Model: M1000-71C-215 1000 Watts M-47 60 Hz Standard Metal Halide Input Volts 120 208 240 277 CWA Wiring Diagram CWA Circuit Type 0.98 Power Factor Regulation Line Volts ± 10 % Lamp Watts - 10% + 10 % Line Current (Amps) Operating 9.0 5.2 4.5 3.9 Open Circuit 4.6 2.3 2.4 2.0 Starting 7.3 4.2 3.6 3.2 Recommended Fuse 20 15 10 10 UL Temperature Ratings Insulation Class H (180°C) Coil Temperature Code Benchtop Coil Rise Primary Benchtop Coil Rise Secondary D D D D < 90 < 90 < 90 < 90 < 90 < 90 < 90 < 90 1106 1106 1052 1082 71 143 153 192 min 3.0 1.6 1.7 1.4 max 4.8 2.6 2.7 2.2 min 5.7 3.2 2.8 2.4 max 8.7 5.1 4.5 3.8 Input Watts 430 1.62 NOM Open Circuit Volts Current Crest Factor Input Voltage at Lamp Dropout Min Ambient Starting Temp. -20°F -30°C High Potential Test (Volts) 1 Minute 2000 1 Second 2400 Open Circuit Voltage Test (Volts) 400 - 440 Open Circuit Voltage Input Current Short Circuit Current Test (Amps) Secondary Current 5.1 Input Current Core and Coil Specifications Dimension A" Dimension B" 6.4 2.8 4.8 Weight (lbs.) 21 Lead Lengths (in) 12 Capacitor Specifications Microfarads 24 Volts (min.) 480 Case Size (in.) Height ( in.) Temp Rating °C Oval OIL Filled DRY Film 1.75 Not Available 3.88 90 Starter Specifications Model Number Not Used BTL Temp Rating °C Rev. Date: 5/21/2010 1093-910335-102 Test Ref.: Validation Specifications subject to change without notice. Howard Industries, Inc. Ballast Products Division P.O. Box 1590 Laurel, MS 39441 Phone: 1-800-956-3456 Fax: (601) 422-1652 www.Howard-Lighting.com