Swegon GOLD RX/PX/CX/SD Operation And Maintenance Instructions

Add to my manuals
80 Pages

advertisement

Swegon GOLD RX/PX/CX/SD Operation And Maintenance Instructions | Manualzz

Operation and Maintenance Instructions

GOLD RX/PX/CX/SD, GENERATION D

Applicable to program version 5.13 and newer versions

GOLD RX

GOLD PX

GB.GOLDSKD2.100615

GOLD CX

We reserve the right to alter specifi cations without notice.

www.swegon.com 1

GB.GOLDSKD2.100615

Contents

1 GENERAL ...........................................3

1.1 Field of Application ..................................3

1.2 Mechanical Design ...................................3

1.3 Control System ........................................3

1.4 Environmental Documentation .................3

1.5 Type of heat exchanger ............................3

1.6 The Components of the

Air Handling Units ..........................................4

1.6.1 GOLD RX One-piece air handling unit with rotary heat exchanger ..........................4

1.6.2 GOLD PX One-piece air handling unit with plate heat exchanger ...........................5

2 SAFETY PRECAUTIONS .....................7

2.1 Safety Isolating Switch/Main Switch ..........7

2.2 Risks ........................................................7

2.3 Safety Guards ..........................................7

2.4 Glycol ......................................................7

3 COMMISSIONING .............................8

3.1 General ....................................................8

3.2 Adjusting the Duct System and Air Devices ..............................................9

3.2.1 Adjustment Sequence .........................9

3.2.2 Adjustment Procedure ........................9

3.3 To Adjust the Pressure Balance ................10

3.3.1 General ............................................10

3.3.2 To Ensure the Correct

Leakage Direction ......................................11

4 HAND-HELD MICRO TERMINAL

AND HOW TO USE THE MENUS ........12

4.1 HAND-HELD MICRO TERMINAL ..............12

4.1.1 General ............................................12

4.1.2 Buttons ............................................12

4.3.1 Display Screen ..................................12

4.1.4 Abbreviations ...................................12

4.2 Menu Tree ..............................................13

5 MAIN MENU ....................................14

5.1 General ..................................................14

5.2 Selection of Language ............................14

5.3 Changing Operating Mode ....................14

5.4 Settings .................................................14

6 USER LEVEL .....................................15

6.1 Temperature...........................................15

6.1.1 Readings ..........................................15

6.1.2 Settings ............................................15

6.2 Air fl ow/Pressure ....................................16

6.2.1 Readings ..........................................16

6.2.2 Settings ............................................16

6.3 Switch clock ...........................................17

6.4 Filters .....................................................17

6.4.1 Readings ..........................................17

6.4.2 Calibration - Filters............................17

6.4.3 Calibration - Rotary Heat Exchanger ..17

6.5 Air Adjustment .......................................18

6.6 Alarms ...................................................18

7 INSTALLATION LEVEL .....................19

7.1 Menu Survey ..........................................19

8 FUNCTIONS .....................................20

8.1 Temperature...........................................20

8.2 Temperature Regulation .........................20

8.2.1.1 ERS Regulation ..............................21

8.2.1.2 Supply Air Regulation ....................22

8.2.1.3 Extract Air Regulation ....................22

8.2.1.4 Xzone temperature control ...........22

8.2.2 Outdoor Temperature Compensation 23

8.2.3 Summer Night Cooling .....................24

8.2.4 Intermittent Night-time Heating ........25

8.2.5 Morning BOOST ...............................26

8.2.6 Setpoint Temperature Displacement ..26

8.2.7 Extra Regulation Sequence................27

8.2.8 External Temperature Sensors ...........27

8.3 Flow/Pressure .........................................28

8.3.1 Fan Regulation .................................28

8.3.1.1 Flow Regulation .............................28

8.3.1.2 Pressure Regulation .......................28

8.3.1.3 Demand Control ............................28

8.3.1.4 Slave Control .................................28

8.3.2 Outdoor Temperature

Compensation ...........................................29

8.3.3 Boosting ...........................................29

8.3.4 Downspeed Control of Fan Speed to

Min. Set Point, Airfl ow/pressure .................30

8.3.5 To adjust the fl ow of the slave fan .....30

8.4 To Activate the GOLD SD

Filter Monitoring Function ............................30

8.5 Operation ..............................................31

8.5.1 Switch clock .....................................31

8.5.2 Extended Operation ..........................31

8.5.3 Summer time/Winter time ................31

8.6 Heating ..................................................32

8.6.1 Heat exchanger ................................32

8.6.1.1 Defrosting the rotary heat exchanger..........................................32

8.6.1.2 Exhaust air regulation, rotary heat exchanger ................................32

8.5.2 Reheating .........................................33

8.5.3 Heating BOOST ................................33

8.6.4 Preheat .............................................33

8.7 Cooling ..................................................34

8.7.1 Operation .........................................34

8.7.2 Cooling Regulation ..........................34

8.7.3 Periodic Operation ............................36

8.7.4 Regulation Speed .............................36

8.7.5 Outdoor Temperature Limit ...............36

8.7.6 Restart Time .....................................36

8.7.7 Cooling Min Air Flow ........................36

8.7.8 Neutral Zone ....................................36

8.7.9 Cooling BOOST ................................36

8.8 Humidity ................................................37

8.9 ReCO

2

...................................................38

8.10 IQnomic Plus ........................................38

8.10.1 External supervision .......................38

8.11 All Year Comfort ..................................39

8.12 CONTROL Optimize ..............................40

9 AUTOMATIC FUNCTIONS ...............41

9.1 General ..................................................41

9.1.1 Starting Sequence ............................41

9.1.2 Cooling Recovery ..............................41

9.1.3 Zero Point Calibration .......................41

9.1.4 Anti-frost Monitoring Function –

Air Heater for Hot Water ............................41

9.1.5 Additional cooling –

Electric Air Heater ......................................41

9.1.6 Reduction in output, electric air heater .......................................41

9.1.7 Additional running -

Heat Exchanger .........................................41

9.1.8 Density-corrected Airfl ow .................41

9.1.9 Purging Operation ............................41

9.1.10 Carry-over Control ..........................41

9.1.11 Calculaton of the effi ciency of the rotary heat exchanger ................................41

9.1.12 Pump control for the coil heat exchanger .................................................41

9.1.13 Anti-frosting protection for the plate/coil heat exchanger ...........................42

10 READINGS .....................................42

11 MANUAL TEST ..............................42

12 ALARM SETTINGS .........................43

12.1 Fire Alarms ...........................................43

12.2 External Alarms ....................................43

12.3 Alarm Limits .........................................43

12.4 Alarm Priority .......................................44

12.5 Alarm outputs ......................................44

13 HAND-HELD TERMINAL ...............45

13.1 Language .............................................45

13.2 Air fl ow unit .........................................45

13.3 Min/Max Adjustment ...........................45

13.4 Base Settings ........................................45

14 COMMUNICATION ........................46

14.1 EIA-232 ...............................................46

14.2 EIA-485 ...............................................46

14.3 Ethernet ...............................................46

15 SERVICE LEVEL ..............................46

16 MAINTENANCE .............................47

16.1 Filter Change .......................................47

16.1.1 To remove the Filters .......................47

16.1.2 To fi t new fi lters ..............................47

16.2 Cleaning and Inspection .......................47

16.2.1 General ..........................................47

16.2.2 Filter Space .....................................47

16.2.3 Heat exchangers .............................47

16.2.4 Fans and Fan Space ........................47

16.3 Performance Checks ............................47

16.4 To change the pump, pipework package,

GOLD CX, sizes 35-80 ..................................48

17 ALARMS AND FAULT TRACING ....48

17.1 General ................................................48

17.1.1 A and B-alarms ...............................48

17.1.2 Resetting of alarms .........................48

17.1.3 Changing Alarm Settings ................48

17.1.4 Start up after a power failure ..........48

17.2 Alarm Descriptions with

Factory Settings ...........................................49

18 INFORMATIVE MESSAGES ...........58

19 TECHNICAL DATA .........................59

19.1 Dimensions, GOLD RX one-piece unit with rotary heat exchanger...........................59

19.2 Dimensions, GOLD PX one-piece unit with plate heat exchanger ............................61

19.3 Dimensions, GOLD CX once-piece unit with coil heat exchangers .............................62

19.5 Terminal Connections, Sizes 04-80 .......63

19.6 Electrical data .......................................64

19.6.1 Air handling unit.............................64

19.6.2 Fans ...............................................64

19.6.3 Electrical Equipment Cubicle ...........64

19.6.4 Motor, rotary heat exchanger ..........64

19.6.5 Control Accuracy ............................64

20 APPENDICES ..................................65

20.1 Compliancy Declaration .......................65

20.2 Commissioning Record .........................66

2 www.swegon.com

We reserve the right to alter specifi cations without notice.

GB.GOLDSKD2.100615

1 GENERAL

1.1 Field of Application

The GOLD units are designed for use in comfort ventilation applications. Depending on the variant selected, GOLD units can be utilised in buildings such as offi ce buildings, schools, day nurseries, public buildings, shops, residential buildings, etc.

GOLD units equipped with plate/coil heat exchanger (PX/CX) and separate GOLD supply air and extract air handling units (SD) can also be used for the ventilation of moderately humid buildings; however not where the humidity is continuously high, such as in indoor swimming baths.

The separate GOLD supply air and extract air handling units (SD) are designed for applications in which the supply air and extract air fl ows need to be completely separated from one another or where, due to limited available space, separate units for supply air and extract air are needed. They can also be used individually if only one of the variants is needed.

In order to fully obtain all the benefi ts the GOLD system has to offer, it is important to take the special characteristics of the air handling units into account when planning them into the project, installing, adjusting and operating them.

The air handling unit in its basic version should be installed indoors. The TBTA/TBTB accessory should be used if the air handling units are installed outdoors. If the duct accessories are installed outdoors, they must be housed in an insulated casing

(type TCxx).

Important!

Always read the safety precautions in Section 2 about what generally applies concerning risks involved and who is qualifi ed to carry out the work, and carefully follow the installation instructions that are given in each section.

The product identifi cation plates are located on the inspection side of the air handling unit and on a wall inside the fan section.

Refer to the particulars on the product identifi cation plate when you contact Swegon.

The coil heat exchangers in the one-piece units (CX) are supplied complete from the factory; including mounted the pipework package with all the necessary components. The system is normally fi lled with liquid, vented, adjusted and performance-tested prior to delivery, but can be ordered in unfi lled condition e.g. for housing improvement projects or if a liquid mixture other than

30 % ethylene glycol is required. The pipework package is available loose as an accessory for separate, size 14-80 supply air and extract air handling units (SD)

The supply air and extract air fans are of GOLD Wing+ type, an axi-centrifugal fan with backward-curved blades. The fans are direct-driven and have a motor control system for variable speed control.

1.3 Control System

The control system is microprocessor-based and is integrated into the unit. It controls and regulates the fans, heat exchanger, temperatures, airfl ows, operating times and a large number of internal and external functions as well as alarms.

1.4 Environmental Documentation

Environmental documentation with the Dismantling instructions for recycling and the Environmental Declaration are included as appendices in these instructions.

The air handling unit is designed for simple to dismantling into its natural parts. When the unit has reached the end of its useful product life, engage an approved recycling company for scrapping.

Approximately 94% of the total weight of the GOLD is can be recycled.

Swegon AB is associated with the REPA Register, no.

5560778465.

Get in touch with Swegon AB, phone: +46 (0)512-322 00, if you have any questions regarding the dismantling instructions or the air handling unit’s impact on the environment.

1.2 Mechanical Design

The GOLD is available in 8 physical sizes and for 14 airfl ow ranges.

Its sheet steel exterior is painted in a beige colour. NCS-

2005Y30R. Its door handles and the upper part of the junction hood are painted light grey. NCS 53502-B. Its interior material is mainly galvanized sheet steel with 50 mm thick intervening insulation.

The size 12-30 GOLD units with plate heat exchanger (PX) or rotary heat exchanger (RX) with air intake from above and the separate size 04-08 supply air and extract air units (SD) as well as the GOLD RX Top are equipped with pleated, class F7 fi lters. The units in other variants/sizes have class F7 supply air and extract air fi lters made of glass fi bre.

The type RECOnomic rotary heat exchanger is variable speed controlled and has a temperature effi ciency of up to 85%.

The plate heat exchangers are as standard equipped with by-pass and shut-off damper for variable and automatic control of the heat exchanger’s effi ciency on heat recovery.

1.5 Type of heat exchanger

The GOLD one-piece air handling units are supplied with either rotary heat exchanger (RX), plate heat exchanger (PX) or coil heat exchanger (CX). Coil heat exchangers are optional for the separate supply air and extract air handling units (SD).

Sections, functions, etc. that deal with one specifi c type of heat exchanger are preceded by an appropriate symbol. The three symbols used are as follows:

Rotary heat exchanger (RX)

Plate heat exchanger (PX)

Coil heat exchanger (CX)

We reserve the right to alter specifi cations without notice.

www.swegon.com 3

GB.GOLDSKD2.100615

1.6 The Components of the Air Handling Units

1.6.1 GOLD RX One-piece air handling unit with rotary heat exchanger

The specifi c components are outlined below each individually in a simplifi ed and schematic specifi cation.

7

3 4 5 6

2

8

9

11

1

Right-hand version

Fig. 1a

13 14 15 16 17 18 19 20 21 22

10

12

Outdoor air Supply air Extract air Exhaust air

GOLD 04-80: The air handling units can be ordered in the right-hand version as shown in Fig. 1a or in the left-hand version as shown in Fig. 1b.

GOLD 12-80: The air handling unit in Fig 1a shows Fan

Arrangement 1. The units can also be ordered with Fan

Arrangement 2; the fans and fi lters are then vertically mirror-inverted.

In the left-hand version (Fig. 1b), the components marked with an asterisk change function and designation (the components are named according to whether they are for supply air or extract air).

The location of the components and their designation

1 OUTDOOR AIR* (Left-hand version: Extract air)

2 EXHAUST AIR* (Left-hand version: Supply air)

3 Extract air fan* with motor and motor control system

4 Pressure transducer by extract air fan*

(Position on function selector switch = 1)

5 Pressure transducer by supply air fi lter*

(Position on function selector switch = 3)

Fig 1b

Left-hand version

6 Electrical equipm. cubicle with control unit

7 Hand-held micro terminal

8 Extract air fi lter*

9 Adjustment plates (For left-hand version: by left-hand fi lter section)

10 Supply air temp. sensor (to be mounted in supply air duct)

11 EXTRACT AIR* (Left-hand version: Outdoor air)

12 SUPPLY AIR* (Left-hand version: Exhaust air)

13 Supply air fi lter*

14 Outdoor temperature sensor*

15 Heat exchanger

16 Heat exchanger drive motor

17 Sensor for rotation monitor

18 Control unit for the heat exchanger

19 Pressure transducer by supply air fan*

(Position on function selector switch = 2)

20 Pressure transducer by extract air fi lter*

(Position on function selector switch = 4)

21 Extract air temperature sensor*

22 Supply air fan* with motor and motor control system

4 www.swegon.com

We reserve the right to alter specifi cations without notice.

GB.GOLDSKD2.100615

1.6.2 GOLD PX One-piece air handling unit with plate heat exchanger

The specifi c components are outlined below each individually in a simplifi ed and schematic specifi cation.

8

3 4 5 6 7 9 10

2

21

1

12

11

13

Right-hand version

Fig. 2a

14 15 16 17 23 22 18 19 20

Outdoor air Supply air Extract air Exhaust air

Fig 2b

Left-hand version

The air handling units are supplied in the right-hand or left-hand version as shown in Fig. 2a and 2b. In the lefthand version, the components marked with an asterisk change function and designation (the components are named according to whether they are for supply air or extract air.).

The location of the components and their designation

1 EXHAUST AIR* (Left-hand version: Supply air)

2 OUTDOOR AIR* (Left-hand version: Extract air)

3 Pressure transducer by supply air fi lter*

(Position on function selector switch = 3)

4 Supply air fi lter*

5 Outdoor temperature sensor*

6 Electrical equipm. cubicle with control unit

7 Shut-off and by-pass valve actuator

8 Hand-held micro terminal

9 Temperature/relative humidity sensor in extract air*

We reserve the right to alter specifi cations without notice.

10 Extract air fi lter*

11 Supply air temp. sensor (to be mounted in supply air duct)

12 EXTRACT AIR* (Left-hand version: Outdoor air)

13 SUPPLY AIR* (Left-hand version: Exhaust air)

14 Extract air fan* with motor and motor control system

15 Pressure transducer by extract air fan*

(Position on function selector switch = 1)

16 Sensor for anti-frosting protection

17 Plate heat exchanger with by-pass and shut-off damper

18 Pressure transducer by supply air fan*

(Position on function selector switch = 2)

19 Pressure transducer by extract air fi lter*

(Position on function selector switch = 4)

20 Supply air fan* with motor and motor control system

21. Measurement tappings for measuring the pressure drop across the heat exchanger.

22. Temperature/density sensor, supply air.

23. Temperature/density sensor, extract air.

www.swegon.com 5

GB.GOLDSKD2.100615

1.6.3 GOLD CX One-piece air handling unit with coil heat exchangers

The specifi c components are outlined below each individually in a simplifi ed and schematic specifi cation.

7

5 3 4 25 6

2

23

8

1

13

10

12

Right-hand version

Fan Arrangement 1

Fig. 3a

14 15 16 17 18 19 24 20 21 22

11

Outdoor air Supply air Extract air Exhaust air

The air handling units can be ordered in the right-hand version as shown in Fig. 3a or in the left-hand version as shown in Fig. 3b.

The air handling unit in Fig. 3a shows Fan Arrangement

1. The units can also be ordered with Fan Arrangement 2; the fans and fi lters are then vertically mirror-inverted.

In the left-hand version (Fig. 3b), the components marked with an asterisk change function and designation (the components are named according to whether they are for supply air or extract air).

The location of the components and their designation

1 OUTDOOR AIR* (Left-hand version: Extract air)

2 EXHAUST AIR* (Left-hand version: Supply air)

3 Extract air fan* with motor and motor control system

4 Pressure transducer by extract air fan*

(Position on function selector switch = 1)

5 Pressure transducer by supply air fi lter*

(Position on function selector switch = 3)

6 Electrical equipm. cubicle with control unit

7 Hand-held micro terminal

8 Extract air fi lter*

10 Supply air temp. sensor (to be mounted in supply air duct)

Fig 3b

Left-hand version

Fan Arrangement 1

11 EXTRACT AIR* (Left-hand version: Outdoor air)

12 SUPPLY AIR* (Left-hand version: Exhaust air)

13 Supply air fi lter*

14 Outdoor temperature sensor*

15 Coil heat exchanger with pipework package

16 Valve actuator

17 Temperature sensor for anti-frosting protection

18 Circulation pump

19 Pressure transducer by supply air fan*

(Position on function selector switch = 2)

20 Pressure transducer by extract air fi lter*

(Position on function selector switch = 4)

21 Supply air fan* with motor and motor control system

22 Temperature/relative humidity sensor in extract air*

23. Measurement tappings for measuring the pressure drop across the heat exchanger.

24. Temperature/density sensor, supply air.

25. Temperature/density sensor, extract air.

6 www.swegon.com

We reserve the right to alter specifi cations without notice.

GB.GOLDSKD2.100615

2 SAFETY PRECAUTIONS

All staff concerned shall acquaint themselves with these instructions before beginning any work on the unit.

Any damages to the unit or its components caused by improper handling or misuse by the purchaser or the fi tter cannot be considered subject to guarantee if these instructions have not been followed correctly.

Warning

Only an authorised electrician or qualifi ed service personnel trained by Swegon shall be permitted to modify the air handling unit in conjunction with electrical installations or the wiring of external functions.

2.1 Safety Isolating Switch/Main Switch

Size 04/05, 08, 12, 14/20 and 25/30 one-piece GOLD units with rotary (RX), plate (PX) or coil (CX) heat exchanger: The safety isolating switch is located externally on the junction hood.

Size 35/40, 50/60 and 70/80 one-piece GOLD units with rotary heat exchanger (RX): The safety isolating switch is externally located on the door of the centre section of the unit.

Size 35/40 one-piece GOLD units with coil heat exchanger

(CX): The safety isolating switch is located on the left side of the electric equipment cubicle in the centre section of the unit. Size 50/60 and 70/80 air handling units:

The safety isolating switch is located in a plastic enclosure below the electrical equipment cubicle in the centre section of the unit.

Separate supply air and extract air handling units (SD): The safety isolating switch is located on the inspection side by the inspection door of the fan section.

The air handling unit shall normally be started and stopped via the hand-held micro terminal, not via the safety isolating switch.

Always switch off the safety isolating switch before servicing the unit if not otherwise specifi ed in the pertinent instructions.

We reserve the right to alter specifi cations without notice.

2.2 Risks

Warning

Before carrying out any work, make sure that the power supply to the unit has been isolated.

Risk areas with rotating parts

Moving parts are the fan impeller, drive pulleys of the rotary heat exchanger, if fi tted, and by-pass/shut-off damper of the plate heat exchanger, if fi tted.

The lockable inspection doors serve as protection from contact with the fans and the heat exchanger. If the fan outlets aren’t connected to any duct, they must be fi tted with a protective screen (wire mesh).

Warning

The inspection doors on the fi lter/fan sections must not be opened while the unit is in operation.

Under normal operating conditions, use the stop button on the hand-held terminal to stop the air handling unit.

Wait until the fans have stopped rotating before opening the inspection door.

The air pressure inside the fi lter/fan section is positive, which means that the door can fl y open.

2.3 Safety Guards

The cover of the electric equipment cubicle serves as a safety guard in the size 04/05 and 08 one-piece air handling units with rotary heat exchanger (RX), as well as on all the other variants (PX/CX/SD). On size 12, 14/20,

25/30, 35/40, 50/60 and 70/80 one-piece air handling units with rotary heat exchanger (RX), the lockable door over the electrical equipment cubicle serves as a safety guard.

Only a qualifi ed electrician or trained service technicians shall be allowed to remove the safety guards.

Warning

The power supply to the unit shall be isolated by switching off the safety isolating switch before removing the safety guard.

As long as the air handling unit is operating, the safety guards must always be mounted, all inspection doors must be closed, and the junction hood on the top of the unit must be mounted.

2.4 Glycol

Glycol is used in the GOLD air handling units with coil heat exchanger. Never pour glycol down a drain; collect it in a receptacle and leave it at a recycling centre, petrol station, or the like. Glycol is highly dangerous to consume and can cause fatal poisoning or damage the kidneys. Contact a doctor! Avoid breathing glycol vapour in confi ned spaces. If you get glycol in your eyes, fl ush them thoroughly with water (for about 5 minutes). If glycol splashes on your skin, wash with soap and water.

www.swegon.com 7

GB.GOLDSKD2.100615

3 COMMISSIONING

3.1 General

Sequence for commissioning:

1. Check that there are no foreign objects in unit, ducting system or functional sections.

2. Check that rotating heat exchangers (only GOLD RX) rotate easily. On sizes 50-80, the rotating heat exchanger must be angled slightly towards the fi lter, see diagram below.

If the angle needs adjusting, see special instructions for angle adjustment, rotating heat exchangers.

L

≈ 0,5xL

≈ 0,5xL

L

GOLD RX,, sizes 50-80: The illustration shows the factorypreset rotor inclination in a unit with Fan Arrangement 1.

The inclination must always be towards the fi lter, which means that the inclination for Fan Arrangement 2 is in the other direction.

3. Turn the safety isolating switch to the ON position (I).

4. Select the language desired, if you have not already done so. See Section 5.2 or 13.1.

5. The unit has factory settings which make it ready to use. See Section 19.2 Commissioning record.

However, in many cases, these settings need to be adjusted to suit the current installation.

Program the switch clock, operating conditions, temperatures, airfl ows and functions according to the procedures in Sections 4-15.

Select whether l/s, m3/s or m3/h shall be used as the fl ow unit.

(INSTALLATION LEVEL in the HAND-HELD MICRO TERMI-

NAL menu).

Fill out the Commissioning Record and save it in the document pocket of the unit.

In some cases it might be necessary to adjust the P-band and C-factor if the heating regulation system is oscillating or operates sluggishly. This can be done at service level and requires that you enter a special code. Get in touch with your Swegon representative.

Factory preset values (all types of GOLD):

P-band = 5.00

C-factor = 0.70 (supply air regulation)

0.20 (extract air regulation)

Normal values for the various types of air handling unit:

GOLD RX: P-band = 5.00-10.00

GOLD PX:

GOLD CX:

P-band = 10.00-20.00

P-band = 10.00-20.00

GOLD SD with coil heat exch.: P-band = 10.00-20.00

GOLD SD without coil heat exch.: P-band = 15.00-30.00

The C-Factor can in most cases be unchanged.

6. Activate, if needed, manual or auto operation (MAIN

MENU) or lock the speed of the fans (AIR ADJUSTMENT menu).

Adjust the ducting system and air devices as described in

Section 3.2.

7. Check and adjust, if required, the pressure balance in the unit as described in Section 3.3.

8. Finish off with a fi lter calibration as described in Section

6.4.2.

8 www.swegon.com

We reserve the right to alter specifi cations without notice.

GB.GOLDSKD2.100615

3.2 Adjusting the Duct System and Air Devices

In order to prevent the fans from consuming more power than necessary, it is important to keep the pressure drop in the system as low as possible.

It is also important that ducting systems and air devices are correctly adjusted to provide the comfort expected.

When adjusting air devices and the duct system installed in combination with the GOLD, it is appropriate to follow the proportionality method.

This means that the proportion between the airfl ows in branch ducts stays constant even if the airfl ow in the main ducts is changed. The same proportion applies to the air devices in the installation.

When adjusting the ducting system there is provision for locking the speed of the fans in the unit to a specifi c preset fl ow rate, see Section 6.5.

3.2.1 Adjustment Sequence

The system should be adjusted in the following order:

1. Adjust of the air devices in each branch duct.

2. Adjust the branch ducts.

3. Adjust the main ducts.

3.2.2 Adjustment Procedure

1. Set all the air devices and dampers to the fully open position.

2. Calculate the ratio of the airfl ow reading to the design airfl ow of all the air devices, branch ducts and main ducts.

The air device in every branch that has the lowest ratio should be fully open. Use this air device as an INDEX AIR

DEVICE. The same applies to branch dampers and main dampers.

When you’ve completed the adjustments, one air device in every branch, one branch damper and one main damper should consequently be fully open.

3. Start adjusting the main duct that has the highest ratio and the branch duct in the main duct that has the highest ratio. Starting from this point enables you to “press” the air in front of you toward the sections of the system that have the least air.

4. Adjust the last air device on the duct branch so that it will have the same ratio as the index device. This air device will serve as the REFERENCE AIR DEVICE. Often it is the last air device on the branch that has the lowest ratio and should be open. In this case, the same air device serves as the index device and reference device.

5. Throttle the other air devices in the branch to the same ratio as the reference device.

Note! The ratio in the reference device will change every time another air device is throttled, so in practice the ratio for the reference device can be set slightly higher. The reference device must be measured in between each air device throttled.

6. Go to the branch that had the next highest ratio and adjust the air devices there, etc.

Note! All branch dampers should be fully open until all air devices have been adjusted.

7. Throttle the branch damper that had the highest ratio to the same ratio that the branch of the lowest ratio had.

Note! Keep in mind that the index damper changes ratio; proceed as described in item 5.

8. When all branches have been adjusted, throttle the main dampers in the same manner.

Also see the example below on how to carry out adjustments.

Example on how to carry out adjustments

– Start adjusting duct branch B, since this one has the highest ratio.

– The last air device, B3, has the lowest ratio and should be fully open.

Adjust the other air devices, B1 and B2, so that these will have the same ratio as air device B3 (see item 5 above).

– Now adjust the air devices in branch duct C. Air device C4 should be fully open; throttle the others to the same ratio.

– Adjust the air devices in branch duct A. The index air device here is air device A3, which means that you fi rst throttle air device A4 (the reference device) to device A3:s ratio.

Thereafter the others are adjusted to the same ratio as air device A4.

– Throttle branch damper B to the same ratio as branch damper A, throttle branch damper C to the same ratio as branch damper A.

Check that all dampers have the same ratio.

When the adjustment has been completed, 3 air devices and one branch damper should stand fully open to obtain the lowest possible pressure in the system.

We reserve the right to alter specifi cations without notice.

q p

= design airfl ow (l/s) q m

= airfl ow reading (l/s)

K (Ratio) = q m q p www.swegon.com 9

GB.GOLDSKD2.100615

3.3 To Adjust the Pressure Balance

(applicable to air handling units with rotary heat exchanger)

3.3.1 General

The pressure in the extract airfl ow path should be slightly lower than that in the supply airfl ow path to ensure correct air leakage direction and that the purging sector in the heat exchanger will work correctly. This ensures that extract air will not be carried over to the supply air.

The pressure balance in the unit should be adjusted when the ventilation system has been fully installed, all the air devices have been adjusted and the supply air and extract air fl ows are as they should be while the air handling unit is operating normally.

Adjustment plates

GOLD RX 04-12

1-2 plates

CLOSE OPEN

GOLD RX 14-80

1-5 plates

CLOSE

(Push in one or several adjustment plates)

GOLD RX Top 04-12

1 plate, left-hand

version

EXTRACT AIR

OPEN (Take out adjustment plates)

GOLD RX Top 04-12

1 plate, right-hand

version

EXTRACT AIR

10 www.swegon.com

Mounting screw(s)

Flow adjustment plate

Mounting screw(s)

Flow adjustment plate

Two fl ow adjustment plates are supplied with the GOLD RX Top.

The version of the air handling unit, i.e. right-hand or left-hand, is the factor that determines which of the fl ow adjustment plates you should install in the unit. Install the correct fl ow adjustment plate at its intended location inside the air handling unit. Scrap the other plate. See the illustration above.

Remove the mounting screw(s) and place the airfl ow adjustment plates in the grooves provided for accommodating them.

Refi t the mounting screw(s) and tighten it/them. See illustration above.

The pressure balance can be adjusted by blanking off holes in the fl ow adjustment plate with the plugs supplied with the unit.

We reserve the right to alter specifi cations without notice.

GB.GOLDSKD2.100615

3.3.2 To Ensure the Correct Leakage Direction

The adjustment plates fi tted in the extract air inlet are used for adjusting the pressure balance in the unit. The adjustment plates are supplied separately and should be fi tted in the unit by the fi tter when he connects the extract air ducting to the air handling unit. See the illustrations on the previous page.

Connect a pressure gauge to the pressure measurement tappings of the unit.

The unit has four pressure measurement tappings; the two closest to the extract air duct should be used. The blue pressure measurement tapping measures the negative pressure in the extract air section and the white pressure measurement tapping measures the negative pressure in the supply air section.

On the size 04-08 units, the pressure measurement tappings are by the junction hood and on the size 12-80 units they are inside in the centre section of the unit.

See illustration to the right.

Note that both pressure measurement tappings measure negative pressure.

MEASURED VALUES

The negative pressure in the extract air section should be greater or the same as the one in the supply air section.

If the negative pressure in the extract air section is the same or up to 20 Pa more than the negative pressure in the supply air section, then you’ve fi nished this adjustment.

DEVIATIONS

If the negative pressure in the extract air section is less than that in the supply air section, the adjustment plates must be readjusted as follows:

1. Stop the unit, open the inspection door to the extract air fi lter.

GOLD RX Top: blank off a number of holes in the fl ow adjustment plate with the plastic plugs supplied with the unit.

Other models: slightly push the fl ow adjustment plates forward (close them) in the extract air intake opening.

For full face connection (duct accessory in insulated

casing): If the commissioning plate(s) is/are completely closed and the sub-atmospheric pressure in the extract air section is still less than in the supply air section, blank off a number of holes in the commissioning plate with the plastic plugs supplied.

3. Close the inspection door and restart the unit.

4. Measure the pressures.

Repeat until the negative pressure in the extract air section is the same or up to 20 Pa higher than the negative pressure in the supply air section (0–20 Pa).

Pressure measurement nipples - leakage direction

(Unit in right-hand version)

GOLD 04-08

GOLD 12-80

- (blue)

+ (white)

EXTRACT AIR

– (blue)

+ (white)

EXTRACT

AIR

5. If the negative pressure in the extract air section is higher than 20 Pa compared to the supply air section, although the adjustment plates are completely open, the leakage and purging air fl ow will be more than anticipated. This means that the actual extract air fl ow will deviate from the preset extract airfl ow. The deviation increases with increased pressure differential.

We reserve the right to alter specifi cations without notice.

www.swegon.com 11

GB.GOLDSKD2.100615

4 HAND-HELD MICRO TERMINAL

AND HOW TO USE THE MENUS

4.1 HAND-HELD MICRO TERMINAL

4.1.1 General

The hand-held micro terminal consists of an encapsulated control box with a 3-metre long cable for connection to the air handling unit by means of a quick connector.

The hand-held terminal has an illuminated display, 6 pushbuttons and a red LED for indicating alarms.

4.1.2 Buttons

The buttons have the following functions:

ENTER confi rms your selection and proceeds to next menu level.

ESCAPE reverts to the previous menu.

ADVANCE UPWARD or to the LEFT.

ADVANCE DOWNWARD or to the RIGHT.

DECREASES the value of the highlighted setting.

INCREASES the value of the highlighted setting.

4.3.1 Display Screen

The display screen has 4 lines. Many of the menus however have several lines and these are shown line for line as you press the ADVANCE DOWNWARD button. The position indicator shows where you are in the menu.

GOLD TUE 14:40

STOP

MANUAL OPERATION

STOP?

GOLD TUE 14:40

STOP

MANUAL OPERATION

STOP?

MAN/AUTO.OP

SETTINGS

Position indicator

4.1.4 Abbreviations

The following abbreviations are used in the menus

SA = Supply air (E.g. SA FAN = Supply air fan)

EA = Extract air

OUTD = Outdoor air

FV = Anti-frosting monitor

HEAT EXCH = Heat exchanger

12 www.swegon.com

We reserve the right to alter specifi cations without notice.

4.2 Menu Tree

MAIN

MENU

(Section 5)

GOLD RX TUE 14:40

STOP

MANUAL OPERATION

STOP?

GOLD RX TUE 14:40

MANUAL OPERATION

STOP?

MAN/AUTO.OP

GOLD RX TUE 14:40

STOP?

MAN/AUTO.OP

SETTINGS

USER LEVEL

(Section 6)

AUTO OPERATION

MANUAL LOW SPEED

MANUAL HIGH SPEED

TEMPERATURE

ALL YEAR COMFORT

Xzone

FLOW/PRESSURE

SWITCH CLOCK

FILTERS

AIR ADJUSTMENT

ALARMS

GB.GOLDSKD2.100615

Important! The appearance of the menus varies depending on the type of air handling unit and functions selected.

*TEMPERATURE*

READINGS

SETTINGS

*ALL YEAR COMFORT*

READINGS

SETTINGS

*Xzone*

READINGS

SETTINGS

*FLOW/PRESSURE*

READINGS

SETTINGS

*SWITCH CLOCK*

TIME/DATE

TIME CHANNEL

YEAR CHANNEL

*FILTERS*

READINGS

CALIBRATION

*AIR ADJUSTMENT*

LOCKS FAN SPEED

TIME SETTING: 0 h

*ALARMS*

ACTIVE ALARMS

ALARM HISTORY

INSTALLATION LEVEL

(Section 7-15)

We reserve the right to alter specifi cations without notice.

INSTALLATION www.swegon.com 13

GB.GOLDSKD2.100615

5 MAIN MENU

5.1 General

The main menu is normally shown if no other menu has been selected.

The display automatically returns to the main menu after 30 minutes.

The content in the menu changes depending on the operating mode selected other functions that affect the present operating mode and possible tripped alarms.

5.2 Selection of Language

When the air handling unit is started up for the fi rst time, a language selection menu is displayed.

Select the language desired.

If you want to change language at a later opportunity – or if you’ve selected the wrong language

– you can change the language at INSTALLATION

LEVEL under HAND TERMINAL. See Section 13.1.

5.3 Changing Operating Mode

You can start and stop the air handling unit or change over to manual or automatic operation from the main menu.

The air handling unit should normally be started and stopped from the hand-held micro terminal; not by switching the safety isolating switch on and off.

When the air handling unit is started up, menus for the various delays that are part of the starting sequence are shown.

See also Section 9.1.1, Starting Sequence.

5.4 Settings

When selecting SETTINGS in the main menu, you will advance to User Level and Installation Level.

See Section 6.

GOLD RX TUE 14:40

STOP

MANUAL OPERATION

STOP?

GOLD RX TUE 14:40

MANUAL OPERATION

STOP?

MAN/AUTO.OP

GOLD RX TUE 14:40

STOP?

MAN/AUTO.OP

SETTINGS

USER LEVEL

INSTALLATION LEVEL

AUTO OPERATION

MANUAL LOW SPEED

MANUAL HIGH SPEED

14 www.swegon.com

We reserve the right to alter specifi cations without notice.

GB.GOLDSKD2.100615

6 USER LEVEL

6.1 Temperature

The basic functions can be preset at INSTALLATION

LEVEL and the values can be read and set at USER

LEVEL.

See also Section 8.2 in which the functions for temperature are described in detail.

IMPORTANT! If you intend to substantially alter the temperature settings, you should fi rst stop the air handling unit before doing so.

If only GOLD SD supply air handling units are installed, they require an external room sensor for ERS and extract air control.

6.1.1 Readings

Used for checking the performance.

6.1.2 Settings

ERS REGULATION 1

The control unit regulates the relationship between the supply air and the extract air temperatures according to a factory preset curve.

Settings (see the chart to the right as well):

Value Setting Factory

Step

EA/SA Differential

Breakpoint (refers to extract air temperature)

1 - 4

1-5 °C*

15-23 °C*

2

3 °C

22 °C

ERS REGULATION 2

The control unit regulates the relationship between the supply air and extract air temperatures according to a custom-plotted curve. The curve has three adjustable breakpoints.

Settings (see the chart to the right as well):

Value Setting Factory

Extract air temperature

X1

X2

X3

Supply air temperature

Y1

Y2

Y3

SUPPLY AIR REG.

Settings:

Value

10-40 °C

10-40 °C

10-40 °C

10-40 °C

10-40 °C

10-40 °C

Setting

15 °C

20 °C

22 °C

20 °C

18 °C

14 °C

Factory

Supply air temperature setpoint

EXTRACT AIR REG.

Settings:

Value

15-40 °C* 21.5 °C

Setting Factory

Extract air/room temp.

Setpoint

Min. supply air temperature

15-40 °C*

13-25 °C*

21.5 °C

15 °C

Max. supply air temperature 18-45 °C* 28 °C

*) The setting range can be changed. See 13.3, Min/Max Adjustment.

We reserve the right to alter specifi cations without notice.

TEMPERATURE

*TEMPERATURE*

READINGS

SETTINGS

*TEMPERATURE*

READINGS

SETTINGS

ERS REGULATION 1

ERS REGULATION 2

SUPPLY AIR REG.

EXTRACT AIR REG.

ERS Regulation 1

20

15

10

12

Step 3 ferential

EA/SA dif

Step 4

15 20

Extract air temperature °C

25

ERS Regulation 2

22

1

20

15

Important! The appearance of the menus varies depending on the type of air handling unit and functions selected.

Breakpoint

2

3

Ste p 1

Step 2

10

9

12 15 20

X = Extract air temperature °C

25 27 www.swegon.com 15

GB.GOLDSKD2.100615

6.2 Air fl ow/Pressure

Basic functions are set at INSTALLATION LEVEL and values are read and set at USER LEVEL.

Therefore see also Section 8.3, in which the functions for fl ow/pressure are described in detail.

AIR FLOW/PRESSURE

*FLOW/PRESSURE*

READINGS

SETTINGS

SIZE

GOLD 04

GOLD 05

GOLD 08

GOLD 12

GOLD 14

GOLD 20

GOLD 25

GOLD 30

GOLD 35

GOLD 40

GOLD 50

GOLD 60

GOLD 70

GOLD 80

6.2.1 Readings

Used for performance checks.

6.2.2 Settings

The functions selected at INSTALLATION LEVEL and the min. and max. airfl ows of each unit size (see the table below) determine which values can be set.

Values for airfl ow (l/s, m3/s, m3/h), pressure (Pa) or input signal strength (%) can be preset depending on the function selected.

LOW SPEED

Must always be preset! The value for low fan speed cannot be higher than the value for high speed. Low speed can be set to 0, which means that the fan is standing still.

HIGH SPEED

Must always be preset! The value or pressure for high fan speed cannot be lower than the value for low fan speed.

MAX SPEED

Max speed is only appropriate for functions such as pressure regulation, fl ow boost, Heating BOOST or Cooling

BOOST. The value for max fan speed cannot be lower than the value for high fan speed.

MIN/MAX SPEED

Min/max fan speed is only appropriate for demand-controlled operation. The lowest and highest permissible fl ows are preset for each of the fans. This means that the fans will not operate outside these limits, regardless the load.

Min./Max. fl ows

AIRFLOW MIN. FLOW FOR

AIRFLOW REG. ALL

VARIANTS***

1800

1800

2700

2700

3600

3600

5400

5400

MAX FLOW

ONE-PIECE UNIT

ROTARY HEAT

EXCH. (RX) m

3

/h * m

3

/s m

3

/h

288

288

720

720

1080

1080

0.08

0.08

0.20

0.20

0.30

0.30

1620

2340

3600

5040

5940

7560

0.50

0.50

0.75

0.75

1.00

1.00

1.50

1.50

9000

11520

14040

18000

18000

23400

27000

34200

2.50

3.20

3.90

5.00

5.00

6.50

7.50

9.50

m

3

/s

0.45

0.65

1.00

1.40

1.65

2.10

MAX FLOW

ONE-PIECE UNIT

PLATE HEAT EXCH.

(PX) m

3

/h

1800

2520

3600

5040

5940

7560

9000

11520

2.50

3.20

m

3

/s

0.5

0.7

1.00

1.40

1.65

2.10

*FLOW/PRESSURE*

READINGS

SETTINGS

LOW SPEED

HIGH SPEED

MAX. SPEED

MIN/MAX. SPEED

* When entering settings, round off the values to the nearest adjustable step.

** Air handling unit incl. coil heat exchanger may give rise to a lower max. fl ow.

*** If pressure regulation is used, the airfl ow can be regulated to zero, however this presupposes a certain static duct pressure drop

(approx. 50 Pa).

MAX FLOW

ONE-PIECE UNIT

COIL HEAT EXCH.

(CX) m

3

/h

14040

18000

18000

23400

27000

34200

3.90

5.00

5.00

6.50

7.50

9.50

SMALLEST

STEP m

3

/s m

3

/h m

3

/s

25

25

25

25

25

25

0.01

0.01

0.01

0.01

0.01

0.01

25

25

100

100

100

100

100

100

0.01

0.01

0.05

0.05

0.05

0.05

0.05

0.05

16 www.swegon.com

We reserve the right to alter specifi cations without notice.

GB.GOLDSKD2.100615

6.3 Switch clock

Basic functions for the switch clock can be preset at INSTALLATION LEVEL under FUNCTIONS/OPERA-

TION and the values can be read and set at USER

LEVEL.

TIME/DATE

The current date and time can be set and adjusted whenever required.

The switch clock automatically takes leap years into consideration.

Automatic changeover between summer time/winter time to EU

Standard has been preset.

This changeover function can be blocked at INSTALLATION LEVEL under FUNCTIONS/OPERATION.

TIME CHANNEL

Times and days can be set when the unit is to run at high speed, low speed or be stopped.

Eight different time channels can be set. If the same in-operation times are to apply every day of the week (Mon-Sun), you need only program one time channel. Different operation times for each day of the week can be programmed by programming a time channel for each day (Mon-Fri, Sat-Sun or Mon, Tues, Wed, etc)

The time can be set as 00:00-00:00 if the deviating in-operation period is desirable for the entire 24 hours period.

YEAR CHANNEL

The year channels make it possible to set deviating in-service times for parts of the day during certain parts of the year. Eight different year channels (yearly time schedules) can be set. The year channels over-modulate the time channel during the hours of the day and the days that the year channel is active. The year channel dates indicate the dates between which the year channel shall apply and the year channel hours indicate the hours of the day between which the year channel will steer the controller to operate the rotary heat exchanger at a specifi ed speed. Other times within the year channel still apply to that time channel.

The time can be set as 00:00-00:00 if the deviating in-operation period is desirable for the entire 24 hours period.

Functions for summer night cooling, prolonged operation, etc., operate also when the year channel is active.

SWITCH CLOCK

*SWITCH CLOCK*

TIME/DATE

TIME CHANNEL

YEAR CHANNEL

Settings:

TIME/DATE

Day

Time

Date

TIME CHANNEL 1-8

Operation

Time

Period

range setting

Mon-Sun

00:00-23:59

Day/Month/Year

Automatic

Current

Current

Low speed/High speed* High speed

00:00-23:59 00:00-00:00

Not active Not active

Mon, Tues, Wed etc

Mon-Fri

Mon-Sun

Sat-Sun

YEAR CHANNEL 1-8

Operation Not active

Stop/Low sp./High sp.

Not active

Period From Day/Month/Year

To Day/Month/Year

01/01/2005

01/01/2005

*) Shows Stop/Low speed/High speed if this function is selected at INSTALLATION LEVEL under FUNCTIONS/OPERATION.

FILTERS

*FILTERS*

READINGS

CALIBRATION

*FILTERS*

READINGS

CALIBRATION

*FILTER CALIBRATION*

STD.FILTER

PREFILTER

HEAT EXCHANGER

6.4 Filters

(and anti-frosting function of rotary heat exchanger)

6.4.1 Readings

When reading of fi lter status the fi rst value shows current pressure and the second value shows current alarm limit.

6.4.2 Calibration - Filters

The fi lters should be calibrated for the fi rst time in conjunction with commissioning, when the duct system, air devices and eventual adjustment plates have been fi tted and adjusted; after that every time the fi lter media are changed.

Calibration should be activated for both the supply air and the extract air if both fi lters are changed or for only for one airfl ow direction if only one fi lter has been changed.

When fi lter calibration is enabled, the air handling unit operates in the high speed or max. speed mode (depending on the functionality selected) for approx. 3 minutes.

We reserve the right to alter specifi cations without notice.

After the fi lters have been calibrated, a pressure rise of up to 100

Pa is permissible (=as the fi lters arrest impurities). Higher pressure will cause the fouled fi lter alarm to trip.

The alarm limit can be changed at INSTALLATION LEVEL under

ALARM SETTINGS.

The fi lter function must be activated in order to make it possible to obtain fi lter calibration and alarm functions in GOLD SD supply air and extract air handling units, see Section 8.4, Filters.

6.4.3 Calibration - Rotary Heat Exchanger

If the anti-frosting function accessory for heat exchanger is installed (see 8.5.1.1) calibration can be selected from this menu.

When calibration R-HX is activated the fans are accelerated to high speed for about 3 minutes. www.swegon.com 17

6.5 Air Adjustment

The speed of the fans can be locked for up to 72 hours.

This is practical when making air adjustments in the duct system and air devices.

The period desired is preset but can be interrupted earlier by selecting STOP in the menu or by changing the time setting to 0.

AIR ADJUSTMENT

*AIR ADJUSTMENT*

LOCKS FAN SPEED.

TIME SETTING: 0 h

6.6 Alarms

If an alarm is initiated, this is shown in the hand-held terminal both as clear text and by a blinking red diode.

This menu enables you to read alarms quickly.

ACTIVE ALARMS

Shows alarms that are active but have not initiated an alarm signal in the display. This applies to alarms that have a long delay, i.e. airfl ow or temperature alarms.

ALARM HISTORY

The 10 most recent tripped alarms are shown.

ALARMS

*ALARMS*

ACTIVE ALARMS

ALARM HISTORY

Alarm settings can be entered at INSTALLATION

LEVEL under ALARM SETTINGS.

For complete description of alarms, see Section 17.

GB.GOLDSKD2.100615

18 www.swegon.com

We reserve the right to alter specifi cations without notice.

7.1 Menu Survey

INSTALLATION

*INSTALLATION*

CODE: 0000

Code = 1111

FUNCTIONS

READINGS

MANUAL TEST

ALARM SET

HAND TERMINAL

COMMUNICATION

SERVICE LEV.

Section 9

Automatic functions

We reserve the right to alter specifi cations without notice.

GB.GOLDSKD2.100615

Important! The appearance of the menus varies depending on the type of air handling unit and functions selected.

*FUNCTIONS*

TEMPERATURE

AIR FLOW/PRESSURE

FILTER

OPERATION

HEATING

COOLING

HUMIDITY

ReCO

2

IQnomic Plus

ALL YEAR COMFORT

CONTROL Optimize

*READINGS*

TEMPERATURE

FANS

HEAT EXCHANGE

REGULATION SIGNALS

IN/OUTPUTS

HUMIDITY

ReCO

2

IQnomic Plus

ALL YEAR COMFORT

OPERATION TIME

PROGRAMVERSIONS

*MANUAL TEST*

TEMPERATURE

FANS

HEAT EXCHANGE

REHEAT

EXTRA REG.SEQ.

COOLING

IN/OUTPUTS

ReCO

2

IQnomic Plus

ALL YEAR COMFORT

*ALARM SETTINGS*

FIRE ALARM

EXTERNAL ALARMS

ALARM LIMITS

ALARM PRIORITY

*HANDTERMINAL SET*

LANGUAGE

AIR FLOW UNIT

MIN/MAX SETTING

BASE SETTINGS

*COMMUNICATION*

EIA-232

EIA-485

ETHERNET

*SERVICE LEV.*

CODE: 0000

Section 8

Section 10

Section 11

Section 12

Section 13

Section 14

Section 15

www.swegon.com 19

GB.GOLDSKD2.100615

8 FUNCTIONS

8.1 Temperature

Basic functions can be set at INSTALLATION LEVEL and values are read and set at USER LEVEL.

IMPORTANT! If you intend to substantially alter the tem-

perature settings, you should fi rst stop the air handling unit before doing so.

If only GOLD SD supply air handling units are installed, they require an external room sensor for ERS and extract air control.

8.2 Temperature Regulation

Select ERS Regulation, Supply air regulation or Extract air regulation.

If ERS Regulation is selected, select between 1 and 2.

Control sequence for ERS regulation and Supply air regulation:

1. The temperature effi ciency of the air handling unit’s

heat exchanger is modulated to provide max. heat

recovery. (Not applicable to GOLD SD without heat

exchanger).

2. After that the air heater, if installed, will begin to

INSTALLATION

FUNCTIONS

*FUNCTIONS*

TEMPERATURE

AIR FLOW/PRESSURE

FILTER

OPERATION

HEATING

COOLING

HUMIDITY

ReCO

2

IQnomic Plus

ALL YEAR COMFORT

CONTROL Optimize

* TEMPERATURE *

TEMPERATURE REG

TEMP.REG. Xzone

OUTDOOR TEMP COMP

SUMMER NIGHT COOL

INTERM. NIGHT HEAT

MORNING BOOST

SETPOINT TEMP DISPL

EXTRA REG. SEQUENCE

EXT. SENSORS

Important! The appearance of the menus varies depending on the type of air handling unit and functions selected.

3. If a downstream heating coil is not installed, or if the

its output is not adequate, the supply air fan will be

automatically and variably downspeed-regulated to

convey air at a lower fl ow rate. (If the unit is a GOLD

SD without heat exchanger, this function can be deacti

vated).

A neutral zone can be preset, which allows a lower supply air temperature setpoint before regulation to a lower fl ow rate begins. See 8.3.4

When the supply airfl ow is regulated to a lower rate, the heat exchanger will have ”excess heat”, i.e. warm extract air, giving it capacity to maintain the supply air temperature required.

As the supply airfl ow is regulated to a lower rate, the air pressure in the premises will become negative and this will instead cause outdoor air to be sucked in through leakage spots such as doors and windows. This outdoor air will then be heated by the ordinary heating system of the premises. (Not applicable if only a GOLD SD supply air or extract air handling units are installed)

Downspeed regulation to lower the airfl ow rate occurs from the current preset fl ow (high speed or low speed), down to half of this fl ow rate. The degree of regulation to a lower rate is also limited by the min fl ow setting of the unit. When preset fl ow for low speed is near the min fl ow rate, the effect of this regulation to a lower rate will be small.

Control sequence for Extract air regulation:

1. The temperature effi ciency of the air handling unit’s heat exchanger is modulated to provide max. heat recovery. (Not applicable to GOLD SD without heat

exchanger).

2. After that, the re-heating coil, if installed, will begin to generate heat.

20 www.swegon.com

We reserve the right to alter specifi cations without notice.

GB.GOLDSKD2.100615

8.2.1.1 ERS Regulation

ERS regulation means Extract air temperature-Related

Supply air temperature regulation. This means that the temperature of the supply air is regulated in relation to the temperature of the extract air. Under normal circumstances, the supply air temperature is regulated to be a few degrees lower than the extract air temperature. In this way, the heat exchanger will provide optimal performance, and this means excellent operating economy. ERS regulation is suitable for use when there is excess heat in the premises generated, for example, by machinery, lighting or people and the supply air devices in the premises are suitable diffusing air below room temperature.

ERS REGULATION 1

The control unit regulates the relationship between the supply air and extract air temperatures according to a factory-preset curve.

See the chart to the right.

The steps, breakpoint and EA/SA differential plotted in the curve can be changed at USER LEVEL under TEMPERA-

TURE/SETTINGS.

Settings:

Value

range

Step

Breakpoint

(refers to extract air temp.)

Setting setting

1 – 4

15-23 °C

Factory

2

22 °C

EA/SA-Differential 1-5 °C

The setting range for the breakpoint and EA/SA differential is limited by the Min. and Max. settings at INSTALLA-

TION LEVEL under HAND TERMINAL.

ERS REGULATION 2

This is used when special needs and conditions are such that the factory preset ERS regulation 1 curve cannot provide the results required. Conditional on which settings are made, it may be necessary to install a post-heating coil.

An individually adapted curve regulates the relationship between the supply air and extract air temperature.

See the chart to the right.

The following settings are possible at USER LEVEL under

TEMPERATURE/SETTINGS:

Value Setting Factory

ERS regulation 1

20

15

10

12

EA-/SA dif

15 ferential

Breakpoint

20

Extract air temperature °C

15 20

X = Extract air temperature °C

Ste p 1

Step 2

Step 3

Step 4

25

Factory setting means:

If the extract air temperature is below 22 °C (breakpoint), the supply air temperature setpoint will be automatically regulated to be 3 °C (EA/SA differential) lower.

If the extract air temperature is above 22 °C, the supply air temperature setpoint will be constantly 19 °C (step 2).

ERS regulation 2

22

20

15

10

9

12

1

2

3

25 27

Extract air temperature

Supply air temperature setpoint

X1 10-38 °C 15 °C

X2 11-39 °C 20 °C

X3 12-40 °C 22 °C

Y1 10-40 °C 20 °C

Y2 10-40 °C 18 °C

Y3 10-40 °C 14 °C

The setpoint displacement and summer night cooling functions can also affect the preset temperatures.

Breakpoints according to factory setting means:

If the extract air temperature is below 15 °C (X1) the setpoint for supply air temperature is constant 20 °C (Y1).

If the extract air temperature is 20 °C (X2) the supply air temperature set point will be 18 °C (Y2).

If the extract air temperature is above 22 °C (X3), the supply air temperature setpoint will be constantly 14 °C

(Y3).

We reserve the right to alter specifi cations without notice.

www.swegon.com 21

GB.GOLDSKD2.100615

8.2.1.2 Supply Air Regulation

Supply air regulation involves keeping a constant supply air temperature without consideration to the load in the premises.

This type of regulation can be used when the load and temperatures of the premises are predictable. In most cases a reheating coil needs to be installed; possibly a cooling coil as well.

The following settings can be entered at USER LEVEL under TEMPERATURE/SETTINGS:

Value Setting Factory

Supply air temperature setpoint 15-40 °C 21.5 °C

Setting range for the setpoint is limited by Min. and Max. settings at INSTALLATION LEVEL under HAND TERMINAL.

8.2.1.3 Extract Air Regulation

Extract air regulation involves keeping a constant temperature in the extract air duct (premises), by regulating the supply air temperature. This provides a uniform temperature in the premises regardless of the load and this type of regulation requires the installation of a reheating coil; possibly a cooling coil as well.

The extract air temperature is measured by the temperature sensor inside the GOLD unit. If this internal temperature sensor does not give adequate representative extract air temperature readings, an external room temperature sensor can be installed and wired to terminals 40-41 on the control unit.

The following settings can be entered at USER LEVEL under TEMPERATURE/SETTINGS:

Value Setting Factory

Extract air-/room temp. setpoint 15-40 °C

Min. Supply air temperature 13-18 °C

Max. Supply air temperature 25-45 °C

21.5 °C

15 °C

28 °C

INSTALLATION

FUNCTIONS

*FUNCTIONS*

TEMPERATURE

AIR FLOW/PRESSURE

FILTER

OPERATION

HEATING

COOLING

HUMIDITY

ReCO

2

IQnomic Plus

ALL YEAR COMFORT

CONTROL Optimize

* TEMPERATURE *

TEMPERATURE REG

TEMP.REG. Xzone

OUTDOOR TEMP COMP

SUMMER NIGHT COOL

INTERM. NIGHT HEAT

MORNING BOOST

SETPOINT TEMP DISPL

EXTRA REG. SEQUENCE

EXT. SENSORS

Setting range for the various values is limited by Min. and

Max. settings at INSTALLATION LEVEL under HAND TERMI-

NAL.

8.2.1.4 Xzone temperature control

Requires the TBLZ-2-50 zone control box. See separate instructions.

The Xzone temperature control function is designed for controlling one extra temperature zone via the ventilation system.

Xzone can be used for all types of GOLD air handling unit, and both postheating and cooling can be controlled in the extra zone.

You can activate the function; select the type of coil connected and set the required neutral zone under IQNOMIC

PLUS/Xzone.

When one of the XZONE HEATING or XZONE COOLING functions is activated, a new menu image is displayed in the hand-held micro terminal: TEMP.REG.Xzone, under

INSTALLATION – FUNCTIONS - TEMPERATURE”. The extra zone has the same settings as the ordinary menu of the air handling unit for setting the temperature regulation modes, see 8.2 Temperature regulation.

A new menu group: XZONE, is displayed between TEM-

PERATURE and FLOW/PRESSURE under SETTINGS at the user level. The selected temperature control function setpoint settings required for the extra zone can be set there.

See also the guide to the Xzone functions for more detailed information.

22 www.swegon.com

We reserve the right to alter specifi cations without notice.

GB.GOLDSKD2.100615

8.2.2 Outdoor Temperature Compensation

Temperature

Outdoor temperature compensation can be activated if the premises are abnormally subjected to the effects of seasonal cold air or hot air due to leakage through large windows, for instance.

The supply air temperature setpoint is compensated if the air handling unit is operating in the supply air regulation mode, and the extract air temperature setpoint is compensated if the air handling unit is operating in the extract air regulation mode. This function will have no effect if the unit is operating in the ERS regulation mode.

The preset temperature setpoint is infl uenced if the outdoor temperature drops below the preset X2 breakpoint

(winter compensation) and above the preset X3 breakpoint (summer compensation).

The settings are also applicable to one extra temperature zone (Xzone), if required.

See the chart to the right.

It is possible to set negative summer compensation.

Settings:

Value Setting Factory

Winter compensation

Temperature displacement Y1 +0 – +10 °C +3 °C

Breakpoint X1

Breakpoint X2

-30 – -10 °C -20 °C

-10 – +15 °C +10 °C

Summer compensation

Breakpoint X3

Breakpoint X4

+15 – +25 °C +25 °C

+25 – +40 °C +40 °C

Temperature displacement Y2 -10 – +10 °C +2 °C

INSTALLATION

FUNCTIONS

*FUNCTIONS*

TEMPERATURE

AIR FLOW/PRESSURE

FILTER

OPERATION

HEATING

COOLING

HUMIDITY

ReCO

2

IQnomic Plus

ALL YEAR COMFORT

CONTROL Optimize

Outdoor temperature compensation

* TEMPERATURE *

TEMPERATURE REG

TEMP.REG. Xzone

OUTDOOR TEMP COMP

SUMMER NIGHT COOL

INTERM. NIGHT HEAT

MORNING BOOST

SETPOINT TEMP DISPL

EXTRA REG. SEQUENCE

EXT. SENSORS

Y1

X1

X2 X3

X4

Y2

We reserve the right to alter specifi cations without notice.

X = Outdoor temperature °C

Winter compensation in accordance with factory setting involves:

Outdoor temperature +10 °C (Breakpoint X2): Compensation starts and gradually takes place between 0–3 °C down to outdoor temperature -20 °C.

Outdoor temperature -20 °C (Breakpoint X1): Constant compensation takes place with 3 °C (temperature displacement Y1).

Summer compensation in accordance with factory setting involves:

Outdoor temperature +25 °C (Breakpoint X3): Compensation starts and gradually takes place between 0–2 °C up to outdoor temperature +40 °C.

Outdoor temperature +40 °C (Breakpoint X4): Constant compensation takes place with 2 °C (temperature displacement Y2).

www.swegon.com 23

GB.GOLDSKD2.100615

8.2.3 Summer Night Cooling

The lower temperature at night is utilized to cool down the building structure. This reduces the cooling load during the fi rst hours of the day. If a cooling unit is installed, its in-operation hours will be minimized, thus offering savings. If no cooling unit is installed, a certain cooling effect will still be realized.

When summer night cooling function is activated, the unit fans operate at high speed, with a supply air setpoint of

10°C, from the preset time until the conditions necessary for stop are satisfi ed.

The extra temperature zone (Xzone), if any, will obtain the same supply air set point if summer night cooling is in operation.

Conditions to be met to start summer night cooling at the preset time:

• The extract air temperature should be higher than the preset value

• The extract air should be at least 2°C warmer than the outdoor air.

• The outdoor temperature should be above the preset value.

• Heating has not been required between 12.00–23.00 hours.

• The unit must not operate in the high speed mode or be stopped from an external source or manually from the hand-held micro terminal.

Conditions to be met to stop summer night cooling at the preset time:

• The extract air temperature drops below the preset value.

• The outdoor temperature drops below the preset value.

• Switch clock or external input calls for high speed.

• The extract air is less than 1 °C warmer than the outdoor air.

INSTALLATION

FUNCTIONS

*FUNCTIONS*

TEMPERATURE

AIR FLOW/PRESSURE

FILTER

OPERATION

HEATING

COOLING

HUMIDITY

ReCO

2

IQnomic Plus

ALL YEAR COMFORT

CONTROL Optimize

* TEMPERATURE *

TEMPERATURE REG

TEMP.REG. Xzone

OUTDOOR TEMP COMP

SUMMER NIGHT COOL

INTERM. NIGHT HEAT

MORNING BOOST

SETPOINT TEMP DISPL

EXTRA REG. SEQUENCE

EXT. SENSORS

The function starts once per set time period.

Settings:

Value Setting Factory

Extract air temperature for start 17 - 27 °C

Extract air temperature for stop 12 - 22 °C

Outdoor temperature for stop -5 - 15 °C

Supply air setpoint 0 - 20 °C

Operating period

22 °C

16 °C

10 °C

10 °C

00:00-00:00 23:00-06:00

24 www.swegon.com

We reserve the right to alter specifi cations without notice.

GB.GOLDSKD2.100615

8.2.4 Intermittent Night-time Heating

The unit is utilized to heat the premises when it is normally stopped by the switch clock.

The function requires that an external room sensor is connected (control unit terminals 40-41) and that a reheating coil be installed downstream of the air handling unit. The function works best if the GOLD is equipped with an air recirculation section and shut-off dampers for the outdoor air and the exhaust air.

When the function is activated, the air handling unit detects when the room temperature drops below the preset start temperature. The unit starts with preset fl ows and the supply air temperature setpoint.

If extract air fan operation is not desirable, the extract airfl ow can be set to 0.

The damper output can be set to 0. This means that the connected dampers (such as shut-off dampers for outdoor air and extract air) will not be affected. These dampers are normally closed when the air handling unit is stopped and they also remain closed. The damper in the air recirculation section is opened at the same time, if one is installed.

Intermittent nighttime heating does not affect a possible extra temperature zone (Xzone) that regulates according to its ordinary set point, if intermittent nighttime heating is in operation.

Conditions to be met for intermittent night-time heating to start:

• The unit should operate in a time channel/switch clock stop.

• The room temperature should be below set start temperature.

Conditions to be met for intermittent night-time heating to stop:

• High speed or external/manual stop should be activated.

• Room temperature should be above the preset stop temperature.

• Alarm with preset stop priority has tripped.

If the needed, the air handling unit fans will continue to operate to cool the electric air heater although other conditions for stop have been met.)

Settings:

Value Setting Factory

INSTALLATION

FUNCTIONS

*FUNCTIONS*

TEMPERATURE

AIR FLOW/PRESSURE

FILTER

OPERATION

HEATING

COOLING

HUMIDITY

ReCO

2

IQnomic Plus

ALL YEAR COMFORT

CONTROL Optimize

* TEMPERATURE *

TEMPERATURE REG

TEMP.REG. Xzone

OUTDOOR TEMP COMP

SUMMER NIGHT COOL

INTERM. NIGHT HEAT

MORNING BOOST

SETPOINT TEMP DISPL

EXTRA REG. SEQUENCE

EXT. SENSORS

EXTRACT AIR

SUPPLY AIR

Intermittent night-time heating with air recirculation section:

If the extract airfl ow is set to 0 and the damper output is not activated, the following takes place:

When conditions for start are met, outdoor air and exhaust air shut-off dampers remain closed. The damper in the air recirculation section is opened. The extract air fan is idle.

The supply air fan operates according to the preset supply airfl ow and the heating coil downstream of the air handling unit operates according to the supply air temperature setpoint, until the conditions for stop are met.

Room temperature for start 5 - 25 °C 16 °C

Room temperature for stop 5 - 25 °C 18 °C

Supply air temperature setpoint 10 - 40 °C 28 °C

*) The setting range is the same as the min/max settings of the

Supply airfl ow *) m3/s/Pa **) m3/s/Pa air handling unit.

Extract airfl ow *) m3/s/Pa 0 m3/s/Pa

**) According to the setting for low speed at USER LEVEL under

Damper output

FLOW/PRESSURE.

1=

*** If IQnomic Plus is selected, extra control sequence and inter-

Control output***

0=not activated 0

0=IQnomic 0 mittent nighttime heating can be used at the same time.

1 =IQnomic Plus

We reserve the right to alter specifi cations without notice.

www.swegon.com 25

GB.GOLDSKD2.100615

8.2.5 Morning BOOST

The unit is utilised to heat the premises during a preset period prior to the switch-in time set on the switch clock.

The function is used if the air recirculation section is installed.

The unit starts early and uses the same operation and temperature regulation settings as it would at the regular start time.

If the extract air fan is not required to operate, the extract airfl ow can be set to 0.

Damper output can be set to be inactive. This means that connected dampers (e.g. outdoor air and exhaust air shutoff dampers) are not affected. Normally these dampers are closed when the unit is stopped and thus they remain closed. At the same time damper in the air recirculation section opens, if one is installed.

Settings:

Value Setting Factory

Time for start prior to regular start time according to switch clock

00:00

Damper output

Extract air fan

Control output***

Inactive

Inactive

Inactive

Inactive

0=IQnomic 0 hour, min.

Max. fl ow, supply air

Max. fl ow, extract air

*

*

**

**

*) The adjusting range is the same as the unit’s min./max. setting.

**) According to the setting for max. speed at the USER LEVEL under FLOW/PRESSURE.

*** If IQnomic Plus is selected, extra control sequence and

Morning BOOST can be used at the same time.

8.2.6 Setpoint Temperature Displacement

Used for changing the supply air and extract air temperature setpoints by means of an external 0-10 VDC signal

(control unit terminals 34-35). The temperature can be increased or decreased at certain times of the day by means of an external switch clock or potentiometer, for instance.

The setpoint can be infl uenced ±5 °C.

If the unit is operating in the supply air regulation mode, the supply air temperature is displaced and if the unit is operating in the extract air regulation mode, the extract air temperature is displaced.

When the unit is operating in the ERS regulation 1 mode, the difference between extract air and supply air is infl uenced. The difference cannot be less than 0 °C. The difference will decrease as the input signal increases.

If the unit is operating in the ERS regulation 2 mode, the supply air setpoint will be offset.

When the function is activated, the setpoint is offset as illustrated in the chart to the right.

Set point displacement does not affect a possible extra temperature zone (Xzone) that regulates according to its ordinary set point, if set point displacement is in operation.

26 www.swegon.com

INSTALLATION

FUNCTIONS

*FUNCTIONS*

TEMPERATURE

AIR FLOW/PRESSURE

FILTER

OPERATION

HEATING

COOLING

HUMIDITY

ReCO

2

IQnomic Plus

ALL YEAR COMFORT

CONTROL Optimize

* TEMPERATURE *

TEMPERATURE REG

TEMP.REG. Xzone

OUTDOOR TEMP COMP

SUMMER NIGHT COOL

INTERM. NIGHT HEAT

MORNING BOOST

SETPOINT TEMP DISPL

EXTRA REG. SEQUENCE

EXT. SENSORS

INSTALLATION

FUNCTIONS

*FUNCTIONS*

TEMPERATURE

AIR FLOW/PRESSURE

FILTER

OPERATION

HEATING

COOLING

HUMIDITY

ReCO

2

IQnomic Plus

ALL YEAR COMFORT

CONTROL Optimize

* TEMPERATURE *

TEMPERATURE REG

TEMP.REG. Xzone

OUTDOOR TEMP COMP

SUMMER NIGHT COOL

INTERM. NIGHT HEAT

MORNING BOOST

SETPOINT TEMP DISPL

EXTRA REG. SEQUENCE

EXT. SENSORS

+5

+4

+3

-1

-2

-3

+2

+1

0

-4

-5

0 5

Control signal V DC

10

Setpoint temp displacement involves:

Control signal 0 V DC: The setpoint is lowered by 5 °C.

Control signal 5 V DC: Unchanged setpoint.

Control signal 10 V DC: The setpoint is increased by 5 °C.

Settings:

Value

Setpoint temp displacement

Setting Factory

Inactive/active Inactive

We reserve the right to alter specifi cations without notice.

GB.GOLDSKD2.100615

8.2.7 Extra Regulation Sequence

Used for extra control functions controlled by a 0-10V signal with ordinary temperature regulation sequence.

The function can be used for utilizing existing heating or cooling sources, such as from a refrigerating plant. The function can also be used for an extra cooling or heat coil.

The out signal for the extra regulation sequence is transmitted via the same terminals on the control unit as for an air recirculation damper, if fi tted (terminals 44-45).

The maximal output signal can be limited from 100 % down to 0 %.

It is possible to combine extra control sequence with intermittent nighttime heating or Morning BOOST (requires the

IQnomic Plus accessory).

Extra regulation sequence can be selected to work in four different positions as follows:

Cooling operation

• Comfort: 0-10 V output signal sequence after the cooling function is controlled to 100 %.

• Economy: 0-10 V output signal sequence before the regular cooling function.

Heating operation

• Comfort: 0-10 V output signal sequence after the reheating function is controlled to 100 %.

• Economy: 0-10 V output signal sequence before the regular reheating function.

Settings:

Value

Max output signal

Cooling function

Heating function

Setting range Factory setting

0-100%

Inactive

Comfort

Economy

Inactive

Comfort

Economy

100%

Inactive

Inactive

8.2.8 External Temperature Sensors

There are two inputs on the IQnomic for external sensors, which can be used when the internal sensor of the unit does not provide representative values.

External Extract air/Room (control unit terminals 40-41) measures the extract air temperature in a larger room or in the duct system, instead of the temperature inside the air handling unit.

External Outdoor (control unit terminals 38-39) measures the outdoor air temperature outdoors, instead of the temperature inside the air handling unit.

As an alternative, a temperature reading can be communicated to the air handling unit from a supervisory system, for instance.

Settings:

Value

External Outdoor

Alarms

Setting range Factory setting

External Extract air/Room Inactive//IQnomic

Communication

Inactive//IQnomic

Communication

0 - 9990 min.

Inactive

Inactive

5 min.

INSTALLATION

FUNCTIONS

*FUNCTIONS*

TEMPERATURE

AIR FLOW/PRESSURE

FILTER

OPERATION

HEATING

COOLING

HUMIDITY

ReCO

2

IQnomic Plus

ALL YEAR COMFORT

CONTROL Optimize

* TEMPERATURE *

TEMPERATURE REG

TEMP.REG. Xzone

OUTDOOR TEMP COMP

SUMMER NIGHT COOL

INTERM. NIGHT HEAT

MORNING BOOST

SETPOINT TEMP DISPL

EXTRA REG. SEQUENCE

EXT. SENSORS

INSTALLATION

FUNCTIONS

*FUNCTIONS*

TEMPERATURE

AIR FLOW/PRESSURE

FILTER

OPERATION

HEATING

COOLING

HUMIDITY

ReCO

2

IQnomic Plus

ALL YEAR COMFORT

CONTROL Optimize

* TEMPERATURE *

TEMPERATURE REG

TEMP.REG. Xzone

OUTDOOR TEMP COMP

SUMMER NIGHT COOL

INTERM. NIGHT HEAT

MORNING BOOST

SETPOINT TEMP DISPL

EXTRA REG. SEQUENCE

EXT. SENSORS

We reserve the right to alter specifi cations without notice.

www.swegon.com 27

GB.GOLDSKD2.100615

8.3 Flow/Pressure

Basic functions are set at INSTALLATION LEVEL and the values are read and set at USER LEVEL.

8.3.1 Fan Regulation

The type of regulation used for the supply air fan and the extract air fan respectively can be selected individually.

8.3.1.1 Flow Regulation

Flow regulation involves operating the air handling unit to keep the preset airfl ow constant. The speed of the fans is automatically regulated to provide correct airfl ow even if the fi lters begin to become clogged, air devices are blocked, etc.

Constant airfl ow is advantageous, since the airfl ow always is exactly as it was from the beginning.

It should however be noted that everything that increases the pressure drop in the ventilation system, such as the blocking of air devices and dust accumulating in the fi lters, causes the fans to run at a higher speed. This causes higher power consumption and may also cause discomfort in the form of noise.

8.3.1.2 Pressure Regulation

The airfl ow automatically varies to provide constant pressure in the ducting. This type of regulation is also called

VAV regulation (Variable Air Volume).

Pressure regulation is used when damper operations increase the air volume in parts of the ventilation system.

The duct pressure is measured by an external in-duct pressure transducer which is wired to the BUS communication of the control unit. The setpoint setting required (separate for low speed and high speed) is entered in Pa.

The function can be limited so that the fan speed will not exceed the preset max. permissible values.

8.3.1.3 Demand Control

The airfl ow required is regulated in response to 0-10 V input signals from an external sensor, such as a carbon dioxide sensor, connected to control unit terminals 30-33.

Required setpoint (separate for low speed and high speed) is set as a percentage of the input signal.

The function can be limited so that the fl ow will not be higher or lower than the preset max. and min. permissible values respectively.

8.3.1.4 Slave Control

The fl ow is constantly regulated to be the same from the one fan as from the other fan. If one fan is pressure-controlled or demand-controlled, the other one can be controlled as a slave to generate the same airfl ow.

The performance of the fan controlled as a slave can be restricted if its maximum fl ow is set to a lower airfl ow rate.

Both fans cannot be controlled as slaves. If both are selected by mistake, the extract air fan will be forced to operate in the fl ow regulation mode.

28 www.swegon.com

INSTALLATION

FUNCTIONS

*FUNCTIONS*

TEMPERATURE

AIR FLOW/PRESSURE

FILTER

OPERATION

HEATING

COOLING

HUMIDITY

ReCO

2

IQnomic Plus

ALL YEAR COMFORT

CONTROL Optimize

* AIRFLOW/PRESSURE *

SA FAN REGULATION

EA FAN REGULATION

OUTDOOR TEMP COMP.

BOOSTING

SA DOWN REGULATION

SLAVE CONTROL

* AIRFLOW/PRESSURE *

SA FAN REGULATION

EA FAN REGULATION

OUTDOOR TEMP COMP.

BOOSTING

SA DOWN REGULATION

SLAVE CONTROL

Settings:

Value

Fan regulation (SA/EA)

Detting

Flow regulation

We reserve the right to alter specifi cations without notice.

GB.GOLDSKD2.100615

8.3.2 Outdoor Temperature Compensation

Airfl ow

Outdoor temperature compensation of the airfl ow can be activated if it is desired to reduce the airfl ow in the wintertime.

In the fl ow regulation mode, the current airfl ow is reduced. In the pressure regulation mode, the current setpoint for pressure is reduced.

The function has no effect if the airfl ow is demand-controlled.

The airfl ow is reduced as a percentage of the current airfl ow/pressure.

Settings:

Value Setting Factory

Y1, max permissible reduction 0-50%

X1, breakpoint -30 – -10 °C

30 %

-20 °C

X2, breakpoint -10 – +15 °C +10 °C

8.3.3 Boosting

The airfl ow is regulated between two fl ows in response to a 0-10 V DC input signal from an external source, such as a potentiometer (connected to control unit terminals

30-33).

Boosting can be used, for example, in assembly halls, where a higher rate of air change is needed under fullload conditions.

The function is activated only when the unit fans operate at high speed.

On a 0-10 V DC signal, the fans are gradually accelerated from the unit’s initial high speed setting to its initial max speed setting. On a max input 10 V DC signal, the unit fans operate at max speed.

The function must be activated separately for the supply air fan and for the extract fan.

Settings:

Value

Supply air fan

Extract air fan

Setting range

Inactive/active

Inactive/active

Factory settings

Inactive

Inactive

INSTALLATION

FUNCTIONS

*FUNCTIONS*

TEMPERATURE

AIR FLOW/PRESSURE

FILTER

OPERATION

HEATING

COOLING

HUMIDITY

ReCO

2

IQnomic Plus

ALL YEAR COMFORT

CONTROL Optimize

* AIRFLOW/PRESSURE *

SA FAN REGULATION

EA FAN REGULATION

OUTDOOR TEMP COMP.

BOOSTING

SA DOWN REGULATION

SLAVE CONTROL

0%

-10%

-20%

-30%

Y1

-40%

-50%

X1

X2

-30 -20 -10 0 +10

X = Outdoor air temperature °C

+20

Outdoor air compensation according to factory settings involves:

Outdoor temperature +10 °C (Breakpoint X2): Compensation starts and gradually proceeds between 0–30 % down to outdoor air temperature -20 °C.

Outdoor air temperature -20 °C (Breakpoint X1): Constant compensation proceeds at 30 % (max reduction

Y1).

INSTALLATION

FUNCTIONS

*FUNCTIONS*

TEMPERATURE

AIR FLOW/PRESSURE

FILTER

OPERATION

HEATING

COOLING

HUMIDITY

ReCO

2

IQnomic Plus

ALL YEAR COMFORT

CONTROL Optimize

* AIRFLOW/PRESSURE *

SA FAN REGULATION

EA FAN REGULATION

OUTDOOR TEMP COMP.

BOOSTING

SA DOWN REGULATION

SLAVE CONTROL

We reserve the right to alter specifi cations without notice.

www.swegon.com 29

GB.GOLDSKD2.100615

8.3.4 Downspeed Control of Fan Speed to Min. Set

Point, Airfl ow/pressure

Regulation of the supply airfl ow to a lower fl ow rate is the last step in the regulation sequence on increasing heating load for ERS regulation or supply air regulation. The extract air fan cannot be selected alone; only the supply air fan or both the supply air and extract air fans can be selected.

See Section 8.2 as well.

An adjustable temperature decrease allows a lower supply air temperature setpoint, before down regulation begins.

This neutral zone can be set on line NZ SA DOWN REGU-

LATION in the appropriate menu.

Settings:

Value Setting range

Factory settings

Neutral zone 0.0-10.0 °C 0.0 °C

INSTALLATION

FUNCTIONS

*FUNCTIONS*

TEMPERATURE

AIR FLOW/PRESSURE

FILTER

OPERATION

HEATING

COOLING

HUMIDITY

ReCO

2

IQnomic Plus

ALL YEAR COMFORT

CONTROL Optimize

* AIRFLOW/PRESSURE *

SA FAN REGULATION

EA FAN REGULATION

OUTDOOR TEMP COMP.

BOOSTING

SA DOWN REGULATION

SLAVE CONTROL

8.3.5 To adjust the fl ow of the slave fan

It is possible to preset the set point of the slave fan to provide a higher or lower airfl ow than the current airfl ow of the controlling fan.

The deviation from the airfl ow of the controlling fan can be preset by entering a COP. A cooling COP of 0.5 denotes that the airfl ow of the slave will be 50% of the master fan’s airfl ow.

Settings:

Value

Cooling COP

Setting range

0.5-2,0

Factory settings

1,0

INSTALLATION

FUNCTIONS

*FUNCTIONS*

TEMPERATURE

AIR FLOW/PRESSURE

FILTER

OPERATION

HEATING

COOLING

HUMIDITY

ReCO

2

IQnomic Plus

ALL YEAR COMFORT

CONTROL Optimize

* AIRFLOW/PRESSURE *

SA FAN REGULATION

EA FAN REGULATION

OUTDOOR TEMP COMP.

BOOSTING

SA DOWN REGULATION

SLAVE CONTROL

8.4 To Activate the GOLD SD Filter Monitoring Function

The fi lter monitoring function must be activated for the fi lters that are to be monitored.

Settings:

Value Setting Factory

INSTALLATION

Standard fi lter Inactive/SA/EA Inactive

SA+EA

Prefi lter Inactive/SA/EA Inactive

SA+EA

FUNCTIONS

*FUNCTIONS*

TEMPERATURE

AIR FLOW/PRESSURE

FILTER

OPERATION

HEATING

COOLING

HUMIDITY

ReCO

2

IQnomic Plus

ALL YEAR COMFORT

CONTROL Optimize

30 www.swegon.com

We reserve the right to alter specifi cations without notice.

GB.GOLDSKD2.100615

8.5 Operation

8.5.1 Switch clock

Basic functions are set at INSTALLATION LEVEL and the values are read and set at USER LEVEL.

The switch clock controls the operating times of the unit.

The following two basic functions can be set:

LOW SPEED – HIGH SPEED

Low speed is the basic level and times for high speed operation are set at USER LEVEL under SWITCH CLOCK.

STOP – LOW SPEED – HIGH SPEED

Stop is basic level and times for low speed and high speed operation are set at USER LEVEL under SWITCH CLOCK.

Settings:

Value Setting range

Function Low speed/High speed

Stop/Low speed/High speed

Factory settings

Low speed/High speed

INSTALLATION

FUNCTIONS

*FUNCTIONS*

TEMPERATURE

AIR FLOW/PRESSURE

FILTER

OPERATION

HEATING

COOLING

HUMIDITY

ReCO

2

IQnomic Plus

ALL YEAR COMFORT

CONTROL Optimize

*OPERATION FUNCTION*

SWITCH CLOCK

EXTENDED OPERATION

SUMMER/WINTER TIME

8.5.2 Extended Operation

The inputs for external low speed (control unit terminals

46-47) and external high speed (control unit terminals

48-49) respectively, can be supplemented with extended operation. They can be used for overtime running activated by a pushbutton, for example.

Desired time in hours and minutes can be set as follows.

Settings:

Value Setting Factory

External low speed

External high speed

0:00 - 23:59 0:00

0:00 - 23:59 0:00

8.5.3 Summer time/Winter time

The time and date readings include factory-preset automatic changeover from summer time to normal time and vice versa, thus conforming to EU standard (the last

Sunday in March and the last Sunday in October respectively).

This automatic changeover can be blocked and set as inactive.

Settings:

Value Setting Factory

Summer time/Winter time Inactive/active Active

We reserve the right to alter specifi cations without notice.

*OPERATION FUNCTION*

SWITCH CLOCK

EXTENDED OPERATION

SUMMER/WINTER TIME

*OPERATION FUNCTION*

SWITCH CLOCK

EXTENDED OPERATION

SUMMER/WINTER TIME

www.swegon.com 31

GB.GOLDSKD2.100615

8.6 Heating

8.6.1 Heat exchanger

8.6.1.1 Defrosting the rotary heat exchanger

In environments where the extract air can occasionally be humid, the defrosting function can be activated to protect the heat exchanger from frosting.

The function continuously monitors the condition of the heat exchanger rotor to prevent condensate from freezing in the rotor passages and clogging them.

The function requires a separate pressure transducer

(preset for heat exchanger defrosting) wired to the control unit inputs for external BUS communication and connected by hoses to the pressure measuring tappings of the unit.

See special installation instruction for the TBLZ-1-23-aa

Pressure sensor.

The pressure drop across the rotor must then be calibrated to establish a reference pressure drop for monitoring purposes. See 6.4.3 Calibration - Heat exchanger.

When the function is activated the pressure drop across the heat exchanger is continuously measured and the reading is compared with the calibration reading.

If the pressure drop exceeds the preset limit value, a defrosting sequence is carried out. This involves, decreasing the rotor speed to approx. 0.5 rpm to allow warm extract air to melt possible frost.

The defrosting sequence will be cancelled when the pressure drop has fallen to half the limit value. The defrosting operates for a max permissible period of 30 minutes.

If the pressure drop has not decreased within that max permissible period after six tries during a 24-hour period, an alarm will be initiated.

Note that the heat exchanger performs less effi ciently while defrosting is in progress and that the supply air temperature will decrease downstream of the heat exchanger.

Settings:

Value Setting Factory

Defrosting Inactive/active Inactive

8.6.1.2 Exhaust air regulation, rotary heat exchanger

The exhaust air regulation function can be used whenever the exhaust air temperature is not permitted to be below a predetermined value.

The function controls the heat exchanger rotor speed

(effi ciency) in order to limit the exhaust air temperature to the required value. The function decelerates the heat exchanger rotor speed from the current level, until the exhaust air temperature drops to the preset min. permissible setting.

INSTALLATION

FUNCTIONS

*FUNCTIONS*

TEMPERATURE

AIR FLOW/PRESSURE

FILTER

OPERATION

HEATING

COOLING

HUMIDITY

ReCO

2

IQnomic Plus

ALL YEAR COMFORT

CONTROL Optimize

*HEAT*

HEAT EXCHANGE

REHEAT

HEATING BOOST

Defrosting function with separate pressure transducers, in principle

Exhaust air regulation Inactive/Activated

Min. exhaust air -10 – + 20.0 °C

temperature

EXTRACT AIR

Exhaust air regulation requires a separate temperature sensor (TBLZ-1-58-aa; accessory) fi tted in the air handling unit exhaust air path.

See special installation instructions for the internal TBLZ-1-

58-aa temperature sensor.

Settings:

Value Setting Factory

Inactive

5.0 °C

32 www.swegon.com

We reserve the right to alter specifi cations without notice.

GB.GOLDSKD2.100615

8.5.2 Reheating

AIR HEATER FOR HOT WATER

If the “pump or pump + valve” exercising mode is selected, the relay output is activated (control unit terminals 5 and 6) whenever heating is required and this starts the circulation pump of the air heater.

If the outdoor temperature is low (colder than +12 °C), the pump output contact is continuously activated. During other times, the pump output contact is activated 2 min/24 hours for exercising of circulation pump.

ELECTRIC AIR HEATER

If “pump exercising mode inactive” has been selected, the relay output is activated (control unit terminals 5 and 6) whenever heating is required.

The relay output can be used for indicating or blocking the external function.

EXERCISING MODE

Settings:

Value Setting Factory

INSTALLATION

FUNCTIONS

*FUNCTIONS*

TEMPERATURE

AIR FLOW/PRESSURE

FILTER

OPERATION

HEATING

COOLING

HUMIDITY

ReCO

2

IQnomic Plus

ALL YEAR COMFORT

CONTROL Optimize

INSTALLATION

*HEAT*

HEAT EXCHANGE

REHEAT

HEATING BOOST

FUNCTIONS

pump+valve/

*FUNCTIONS*

valve

TEMPERATURE

Exercise period 1 – 60 min. 3 min.

AIR FLOW/PRESSURE

Interval 1 – 168 hrs. 24 hrs.

FILTER

8.5.3 Heating BOOST

Heating boost means that the air handling unit, operating in the normal fl ow regulation mode, increases both the supply airfl ow and the extract airfl ow in order to carry more heat into the premises.

OPERATION

HEATING

COOLING

HUMIDITY

ReCO

2

IQnomic Plus

ALL YEAR COMFORT

CONTROL Optimize

The fans are allowed to work in the range between current fl ows (low speed, high speed) and preset max speed fl ow.

8.6.4 Preheat

The function only works if the air handling unit is operating in the extract air regulation mode. If demand control or boost is selected in combination with heating boost, the fl ow is controlled by the function that transmits the highest output signal to the fans.

This function cannot be combined with pressure regulation.

*HEAT*

HEAT EXCHANGE

REHEAT

HEATING BOOST

The following accessories are required for the preheat function:

TBLF/TCLF air heater for preheat (TBLZ-1-53-1 control system for the air heater is included) or, if an air heater other than a TBLF/TCLF is used, TBLZ-1-53-a control system for the air heater for preheat. TBLZ-1-53-1 control system for the air heater includes a TBLZ-1-30 temperature sensor and a TBIQ-2-1 IQnomic Plus-module, see separate instructions.

A regulated ramp function begins and increases the airfl ow if the temperature exceeds its setpoint and it differs

2-10°C (3°C has been factory preset) to the preset max. supply air temperature. The control reaction speed (ramp time = % fl ow increase/minute) can be set. The highest possible airfl ow is limited by the max. fl ow. For particulars on setting the max. fl ow, see Section 6.3.2.

By preheating the outdoor air, it is possible to prevent moisture precipitation in the outdoor air fi lter of the air handling unit, to reduce the risk of frosting in the heat exchanger and to eliminate the risk that the ambient temperature will drop lower than minimum permissible where the pressure sensors and frequency inverters operate.

Settings:

Value Setting Factory

You can activate the function, select the type of coil connected and set the required setpoint under INSTALLATION/

FUNCTIONS/IQNOMIC PLUS/PREHEAT.

Heating BOOST

Starting limit

Ramp time

Inactive/Activated Inactive

2-10 °C 3 °C

0.5-15% 2.5%

See also the guide to the functions for more detailed information.

We reserve the right to alter specifi cations without notice.

www.swegon.com 33

GB.GOLDSKD2.100615

8.7 Cooling

8.7.1 Operation

Activate the cooling function.

8.7.2 Cooling Regulation

CoolDX -Economy (without heat exchanger)

Used when the CoolDX cooling unit is connected via bus cable.

Both cooling relays of the air handling unit operate in parallel with each relay on the IQnomic plus module in the CoolDX cooling unit.

CoolDX - Comfort

Used when the CoolDX cooling unit is connected via bus cable. The heat exchanger in the GOLD unit operates in sequence with the cooling unit to even out the supply air temperature.

Applies to the COOL DX, versions A and B:

Important! Requires an extra outdoor temperature sensor.

Use the TBLZ-1-30 accessory for mounting an outdoor air temperature sensor in the ductwork upstream of the CoolDX.

Use the TBLZ-1-2 4/5 accessory for installing the outdoor air temperature sensor outdoors.

COOL DXS

For use when the COOL DXS cooling unit is connected via a bus cable. The COOL DXS operates downstream of the heat exchanger in the GOLD air handling unit.

Stepless 0-10 V DC

Used when variable cooling control is connected. The air handling unit cooling controller modulates a 0-10 V DC signal that is linear with the cooling load (control unit terminals 42-43).

Both the cooling relays of the unit operate in parallel with the signal and are energized when the cooling signal exceeds 0.5

V DC and are de-energized when the signal drops below 0.2

V DC.

The output for cooling relay 1 is connected to terminals 7-8 and for cooling relay 2 to terminals 9-10.

Stepless 10-0 V DC

Same as above, but the control signal is inverted where a 10 V output signal means a 0 % cooling load.

On/off, 1 Step

Used if cooling in one step is connected. The air handling unit’s cooling controller regulates the cooling load at 0-100

%. Cooling relays 1 and 2 are energized when the cooling load exceeds 5 % and are de-energized when the cooling load is less than 2 %.

The output contact for 0-10 V DC control signals (terminals

42-43) operates in parallel with the 0-100 % cooling demand and can be used for indicating the cooling demand, for instance.

INSTALLATION

FUNCTIONS

*FUNCTIONS*

TEMPERATURE

AIR FLOW/PRESSURE

FILTER

OPERATION

HEATING

COOLING

HUMIDITY

ReCO

2

IQnomic Plus

ALL YEAR COMFORT

CONTROL Optimize

* COOLING *

OPERATION MODE

COOL REGULATION

PERIODIC OPERATION

REGULATION SPEED

OUTDOOR TEMP LIMIT

RESTART TIME

COOL MIN AIR FLOW

NEUTRAL ZONE

COOLING BOOST

On/off, 2 steps

Used when cooling in 2 steps is connected. The air handling unit’s cooling controller regulates the cooling load at 0-100 %.

Cooling relay 1 is energized when the cooling load exceeds 5

% and is de-energized when the cooling load is less than 2 %.

Cooling relay 2 is energized when the cooling load exceeds 55

% and is de-energized when the cooling load is less than 50

%.

The 0-10 V DC control signal output (terminals 42-43) operates in parallel with the 0-100 % cooling demand and can be used for indicating the cooling demand, for instance.

On/off, 3 Steps - Binary

Used when cooling with two inputs controlled with three binary steps is connected. The cooling controller of the unit regulates the cooling demand at 0-100 %.

On an increasing cooling load:

Cooling relay 1 is energized when the cooling load is above 5 % and is de-energised when the cooling load is between 40-70 %. Cooling relay 2 is energized when the cooling load is above 40 %. Cooling relay 1 is energized again (together with cooling relay 2) when the cooling load is above 70%.

On a decreasing cooling load:

Cooling relay 1 drops when cooling load is below 60 %, it is energized again when cooling load is below 30 % and drops again when cooling load is below 2 %. Cooling relay 2 drops when cooling load is below 30 %.

The output for 0-10 V DC control signals (terminals 42-43) operates in parallel with the 0-100 % cooling load and can be used for indicating the cooling demand, for instance.

34 www.swegon.com

We reserve the right to alter specifi cations without notice.

Settings for cooling functions on this page and the next:

Value Setting Factory

Operation mode

Cooling regulation

Inactive/active Inactive

CoolDX

Stepless 0-10 V Stepless 0-10 V

On/Off 1 step

On/Off 2 step

On/Off 3 step binary

Periodic operation

Cooling relay 1 Inactive/pump/ Inactive

pump+valve/valve

Cooling relay 2 Inactive/pump/ Inactive

3 min.

Interval

Regulation speed between steps

Outdoor temperature limit

Step 1

Step 2

Step 3

Exercise period 1 – 60 min.

1 – 168 hrs.

0-600 sec

0-25 °C

0-25 °C

0-25 °C

0-900 sec

24 hrs.

300 sec

3 °C

5 °C

7 °C

480 sec Restart time

Cooling min air fl ow

Supply air

Extract air

0-Max fl ow –

0-Max fl ow –

Neutral zone 0-10 °C 2.0 °C

Cooling BOOST Inactive

Comfort

Inactive

Economy

Sequence

Comfort+economy

Start limit in connection to min supply air temp 2-10 °C 3 °C

GB.GOLDSKD2.100615

We reserve the right to alter specifi cations without notice.

www.swegon.com 35

GB.GOLDSKD2.100615

See preceding page for possibilities of setting.

8.7.3 Periodic Operation

Can be selected to run pumps if cooling relay 1 and/or 2 are used.

The exercising mode can be selected for “pump, pump + valve” or “valve” only (0 - 10 V output). The pumps are exercised 2 minutes per day if this is activated.

8.7.4 Regulation Speed

The required delay period between the various cooling steps can be set.

This is done so that a compressor, for instance, will have time generate required cooling capacity before the next cooling step is switched in.

This applies to changeover from step 1 to step 2 and from step 2 to step 3; and only on an increasing cooling load.

8.7.5 Outdoor Temperature Limit

Provision is available for setting an outdoor temperature-related blocking function in 3 steps. If the outdoor temperature is below each step limit, the function of the cooling relays will be blocked.

This function also restricts the 0-10 V output signal to transmission in steps.

Step 1 maximises the output signal to 2.5 V, step 2 to 5.0

V and step 3 to 7.5 V.

8.7.6 Restart Time

The time should be set in such a way that it follows the recommendations of the cooling machine supplier for the number of starts per hour.

The restart time is calculated from the time when a relay is energized to when it is allowed to be energized again.

The 0-10 V signal is delayed during the same period.

8.7.7 Cooling Min Air Flow

In order for the cooling function to operate the supply air and extract air airfl ows must be greater than their respective limit values (preset at USER LEVEL under FLOW/PRES-

SURE).

The cooling min fl ow function can be blocked by setting both fl ow limits to 0.

8.7.8 Neutral Zone

The neutral zone prevents the cooling and heating systems from counteracting each other.

Preset neutral zone is added to the setpoint for heating and the sum of these provides the setpoint for cooling.

8.7.9 Cooling BOOST

Cooling BOOST means that the supply air and extract air airfl ows are increased to convey more cooling energy to the premises.

Cooling BOOST cannot be combined with pressure regulation.

The fl ow increase takes place between current fl ow and preset max fl ow.

The function can be selected in three variants as follows:

Comfort

The cooling outputs are activated if there is a cooling load.

When the temperature exceeds its setpoint and the supply air temperature is within the preset limit, a regulated ramp function begins and increases the fl ow. The control reaction speed (ramp time = % fl ow increase/minute) can be set. The highest possible airfl ow is limited by the max. fl ow. For particulars on setting the max. fl ow, see Section

6.3.2.

Economy

Cooling BOOST Economy fi rst uses a higher airfl ow to cool the premises, before a start signal is transmitted to the cooling machines.

The function can also operate without the cooling function being activated.

On a cooling load, the fl ows are slowly increased up to preset maximum fl ow. When the fl ows are up to max and if a cooing load is still present, the output contacts for cooling are activated.

The cooling boost function requires an outdoor air temperature of at least 2 °C lower than the extract air temperature for it to be activated. Normal cooling operation is activated if the temperature difference is too small.

Sequence

The cooling BOOST Sequence is used if a cooling machine is sized for a higher than normal cooling fl ow.

If there is a cooling load, the fl ow is increased up to the preset max fl ow before the cooling function is activated.

The cooling function is delayed 1 minute after the airfl ow is increased.

The cooling boost sequence is blocked if no cooling function has been selected.

36 www.swegon.com

We reserve the right to alter specifi cations without notice.

GB.GOLDSKD2.100615

8.8 Humidity

Dehumidifi cation control

The dehumidifi cation function controls the moisture in the supply air duct by switching in and switching out a cooling coil and a postheating coil.

The function requires that a cooling coil be mounted upstream of a postheating coil in the supply air duct, see the example to the right.

The TBLZ-1-31-1 moisture sensor is mounted in the supply air duct and its cable is connected to the appropriate terminal on the GOLD unit.

Cooling energy is emitted to condense the moisture in the supply air fl ow, which then is heated to the desired supply air temperature. This causes a reduction in the moisture content of the supply air.

The cooling unit used must be sized so that the temperature of the supply air will be below the dew point, otherwise no condensation will arise and no dehumidifi cation will occur.

Settings:

Value Setting Factory

Dehumidifi cation Inactive/active Inactive

Supply air – rel. humidity (%RH) 10-90% 50%

INSTALLATION

FUNCTIONS

*FUNCTIONS*

TEMPERATURE

AIR FLOW/PRESSURE

FILTER

OPERATION

HEATING

COOLING

HUMIDITY

ReCO

2

IQnomic Plus

ALL YEAR COMFORT

CONTROL Optimize

*HUMIDITY*

DEHUMIDIF. CTRL.

Example of dehumidifi cation control

Temperature sensor, supply air

Moisture sensor, TBLZ-1-31-1

We reserve the right to alter specifi cations without notice.

www.swegon.com 37

GB.GOLDSKD2.100615

8.9 ReCO

2

The ReCO

2

function is used for controlling the TBBR air recirculation section in sequence with CO

2

control or temperature control, for instance.

If both the CO2 and the temperature functions are selected, the function with the presently lowest signal

(highest outdoor air set point) will apply.

CO

2

function:

The air recirculation rate increases if the input signal for

CO

2

(0-10 V DC) is low and decreases if the input signal is high.

CO

2

+ fl ow function:

The air recirculation rate increases if the input signal for

CO

2

(010 V DC) is low and decreases if the input signal is high. If the input signal for CO

2

still is too high without air recirculation, the airfl ow will be steplessly increased to the max. preset fl ow setting.

Temperature function for heating, economy:

Recirculation takes place upstream of the reheater.

Temperature function for heating, comfort:

Recirculation takes place downstream of the reheater.

Temperature function for cooling, economy:

Recirculation takes place upstream of air cooler.

Temperature function for cooling, comfort:

Recirculation takes place downstream of the air cooler.

Settings:

Value Setting Factory

INSTALLATION

FUNCTIONS

*FUNCTIONS*

TEMPERATURE

AIR FLOW/PRESSURE

FILTER

OPERATION

HEATING

COOLING

HUMIDITY

ReCO

2

IQnomic Plus

ALL YEAR COMFORT

CONTROL Optimize

*ReCO

2

*

FUNCTION OFF/ON

SETTINGS

Outdoor air

Outdoor air

Extract air

Supply air

Pressure sensor for outdoor air measurements.

CO

2

function

Inactive

Inactive/CO

2

/ CO

2

+fl ow

The outdoor airfl ow is kept constant in response to pressure sensor readings. See special installation instruction for the TBLZ-

Temp. function – heating Inactive/ Inactive

1-23-aa Pressure sensor.

economy/

Temp. function – cooling Inactive/ Inactive

air fan is reduced and vice versa.

economy/

comfort

Min. outdoor air * m 3 /s * m 3 /s

Min. exhaust air * m

3

/s * m

3

/s

* The setting range is equivalent to the min./max. setting range of the air handling unit.

8.10 IQnomic Plus

IQnomic Plus is a name given to additional modules for extra control functions.

See Section 8.2.1.4 for the Xzone temperature regulation function and Section 8.6.4 for the preheat function.

8.10.1 External supervision

The TBIQ-2-1 IQnomic Plus-module accessory is required for external supervision. See separate instructions. The function can be activated under IQNOMIC PLUS/EXTER-

NAL SUPERV.

INSTALLATION

FUNCTIONS

*FUNCTIONS*

TEMPERATURE

AIR FLOW/PRESSURE

FILTER

OPERATION

HEATING

COOLING

HUMIDITY

ReCO

2

IQnomic Plus

ALL YEAR COMFORT

*IQnomic Plus*

CONTROL Optimize

38 www.swegon.com

We reserve the right to alter specifi cations without notice.

GB.GOLDSKD2.100615

8.11 All Year Comfort

The All Year Comfort function controls the supply fl ow temperature to comfort modules, chilled beams, perimeter climate systems, etc. via regulating valves. Two strap-on temperature sensors fi tted either to the water pipe or the regulating valve are used for measuring the water temperature.

The function requires the electrical equipment cubicle accessory (TBLZ-1-59-a-b-cc) for controlling the supply fl ow water temperature. The function selector switch of the electrical equipment cubicle must be set to position 7.

All Year Comfort has functions for outdoor compensation, room compensation, night compensation, dew point compensation and for controlling pump and valve exercising.

INSTALLATION

FUNCTIONS

*FUNCTIONS*

TEMPERATURE

AIR FLOW/PRESSURE

FILTER

OPERATION

HEATING

COOLING

HUMIDITY

ReCO

2

IQnomic Plus

ALL YEAR COMFORT

CONTROL Optimize

*ALL YEAR COMFORT*

FUNCTION ON/OFF

SETTINGS

For further information, see the Guide to the All Year

Comfort Function.

Settings:

Monday

Tuesday

Wednesday

Thursday

Value Setting Factory

range

All Year Comfort Inactive Inactive

Saturday

Cooling

Heating

Heating water temperature (°C) 10-80°C

Cooling water temperature (°C) 5-30°C

Outdoor comp. Heat. water Active

30

14

Inactive

Channel

Pump op., Heating water

Inactive

Outdoor temp. (X1) (°C)

Heating water (Y1)(°C)

-40 - 40°C

10 - 80°C

-20

40

Pump op., Heating water

Outdoor temp. Stop (°C)

Outdoor temp. (X2)(°C) -40 - 40°C 5

Pump op., Cooling water

Heating water (Y2)(°C) 10 - 80°C 30

Outdoor temp. Start (°C)

Outdoor temp. (X3)(°C) -40 - 40°C 15

Pump op., Cooling water

1-2

-40 - 40°C

-40 - 40°C

-40 - 40°C

15

18

-20

Heating water (Y3)(°C) 10 - 80°C

Outdoor comp., Cool. water Active

20

Inactive

Outdoor temp. Stop (°C)

Pump/valve

Inactive

Outdoor temp. (X1) (°C) -40 - 40°C 10

Cooling water (Y1)(°C) 5 - 30°C 22

Outdoor temp. (X2)(°C)

Cooling water (Y2)(°C)

-40 - 40°C

5 - 30°C

20

18

Contactor

Valve, heating water

-40 - 40°C

Inactive

Normally closed

Normally open

Active

-25

Inactive

Inactive

Outdoor temp. (X3)(°C) -40 - 40°C 25

Inactive

Cooling water (Y3)(°C) 5 - 30°C 14

Pump alarm, cooling water Inactive Inactive

Room comp., Heating water Active Inactive

Normally closed

Normally open

Room temperature (°C)

P-band (°C)

0 - 40°C

1 - 10°C

21

5

Valve, cooling water Active Inactive

Inactive

Night blocking Active Active

Exercising, heating water Inactive Inactive

Pump

Room comp., Cooling water Active Inactive

Inactive

Room temperature (°C) 0 - 40°C 21

Valve

P-band(°C) 1 - 10°C 5

Exercising period, (min) 1-60 min 3

Night blocking Active Active

Interval (h) 1-168 h 24

Exercising, Cooling water Inactive Inactive

Night comp., heating water Active Inactive

Pump

Inactive

Temp. comp. (°C) -10 - +10°C -2

Valve

Night comp., Cooling water Active Inactive

Exercising period, (min) 1-60 min 3

1-168 h 24

Temp. comp. (°C) -10-+10 °C 2

Inactive

Neutral zone(°C)

Comp. fl ow (%)

0-5°C

0-30%

2

10

We reserve the right to alter specifi cations without notice.

www.swegon.com 39

8.12 CONTROL Optimize

The CONTROL Optimize function optimizes the GOLD unit’s airfl ow rates for the connected WISE system. See the special documentation for WISE.

INSTALLATION

FUNCTIONS

*FUNCTIONS*

TEMPERATURE

AIR FLOW/PRESSURE

FILTER

OPERATION

HEATING

COOLING

HUMIDITY

ReCO

2

IQnomic Plus

ALL YEAR COMFORT

CONTROL Optimize

GB.GOLDSKD2.100615

40 www.swegon.com

We reserve the right to alter specifi cations without notice.

GB.GOLDSKD2.100615

9 AUTOMATIC FUNCTIONS

9.1 General

The GOLD has a number of automatic functions. The operation of the unit is infl uenced when certain functions are activated.

9.1.1 Starting Sequence

The GOLD has a starting sequence with factory-preset time delay between every step as follows:

1. The damper relay is energized and opens the shut-off damper

(if installed).

Time delay: 30 seconds.

2. The extract air fan starts (not applicable if only GOLD SD supply air handling units are installed) and the heat exchanger is controlled to provide max. heat recovery (Not applicable to

GOLD SD units without heat exchanger). Additional heating (if installed) is activated to generate 40% of its max capacity.

Time delay: 90 seconds.

3. The supply air fan starts (not applicable if only GOLD SD extract air handling units are installed)

Time delay: 180 seconds (from the time when the extract air fan has started).

4. The temperature regulation function begins according to its regular settings.

The starting sequence prevents the extract air fan from starting if the shut-off damper is closed. By starting the extract air fan fi rst, and the heat exchanger as well, the system also avoids chilling the premises with cool supply air under cold weather conditions.

9.1.2 Cooling Recovery

Cooling energy recovery is an automatic function that helps the air handling unit utilize the relative “cooling energy” that may be present indoors if cooling is required and the outdoor temperature is high.

The heat exchanger rotates at max. speed and in this way recovers the relative cooling energy or chilliness in the extract air.

The conditions for this function to be activated are that there is a cooling demand and that the outdoor temperature is 1 °C higher than the extract air. The function is switched out when the cooling load ceases to exist or when the outdoor temperature is the same as that of the extract air.

The text COOLING RECOVERY is shown in the hand-held micro terminal.

9.1.3 Zero Point Calibration

The pressure transducer of the unit is automatically calibrated.

This calibration is carried out 3 minutes after the unit has been stopped.

The text ZERO PT CALIBR is shown in the hand-held micro terminal.

The fans cannot start while calibration is in progres s.

9.1.4 Anti-frost Monitoring Function – Air Heater for

Hot Water

The anti frost monitoring function is always active if the air heater for hot water connected has been supplied by Swegon.

The function activates a heating device that maintains 13 °C in the coil while the air handling unit is in operation and 25 °C in the coil when the unit is stopped. An alarm is initiated and the unit is stopped if the temperature sensor senses a temperature below 7 °C.

9.1.5 Additional cooling – Electric Air Heater

The fans continue to operate at min speed for 3 minutes after the air handling unit has been stopped to cool the electric heating elements if the electric air heater has been operating.

The text ADD COOLING appears in the hand-held micro terminal.

9.1.6 Reduction in output, electric air heater

A min. permissible air velocity of 1.5 m/s is required for preventing the electric heating elements from becoming overheated when they are generating full heating output.

If the air handling unit supply airfl ow drops below the value that corresponds to an air velocity of 1.5 m/s across the heat exchanger the heating output of the air heater will be automatically reduced.

The text REDUCTION IN OUTPUT appears in the hand-held micro terminal.

9.1.7 Additional running - Heat Exchanger

The rotary heat exchanger automatically continues to rotate ca 1 minute after the air handling unit has been stopped.

It takes a little time for the fans to stop rotating after a stop order has been entered in the micro terminal. This prevents the admission of cool supply air into the premises.

9.1.8 Density-corrected Airfl ow

The density of the air is different at different temperatures. This means that a specifi c volume of air will change at different air densities.

The GOLD automatically corrects this, so that correct air volume is always obtained.

The control equipment always shows the corrected airfl ow.

9.1.9 Purging Operation

Purging is an automatic function that prevents the rotary heat exchanger from standing still in the same position for a longer period when no heating is necessary.

Purging operation is activated when the unit is operating but the heat exchanger rotor is not rotating. The heat exchanger rotor then rotates for 10 seconds every 10 minutes to purge its surfaces clean of impurities.

9.1.10 Carry-over Control

Whenever the fans generate low airfl ows, the speed of the rotary heat exchanger is reduced to an appropriate level for correct purging airfl ow through the heat exchanger.

9.1.11 Calculaton of the effi ciency of the rotary heat exchanger

The effi ciency is calculated and displayed (0 – 100%).

9.1.12 Pump control for the coil heat exchanger

The pump of the pipework package starts when heat recovery is needed.

If heat recovery is not needed for more than 24 hours, the pump is exercised once a day.

We reserve the right to alter specifi cations without notice.

www.swegon.com 41

GB.GOLDSKD2.100615

9.1.13 Anti-frosting protection for the plate/coil heat exchanger

In cold weather, and if the extract air is humid, there is risk of frosting in plate/coil heat exchangers. The GOLD PX/CX is equipped with anti-frosting protection.

GOLD PX (plate heat exchanger)

The temperature inside the heat exchanger’s ”cold corner” and the humidity in the extract air are measured.

Taking the humidity into consideration, the control system calculates the lowest permissible temperature without risk of frosting inside the heat exchanger. The by-pass damper is then controlled to prevent the temperature from dropping below this limit.

GOLD CX (coil heat exchanger) and

GOLD SD with coil heat exchanger

The temperature of the liquid circulated to the extract air coil and the humidity in the extract air are measured.

Taking the humidity into consideration, the control system calculates the lowest permissible temperature without risk of frosting inside the coil.

The valve in the pipework package is then controlled to prevent the temperature from dropping below this limit.

10 READINGS

The operating status and the values can be read. Used for performance checks and for generally checking values, settings, power consumption, etc.

No values can be altered in this menu group.

Each menu indicates which values can be read.

The operation times per 24 hour period are given under the OPERATION TIME menu.

INSTALLATION

READINGS

*READINGS*

TEMPERATURE

FANS

HEAT EXCHANGE

REGULATION SIGNALS

IN/OUTPUTS

HUMIDITY

ReCO

2

IQnomic Plus

ALL YEAR COMFORT

OPERATION TIME

PROGRAM VERSIONS

11 MANUAL TEST

Note! Manual test running can cause indoor comfort problems. There is also risk of overloading the system. The responsibility for discomfort and overload rests totally on the person who activates the function.

Manual test run can take place for testing the inputs and outputs, fans and heat exchanger, etc.

Used when the air handling unit is fi rst installed to make sure that all the connections have been correctly wired.

Most alarms, functions and normal control modes will be blocked while manual testing is in progress.

On a return to the other menu groups, the controller resumes normal operation and all settings for manual testing will be terminated.

Each menu indicates which functions can be test run.

42 www.swegon.com

INSTALLATION

MANUAL TEST

*MANUAL TEST*

TEMPERATURE

FANS

HEAT EXCHANGE

REHEAT

EXTRA REG. SEQ.

COOLING

IN/OUTPUTS

ReCO

2

IQnomic Plus

ALL YEAR COMFORT

We reserve the right to alter specifi cations without notice.

GB.GOLDSKD2.100615

12 ALARM SETTINGS

12.1 Fire Alarms

EXTERNAL FIRE ALARM

Inputs 54 and 55 are used for external fi re protection equipment.

The resetting of alarms can be selected to occur manually or automatically.

INTERNAL FIRE ALARM

The air handling unit’s internal temperature sensors serve as fi re protection thermostats. An alarm is initiated if the supply air temperature sensor registers more than 70 °C or when the extract air temperature sensor registers more than 50 °C.

If an external Extract air/Room temperature sensor is connected and activated, this works parallel with the extract air temperature sensor of the unit.

FANS IN THE EVENT OF A FIRE

The fans in the air handling unit can be used for evacuating gases, etc.

The activated function works together with the External fi re/smoke function or Internal fi re alarm.

If the air handling unit is idle, the pre-selected fans will start up regardless of whether External Stop or Manual Stop has been activated in the hand-held micro terminal.

The damper relay in the air handling unit is energized and the operating relay drops.

The dampers pre-selected for service in the event of a fi re, should be wired to the damper relay (control unit terminals 22-24) and these dampers will open.

The dampers that are meant to close in the event of a fi re, should be wired to the in-operation relay (control unit terminals 19-21) and these dampers will close.

FAN SPEED IN THE EVENT OF FIRE

Will be activated automatically if the fans have been activated in event of fi re (see above), and make it possible to restrict the max speed of the fans.

Settings:

Value

Internal fi re alarm

External fi re alarm

Fan in event of fi re

Fan speed in event of fi re, SA

Fan speed in event of fi re, EA

Setting range Factory setting

0=inactive

1=activated auto/manual

Inactive/EA/SA/

SA+EA

10-100%

0 manual

Inactive

100%

10-100% 100%

Settings:

Value

Time delay

Alarm at closure

1-600 sec

1=closure

0=disconnection

10 sec

1

Alarm reset 0=auto/1=man 0

12.3 Alarm Limits

Changes in the factory-preset alarm limits should only be made if you have special reasons for doing so and you should be aware of the consequences.

TEMPERATURE

DEVIATION SA-TEMP (deviating supply air temperature) indicates how much the supply air temperature is allowed to be below the supply air temperature setpoint before an alarm is initiated.

MIN EA-TEMP (min extract air temperature) indicates how low the extract air temperature is allowed to be before alarm is initiated.

FILTERS

SUPPLY AIR/EXTRACT AIR indicates at which level of contamination in the supply air fi lter that an alarm will trip.

HEAT EXCHANGER

ALARM LIMIT indicates at which pressure rise an alarm will trip, if there is an extra installed pressure transducer for the defrosting function of the heat exchanger.

SERVICE PERIOD

SERVICE PERIOD indicates the period until the next service.

Settings:

Value Setting Factory

TEMPERATURE

Deviating supply air temp.

Min extract air temp.

FILTERS

Supply air

Extract air

Supply air, prefi lter.

Extract air, prefi lter.

HEAT EXCHANGER

Alarm limit

SERVICE PERIOD

Alarm limit

2-15 °C

-10 - 20 °C

50-300 Pa

50-300 Pa

50-300 Pa

50-300 Pa

30-100

5 °C

12 °C

100 Pa

100 Pa

100 Pa

100 Pa

Pa 50 Pa

0-99 months 12 months

12.2 External Alarms

EXTERNAL ALARMS 1 and 2

The external alarms can be used for external functions (control unit terminals 50-51 and 52-53).

Typical uses:

– Motor protection for the circulation pump in the heating or cooling circuit.

– Service alarm actuated by smoke detectors.

Set the time delay and set whether the alarm shall be activated on closure or disconnection of the input.

INSTALLATION

ALARM SET

*ALARM SETTINGS*

FIRE ALARM

EXTERNAL ALARMS

ALARM LIMITS

ALARM PRIORITY

ALARM OUTPUTS

Setting Factory

We reserve the right to alter specifi cations without notice.

www.swegon.com 43

12.4 Alarm Priority

There should be special reasons for alteration of alarm priority and you should be aware of the consequences.

Changes in priority should only be made if you have special reasons for doing so and you should be aware of the consequences. The priority of certain alarms cannot be changed.

Settings:

See 17.2 Alarm Descriptions.

12.5 Alarm outputs

Alarm outputs A and B can be selected with normally open or normally closed function.

Settings:

Value Setting Factory

Output A

Output B

NO/NC

NO/NC

Normally open

Normally open

GB.GOLDSKD2.100615

44 www.swegon.com

We reserve the right to alter specifi cations without notice.

GB.GOLDSKD2.100615

13 HAND-HELD TERMINAL

13.1 Language

The language desired can be set here. Normally this setting is entered when the air handling unit is started for the fi rst time and the question ÄNDRA/CHANGE? automatically appears in the hand-held terminal.

However, the language setting can be changed at any time.

Settings:

Value Setting Factory

Language Current languages English is listed in the menu.

13.2 Air fl ow unit

The air fl ow unit desired can be set here.

Settings:

Value Setting

Flow unit l/s

m3/s

m3/h

Factory

m3/s

13.3 Min/Max Adjustment

Used for restricting the setting range at user level for setpoints as well as for min. and max. temperature limits.

Settings:

Value Setting Factory

For EA and SA regulation

Setpoint, min

Setpoint, max

For EA regulation

Min SA, min

Max SA, min

Min SA, max

Max SA, max

For ERS regulation 1

Breakpoint, min

Breakpoint, max

EA/SA Diff, min

EA/SA Diff, max

0-30°C

10-40°C

0-20°C

8-20°C

16-50°C

16-50°C

12-26°C

12-26°C

1-7°C

1-7°C

15°C

40°C

13°C

18°C

25°C

45°C

15°C

23°C

1°C

5°C

INSTALLATION

HAND TERMINAL

*HANDTERMINAL SET*

LANGUAGE

AIR FLOW UNIT

MIN/MAX SETTING

BASE SETTINGS

13.4 Base Settings

Used for saving and resetting the settings.

BASE SETTINGS 1 and 2 are two levels where the user him-/herself saves current settings and activates them when needed.

The two base settings can be used as a summer setting and as a winter setting of the air handling unit.

The values in INITIAL SETTING 1 and 2 saved in the internal memory can be transferred to the external MMC memory by entering SAVE SETTINGS. EXTERNAL MEMORY.

The values can be transferred from the external MMC memory to the internal memory by entering FETCH

EXTERNAL MEMORY.

INITIAL SETTING 1 and 2 must be downloaded into the control unit by entering INTERNAL MEMORY, LOAD NEW

SETTINGS.

Under SAVE EXTERNAL MEMORY, there is a function that can save current settings to the MMC memory.

Current settings can be stored directly in the control unit under FETCH EXTERNAL MEMORY

FACTORY SETTINGS resets the air handling unit’s settings to the original values it had when it was supplied (See

19.2 Commissioning Record).

The preset values for communication and alarm priority are not reset if the factory settings are reinstated.

Settings:

Save/fetch setting

Save setting – internal memory Save new setting 1

Save new setting 2 external memory Save setting 1

Save setting 2

Save current setting

EA = Extract air

SA = Supply air

ERS= Extract air temperature-related supply air temperatureregulation

Load/fetch – internal memory Load new setting 1

Load new setting 2 external memory Fetch setting 1

Fetch setting 2

Fetch current setting

Factory setting Activate

We reserve the right to alter specifi cations without notice.

www.swegon.com 45

GB.GOLDSKD2.100615

14 COMMUNICATION

Provision for communication and supervision is integrated as standard into the GOLD. The unit is ready to be connected via EIA-232, EIA-485 and Ethernet.

For particulars of connecting and wiring the air handling unit, see Section 19.5 Wiring to Terminals,

Sizes 04-80.

Communication can also be established via Ethernet without software other than an ordinary web browser such as Internet Explorer.

Further information about interfaces, protocol and confi guration is available at www.

swegon.com.

14.1 EIA-232

Protocol and settings for EIA-232 is specifi ed.

Settings:

Modbus RTU

GSM-modem

Analogue modem

Address, speed, parity, stop bits

14.2 EIA-485

Protocol and settings for EIA-485 is specifi ed.

Settings:

Modbus RTU

Metasys N2 OPEN

Lon Works/TREND

Exolinc

Address, speed, parity, stop bits

14.3 Ethernet

Protocol and settings for Ethernet is specifi ed.

Settings:

INSTALLATION

COMMUNICATION

DHCP SERVER

(active or inactive)

IP ADDRESS

(static or dynamic)

SUBNETM.

GATEWAY

DNS-SERVER

MODBUS TCP CLIENT

(IP address and mesh)

(active or inactive, Device ID,

*COMMUNICATION*

EIA-232

EIA-485

ETHERNET

15 SERVICE LEVEL

A code and special training are required for access to this menu group.

INSTALLATION

SERVICE LEV.

*SERVICE LEV.*

CODE:0000

46 www.swegon.com

We reserve the right to alter specifi cations without notice.

GB.GOLDSKD2.100615

16 MAINTENANCE

Warning

Before carrying out any work, make sure that the power supply to the unit has been isolated.

A

16.1 Filter Change

The fi lters should be changed when the fi lter alarm has been activated.

Order new fi lters from Swegon or its representative!

State the size of the GOLD unit and whether the change involves one or two air directions.

16.1.1 To remove the Filters

Pull out the handles (A) to free the fi lters from the fi lter holder.

Withdraw the fi lters.

It is advisable to clean inside the fi lter space while the fi lters are gone.

16.1.2 To fi t new fi lters

Insert the fi lters into the fi lter holder. At the same time, stretch out the fi lter bags, so that they will not get caught, hurt or become folded.

Insert the fi lters as far as possible into the unit and press lightly on the fi lter frames, so that they will fi t tightly.

Push in the handles (A) so that the fi lters are clamped in place in the fi lter holder.

Carry out a fi lter calibration as described in Section 6.4.2.

16.2 Cleaning and Inspection

16.2.1 General

Clean the interior of the air handling unit as the need arises.

Inspect the air handling unit thoroughly at the same time that you replace the fi lters or at least twice a year.

16.2.2 Filter Space

Cleaning is most appropriate when you change the fi lters.

16.2.3 Heat exchangers

Check at least twice a year whether cleaning is necessary.

The cleaning work is carried out from the fi lter space.

Rotary heat exchanger

The heat exchanger should preferably be cleaned by vacuum cleaning with a soft nozzle to prevent damaging the air passages in the rotor.

Turn the rotor by hand to enable you to vacuum clean its entire surface.

If the heat exchanger is substantially fouled, it can be blown clean with compressed air.

If necessary, the heat exchanger can be withdrawn from the unit casing and washed with degreasing solvent. Only service personnel trained by Swegon shall be permitted to use this cleaning method.

FABRIC SEAL

Lift up the fabric seal and inspect its underside. Clean if needed by brushing or vacuum cleaning.

If the fabric seal is worn or substantially fouled, it should be replaced. Do not lubricate it!

A

BELT TENSION

Replace the drive belt if it feels loose or worn and slightly slips if it meets resistance. Contact service personnel trained by

Swegon!

Plate heat exchanger

Always clean against the regular direction of airfl ow.

Cleaning shall only be done by blowing with compressed air, vacuum cleaning with a soft nozzle or wet cleaning with water and/or solvent. Before you begin cleaning, cover adjacent functional sections to protect them.

If cleaning solvent is used, do not use solvent that will corrode aluminium or copper. Swegon’s cleaning agent is recommended.

This cleaning agent is sold by Swegon Service.

Inspect the condensate drain to make sure that it isn’t clogged.

The by-pass and shut-off dampers do not require maintenance.

Coil heat exchanger

Make sure that the coils are purged of air. If a droplet eliminator is fi tted, remove it and fl ush it clean with water.

Always clean against the regular direction of airfl ow.

Cleaning shall only be done by blowing with compressed air, vacuum cleaning with a soft nozzle or wet cleaning with water and/or solvent. Before you begin cleaning, cover adjacent functional sections to protect them.

If cleaning solvent is used, do not use solvent that will corrode aluminium or copper. Swegon’s cleaning agent is recommended.

This cleaning agent is sold by Swegon Service.

While cleaning, check the content of glycol in the water and the condition of the coil for tightness. Also check that the condensate drain is not clogged.

16.2.4 Fans and Fan Space

Inspect and clean the fan impellers to remove possible dirt deposits.

Check the impeller to make sure that it is not out of balance.

Clean or brush off the fan motor. It can also be cleaned by carefully wiping it with a damp cloth that has been dipped in a solution of water and dishwashing detergent.

Clean the fan space, if needed.

16.3 Performance Checks

General performance checks should be carried out in conjunction with fi lter change or at least once a year.

It is then appropriate to compare the current performance values of the unit with the Commissioning Record. Eventual deviations should be remedied.

We reserve the right to alter specifi cations without notice.

www.swegon.com 47

GB.GOLDSKD2.100615

16.4 To change the pump, pipework package, GOLD CX, sizes 35-80

Before the pump can be replaced, the coils will have to be partially emptied.

An electrician or a duly qualifi ed person skilled in electrical installations is required to disconnect and connect the power supply cable to the pump.

To empty the coils:

It isn’t necessary to completely empty the system; it will be suffi cient to empty to a level just below the pump.

For the variants in which the pump is arranged above the expansion vessel, the system can be emptied from the header by the expansion vessel.

For the other variants, the venting or drain nipples on the lower coils should be used for emptying.

Open the venting valve on the upper coil as well.

To remove the old pump:

Remove the insulation material around the pump and make note of the direction of liquid fl ow.

Disconnect the electrical connections from the pump.

Remove the bolts on the pump’s fl ange connections and remove the pump.

Remove the old gaskets and clean the surfaces where they have been seated.

To mount the new pump:

Fit the new gaskets.

Check the direction of fl ow of the new pump and mount it so that the direction of liquid fl ow will be the same as before.

Tighten the bolts on the pump’s fl ange connections.

Wire the electrical connections to the pump.

To refi ll the coils:

When refi lling, fi ll with glycol of the type used in brine systems; not the type used in motor vehicles!

The glycol content is always 30% from the factory.

The total volume of glycol/water is 122 litres in size 35/40,

176 litres in size 50/60 and 231 litres in size 70/80 units.

Open the valve on the header by the expansion vessel and connect the fi lling hose.

Start the external fi lling pump and refi ll the coils. The fi lling pump should hold a pressure of approx 1 bar .

Use the venting valves to vent both the upper and lower coils.

Close the lower venting valve when liquid, free of air bubbles, fl ows out.

Close the upper venting valve when liquid, free of air bubbles, fl ows out.

Start the internal circulation pump and make sure that the direction of rotation is correct.

The green LED on the terminal box of the pump shall be lit while the pump is operating. If the red LED is lit, the pump impeller is rotating in the wrong direction.

Operate the unit for approx. 10 minutes, then vent both the upper and lower coils.

Close the fi lling valve and switch off the pump.

Remove the hoses and re-insulate the pump.

Operate the unit for approx. 1 week, then vent both the upper and lower coils again.

17 ALARMS AND FAULT TRACING

17.1 General

Alarms are indicated by an alarm text and fl ashing LED in the hand-held micro terminal.

Fire alarms and frost alarms are shown in all the menu images. Other alarms are only shown if you are in the

Main menu.

Active, but time-delayed alarms can be viewed quickly at

USER LEVEL under ALARMS. The 10 most recently initiated alarms can also be read in this menu.

A fault can be traced by examining the function or function section indicated in the alarm text.

Faults can also be traced via the READINGS menu or the

MANUAL TEST menu at Installation level.

If the fault cannot immediately be remedied:

Consider whether the air handling unit can continue to operate until the fault has been remedied. Choose to block the alarm and/or to change it from STOP to OPERA-

TION (See Section 12, Alarm settings).

17.1.1 A and B-alarms

Type A alarms transmit an alarm signal to the alarm relay A output (control unit terminals 15-16).

Type B alarms transmit an alarm signal to the alarm relay B output (control unit terminals 17-18).

From these terminals, alarms can be forwarded with different priority.

The alarm relays can be selected to have normally open or normally closed function.

17.1.2 Resetting of alarms

Alarms that require manual resetting can be reset from the hand-held micro terminal. Select RESET in the current alarm menu.

Alarms that reset themselves automatically do so as soon as the fault has been remedied.

Alarms can also be reset via a communication network.

17.1.3 Changing Alarm Settings

See Section: 12 Alarm Settings.

17.1.4 Start up after a power failure

Automatic or manual start up after a power failure can be selected.

48 www.swegon.com

We reserve the right to alter specifi cations without notice.

GB.GOLDSKD2.100615

17.2 Alarm Descriptions with Factory Settings

Alarm text

Function

Priority Stop

0=blocked 0=In operat.

A=A alarm 1=Stop

B=B alarm

Indication

LED

0=Off

1=On

Delay Resetting

s=seconds M=manual

m=minutes A=automatic

1

EXTERNAL FIRE ALARM TRIPPED

For the fi re protection function connected to terminals 54-55.

2 INTERNAL FIRE ALARM TRIPPED

The air handling unit’s supply air sensor measures a temperature more than 70 °C and/or its extract air sensor measures a temperature more than 50 °C.

The function must be activated manually in the

ALARM SETTINGS menu.

3 FROST PROTECTION BELOW ALARM LIMIT

The anti-frosting monitor sensor measures a temperature lower than the preset temperature. Factory setting: 7 °C.

4 R.HX.SPEED MONITOR TRIPPED

No impulses from the rotation detector are registered with the heat exchanger controller. The air handling unit will be switched out only if the outdoor temperature drops below 5 °C.

5 FROST PROTECTION SENSOR DEFECTIVE

The anti-frosting monitor temperature sensor is lacking, is not connected or is faulty; an air heater for hot water is connected.

6

7

SUPPLY AIR TEMP SENSOR DEFECTIVE

EXTRACT AIR TEMP SENSOR DEFECTIVE

The supply air/extract air temperature sensor is not connected or is faulty.

(Not applicable if only GOLD SD supply air or extract air handling units are installed, see Alarm No. 82)

8 OUTDOOR AIR TEMP SENSOR DEFECTIVE

The outdoor air temperature sensor is not connected or is faulty. (Not applicable to GOLD SD units, see

Alarm No. 81)

9 NO COMMUNICATION TO R.HX. CONTROLLER

The air handling unit’s control unit cannot establish correct communication with the heat exchanger controller.

10

11

12

13

14

15

NO COMMUNICATION TO SA FREQUENCY CONV.

NO COMMUNICATION TO EA FREQUENCY CONV.

The air handling unit’s control unit cannot establish correct communication with frequency inverter.

OVER CURRENT IN SA FREQUENCY CONV.

OVER CURRENT IN EA FREQUENCY CONV.

Current above the normal level is supplied to the motors.

UNDER VOLTAGE IN SA FREQUENCY CONV.

UNDER VOLTAGE IN EA FREQUENCY CONV.

Voltage below the normal level is supplied.

A****

A ****

A ****

A

A ****

A

A

B

A***

A ***

A ***

A ***

A ***

A ***

A ***

1*

1*

1*

0**

1*

1

1

0

1

1

1

1

1

1

1

16

17

OVER VOLTAGE IN SA FREQUENCY CONV.

OVER VOLTAGE IN EA FREQUENCY CONV.

Voltage above the normal level is supplied.

A ***

A ***

1

1

* Not adjustable, always stops the air handling unit.

** Not adjustable, stops the air handling unit if the temperature to below +5 ºC.

*** Blocked if the hand terminal does not display the main menu.

**** Cannot be blocked.

We reserve the right to alter specifi cations without notice.

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

3 s

3 s

3 s

3 s

3 s

3 s

3 s

3 s

10 s

10 s

10 s

3 s

3 s

3 s

3 s

3 s

3 s

M

M

M

M

A

A

A

A

A

A

A

M

M

M

M

M

M www.swegon.com 49

GB.GOLDSKD2.100615

Alarm text

Function

Priority Stop

0=blocked 0=In operat.

A=A alarm

B=B alarm

1=Stop

Indication

LED

0=Off

1=On

Delay Resetting

s=seconds M=manual

m=minutes A=automatic

18

19

20

21

OVER TEMPERATURE IN SA FREQUENCY CONV.

OVER TEMPERATURE IN EA FREQUENCY CONV.

High temperature inside the inverter.

NO COMMUNICATION TO SA-2 FREQUENCY CONV.

NO COMMUNICATION TO EA-2 FREQUENCY CONV.

The air handling unit’s control unit cannot establish correct communication with slave frequency inverter.

Applicable to only sizes 50-80.

22

23

24

25

26

27

28

29

OVER CURRENT IN SA-2 FREQUENCY CONV.

OVER CURRENT IN EA-2 FREQUENCY CONV.

Current above the normal level is supplied to slave motor.

Applicable to sizes 50-80 only

UNDER VOLTAGE IN SA-2 FREQUENCY CONV.

UNDER VOLTAGE IN EA-2 FREQUENCY CONV.

Voltage below the normal level is supplied to slave frequency inverter.

Applicable to sizes 50-80 only.

OVER VOLTAGE IN SA-2 FREQUENCY CONV.

OVER VOLTAGE IN EA-2 FREQUENCY CONV.

Voltage above the normal level is supplied to slave frequency inverter.

Applicable to sizes 50-80 only.

OVER TEMPERATURE IN SA-2 FREQUENCY CONV.

OVER TEMPERATURE IN EA-2 FREQUENCY CONV.

High temperature inside the slave frequency inverter.

Applicable to sizes 50-80 only

30 EXT.EA/ROOM TEMP SENSOR DEFECTIVE

Temperature sensor in extract air duct or room is not connected (terminals 40-41) or is faulty; or has been selected with communication.

Applicable if the External sensor, extract air/room or

Intermittent night-time heating function is selected.

31 EXT.OUTDOOR TEMP SENSOR DEFECTIVE

Temperature sensor for outdoor temperature is not connected (terminals 38-39) or is faulty; or has been selected with communication.

Applicable if the External outdoor sensor function is selected.

32 PLATE HEAT EXCH SENSOR FAULTY

The temperature sensor in the exchanger cube for the anti-frosting monitor is absent or is faulty.

33 COIL HEAT EXCH SENSOR FAULTY

The temperature sensor on the coil heat exchanger’s pipework package for the anti-frosting monitor is absent or is faulty.

34 OVER CURRENT IN R.HX. CONTROLLER

Current above the normal level is supplied to the rotary heat exchanger’s drive motor.

35 UNDER VOLTAGE IN R.HX. CONTROLLER

Feed voltage (25V) is supplied to the rotary heat exchanger’s drive motor.

36 OVER VOLTAGE IN R.HX. CONTROLLER

Voltage above the normal level (55 V) is supplied to the rotary heat exchanger’s drive motor.

A ***

A ***

A ***

A ***

A ***

A ***

A ***

A ***

A ***

A ***

A ***

A ***

A ***

B ***

A ***

A ***

A ***

A ***

A ***

*** Blocked if the hand terminal does not display the main menu.

50 www.swegon.com

1

1

1

1

1

1

1

1

1

1

1

1

1

0

0

0

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

3 s

3 s

10 s

10 s

3 s

3 s

3 s

3 s

3 s

3 s

3 s

3 s

3 s

3 s

3 s

3 s

3 s

3 s

3 s

M

M

A

A

M

M

M

M

M

M

M

M

A

A

A

A

M

M

M

We reserve the right to alter specifi cations without notice.

GB.GOLDSKD2.100615

Alarm text

Function

37 OVER TEMPERATURE IN R.HX. CONTROLLER

High internal temperature (90°C for the rotary heat exchanger’s controller).

38 R.HX. PRESSURE DROP ABOVE ALARM LIMIT

The heat exchanger’s defrosting function has operated for the full max period 6 times during one

24-hour period.

39 EL.HEATING COIL TRIPPED

The thermal overload protection has tripped or is not connected.

40 EXTRACT AIR TEMP BELOW ALARM LIMIT

The extract air temperature is below preset alarm limit for more than 20 minutes.

41 SUPPLY AIR TEMP BELOW SETPOINT

The supply air temperature is below the preset setpoint (for ERS and Supply air regulation) or Min

SA temp (for Extract air regulation) longer than 20 minutes.

42 EXT. ALARM No.1 TRIPPED

External alarm, connected to control unit terminals

50-51, has tripped.

43 EXT. ALARM No.2 TRIPPED

External alarm, connected to control unit terminals

52-53, has tripped..

44

45

SA DUCT PRESSURE BELOW SETPOINT

EA DUCT PRESSURE BELOW SETPOINT

Pressure in supply/extract air duct, if pressure transducers are connected, has been more than 10% below its setpoint for more than 20 minutes.

46

47

48

49

SA DUCT PRESSURE ABOVE SETPOINT

EA DUCT PRESSURE ABOVE SETPOINT

Pressure in supply/extract air duct, if pressure transducers are connected, has been more than 10% above its setpoint for more than 20 minutes.

SUPPLY AIRFLOW BELOW SETPOINT

EXTRACT AIRFLOW BELOW SETPOINT

The supply/extract airfl ow has been more than 10% below its setpoint for more than 20 minutes.

50

51

52

53

SUPPLY AIRFLOW ABOVE SETPOINT

EXTRACT AIRFLOW ABOVE SETPOINT

The supply/extract airfl ow has been more than 10% above its setpoint for more than 20 minutes.

SUPPLY AIR FILTER DIRTY

EXTRACT AIR FILTER DIRTY

The pressure across the supply /extract air fi lters has exceeded the preset alarm limit for more than 10 minutes.

Priority Stop

0=blocked 0=In operat.

A=A alarm

B=B alarm

1=Stop

A *** 1

Indication

LED

0=Off

1=On

1

Delay

s=seconds M=manual

m=minutes A=automatic

3 s

Resetting

M

B ***

A ***

A ***

A ***

A ***

B ***

B ***

B ***

B ***

B ***

B ***

B ***

B ***

B ***

B ***

B ***

0

1

1

1

1

0

0

0

0

0

0

0

0

0

0

0

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

3 s

3 s

20 m

20 m

Set time

Set time

20 m

20 m

20 m

20 m

20 m

20 m

20 m

20 m

10 m

10 m

M

M

M

M

M

M

M

M

M

M

M

M

M

M

M

M

*** Blocked if the hand terminal does not display the main menu.

We reserve the right to alter specifi cations without notice.

www.swegon.com 51

GB.GOLDSKD2.100615

Alarm text

Function

54 SERVICE PERIOD PAST ALARM LIMIT

The preset service period has expired.

If the alarm is RESET via the hand-held micro terminal, the alarm will be initiated again after 7 days.

A new service period can be set in the ALARM SET-

TINGS menu.

55

56

57

58

59

60

NO COMM. SA AIR FLOW PRESSURE SENSOR

NO COMM. EA AIR FLOW PRESSURE SENSOR

The air handling unit’s control unit cannot establish correct communication with the supply/extract air fl ow pressure transducer.

NO COMM. SA FILTER PRESSURE SENSOR

NO COMM. EA FILTER PRESSURE SENSOR

The air handling unit’s control unit cannot establish correct communication with the supply/extract air fi lter pressure transducer.

NO COMM. SA DUCT PRESSURE SENSOR

NO COMM. EA DUCT PRESSURE SENSOR

The air handling unit’s control unit cannot establish correct communication with the pressure transducer connected in the supply/extract air ducting.

Applicable to SA /EA pressure regulation only.

61 NO COMM. R.HX. PRESSURE SENSOR

The air handling unit’s control unit cannot establish correct communication with the pressure transducer connected for the heat exchanger.

Applicable to the defrosting function only.

62-71 NO COMMUNICATION TO I/O-MODUL NR 1–9

The air handling unit’s control unit cannot establish correct communication with the connected I/O module 1–9

72 Correct communication can be established between the CPU circuit card and the control unit*s I/O processor.

73 PLATE HEAT EXCH, DAMPER MOTOR FAULTY

The damper motor does not move to the right position. The position-confi rming output signal from the damper is not equivalent to the input control signal.

74 COIL HEAT EXCH, PUMP TRIPPED

No response is received from the contactor. The motor prot. or the contactor may be faulty.

75 SUPPLY AIR HUMIDITY SENSOR FAULTY

The communication with the humidity sensor in the supply air duct is faulty or the sensor reading is erroneous.

76 EXTRACT AIR HUMIDITY SENSOR FAULTY

The communication with the humidity sensor in the extract air duct is faulty or the sensor reading is erroneous.

Priority Stop

0=blocked 0=In operat.

A=A alarm

B=B alarm

1=Stop

B *** 0

Indication

LED

0=Off

1=On

1

Delay

s=seconds M=manual

m=minutes A=automatic

Set time

Resetting

M

A ***

A ***

B ***

B ***

A ***

A ***

B ***

B ***

A

A ***

A ***

A ***

A ***

1

1

0

0

1

1

0

0

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

10 s

10 s

10 s

10 s

10 s

10 s

10 s

10 s

30 s

10 m

20 s

10 s

10 s

A

A

A

A

A

A

A

A

A

M

M

A

A

*** Blocked if the hand terminal does not display the main menu.

52 www.swegon.com

We reserve the right to alter specifi cations without notice.

GB.GOLDSKD2.100615

Alarm text

Function

Priority Stop

0=blocked 0=In operat.

A=A alarm

B=B alarm

1=Stop

Indication

LED

0=Off

1=On

Delay Resetting

s=seconds M=manual

m=minutes A=automatic

77 SPARE

78 HUMIDITY SENSOR, HEAT EXCH FAULTY

Communication with the humidity sensor in the extract air upstream of the heat exchanger is faulty or the sensor reading is erroneous.

79 COIL HEAT EXCH, VALVE FAULTY

The valve actuator does not move to the right position. The position-confi rming output signal from the actuator is not equivalent to the input control signal.

80 TEMPERATURE MONITOR - BELOW ALARM LIMIT

The temperature reading from the sensor in the inlet of the supply air fan is below the preset alarm limit.

81 SUPPLY AIR-D TEMP SENSOR FAULTY (RX/PX/CX)

The temperature sensor in the supply air fan inlet has no comm. or its reading is erroneous.

OUTD. AIR TEMP SENSOR DEFECTIVE (SD)

The sensor for outdoor temperature is not connected or is faulty.

82 EXTRACT AIR-D TEMP SENSOR FAULTY

Air handling unit with coil or plate heat exch.

The temperature sensor in the extract air fan inlet has no comm. or its reading is erroneous.

Air handling unit with rotary heat exch.

Exhaust air regulation has been selected, but the temperature sensor in the exhaust air is not connected or is faulty.

SA SENSOR DEFECTIVE (SD, supply AHU only)

EA SENSOR DEFECTIVE (SD, extract AHU only)

The sensor for supply air/extract air temperature is not connected or is faulty.

83 SA PREFILTER FOULED

The pressure across the supply air prefi lter has constantly exceeded the preset alarm limit for 0 minutes.

84 EA PREFILTER FOULED

The pressure across the extract air prefi lter has constantly exceeded the preset alarm limit for 0 minutes.

85 COOLDX, C1 TRIPPED

No contactor replay received at DI1 I/0-module 6 in cooling unit. The motor protection or the pressure switch may have tripped.

86 COOLDX, C2 TRIPPED

No response is received from the contactor at DI2

I/0-modul 6 in cooling unit. The motor prot. or the pressure switch may have tripped.

87 COOLDX C1 TOO MANY RESTARTS

Compressor 1 has started more than 20 times in 2 hours, due to a tripped in-service pressure switch.

88 COOLDX C2 TOO MANY RESTARTS

Compressor 2 has started more than 20 times in 2 hours, due to a tripped in-service pressure switch.

B ***

A ***

A ***

B ***

B

B ***

A

A

B ***

B ***

A

A

A

A

0

1

1

0

0

0

1

1

0

0

0

0

1

1

1

1

1

1

1

1

!

1

1

1

1

1

1

1

10 s

10 m

30 s

10 s

3 s

10 s

3 s

3 s

10 m

10 m

20 s

20 s

3 s

3 s

A

M

A

A

A

A

A

A

M

M

M

M

M

M

*** Blocked if the hand terminal does not display the main menu.

We reserve the right to alter specifi cations without notice.

www.swegon.com 53

GB.GOLDSKD2.100615

Alarm text

Function

89 NO COMM. SA PREFILTER PRESS. SENSOR

The air handling unit’s control unit cannot establish correct communication with supply air prefi lter pressure sensor.

90 NO COMM. EA PREFILTER PRESS. SENSOR

The air handling unit’s control unit cannot establish correct communication with extract air prefi lter pressure sensor.

91 FROST PROTECTION, PREHEATING, BELOW ALARM LIMIT

The sensor for the frost protection monitor, preheating, has measured a temperature lower than the preset temperature. Factory setting: 7 °C.

92 FROST PROTECTION PREHEATING SENSOR DEFECTIVE

The sensor for the frosting protection monitor, preheating, is lacking, is not connected or is faulty, if an air heater for hot water is connected.

93 PREHEATING SENSOR DEFECTIVE

The sensor for preheating is lacking, is not connected or is faulty, if an air heater for hot water is connected.

94 EL. AIR HEATER, PREHEATING, TRIPPED

The thermal overload protection for the connected electric air preheater, has tripped or is not connected.

95 PREHEATING BELOW SETPOINT

The preheating temperature is below the preset setpoint (for ERS and Supply air control) or Min SA temp

(for Extract air control) longer than 0 minutes.

96 SPARE

97 NO COMMUNICATION ReCO PRESSURE SENSOR

The air handling unit’s control unit cannot establish correct communication with the fl ow pressure sensor for ReCO.

98 ReCO DAMPER MOTOR FAULTY

The damper motor does not actuate damper to the right position. The position-confi rming output signal from the damper is not equivalent to the input control signal.

99 TIME LOCK TRIPPED

Contact Swegon or their representative.

Priority Stop

0=blocked 0=In operat.

A=A alarm

B=B alarm

1=Stop

B*** 0

Indication

LED

0=Off

1=On

1

B***

A

A

A

A***

A***

A***

A***

0

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

100-

101

SPARE

102 COOLING VALVE I/O-7 DEFECTIVE

Controls of the Cooling valve do not obtain the same signal on AI 1 as on AU1 on I/O-module.

103 HEATING VALVE I/O-7 DEFECTIVE

Controls of the Heating valve do not obtain the same signal on AI 2 as on AU2 on I/O-module

104 COOL. CIRCUIT PUMP I/O-7 TRIPPED.

Controls of the cooling circuit pump do not obtain correct signal according to set function.

B***

A***

B***

1

1

1

0

0

0

Delay

s=seconds M=manual

m=minutes A=automatic

10 s

10 s

3 s

3 s

3 s

3 s

20 m

10 s

10 m

–****

10 m

10 m

30 s

Resetting

A

A

M

A

A

M

M

A

M

M

M

M

M

*** Blocked if the hand terminal does not display the main menu.

**** Adjustable: 0-99 months.

54 www.swegon.com

We reserve the right to alter specifi cations without notice.

GB.GOLDSKD2.100615

Alarm text

Function

105 HEAT. CIRCUIT PUMP I/O-7 TRIPPED

Controls of the heating circuit pump do not obtain correct signal according to set function.

106 COOLING WATER TEMP I/O-7 BELOW SET POINT

Temperature for cooling water control on I/O module is continuously 7°C below its current set point.

107 HEATING WATER TEMP I/O-7 BELOW SET POINT.

Temperature for heating water control on I/O module is continuously 7°C below its current set point.

108 COOLING WATER TEMP I/O-7 ABOVE SET POINT

Temperature for cooling water control on I/O module is continuously 7°C above its current set point.

109 HEATING WATER TEMP I/O-7 ABOVE SET POINT

Temperature for heating water control on I/O module is continuously 7°C above its current set point.

110 COOLING WATER TEMP SENSOR I/O-7 DEFECTIVE

Obtained if the cooling water temperature sensor temp is not connected or is defective.

111 HEATING WATER TEMP SENSOR I/O-7 DEFECTIVE

Obtained if the heating water temperature sensor is not connected or is defective.

112-

134

SPARE

135 SA FAN MOTOR BLOCKED

Motor shaft does not rotate during start up.

136 EA FAN MOTOR BLOCKED

Motor shaft does not rotate during start up.

137 SA-2 FAN MOTOR BLOCKED

Motor shaft does not rotate during start up.

138 EA-2 FAN MOTOR BLOCKED

Motor shaft does not rotate during start up.

139 FLUCTUATION VOLTAGE BETWEEN THE PHASES, SA

High voltage difference between the phases

(3-phase, 400 V), which causes rippling.

140 FLUCTUATION VOLTAGE BETWEEN THE PHASES, EA

High voltage difference between the phases

(3-phase, 400 V), which causes rippling.

141 FLUCTUATION VOLTAGE BETWEEN THE PHASES,

SA-2

High voltage difference between the phases

(3-phase, 400 V), which causes rippling.

142 FLUCTUATION VOLTAGE BETWEEN THE PHASES,

EA-2

High voltage difference between the phases

(3-phase, 400 V), which causes rippling.

Priority Stop

0=blocked 0=In operat.

A=A alarm

B=B alarm

1=Stop

A*** 1

Indication

LED

0=Off

1=On

1

Delay

s=seconds M=manual

m=minutes A=automatic

30 s

Resetting

M

B***

A***

0***

0***

B

A

A***

A***

A***

A***

A***

A***

A***

A***

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

30 m

30 m

30 m

30 m

3 s

3 s

3 sec.

3 sec.

3 sec.

3 sec.

3 sec.

3 sec.

3 sec.

3 sec.

M

M

M

M

A

A

M

M

M

M

M

M

M

M

We reserve the right to alter specifi cations without notice.

www.swegon.com 55

GB.GOLDSKD2.100615

Alarm text

Function

143 NO COMMUNICATION W CONTROL OPTIMIZE

The AHU control unit cannot establish correct communication with CONTROL Optimize.

144-

149

NO COMMUNICATIONI/O-MODULE No. A-F

The air handling unit’s control unit cannot establish correct communication with the connected I/O module A–F

150 FROST PROTECTION, EXTRA ZONE, BELOW ALARM LIMIT

The sensor for the frost protection monitor, extra zone, has measured a temperature lower than the preset temperature. Factory setting: 7 °C

151 FROST PROTECTION, EXTRA ZONE, FAULTY

The sensor for the frosting protection monitor, extra zone, is lacking, is not connected or is faulty, if an air heater for hot water is connected.

152 SUPPLY AIR SENSOR, EXTRA-ZONE, FAULTY

The supply air sensor for the extra zone, is lacking, is not connected or is faulty, if an air heater for hot water is connected.

153 EXTRACT AIR SENSOR, EXTRA-ZONE, FAULTY

The extract air sensor for the extra zone, is lacking, is not connected or is faulty, if an air heater for hot water is connected.

154 EL. AIR HEATER, EXTRA-ZONE, FAULTY

The thermal overload protection for the connected electric air heater for the extra zone has tripped or is not connected.

155 EA TEMP IN EXTRA ZONE BELOW ALARM LIMIT

The extract air temperature in the extra zone is below preset alarm limit for more than 0 minutes.

156 SA TEMP IN EXTRA ZONE BELOW ALARM LIMIT

The supply air temperature in the extra zone is below the preset setpoint (for ERS and Supply air control) or Min SA temp (for Extract air control) longer than

0 minutes.

157-

158

SPARE

159 NO COMMUNICATION, COOL DXS MODULE

The air handling unit’s control unit cannot establish correct communication with the connected I/O module of the COOL DXS

160 COOL DX/DXS, LOW PRESSURE, BELOW ALARM

LIMIT

The sensor for low pressure measures pressure lower than the preset limit.

161 COOL DX/DXS, HIGH PRESSURE, ABOVE ALARM

LIMIT

The sensor for high pressure measures pressure higher than the preset limit.

162 COOL DX/DXS LOW PRESSURE SENSOR DEFECTIVE

The sensor for low pressure is not connected or is defective.

163 COOL DX/DXS HIGH PRESSURE SENSOR DEFECTIVE

The sensor for high pressure is not connected or is defective.

Priority Stop

0=blocked 0=In operat.

A=A alarm

B=B alarm

1=Stop

B*** 0

Indication

LED

0=Off

1=On

1

B***

A

A

A

A

A

A***

A***

A***

A

A

A

A

A

0

1

1

1

1

1

1

1

1

0

0

0

0

0

1

1

1

1

1

1

1

1

1

1

1

1

1

1

Delay

s=seconds M=manual

m=minutes A=automatic

10 s

10 s

3 s

3 s

3 s

3 s

3 s

20 m

20 m

3 s

3 s

3 s

3 s

3 s

Resetting

A

A

M

A

A

A

A

M

M

M

M

M

M

M

M

*** Blocked if the hand terminal does not display the main menu.

56 www.swegon.com

We reserve the right to alter specifi cations without notice.

GB.GOLDSKD2.100615

Alarm text

Function

164 COOL DX/DXS K1 HAS TRIPPED

No contact reply is obtained for K1 on the I/0 module of the COOL DX/DXS. The motor protection or pressure switch may have tripped.

165 COOL DX/DXS K2 HAS TRIPPED

No contact reply is obtained for K2 on the I/0 module of the COOL DX/DXS. The motor protection or pressure switch may have tripped.

166 COOL DX/DXS K3 HAS TRIPPED

No contact reply is obtained for K3 on the I/0 module of the COOL DX/DXS. The motor protection or pressure switch may have tripped.

167 COOL DX/DXS K1 TOO MANY RESTARTS

COOL DX/DXS Compressor 1 has done too many restarts.

168 COOL DX/DXS K2 TOO MANY RESTARTS

COOL DX/DXS Compressor 2 has done too many restarts. starter.

Priority Stop

0=blocked 0=In operat.

A=A alarm

B=B alarm

1=Stop

A 0

Indication

LED

0=Off

1=On

1

A

A

A

A

0

0

0

0

1

1

1

1

169 COOL DX/DXS K3 TOO MANY RESTARTS

COOL DX/DXS Compressor 3 has done too many restarts.

170 COOL DXS FAN HAS TRIPPEDThe thermostatic contacts in the COOL DXS condenser fan motor may have tripped.

A

A

0

0

1

1

Delay

s=seconds M=manual

m=minutes A=automatic

10 s

10 s

10 s

3 s

3 s

3 s

3 s

Resetting

M

M

M

M

M

M

M

171 COOL DX/DXS INCORRECT PHASE SEQUENCEThe phase-sequence protection for the voltage supplied to the COOL DX/DXS has tripped.

A 0 1 3 s M

172 OUTD.AIR TEMP.SENS COOL DX DEFECT

The sensor for low outdoor air temperature readings is not connected or is defective.

173-

199

SPARE

B 0 1 3 sec.

A

We reserve the right to alter specifi cations without notice.

www.swegon.com 57

GB.GOLDSKD2.100615

18 INFORMATIVE MESSAGES

Informative messages are displayed in the hand-held micro terminal. Informative messages are displayed only when the user is viewing the Main menu.

Informative messages provide particulars about necessary settings that have not been entered or unfavourable operating scenarios, for instance.

Message No.

1

2

3

4

5

6

7

8

Message Text

FILTER CALIBRATION NOT EXECUTED

The pressure across the fi lters was not calibrated after the fi rst start. Recurrent at 24-hour intervals. The message will not be received after the pressure across the fi lters has been calibrated.

H EXCH CALIBRATION NOT EXECUTED

The pressure across the heat exchanger was not calibrated after the function was activated for the fi rst time.

Recurrent at 24-hour intervals. The message will not be received after the pressure across the heat exchanger has been calibrated.

INCORRECT DIP SWITCH SETTINGS

DIL switches on the control circuit card are set in a forbidden combination.

SPARE

MODEM/E-MAIL ERROR

Error in communication to the modem or error when e-mail is being delivered. The message will be displayed after ten attempts.

PREFILTER CAL NOT EXECUTED

The pressure across the prefi lters was not calibrated after the fi rst start. Recurrent at 24-hour intervals. The message will not be received after the pressure across the prefi lters has been calibrated.

ReCO

2

CALIBRAT NOT EXECUTED

ReCO was not calibrated after the function was activated for the fi rst time. Recurrent at 24-hour intervals. The message will not be received after the RecCO has been calibrated.

INCORRECT ReCO

2

SETTING

Pressure control, slave control or wrong type of air handling unit has been selected. Recurrent at 5-minute intervals

58 www.swegon.com

We reserve the right to alter specifi cations without notice.

GB.GOLDSKD2.100615

19 TECHNICAL DATA

19.1 Dimensions, GOLD RX one-piece unit with rotary heat exchanger

GOLD 04/05, 08

* The air handling unit is supplied without end connection panel if a duct accessory housed in an insulated casing will be connected.

GOLD 12

K

16

50 J 50

GOLD Top 04/05, 08

52

K

52

50

GOLD Top 12

J

16

50

16

* The air handling unit is supplied without end connection panel if a duct accessory housed in an insulated casing will be connected.

52 52

50 J 50

C K C

Size

04/05

Top 04/05

08

Top 08

12

Top 12

A

750

750

800

800

655

655

B

825

995

1199

1199

C

240

276

324

332

D

345

1048

550

550

F

230

825 233.5

1033 237.5

350

995 277.5

440 271 543

280

324

333

We reserve the right to alter specifi cations without notice.

G

460

435

647

533

H

920

920

1085

1085

1295

1295

J

935

935

K

L

1500

1500

1600

551

1600

1860

1196 1860

Ø

315

315

400

400

500

500

Weight, kg

243

247

309

310

518

504 www.swegon.com 59

GB.GOLDSKD2.100615

GOLD 14/20, 25/30

E

M

M

50

52 52

50 50 50

* The air handling unit is supplied without end connection panel if a duct accessory housed in an insulated casing will be connected.

The dimension print shows the connection confi guration for fan arrangement 1. For fan arrangement 2 the connections are mirrorinverted.

GOLD 35/40

34

M

M

52 52

50 50 50 50

* The air handling unit is supplied without end connection panel if a duct accessory housed in an insulated casing will be connected.

The dimension print shows the connection confi guration for fan arrangement 1. For fan arrangement 2 the connections are mirrorinverted.

GOLD 50/60 GOLD 70/80

34

28*

28*

28

76 76

28

76 76

* The air handling unit is supplied without end connection panel if a duct accessory housed in an insulated casing will be connected.

Size

14/20

25/30

35/40

50/60

70/80

A

765

835

948

1050

1250

60 www.swegon.com

B

1400 1136

1600

1990

2318

2637

C

1336

1726

D

550

550

550

570

570

E

208

193

200

150

150

F G H

400 1000 1395

500 1200 1595

600 1400 1985

800 1600 2253

1000 1800 2640

I

298

298

392

423

319

J

109

94

153

115

161

K

200

200

295

360

419

L

2080

2220

2446

2670

3070

M

188

203

240

Weight, kg

625

786

1120

1498

2231

We reserve the right to alter specifi cations without notice.

19.2 Dimensions, GOLD PX one-piece unit with plate heat exchanger

GOLD 04/05, 08

16 52*

GB.GOLDSKD2.100615

180

52

52

28

50

32

50

80 80

* The air handling unit is supplied without end connection panel if a duct accessory housed in an insulated casing will be connected.

GOLD 12

K K

16 52*

50

50 J 50

52 E E 52

50 J

80

D

* The air handling unit is supplied without end connection panel if a duct accessory housed in an insulated casing will be connected.

GOLD 14/20, 25/30

M M

N

50

52 E E 52 50

80

D

* The air handling unit is supplied without end connection panel if a duct accessory housed in an insulated casing will be connected.

Size A

04/05 800

08

12

B

825

C

240

D

345

E

915 995 277.5

440 –

655 1199 324 1200 397

14/20 765 1400 1136 1300 450

25/30 835 1600 1336 1500 550

F

230

271

324

G

460

543

647

H

920

1085

1295

400 1000 1395 298

500 1200 1595 298

I

We reserve the right to alter specifi cations without notice.

J

935

188

203

K

L

2000

– 2230

551 2510

200 2830 208

200 3170 193

M

N

109

94

Ø

315

400

500

Weight, kg

320

420

617

764

1002 www.swegon.com 61

19.3 Dimensions, GOLD CX once-piece unit with coil heat exchangers

GOLD 35/40

GB.GOLDSKD2.100615

N

N

50

50

52 50

250

M

52

50

250

M

* The air handling unit is supplied without end connection panel if a duct accessory housed in an insulated casing will be connected.

The dimension print shows the connection confi guration for fan arrangement 1. For fan arrangement 2 the connections are mirrorinverted.

GOLD 50/60

28*

28

76

76

254

M

* The air handling unit is supplied without end connection panel if a duct accessory housed in an insulated casing will be connected.

GOLD 70/80

27

28*

28

76

76

254

M

* The air handling unit is supplied without end connection panel if a duct accessory housed in an insulated casing will be connected.

Size A B C D

35/40 948 1990 1726 680

50/60 1050 2318

70/80 1250 2637

760

760

E

200

F G H I

600 1400 1985 392

150 800 1600 2253 423

150 1000 1800 2640 319

J

153

115

161

K L M

295 2575 600

360 2860 650

419 3260 800

N

240

Weight, kg

1501

2045

2944

62 www.swegon.com

We reserve the right to alter specifi cations without notice.

19.5 Terminal Connections, Sizes 04-80

Ethernet

GB.GOLDSKD2.100615

Digital inputs, terminals 46-57, are of low voltage type.

Analogue inputs, terminals 30-35, have input impedance 66 k

Ω.

EIA-232/Modem

Terminals Function Remarks

1 and 2

3 and 4

5 and 6

7 and 8

9 and 10

11 and 12

13 and 14

15 and 16

Not used

Not used

Circulation pump, heating

Cooling, on/off, step 1

Cooling, on/off, step 2

In-op. indication, low speed Independent contacts, max 12A/AC1, 5A/AC3, 250VAC. Close when the fans operate at low speed.

In-op. indication, high speed Independent contacts, max 12A/AC1, 5A/AC3, 250VAC. Close when the fans operate at high speed.

Group alarm A (1)

17 and 18 Group alarm B (2)

19 , 20 and 21 In-operation indication

22 , 23 and 24 Damper control

Independent contacts, max 12A/AC1, 5A/AC3, 250VAC. Close when heating is needed.

Independent contacts, max 12A/AC1, 5A/AC3, 250VAC. Close when cooling is needed.

Independent contacts, max 12A/AC1, 5A/AC3, 250VAC. Close when cooling is needed.

Independent contacts, max 12A/AC1, 5A/AC3, 250VAC. Closes or opens (setting) if an A alarm trips.

Independent contacts, max 12A/AC1, 5A/AC3, 250VAC. Closes or opens (setting) if an B alarm trips.

Independent contacts, max 12A/AC1, 5A/AC3, 250VAC. 19 NC, 20 C, 21 NO. Close when AHU is in operation.

230VAC. 22: controlled phase, 23: fi xed phase, 24: zero conductor. 22 is energized while the AHU operations.

25 and 26 Control voltage, output

27, 28 and 29 Connections for EIA-485 network

30 and 31

32 and 33

34 and 35

Supply air boost

Extract air boost

External

36 and 37

38 and 39

Control voltage 230VAC. Max load 1.5A. Interrupted by safety switch and burdens the supply voltage fuse.

27 communication connection A/RT+, 28 communication connection B/RT-, 29 GND/COM.

Input for 0-10VDC. Input signal acts upon the supply air fl ow/pressure setpoint.

Input for 0-10VDC. Input signal acts upon the extract air fl ow/pressure setpoint.

0-10VDC input. Acts on the supply air setpoint if the AHU is operating in the supply air regulation mode. Acts on the extract air setpoint if the AHU is operating in the extract air regulation mode. Effect: ±5°C. If the AHU is operating in the ERS regulation mode, it acts on the EA/SA differential. The differential cannot be <0°C. The

EA/SA differential decreases on an increasing input signal. Can be activated from the hand-held micro terminal.

Output for constant 10VDC. Max. permissible load: 2mA.

38 GND, 39 signal. Connection for externally mounted digital outdoor temperature sensor.

40 and 41

42 and 43

44 and 45

46 and 47

48 and 49

50 and 51

52 and 53

54 and 55

56 and 57

58 and 59

60 and 61

Reference voltage

External outdoor temperature sensor

External EA/room temperature sensor

Variable control, cooling

Control: extra control sequence/recirculation damper

External low speed

External high speed

External alarm 1

External alarm 2

External fi re/smoke function

External stop

Control voltage

Control voltage

40 GND, 41 signal. Connection for externally mounted digital extract air/room temperature sensor.

Output for cooling, 0-10VDC. Max. permissible load: 2mA at 10VDC.

Use of the control output steered by the function selected in the hand-held micro terminal. Max. permissible load: 2mA at 10VDC.

External contact function. Overrides the switch clock from stop to low speed operation.

External contact function. Overrides the switch clock from stop or low speed to high speed operation.

External contact function. Optional normally open/normally closed. External alarm is available in the GOLD.

External contact function. Optional normally open/normally closed. External alarm is available in the GOLD.

External fi re and smoke function. On delivery, this function is fi tted with a jumper. The contacts connected between 54 and 55 are closed while the unit is operating. If they open, the function will trip and initiate an alarm.

Stops the AHU via normally-closed contacts. Fitted with jumper on delivery. AHU operation presupposes connection between 56 and 57. If the connection is interrupted, the AHU will stop.

24VAC control voltage. Terminals 58-61 can bear a combined total load of max 16VA all total. Can be interrupted by safety switch.

24VAC control voltage. Terminals 58-61 can bear a combined total load of max 16VA all total. Can be interrupted by safety switch.

We reserve the right to alter specifi cations without notice.

www.swegon.com 63

GB.GOLDSKD2.100615

19.6 Electrical data

19.6.1 Air handling unit

MIN. POWER SUPPLY TO GOLD ONE-PIECE UNIT WITH ROTARY

(RX), PLATE (PX) OR COIL (CX) HEAT EXCHANGER.

GOLD 04: 1-phase, 3-wire cable, 230 V -10/+15%, 50 Hz, 10AT

GOLD 05: 1-phase, 3-wire cable, 230 V -10/+15%, 50 Hz, 10AT

GOLD 08: 1-phase, 3-wire cable, 230 V -10/+15%, 50 Hz, 16AT

GOLD 12: 3-phase, 5-wire cable, 400 V -10/+15%, 50 Hz, 10 AT

GOLD 14: 3-phase, 5-wire cable, 400 V -10/+15%, 50 Hz, 10 AT

GOLD 20: 3-phase, 5-wire cable, 400 V -10/+15%, 50 Hz, 10 AT

GOLD 25: 3-phase, 5-wire cable, 400 V -10/+15%, 50 Hz, 16 AT

GOLD 30: 3-phase, 5-wire cable, 400 V -10/+15%, 50 Hz,

20 AT (RX), 16 AT (PX)

GOLD 35: 3-phase, 5-wire cable, 400 V -10/+15%, 50 Hz,

16 AT (RX), 20 AT (CX)

GOLD 40: 3-phase, 5-wire cable, 400 V -10/+15%, 50 Hz,

25 AT (RX), 32 AT (CX)

GOLD 50: 3-phase, 5-wire cable, 400 V -10/+15%, 50 Hz, 25 AT

GOLD 60: 3-phase, 5-wire cable, 400 V -10/+15%, 50 Hz,

32 AT (RX), 40 AT (CX)

GOLD 70: 3-phase, 5-wire cable, 400 V -10/+15%, 50 Hz, 32 AT

GOLD 80: 3-phase, 5-wire cable, 400 V -10/+15%, 50 Hz, 50 AT

19.6.2 Fans

RATED DATA PER FAN

GOLD 04: Motor shaft power: 0.8 kW (0.41 kW)*, motor control system, 1 x 230 V, 50 Hz

GOLD 05: Motor shaft power: 0.8 kW, motor control system, 1 x 230 V, 50 Hz

GOLD 08: Motor shaft power: 1.15 kW, motor control system, 1 x 230 V, 50 Hz

GOLD 12: Motor shaft power: 1.6 kW, motor control system, 3 x 400 V, 50 Hz

GOLD 14: Motor shaft power: 2.4 kW (1.5 kW)*, motor control system, 3 x 400 V, 50 Hz

GOLD 20: Motor shaft power: 2.4 kW, motor control system, 3 x 400 V, 50 Hz

GOLD 25: Motor shaft power: 4.0 kW (2.4 kW)*, motor control system, 3 x 400 V, 50 Hz

GOLD 30: Motor shaft power: 4.0 kW, motor control system, 3 x 400 V, 50 Hz

GOLD 35: Motor shaft power: 6.5 kW (3.9 kW)*, motor control system, 3 x 400 V, 50 Hz

GOLD 40: Motor shaft power: 6.5 kW, motor control system, 3 x 400 V, 50 Hz

GOLD 50: Motor shaft power: 2 x 4.0 kW (2 x 2.4 kW)*, motor control system, 3 x 400 V, 50 Hz

GOLD 60: Motor shaft power: 2 x 4.0 kW, motor control system, 3 x 400 V, 50 Hz

GOLD 70: Motor shaft power: 2 x 6.5 kW (2 x 3.9 kW)*, motor control system, 3 x 400 V, 50 Hz

GOLD 80: Motor shaft power: 2 x 6.5 kW, motor control system, 3 x 400 V, 50 Hz

*) The motor control system limits the output power to the value specifi ed.

19.6.3 Electrical Equipment Cubicle

SAFETY ISOLATING SWITCH

GOLD RX/PX/SD** 04-08: 20 A

GOLD RX/PX** 12-30 and GOLD SD* 14-80: 25 A

GOLD RX/CX** 35-40: 40 A

GOLD RX/CX** 50-80: 63 A

FUSES IN THE ELECTRICAL EQUIPMENT CUBICLE

GOLD 04-08: One 2-pole 6A Automatic circuit breaker

for 230V control current

RX/PX** Two 2-pole 10A Automatic circuit breakers

for fans (Not applicable to GOLD SD)

GOLD 12-20: One 2-pole 6A Automatic circuit breaker

for 230V control current

RX/PX** Two 6.3A protective motor switches for

SD** One 6.3A protective motor switch for the fans

GOLD 25-30: One 2-pole 6A Automatic circuit breaker

for 230V control current

RX/PX** Two 10A protective motor switches for the fans

SD** One 10A protective motor switch for the fans

GOLD 35-40: One 2-pole 6 A Automatic circuit breaker

for 230V control current

RX/CX** Two 12,5A protective motor switches for the fans

CX** One 1.8 A protective motor switch for the

SD** One 12,5A protective motor switch for the fans

GOLD 50-60: One 2-pole 6 A Automatic circuit breaker

for 230V control current

RX/CX** Four 10A protective motor switches for the fans

CX** One 1.8 A protective motor switch for the

SD** Two 10A protective motor switches for the fans

GOLD 70-80: One 2-pole 6 A Automatic circuit breaker

for 230V control current

RX/CX** Four 12.5A protective motor switches for

CX** One 2.35 A protective motor switch for

the circulation pump

SD** Two 12.5A protective motor switches for

FUSES IN THE CONTROL UNIT

3.15 AT, incoming 230V.

19.6.4 Motor, rotary heat exchanger

GOLD RX 04-30: 2-phase step motor, 2 Nm. On starting: max 3.2

A/160 W. During operation: max 2.5 A/125 W.

GOLD RX 35-40: 2-phase step motor, 4 Nm. On starting: max 4.1

A/205 W. During operation: max 3.5 A/175 W.

GOLD RX 50-80: 2-phase step motor, 6 Nm. On starting: max 5.1

A/255 W. During operation: max 4.5 A/225 W.

19.6.5 Control Accuracy

Temperature ± 1° C

Airfl ow ± 5%

** RX = One-piece air handling unit with rotary heat exchanger

PX = One-piece air handling unit with plate heat exchanger

CX = One-piece air handling unit with coil heat exchangers

SD = Separate supply air and extract air handling units

64 www.swegon.com

We reserve the right to alter specifi cations without notice.

GB.GOLDSKD2.100615

20 APPENDICES

20.1 Compliancy Declaration

We, Swegon AB

Box 300

S-535 23 Kvänum

declare under our own sole responsibility that

Air handling units with the following designation:

GOLD RX, GOLD PX, GOLD CX, GOLD LP, GOLD SD, COOL DX, COOL DXS and any accessories to the respective designation covered by these directives

comply with the Machinery Directive 2006/42/EC and also to the following directives

97/23/EC PED, (the Pressure Equipment Directive)

2004/108/EC EMC, (Electromagnetic Compatibility)

2006/95/EC LVD, (the Low Voltage Directive)

The following harmonised standards have been applied:

EN ISO 12100-1, -2 (Safety of machinery, general principles for design)

EN ISO 13857:2008 (Safety distances)

EN ISO 14121-1:2007 (Risk assessment)

EN 60204-1 (Electrical equipment of machines)

EN 61000-6-2, -3 (Electromagnetic compatibility)

EN 61800-3 (Adjustable speed electrical power drive systems)

EN 378-2:2008+A1:2009 (Safety and environmental requirements)

The following other standards and specifications have been applied:

EN 1886:2007 (Ventilation for buildings, air handling units)

EN 13053:2006 (Ventilation for buildings, air handling)

Person authorised to compile the technical documentation:

Dan Örtengren

Box 300

535 23 Kvänum

This declaration is applicable only if the air handling unit(s) has/have been installed according to Swegon’s instructions and provided that the air handling unit(s) has/have not been modified in any way.

Kvänum, 31/05/2010

Thord Gustafsson, Quality and Environmental Manager, Swegon AB

We reserve the right to alter specifi cations without notice.

www.swegon.com 65

GB.GOLDSKD2.100615

20.2 Commissioning Record

Company

Handling offi cer

Customer

Plant

Plant address

Date

Item/AHU

Type/size

SO no.:

Item no.:

Program version:

Filters calibrated

Switch clock, current time preset

Other control system

Switch clock time channel settings

Channel Operating mode Times

1

2

Low

Low

High

High :

:

3

4

5

6

7

8

Low

Low

Low

Low

Low

Low

High

High

High

High

High

High :

:

:

:

:

:

Switch clock year round settings

Channel Operating mode

1 Inactive Stop

2

3

Inactive

Inactive

Stop

Stop

6

7

8

4

5

Inactive

Inactive

Inactive

Inactive

Inactive

Stop

Stop

Stop

Stop

Stop

High

High

High

High

High

High

High

High

Low

Low

Low

Low

Low

Low

Low

Low

Times

:

:

:

:

:

:

:

:

:

:

:

:

:

:

:

:

Week day

:

:

:

:

:

:

:

:

:

:

:

:

:

:

:

:

Period

/

/

/

/

/

/

/

/

/

/

/

/

/

/

/

/

66 www.swegon.com

We reserve the right to alter specifi cations without notice.

GB.GOLDSKD2.100615

Function

Temperature

8)

Temp. regulation function

Differential SA/EA (°C)

Step

Breakpoint (°C)

X1

Y1

X2

Y2

X3

Y3

Setpoint (°C)

Min SA temp (°C)

Temperature control

Xzone 8)

Temp control function

Difference TL/FL (°C)

Steps

Breakpoint (°C)

X1

Y1

X2

Y2

X3

Y3

Setpoint (°C)

Min. SA temp. (°C)

Max. SA temp. (°C)

Max SA temp (°C)

Outdoor temp. compensation

8)

Temperature

Winter comp. Y1 (°C)

End point, winter X1 (°C)

Start point winter X2 (°C)

Start point, summer X3 (°C)

End point, summer X4 (°C)

Summer comp. Y2 (°C)

Summer night cooling

8)

EA temp. start (°C)

EA temp. stop (°C)

Outd. air temp. stop (°C)

SA Setpoint (°C)

Op. period start (hh:mm)

Op. period stop (hh:mm)

Intermittent nighttime heating

8)

SA/Room start (°C)

EA/Room stop (°C)

SA Night setpoint (°C)

SA fl ow (m²/s / Pa)

EA fl ow (m²/s / Pa)

Control output

Damper output

Factory preset value

X ERS 1

3.0

2

22.0

ERS 1

3,0

2

22,0

X

3.0

-20.0

10.0

25.0

40.0

2.0

X

22.0

16.0

10.0

10.0

23:00

06:00

0.0

X

=0

ERS 2

15.0

20.0

20.0

18.0

22.0

14.0

ERS 2 X

15,0

20,0

20,0

18,0

22,0

14,0

Inactive

Inactive

X Inactive

16.0

18.0

28.0

1)

IQnomic

SA

21.5

SA

21,5

Active

Active

Active

IQnomic+

EA

21.5

15.0

EA

21,5

15,0

28,0

28.0

Adjusted value

ERS 1

ERS 1

Inactive

Inactive

Inactive

IQnomic

ERS 2

ERS 2

Active

Active

Active

SA

SA

IQnomic+

EA

EA

We reserve the right to alter specifi cations without notice.

www.swegon.com 67

GB.GOLDSKD2.100615

Function

Morning Boost

8)

Period (hh:mm)

Damper

EA fan

Control output

Setpoint displacement

8)

Extra control sequence

8)

Max output signal (%)

Cooling function

Heating function

External sensor

External SA/Room

External Oudoor

Alarm delay

Flow/pressure

Fan regulation SA

Fan regulation EA

Flow, low speed

Flow, high speed

Flow, max speed

Flow, min. speed

Pressure, low speed

Pressure, high speed

Max. fan speed

Pressure, max. speed

SA Pa

EA Pa

SA Pa

EA Pa

SA (%)

EA (%)

SA Pa

EA Pa

SA

EA

SA

EA

SA

EA

SA

EA

Demand-cont. low speed SA (%)

EA (%)

Demand-cont. high speed SA (%)

EA (%)

Factory preset value

00:00

X Inactive

X Inactive

X IQnomic

X Inactive

100

X Inact.

X Inact.

Comf.

Comf.

Active

Active

IQnomic+

Active

Econ.

Econ.

X Inact.

X Inact.

5 min

IQnom

IQnom

Comm.

Comm.

X Flow

X Flow

2)

2)

1)

1)

4)

4)

Press.

Press.

100

100

200

200

100%

100%

400

7)

400

7)

Reqd.

Reqd.

25

25

50

50

5)

5)

3)

3)

Slave

Slave

2)

2)

1)

1)

4)

4)

Adjusted value

Inactive

Inactive

IQnomic

Inactive

Inact.

Inact.

Inact.

Inact.

Flow

Flow

Comf.

Comf.

IQnom

IQnom

Active

Active

IQnomic+

Active

Econ.

Econ.

Comm.

Comm.

Press.

Press.

Reqd.

Reqd.

Slave

Slave

68 www.swegon.com

We reserve the right to alter specifi cations without notice.

GB.GOLDSKD2.100615

Function

Outdoor temp. compensation

Flow/ Pression

Winter comp. Y1 (%)

End point, winter X1 (°C)

Start point winter X2 (°C)

Boosting

SA

EA

Down-regulation

8)

Function

Neutral zone (°C)

Operation

Switch clock function

Slave control

9)

Cooling COP

Filter function GOLD SD

Prefi lter

Prolonged operation

Ext. low speed (h:mm)

Ext. high speed (h:mm)

Summer/wintertime

Heating

Heat exchanger

Defrosting

Exhaust air regulation

Function

GOLD RX

Min. temp (°C)

Re-heating

8)

Pumpexercizing

Exercizing period

Interval

"Heating boost"

8)

Function Off/On

Start limit SA Temp. (°C)

Ramp time (%)

Factory preset value

Inactive

30

-20

10

5

X

X

Inact. X SA

0.0

X 1. Low - High

1.0

X Inact.

X Inact.

0:00

0:00

X

X Inact.

Inact.

3 Min.

24 h

X

3.0

2.5

Inactive

Inactive

Inactive

Inactive

X Pump

Inactive

SA

SA

Active

Active

Active

SA+EA

2. Stop - Low - High

EA

EA

X Active

Active

Valve

Auto op.

SA+EA

SA+EA

P+V

Adjusted value

Inactive

Inactive

Inact.

1. Low - High

Inact.

Inact.

Inactive

Inactive

Inact.

Inact.

Inactive

SA

SA

SA

Active

Pump

Active

Active

Active

Active

SA+EA

2. Stop - Low - High

EA

EA

Valve

Auto op.

SA+EA

SA+EA

P+V

We reserve the right to alter specifi cations without notice.

www.swegon.com 69

GB.GOLDSKD2.100615

Function

Cooling

Refr. Machine control

8)

Exercising Cooling relay 1

Cooling relay 2

Exercise period

Interval

Response speed

Step period (s)

Outd. temp limit

Reset period (s)

Cool. - min SA fl ow (m³s)

Cool. - min EA fl ow (m³s)

Neutral zone (°C)

Step 1 (°C)

Step 2 (°C)

Step 3 (°C)

"Cooling Boost"

8)

Factory preset value

X

Inactive Active

X

Steppless

0-10 V

CoolDX

Comfort

On/off

3 steps binary

Steppless

10-0 V

On/off

1 step

X Inact.

Pump Valve

CoolDX

Economy

On/off

2 steps

COOL DXS

Adjusted value

Inactive Active

Steppless

0-10 V

CoolDX

Comfort

On/off

3 steps binary

Steppless

10-0 V

On/off

1 step

P+V Inact.

Inact.

Pump

Pump X Inact.

3 min.

24 hrs.

Pump Valve P+V

300

3.0

5.0

7.0

480 (CoolDX: 300)

6)

6)

2.0

X Inact.

Comf.

Comf.+Econ.

3.0

2.5

Econ.

Sequ.

Econ.+Sequ.

Inact.

Comf.

Comf.+Econ.

CoolDX

Economy

On/off

2 steps

COOL DXS

Valve

Valve

P+V

P+V

Econ.

Sequ.

Econ.+Sequ.

Start limit SA temp (°C)

Ramp time (%)

Hunidity

Dehumidifi cation control

8)

Rel. hum., SA (%RH

X

50%

Inactive Active Inactive Active

70 www.swegon.com

We reserve the right to alter specifi cations without notice.

GB.GOLDSKD2.100615

Function

All Year Comfort

Heating water temp. (°C)

Cooling water temp. (°C)

Outdoor comp., Heating water

Outdoor temp. (X1) (°C)

Heating water (Y1)(°C)

Outdoor temp. (X2)(°C)

Heating water (Y2)(°C)

Outdoor temp. (X3)(°C)

Heating water (Y3)(°C)

Outdoor comp., Cooling water

Outdoor temp. (X1) (°C)

Cooling water (Y1)(°C)

Outdoor temp. (X2)(°C)

Cooling water (Y2)(°C)

Outdoor temp. (X3)(°C)

Cooling water (Y3)(°C)

Room comp., Heating water

8)

Room temperature (°C)

P-band (°C)

Night blocking

Room comp., Cooling water

Room temperature (°C)

P-band (°C)

Night blocking

Night comp., Heating water

Temp. comp. (°C)

Night comp., Cooling water

Temp. comp. (°C)

Night comp.

Channel 1, Start, Stop, Weekday

Channel 2, Start, Stop, Weekday

Pump operation, Heating water

Outdoor temp. Start (°C)

Outdoor temp. Stop (°C)

Pump operation, Cooling water

Outdoor temp. Start (°C)

Outdoor temp. Stop (°C)

Alarm function, Heating water

Pump alarm

Valve

Alarm function, Cooling water

Pump alarm

Valve

Exercising, Heating water

Exercising period, (min)

Interval (h)

Exercising, Cooling water

Exercising period, (min)

Interval (h)

Dew point comp.

Neutral zone (°C)

Comp. air fl ow (%)

X Inact.

X Inact.

Open

Active

Close

X Inact.

Open Close

X Inact.

Active

X Inact.

3

24

X Inact.

3

24

X Inact.

2

10

Pump

Pump

Active

P+V

P+V

We reserve the right to alter specifi cations without notice.

Factory preset value

X Inact.

30

14

X Inact.

-20

40

5

30

15

20

X Inact.

10

22

20

18

25

14

X Inact.

21

5

Inact.

Cool.

Active

Active

Active

Active

Heat.

Active X Inact.

21

5

Inact.

X Inact.

-2

2

X Inact.

X Inact.

Inactive

Inactive

Active

Active

Active

Active

15

18

-20

-25

C+H

Cont.

Cont.

Valve

Valvev

Adjusted value

Inact.

Cool.

Inact.

Inact.

Inact.

Inact.

Inact.

Inact.

Inact.

Inact.

Inact.

Inact.

Inact.

Inact.

Inact.

Inact.

Inact.

Inact.

Active

Active

Active

Active

Active

Active

Active

Active

Active

Open

Active

Open

Active

Pump

Pump

Active

Heat.

Close

Close

P+V

P+V

C+H

Cont.

Cont.

Valve

Valve www.swegon.com 71

Function

CONTROL Optimize

8)

Upper damper limit (%)

Lower damper limit (%)

Step size (Pa)

Interval (min)

Permissible deviation (Pa)

Power up start delay (min)

Min. pressure (Pa)

Max. pressure (Pa)

"IQnomic Plus"

I/O module Nr 0 ReCO2

I/O module Nr 1 Coil heat exch.

I/O module Nr 2 Plate heat exch.

I/O module Nr 3 Ext. monitoring

Factory preset value

Active X Inactive

90

70

20

2

10

15

50

400

X Inactive Active

X Inactive Active

X Inactive Active

X Inactive Active

I/O module Nr 6

8)

I/O module Nr 7

I/O module Nr 8 8)

I/O module Nr 9

I/O module Nr A

I/O module Nr B

Ext. cooling

All Year Comfort

Swegon Factory

Preheating

Heating zone

Cooling zone

X Inactive Active

X Inactive Active

X Inactive Active

X Inactive Active

X Inactive Active

X Inactive Active

GB.GOLDSKD2.100615

Adjusted value

Inactive Active

Inactive Active

Inactive Active

Inactive Active

Inactive Active

If active, function:

Inactive Active

Inactive Active

Inactive Active

Inactive Active

Inactive Active

Inactive Active

72 www.swegon.com

We reserve the right to alter specifi cations without notice.

GB.GOLDSKD2.100615

Function

ReCO

2

CO

2

function

Temperature function

Temperature function

Min. outdoor air

Min. exhaust air

Alarm setting

Fire alarm function

Internal fi re alarms

Cooling

Heating

External fi re alarms

Fans in event of fi re

Alarm Reset

SA fan speed in event of fi re (%)

EA fan speed in event of fi re (%)

External alarm

Time delay - alarm 1 (s)

Alarm on closure, alarm 1

Alarm Reset

Time delay- alarm 2 (s)

Alarm on closure, alarm 2

Alarm Reset

Alarm limit temp.

Deviation - SA setpoint

Min EA temperature

Filter alarm limit

SA (Pa)

EA (Pa)

Heat exch. defrosting

Alarm limit (Pa)

8)

GOLD RX

Factory preset value

X Inact.

X Inact.

X Inact.

CO

2

Comf.

Comf.

6)

6)

Co

2

+fl ow

Econ.

Econ.

X Inactive Active

X

X Inact.

100

100

Man.

Auto

SA EA

10

1

X

10

1

X Man.

Man.

Auto

Auto

5.0

12.0

100

100

50

SA+EA

Adjusted value

Inact.

Inact.

Inact.

CO

2

Comf.

Comf.

Co

2

+fl ow

Econ.

Econ.

Inactive

Man.

Inact.

Man.

Man.

SA

Active

Auto

Auto

Auto

EA SA+EA

We reserve the right to alter specifi cations without notice.

www.swegon.com 73

GB.GOLDSKD2.100615

Function

Service period

Alarm limit (Mon)

Alarm priority See also pages that follow

Alarm output A

B

Hand-held terminal settings

Language

Flow unit

Min/max adjustment

Setpoint SA/EA (°C)

Min. limit SA (°C)

Max. limit EA (°C)

8)

8)

8)

8)

Breakpoint- ERS regulation (°C)

8)

Differential SA/EA (°C)

8)

Base settings

Communication

EIA-232

Protocol

Address

Speed

Parity

Stop bit

EIA-485

Protocol

Address

Factory preset value

12

X NO

X NO

English

– l/s

15.0/40.0

13.0/18.0

25.0/45.0

15.0/23.0

1.0/5.0

X m 3

NC

NC

/s m 3 /h

Adjusted value

NO

NO l/s m 3 /s

NC

NC m 3 /h

Speed

Parity

Stop bit

Ethernet

Mac Id

DHCP server

IP-adress

Port No.

Netmask

GateWay

DNS Server

No. 1

No. 2

Modbus TCP

IP

Port No.

Netmask

BACNet IP

Function

Device ID

Port nr.

GSM modem

1

9600

None

1

Modbus RTU

1

PLA (Exoline) 1

ELA (Exoline) 1

9600

None

1

Individual

Inactive

10.200.1.1

80

255.0.0.0

000.000.000.000

000.000.000.000

000.000.000.000

000.000.000.000

502

000.000.000.000

Inactive

0000000

47808

The values refer to the sizes in due succession: 04, 05, 08, 12, 14, 20, 25, 30, 35, 40, 50, 60, 70 and 80.

1) 0.15, 0.20, 0.30, 0.40, 0.40, 0.55, 0.75, 0.85, 0.90, 1.1, 1.5, 1.7, 2.0, 2.2

2) 0.25, 0.30, 0.40, 0.60, 0.60, 1.0, 1.3, 1.65, 1.85, 2.2, 2.8, 3.4, 3.5, 4.6

3) 0.35, 0.50, 0.60, 0.90, 0.90, 1.4, 1.8, 2.5, 2.6, 3.3, 3.5, 4.3, 5.0, 5.8

4) Only in combination with Heating BOOST, Cooling BOOST and Flow BOOST.

5) Only in combination with Demand control. 0.08, 0.08, 0.10, 0.20, 0.20, 0.20, 0.30, 0.30, 0.60, 0.60, 0.80, 0.80, 1.0, 1.0

6) 0.10, 0.10, 0.20, 0.30, 0.30, 0.40, 0.50, 0.60, 0.80, 0.90, 1.2, 1.5, 1.8, 2.0

7) Only in combination with Flow BOOST.

8) Not applicable if the ventilation system consists of GOLD SD extract air handling units only.

9) Not applicable if the ventilation system consists of GOLD SD supply air or extract air handling units only.

74 www.swegon.com

We reserve the right to alter specifi cations without notice.

GB.GOLDSKD2.100615

Function

Factory preset value

Priority

0=blocked

Indication

LED

Effect Priority

0=Operat. 0=blockedt

Adjusted value

Indication

LED

Effect

0=Operat.

1 External fi re alarm tripped

2 Internal fi re alarm tripped

3 Frost protection below alarm limit

4 R.hx. speed monitor tripped

5 Frost protection sensor defective

6 Supply air temp sensor defective

7 Extract air temp sensor defective

8 Outdoor air temp sensor defective

9 No communication to r.hx. controller

10 No communication to SA frequency conv.

11 No communication to EA frequency conv.

12 Over current in SA frequency conv.

13 Over current in EA frequency conv.

14 Under voltage in SA frequency conv.

15 Under voltage in EA frequency conv.

16 Over voltage in SA frequency conv.

17 Over voltage in EA frequency conv.

A ***

A ***

A ***

A ***

18 Over temperature in SA frequency conv.

19 Over temperature in EA frequency conv.

A ***

A ***

20 No communication to SA-2 frequency conv.

A ***

21 No communication to EA-2 frequency conv.

A ***

22 Over current in SA-2 frequency conv.

23 Over current in EA-2 frequency conv.

24 Under voltage in SA-2 frequency conv.

25 Under voltage in EA-2 frequency conv.

26 Over voltage in SA-2 frequency conv.

27 Over voltage in EA-2 frequency conv.

28 Over temperature in SA-2 frequency conv.

29 Over temperature in EA-2 frequency conv.

A ***

A ***

A ***

A ***

A ***

A ***

A ***

A ***

A=A alarm

B=B alarm

A****

A****

A****

A

A****

A

A

B

A ***

A ***

A ***

A ***

A ***

30 Ext. EA/room temp sensor defective

31 Ext. outdoor temp sensor defective

32 Plate heat exch. sensor faulty

33 Coil heat exch. sensor faulty

34 Over current in r.hx. controller

35 Under voltage in r.hx. controller

36 Over voltage in r.hx. controller

37 Over temperature in r.hx. controller

38 R.hx pressure drop above alarm limit

39 El.heating coil tripped

40 Extract air temp below alarm limit

41 Supply air temp below setpoint

42 Ext.alarm No.1 tripped

A ***

B ***

A ***

A ***

A ***

A ***

A ***

B ***

A ***

A ***

A ***

A ***

A ***

1

1

1

0

1

1

1

1

1

0

0

1

0

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

0

1

1=Stop A=A alarm

B=B alarm

1*

1*

1*

0**

1*

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

0=Off

1=On

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

0=Off

1=On

1=Stop

We reserve the right to alter specifi cations without notice.

www.swegon.com 75

GB.GOLDSKD2.100615

Function

43 Ext. alarm No.2 tripped

44 SA duct pressure below setpoint

45 EA duct pressure below setpoint

46 SA duct pressure above setpoint

47 EA duct pressure above setpoint

48 Supply airfl ow below setpoint

49 Extract airfl ow below setpoint

50 Supply airfl ow above setpoint

51 Extract airfl ow above setpoint

52 Supply air fi lter dirty

53 Extract air fi lter dirty

54 Service period past alarm limit

55 No comm. SA air fl ow pressure sensor

56 No comm. EA air fl ow pressure sensor

57 No comm. SA fi lter pressure sensor

58 No comm. EA fi lter pressure sensor

59 No comm. SA duct pressure sensor

60 No comm. EA duct pressure sensor

61 No comm. r.hx. pressure sensor

62 No communication to I/O-module No:0

63 No communication to I/O-module No:1

64 No communication to I/O-module No:2

65 No communication to I/O-module No:3

66 No communication to I/O-module No:4

67 No communication to I/O-module No:5

68 No communication to I/O-module No:6

69 No communication to I/O-module No:7

70 No communication to I/O-module No:8

71 No communication to I/O-module No:9

72 No communication to main controller I/O

73 Plate heat exch., damper motor faulty

74 Coil heat exch. pump tripped

75 Supply air humidity sensor faulty

76 Extract air humidity sensor faulty

78 Humidity sensor for heat exch. faulty

79 Coil heat exch. valve faulty

80 Temperature monitor below alarm limit

81 Supply air-d temperature sensor faulty

82 Extract air-d temperature sensor faulty

85 CoolDX, C1 tripped

0

1

0

0

0

0

0

0

0

0

0

0

0

1

1

1

0

0

1

0

0

1

1

1

1

1

0

0

1

0

0

0

0

0

0

0

0

0

0

0

Factory preset values

Priority

0=blocked

Indication

LED

Effect Priority

0=Operat. 0=blocked

Adjusted value

Indication

LED

Effect

0=Operat.

A=A alarm 0=Off 1=Stop A=A alarm 0=Off 1=Stop

B=B alarm 1=On

B ***

B ***

B ***

B ***

B ***

B ***

B ***

A

B ***

A ***

A ***

B ***

B ***

B ***

B ***

A ***

A ***

A ***

A ***

B ***

A ***

A ***

B ***

B ***

A

B=B alarm

B ***

B ***

B ***

B ***

B ***

B ***

B ***

B ***

B ***

B ***

B ***

B ***

A ***

A ***

B ***

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1=On

1

1

1

76 www.swegon.com

We reserve the right to alter specifi cations without notice.

GB.GOLDSKD2.100615

Function

86 CoolDX, C2 tripped

87 CoolDX, C1 too many restarts

88 CoolDX, C2 too many restarts

89 No comm. with press. sensor by SA prefi lter

90 No comm. with press. sensor by EA prefi lter

91 Frost prot. for preheating, below alarm limit

92 Frost prot. for preheating sensor, faulty

93 Preheating sensor faulty

94 Electric air heater for preheating, tripped

95 Preheating below setpoint

97 No comm. with ReCO2 pressure sensor

98 ReCO2 damper motor faulty

99 Time lock tripped

102 Cooling valve I/O-7 defective

103 Heating valve I/O-7 defective

104 Cool. circuit pump I/O-7 tripped

105 Heat. circuit pump I/O-7 tripped

106 Cooling water temp. I/O-7 below set point

107 Heat. water temp. l I/O-7 below set point

108 Cooling water temp. I/O-7 above set point

109 Heating water temp. I/O-7 above set point

110 Cooling water temp. sensor I/0-7 defective

111 Heating water temp. sensor I/0-7 defective

135 SA fan motor blocked

136 EA fan motor blocked

137 SA-2 fan motor blocked

138 EA-2 fan motor blocked

139 Fluctuation voltage between the phases, SA

140 Fluctuation voltage between phases, EA

141 Fluctuation voltage between the phases, SA-2

142 Fluctuation voltage between phases, EA-2

143 No communication - CONTROL Optimize

144 No communication – I/O Module No. A

145 No communication – I/O Module No. B

146 No communication – I/O Module No. C

147 No communication – I/O Module No. D

148 No communication – I/O Module No. E

149 No communication – I/O Module No. F

150 Frost prot. in extra zone, below alarm limit

151 Frost protection sensor in extra zone, faulty

A***

A***

A***

A***

A***

B***

B***

B***

0***

0***

B

A

A***

A***

A***

B***

B***

B***

B***

A

A

A***

A

B***

A***

B***

A***

B***

A***

B***

A

A

A

A***

A***

A***

Factory preset values

Priority

0=blocked

Indication

LED

Effect Priority

Adjusted value

Indication

0=Operat. 0=blocked

LED

Effect

0=Operat.

A=A alarm 0=Off 1=Stop A=A alarm 0=Off 1=Stop

B=B alarm 1=On B=B alarm

A

A****

A****

B***

1=On

1

!

1

1

0

1

1

0

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

0

0

1

0

1

1

1

1

1

1

0

1

0

0

0

0

0

0

0

1

1

0

0

0

1

0

0

1

1

1

1

1

1

0

1

1

We reserve the right to alter specifi cations without notice.

www.swegon.com 77

GB.GOLDSKD2.100615

Function

152 Supply air sensor in extra zone faulty

153 Extract air sensor in extra zone faulty

154 Electric air heater for extra zone, tripped

155 EA temp. in extra zone below alarm limit

156 Supply air in extra zone below alarm limit

159 No communication with COOL DXS module

160 COOL DX/DXS, low pressure, below alarm limit

161 COOL DX/DXS, high pressure, above alarm limit

162 COOL DX/DXS low pressure sensor defective

163 COOL DX/DXS high pressure sensor defective

164 COOL DX/DXS K1 has tripped

165 COOL DX/DXS K2 has tripped

166 COOL DX/DXS K3 has tripped

167 COOL DX/DXS K1 too many restarts

168 COOL DX/DXS K2 too many restarts

169 COOL DX/DXS K3 too many restarts

170 COOL DXS fan has tripped

171 COOL DX/DXS incorrect phase sequence

172 Outd.air temp.sens COOL DX defective

Factory preset values

Priority

0=blocked

Indication

LED

Effect Priority

Adjusted value

Indication

0=Operat. 0=blocked

LED

Effect

0=Operat.

A=A alarm 0=Off 1=Stop A=A alarm 0=Off 1=Stop

B=B alarm 1=On B=B alarm

A

A

A

A***

A***

A

A

1

1

1

1

1=On

1

1

1

0

0

1

1

1

1

1

A

A

A

A

A

A

A

A

A

A

A

B***

1

1

1

1

1

1

1

1

1

1

1

1

0

0

0

0

0

0

0

0

0

0

0

0

* Not adjustable, always stops the air handling unit

** Not adjustable, stops the air handling unit at temperature below +5 °C

*** Blocked if the hand terminal does not display the main menu.

**** Cannot be blocked.

Adjustments carried out by:

Date

Company

Name

78 www.swegon.com

We reserve the right to alter specifi cations without notice.

GB.GOLDSKD2.100615

We reserve the right to alter specifi cations without notice.

www.swegon.com 79

GB.GOLDSKD2.100615

80 www.swegon.com

All documentation is also available in digital form and can be downloaded from our website: www.swegon.com

We reserve the right to alter specifi cations without notice.

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals

Download PDF

advertisement

Table of contents