to the open position. The internal spring is tensioned at the same time. If the power supply is interrupted, the spring moves the damper back to its fail-safe position.
Dimensions (Inches[mm])
0.68" [16.7]
Standard:
1/4" to 1/2"
1/4" to 5/16"
0.77" [19.5]
6.28" [159.5]
0.2" [5.2]
0.43" [11]
4.5" [114]
Safety Notes
Screw a conduit fitting into the actuator’s bushing. Jacket the actuator’s input and output wiring with suitable flexible conduit. Properly terminate the conduit in a suitable junction box.
Retrofit Safety Note
Use of the FSTF for replacement of other makes of actuators is limited in damper area. The FSLF is preferred for direct coupled applications. The FSTF may be applied for linkage applications on dampers 1.5 sq.ft. and smaller at velocities under 2000 fpm.
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN
Accessories
KH-TF US Crankarm for Shafts to 1/2”
KH-TF-1 US Crankarm for Shafts with 1/4” slot
KH-TF-1.1 US Crankarm for Shafts with 1/4” slot
TF-P
TOOL-06
Anti-Rotation Bracket
8 mm and 10 mm Wrench
ZDB-TF
ZG-TF2
ZG-TF3
ZG-TF112
ZS-100
ZS-150
BAE165 US
Angle of Rotation Limiter for TF
Crankarm Adaptor Kit (includes mounting hardware)
TF mounting tubes and hardware kit
Crankarm Adaptor Kit (includes ZG-113 and KH-TF)
Weather Shield - Galvaneal
Weather Shield - Polycarbonate
165°F electric thermal sensor. SPST, NC
Typical Specification
All smoke and combination fire and smoke dampers shall be provided with Belimo FSTF, FSLF, FSNF, or FSAF actuators. All substitutions must be approved before submission of bid. Damper and actuator shall have UL 555S
Listing for 250°F &/or 350°F. Actuator shall have been tested to UL 2043 per requirements of IMC 602.2 and NEC 300.22 (c). Where position indication is required -S models with auxiliary switches or damper blade switches will be provided per code requirements.
Wiring Diagrams
Provide overload protection and disconnect as required.
45
72
Actuators may also be powered by 24 VDC.
Actuators may be powered in parallel. Power consumption must be observed.
S4 makes to S6 when actuator is powered open.
73
74
Auxiliary switches are for end position indication or interlock control.
Double insulated.
75
Ground present on some models.
Meets cULus requirements without the need of an electrical ground connection.
FSTF24-S US
On/Off, Spring Return, 24 VAC, Auxiliary Switch
C (Blk)
H (Red)
3 1
1 Common
2 Hot
45
24 VAC/DC
Detector or relay
HOT
F&S Damper
165°F
2 1
Manual reset
Actuator
To alarm system
Typical containment damper control wiring
1
N, L2, Com
Hot
45
Parallel Actuator Wiring
Violet
Red
Orange
Auxiliary Switch
Gray
.
1
2
75
S1
S2
NC
S4
10
°
73
S6
NO
80
°
74
72
1
2
N, L2, or COM
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN
Technical Data FSTF120(-S) US
Power supply nominal 120 VAC, 60 Hz tolerance 108 to 132 VAC, 60 Hz running 2 W, 3.5 VA Power consumption holding 1.5 W, 2.5 VA max. inrush current 2.1A
Transformer sizing
Electrical connection
(-S models have 2 cables)
Overload protection
Electrical protection
Angle of rotation
Torque
Direction of rotation
Position indication
Running time
Humidity
Ambient temperature
Operating temperature
Housing
Housing material
Agency listings†
Noise level (max)
5 VA (class 2 power source)
3 ft, 18 GA appliance cable
1/2” conduit connector electronic throughout 0 to 95° rotation actuators are double insulated max 95°, adjust. with mechanical stop min. 18 in-lb [2 Nm] reversible with cw/ccw mounting visual indicator, 0° to 95°
(0° spring return position) motor < 75 sec (0 to 18 in-lb) spring < 25 sec @32°F to 122°F [0°C to 50°C]
5 to 95% RH non-condensing
32°F to 122°F [0°C to 50°C]
Up to 250°F for 1/2 hour per UL555S test
NEMA type 2 / IP42, UL enclosure type 2
UL94-5VA. UL2043 Listed for plenum use cULus acc. to UL60730-1A/-2-14, CAN/CSA
E60730-1:02, CE acc. to 2004/108/EC (and
2006/95/EC for -S versions). UL2043 smoke rated running < 50 db (A)
Servicing
Quality standard spring return 62 dB (A) holding inaudible maintenance free
ISO 9001
Weight FSTF120 US 1.26 lbs (0.57 kg)
FSTF120-S US 1.5 lbs (0.68 kg)
† Rated Impulse Voltage 4kV, Type of action 1.AA (1.AA.B for -S version), Control Pollution Degree 3.
FSTF120-S US
Auxiliary switch 2 x SPST 3A (0.5A) @ 120 VAC, UL approved
One fi xed at 10º and one fi xed at 80º
FSTF120(-S) US
On/Off, Spring Return, 120 VAC
Torque min. 18 in-lb, for control of fire and smoke dampers
Application
The type FSTF spring-return actuator is intended for the operation of smoke and combination fire and smoke dampers in ventilation and air-conditioning systems. The actuator will meet requirements of UL555 and UL555S when tested as an assembly with the damper Square footage of damper operated will depend on make and model and the temperature required.
Operation
Mounting of the actuator to the damper axle shaft or jackshaft is via a cold-weld clamp. Teeth in the clamp and V-bolt dig into the metal of both solid and hollow shafts maintaining a perfect connection. The specially designed clamp will not crush hollow shafts. The bottom end of the actuator is held by an anti-rotation strap or by a stud provided by the damper manufacturer.
The actuator is mounted in its fail safe position with the damper blade(s) typically closed. Upon applying power, the actuator drives the damper to the open position. The internal spring is tensioned at the same time. If the power supply is interrupted, the spring moves the damper back to its fail-safe position.
SAFETY NOTE
Screw a conduit fi tting into the actuator’s bushing. Jacket the actuator’s input and output wiring with suitable fl exible conduit.
Properly terminate the conduit in a suitable junction box.
Dimensions (Inches [mm])
3.30" [83.72]
2.40" [61]
6.28"
[159.5]
Standard:
1/4" to 1/2"
1/4" to 5/16"
3.0" [76.2]
0.77" [19.5]
4.5"
[114]
0.43" [11]
0.2" [5.2]
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA
1
FSTF120(-S) US
On/Off, Spring Return, 120 VAC
Accessories
Tool-06
KH-TF
ZG-TF2
8mm and 10 mm wrench
Crank arm for up to 1/2” round shaft
Crank arm adaptor kit for FSTF
ZG-TF112
ZS-100
Mounting bracket, kit for FSTF
Weather shield (metal)
ZS-150 Weather shield (polycarbonate)
NOTE: When using FSTF120 US and FSTF120-S US actuators, only use accessories listed on this page or those provided by damper manufacturers.
For actuator wiring information and diagrams, refer to Belimo Wiring Guide.
Typical Specification
On/Off fi re and smoke spring return damper actuators shall be direct coupled type which require no crank arm and linkage and be capable of direct mounting to a shaft up to a 1/2” diameter and center a 1/2” shaft. The actuators must be designed so that they may be used for either clockwise or counterclockwise fail-safe operation.
SPDT auxiliary switches shall be provided. Actuators shall be cULus listed and have a 5 year warranty, and be manufactured under ISO 9001 International Quality Control
Standards. Actuators shall be as manufactured by Belimo.
Wiring Diagrams
1
Provide overload protection and disconnect as required.
2
4
CAUTION Equipment Damage!
Actuators may be connected in parallel.
Power consumption must be observed.
Two SPST auxiliary switches for position indication. NC switch opens at
10º and NO switch closes at 80º
Meets cULus requirements without the need of an electrical ground connection.
During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualifi ed licensed electrician or other individual who has been properly trained in handling live electrical components perform these
tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury.
120 VAC
N L1
H L2
1 White Neutral
2 Black Hot
FSTF120 US
2
On/Off wiring for FSTF120 US
120 VAC
1 White Neutral
2 Black Hot
Violet
Red
10°
Orange S4
S6
Gray
80°
FSTF120-S US
On/Off wiring for FSTF120-S US
2
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA
FSTF230 US
On/Off, Spring Return Fail-Safe, 230 VAC
Technical Data
Power Supply
285458
230 VAC ± 10%, 50/60 Hz
Power Consumption Running 5 VA
Power Consumption Holding 4.5 VA
Shaft Diameter
Electrical Connection
1/4” to 1/2” round, centers on 1/2”
3 ft., 18 GA appliance cable, 1/2” conduit connector electronic throughout 0° to 95° rotation Overload Protection
Electrical Protection
Angle of Rotation
Torque
Direction of Rotation
Position Indication
Manual Override
Running Time (Motor)
Running Time (Fail-Safe)
Humidity actuators are double insulated
95°
18 in-lbs [2 Nm] minimum can be selected by CCW/CW mounting visual indicator, 0° to 95° (0° is full spring return position)
No
<75 seconds @ 250°F [121°C]
< 25 seconds @ 32°F to 122°F [0°C to 50°C]
5 to 95% RH non-condensing
Ambient Temperature Range 32°F to +122°F [0°C to +50°C]
Storage Temperature Range -40°F to +176°F [-40°C to +180°C]
Housing
Housing Material
Agency Listings†
Noise Level (Motor)
Noise Level (Fail-Safe)
Servicing
Quality Standard
Weight
NEMA 2, IP42, UL enclosure type 2
UL94-5VA cULus acc. to UL60730-1A/-2-14, CAN/CSA
E60730-1:02, Listed to UL 2043 - suitable for use in air plenums per Section 300.22(C) of the
NEC and Section 602 of the IMC
<45 dB (A)
<62 dB (A) maintenance free
ISO 9001
1.26 lbs. (0.57 kg.)
Part no. Clamp side spring return
FSTF120 US CW
FSTF120.1 US CW (bulk pack)
FSTF120.1 CCW CCW (bulk pack)
FSTF120-S US CW CW
FSTF120-S.1 US CW (bulk pack)
FSTF120-S.1 CCW CCW (bulk pack)
† UL File XAPX.E108966
Torque 18 in-lb, 250°F for 30 min, for fire and smoke dampers
Application
The type FSTF spring-return actuator is intended for the operation of smoke and combination fire and smoke dampers in ventilation and air-conditioning systems. The actuator will meet requirements of UL555 and UL555S when tested as an assembly with the damper. Square footage of damper operated will depend on make and model per damper manufacturer UL testing.
Operation
Mounting of the actuator to the damper axle shaft or jackshaft is via a coldweld clamp. Teeth in the clamp and V-bolt dig into the metal of both solid and hollow shafts maintaining a perfect connection. The specially designed clamp will not crush hollow shafts. The bottom end of the actuator is held by an antirotation strap or by a stud provided by the damper manufacturer. The actuator is mounted in its fail safe position with the damper blade(s) typically closed.
Upon applying power, the actuator drives the damper to the open position. The internal spring is tensioned at the same time. If the power supply is interrupted, the spring moves the damper back to its fail-safe position.
Dimensions (Inches[mm])
0.68" [16.7]
Standard:
1/4" to 1/2"
1/4" to 5/16"
0.77" [19.5]
6.28" [159.5]
0.2" [5.2]
0.43" [11]
4.5" [114]
Safety Notes
Screw a conduit fitting into the actuator’s bushing. Jacket the actuator’s input and output wiring with suitable flexible conduit. Properly terminate the conduit in a suitable junction box.
Retrofit Safety Note
Use of the FSTF for replacement of other makes of actuators is limited in damper area. The FSLF is preferred for direct coupled applications. The FSTF may be applied for linkage applications on dampers 1.5 sq.ft. and smaller at velocities under 2000 fpm.
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN
Accessories
KH-TF US Crankarm for Shafts to 1/2”
KH-TF-1 US Crankarm for Shafts with 1/4” slot
KH-TF-1.1 US Crankarm for Shafts with 1/4” slot
TF-P
TOOL-06
Anti-Rotation Bracket
8 mm and 10 mm Wrench
ZDB-TF
ZG-TF2
ZG-TF3
ZG-TF112
ZS-100
ZS-150
BAE165 US
Angle of Rotation Limiter for TF
Crankarm Adaptor Kit (includes mounting hardware)
TF mounting tubes and hardware kit
Crankarm Adaptor Kit (includes ZG-113 and KH-TF)
Weather Shield - Galvaneal
Weather Shield - Polycarbonate
165°F electric thermal sensor. SPST, NC
Typical Specification
All smoke and combination fire and smoke dampers shall be provided with Belimo FSTF, FSLF, FSNF, or FSAF actuators. All substitutions must be approved before submission of bid. Damper and actuator shall have UL 555S
Listing for 250°F &/or 350°F. Actuator shall have been tested to UL 2043 per requirements of IMC 602.2 and NEC 300.22 (c). Where position indication is required -S models with auxiliary switches or damper blade switches will be provided per code requirements.
Wiring Diagrams
Provide overload protection and disconnect as required.
45
75
Actuators may be powered in parallel. Power consumption must be observed.
Ground present on some models.
Meets cULus requirements without the need of an electrical ground connection.
FSTF230 US
On/Off, Spring Return Fail-Safe, 230 VAC
N (Blue)
L1 (Brown)
1
1 N, L2
2 Hot
230 VAC
Detector or relay
F&S Damper
HOT 2 1
Fusible link F&S or smoke damper
Actuator
To alarm system
Typical smoke or fusible link damper wiringi
Detector or relay F&S Damper
165°F
HOT 2 1
45
N, L2, or COM
N, L2, or COM
Manual reset
Actuator
To alarm system
Typical containment damper control wiring
1
N, L2, Com
Hot
45
Parallel Actuator Wiring
1
2
75
1
2
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN
FSTF230-S US
On/Off, Spring Return, 230 VAC, Auxiliary Switch
Technical Data
Power Supply
285456
230 VAC ± 10%, 50/60 Hz
Power Consumption Running 5 VA
Power Consumption Holding 4.5 VA
Shaft Diameter
Electrical Connection
1/4” to 1/2” round, centers on 1/2”
(2) 3 ft, 18 GA appliance cables with 1/2” conduit connectors electronic throughout 0° to 95° rotation Overload Protection
Electrical Protection
Angle of Rotation
Torque
Direction of Rotation
Position Indication
Manual Override
Running Time (Motor)
Running Time (Fail-Safe)
Humidity actuators are double insulated
95°
18 in-lbs [2 Nm] minimum can be selected by CCW/CW mounting visual indicator, 0° to 95° (0° is full spring return position)
No
<75 seconds @ 250°F [121°C]
< 25 seconds @ 32°F to 122°F [0°C to 50°C]
5 to 95% RH non-condensing
Ambient Temperature Range 32°F to +122°F [0°C to +50°C]
Storage Temperature Range -40°F to +176°F [-40°C to +80°C]
Housing
Housing Material
Agency Listings†
Noise Level (Motor)
Noise Level (Fail-Safe)
Servicing
Quality Standard
Weight
Auxiliary Switch
NEMA 2, IP42, UL enclosure type 2
UL94-5VA cULus acc. to UL60730-1A/-2-14, CAN/CSA
E60730-1:02, Listed to UL 2043 - suitable for use in air plenums per Section 300.22(C) of the
NEC and Section 602 of the IMC
<45 dB (A)
<62 dB (A) maintenance free
ISO 9001
1.5 lbs. (0.68 kg.)
2 x SPST 3A resistive (0.5A inductive) @ 120
VAC, one fixed at 10º and one fixed at 80º
Part no. Clamp side spring return
FSTF120 US CW
FSTF120.1 US CW (bulk pack)
FSTF120.1 CCW CCW (bulk pack)
FSTF120-S US CW CW
FSTF120-S.1 US CW (bulk pack)
FSTF120-S.1 CCW CCW (bulk pack)
† UL File XAPX.E108966
Torque 18 in-lb, 250°F for 30 min, for fire and smoke dampers
Application
The type FSTF spring-return actuator is intended for the operation of smoke and combination fire and smoke dampers in ventilation and air-conditioning systems. The actuator will meet requirements of UL555 and UL555S when tested as an assembly with the damper. Square footage of damper operated will depend on make and model per damper manufacturer UL testing.
Operation
Mounting of the actuator to the damper axle shaft or jackshaft is via a coldweld clamp. Teeth in the clamp and V-bolt dig into the metal of both solid and hollow shafts maintaining a perfect connection. The specially designed clamp will not crush hollow shafts. The bottom end of the actuator is held by an antirotation strap or by a stud provided by the damper manufacturer. The actuator is mounted in its fail safe position with the damper blade(s) typically closed.
Upon applying power, the actuator drives the damper to the open position. The internal spring is tensioned at the same time. If the power supply is interrupted, the spring moves the damper back to its fail-safe position.
Dimensions (Inches[mm])
0.68" [16.7]
Standard:
1/4" to 1/2"
1/4" to 5/16"
0.77" [19.5]
6.28" [159.5]
0.2" [5.2]
0.43" [11]
4.5" [114]
Safety Notes
Screw a conduit fitting into the actuator’s bushing. Jacket the actuator’s input and output wiring with suitable flexible conduit. Properly terminate the conduit in a suitable junction box.
Retrofit Safety Note
Use of the FSTF for replacement of other makes of actuators is limited in damper area. The FSLF is preferred for direct coupled applications. The FSTF may be applied for linkage applications on dampers 1.5 sq.ft. and smaller at velocities under 2000 fpm.
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN
Accessories
KH-TF US Crankarm for Shafts to 1/2”
KH-TF-1 US Crankarm for Shafts with 1/4” slot
KH-TF-1.1 US Crankarm for Shafts with 1/4” slot
TF-P
TOOL-06
Anti-Rotation Bracket
8 mm and 10 mm Wrench
ZDB-TF
ZG-TF2
ZG-TF3
ZG-TF112
ZS-100
ZS-150
BAE165 US
Angle of Rotation Limiter for TF
Crankarm Adaptor Kit (includes mounting hardware)
TF mounting tubes and hardware kit
Crankarm Adaptor Kit (includes ZG-113 and KH-TF)
Weather Shield - Galvaneal
Weather Shield - Polycarbonate
165°F electric thermal sensor. SPST, NC
Typical Specification
All smoke and combination fire and smoke dampers shall be provided with Belimo FSTF, FSLF, FSNF, or FSAF actuators. All substitutions must be approved before submission of bid. Damper and actuator shall have UL 555S
Listing for 250°F &/or 350°F. Actuator shall have been tested to UL 2043 per requirements of IMC 602.2 and NEC 300.22 (c). Where position indication is required -S models with auxiliary switches or damper blade switches will be provided per code requirements.
Wiring Diagrams
Provide overload protection and disconnect as required.
45
72
Actuators may be powered in parallel. Power consumption must be observed.
S4 makes to S6 when actuator is powered open.
73
Auxiliary switches are for end position indication or interlock control.
74
Double insulated.
75
Ground present on some models.
Meets cULus requirements without the need of an electrical ground connection.
FSTF230-S US
On/Off, Spring Return, 230 VAC, Auxiliary Switch
N (Blue)
L1 (Brown)
1
1 N, L2
2 Hot
45
230 VAC
Detector or relay
HOT
F&S Damper
165°F
2 1
Manual reset
Actuator
To alarm system
Typical containment damper control wiring
1
N, L2, Com
Hot
45
Parallel Actuator Wiring
Violet
Red
Orange
Auxiliary Switch
Gray
.
1
2
75
S1
S2
NC
S4
10
°
73
S6
NO
80
°
74
72
1
2
N, L2, or COM
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN