Rosemount 3051S Series of Instrumentation High Pressure Solutions

Rosemount 3051S Series of Instrumentation High Pressure Solutions
Product Data Sheet
December 2015
00813-0100-4851, Rev AA
Rosemount™ 3051S Series of Instrumentation
High Pressure Solutions
Innovation reaching across your operation
With Rosemount 3051S High Pressure Solutions, you can optimize your operation in critical areas such as production,
quality, energy efficiency, and safety and environment. By leveraging the power of the scalable Rosemount 3051S
across your entire operation, you’ll be able to minimize process variability, gain greater process insight, reduce
maintenance and downtime, and meet regulatory demands. What’s more, it’s easy for your people to use, ensuring
you will realize the full potential of your measurement investment.
Rosemount 3051S High Pressure
December 2015
Rosemount 3051S SuperModule™ Platform
The most advanced pressure, flow, and level measurements

The all-welded hermetic design delivers the industry's highest field reliability

Patented electronics within the SuperModule

SIL 3 Capable: IEC61508 certified by an accredited 3rd party agency for use in safety instrumented
systems up to SIL 3 (minimum requirement of single use [1oo1] for SIL2 and redundant use [1oo2]
for SIL 3)
Rosemount 3051S High Pressure Solutions
Rosemount 3051S High Static Differential Pressure Transmitter

Coned and threaded direct connection enables operation in applications with static pressures up to
15,000 psi (1.034 bar)

Coplanar platform enables integrated seal system solutions

Calibrated Differential Pressure spans from 5 inH2O to 150 psi (12.4 mbar to 10.4 bar)

Dual-capacitance Saturn™ sensor technology corrects for overpressure and line pressure effects

Available with Alloy C-276 process isolators
Contents
Rosemount 3051S High Static Differential Pressure
Transmitter. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Product Certifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
2
Dimensional Drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
EmersonProcess.com/Rosemount
December 2015
Rosemount 3051S High Pressure
Advanced functionality
WirelessHART® (IEC 62591) capabilities
Available on coplanar, in-line, and level transmitters

Quickly deploy new pressure, level and flow measurements in 70% less time

Eliminate wiring design and construction complexities to lower costs by 40 - 60%

Extended range antenna capabilities provide access to remote locations

Delivering over a decade of maintenance free performance with 15-year stability and 10-year
power module life
Advanced diagnostic capabilities

Provides diagnostic coverage from the process to the transmitter to the host

Prevent on-scale failures by diagnosing electrical loop issues with Power Advisory diagnostics

Statistical Process Monitoring detects abnormal process conditions enabling more productive
and safer operations

Extend diagnostic coverage to Safety Instrumented Systems with IEC 61508 SIL 2/3 capable
rating
Additional functionality

Remote display and interface allows for direct mounting to process to eliminate impulse lines
and enables access to the transmitter's interface from 100 feet away

Optional differential pressure + temperature measurement option available on the 3051SHP
reduces overall installation cost with a 2-in-1 DP and process temperature measurement
EmersonProcess.com/Rosemount
3
Rosemount 3051S High Pressure
December 2015
Rosemount 3051S High Static Differential Pressure
Transmitter
Rosemount 3051S High Static Differential Pressure Transmitters bring reliability based on the industry
leading 3051S SuperModule design to installations with high static pressure conditions. The
lightweight coplanar design results in a more accurate measurement while reducing transmitter
weight over traditional high static pressure transmitters. Capabilities include:
3051S High Static Differential
Pressure Transmitter

Accurate and reliable measurements up to static lines pressure of 15,000 psi (1.034 bar)

4-20 mA HART®, WirelessHART, FOUNDATION™ Fieldbus protocols

Safety Certification (Options Code QT)

Advanced Diagnostics (Option Code DA2)

Differential Pressure and Temperature (Measurement Type Option Code 7)
Additional information
Specifications: page 10
Certifications: page 17
Dimensional Drawings: page 18
Specification and selection of product materials, options, or components must be made by the purchaser of the equipment. See
page 15 for more information on Material Selection.
Table 1. Rosemount 3051S High Static Differential Pressure Transmitter Ordering Information
★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery.
__The Expanded offering is subject to additional delivery lead time.
Model
Transmitter type
3051SHP
High Static Differential Pressure Transmitter
Performance class(1)
1
Ultra: 0.055 percent span accuracy, 15-yr limited warranty
★
2
Classic: 0.055 percent span accuracy
★
Connection type
C
Coplanar
★
Measurement type
D
Differential Pressure
★
7
Differential Pressure and Temperature
★
Differential pressure range
6
-250 to 250 inH2O (-623 to 623 mbar)
★
7
-700 to 700 inH2O (-1,74 to 1,74 bar)
★
8
-150 to 150 psi (-10,34 to 10,34 bar)
★
Static pressure range
A
4
None
★
EmersonProcess.com/Rosemount
December 2015
Rosemount 3051S High Pressure
Table 1. Rosemount 3051S High Static Differential Pressure Transmitter Ordering Information
★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery.
__The Expanded offering is subject to additional delivery lead time.
Maximum static line pressure
3
★
15,000 psi (1.034 bar)
Temperature input
N
None
R
RTD Input (Type Pt 100, -328 to 1562 °F [-200 to 850 °C])
★
Isolating diaphragm(2)(3)
3
★
Alloy C-276
Process connection
B12(4)(5)
Assemble to two Rosemount 1199 Seals
H11
Coned and threaded, compatible with autoclave type F-250-C
★
Transmitter output
A
4–20 mA with digital signal based on HART protocol
★
F(6)
FOUNDATION Fieldbus protocol
★
X(7)
Wireless (requires wireless options and wireless PlantWeb™ housing)
★
Housing style
Material
Conduit entry size
1A
PlantWeb housing
Aluminum
1 2
/ –14 NPT
★
1B
PlantWeb housing
Aluminum
M20 ⫻ 1.5
★
1C
PlantWeb housing
Aluminum
G/
1J
PlantWeb housing
SST
1 2
/ –14 NPT
★
1K
PlantWeb housing
SST
M20 ⫻ 1.5
★
1L
PlantWeb housing
SST
G1/2
2A
Junction Box housing
Aluminum
1 2
/ –14 NPT
★
2B
Junction Box housing
Aluminum
M20 ⫻ 1.5
★
2C
Junction Box housing
Aluminum
G1/2
2E
Junction Box housing with output for remote display and interface
Aluminum
1 2
/ –14 NPT
★
2F
Junction Box housing with output for remote display and interface
Aluminum
M20 ⫻ 1.5
★
2G
Junction Box housing with output for remote display and interface
Aluminum
G1/2
2J
Junction Box housing
SST
1 2
2M
Junction Box housing with output for remote display and interface
SST
1 2
5A(8)
Wireless PlantWeb housing
Aluminum
1 2
5J(8)
Wireless PlantWeb housing
SST
7J(8)
Quick Connect (A size Mini, 4-pin male termination)
SST
EmersonProcess.com/Rosemount
1 2
/ –14 NPT
★
/ –14 NPT
★
/ –14 NPT
★
1 2
/ –14 NPT
★
N/A
★
5
Rosemount 3051S High Pressure
December 2015
Table 1. Rosemount 3051S High Static Differential Pressure Transmitter Ordering Information
★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery.
__The Expanded offering is subject to additional delivery lead time.
Wireless options (requires option code X and wireless PlantWeb housing)
Update rate
WA
User configurable update rate
★
Operating frequency and protocol
3
2.4 GHz DSSS, IEC 62591 (WirelessHART)
★
Omni-directional wireless antenna
WK
External antenna
WJ
Remote antenna
WM
Extended range, external antenna
WN
High-gain, remote antenna
★
★
SmartPower (8)
1
Adapter for Black Power Module (I.S. power module sold separately)
★
Other options (Include with selected model number)
Extended product warranty
WR3
3-year limited warranty
★
WR5
5-year limited warranty
★
PlantWeb control functionality (9)
A01
FOUNDATION Fieldbus Advanced Control Function Block Suite
★
PlantWeb diagnostic functionality
D01(9)
FOUNDATION Fieldbus Diagnostics Suite
★
DA2(10)(11)
Advanced HART Diagnostics Suite
★
RTD cable (RTD sensor must be ordered separately)
C12
RTD Input with 12 ft. (3.66 m) of shielded cable
★
C13
RTD Input with 24 ft. (7.32 m) of shielded cable
★
C14
RTD Input with 75 ft. (22.86 m) of shielded cable
★
C22
RTD Input with 12 ft. (3.66 m) of armored shielded cable
★
C23
RTD Input with 24 ft. (7.32 m) of armored shielded cable
★
C24
RTD Input with 75 ft. (22.86 m) of armored shielded cable
★
C32
RTD Input with 12 ft. (3.66 m) of ATEX/IECEx flameproof cable
★
C33
RTD Input with 24 ft. (7.32 m) of ATEX/IECEx flameproof cable
★
C34
RTD Input with 75 ft. (22.86 m) of ATEX/IECEx flameproof cable
★
Mounting bracket
B4
6
Coplanar flange bracket, all 316 SST, 2-in. pipe and panel/ bracket
★
EmersonProcess.com/Rosemount
December 2015
Rosemount 3051S High Pressure
Table 1. Rosemount 3051S High Static Differential Pressure Transmitter Ordering Information
★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery.
__The Expanded offering is subject to additional delivery lead time.
Software configuration
C1
Custom software configuration (requires Configuration Data Sheet)
★
Alarm level(11)(12)
C4
NAMUR alarm and saturation levels, high alarm
★
C5
NAMUR alarm and saturation levels, low alarm
★
C6
Custom alarm and saturation signal levels, high alarm (requires C1 and Configuration Data Sheet)
★
C7
Custom alarm and saturation signal levels, low alarm (requires C1 and Configuration Data Sheet)
★
C8
Low alarm (standard Rosemount alarm and saturation levels)
★
Hardware adjustments(11)(12)(13)
D1
Hardware adjustments (zero, span, alarm, security)
★
Ground screw(12)
D4
External ground screw assembly
★
Conduit plug(14)
DO
316 SST Conduit Plug
★
Customer specified barcode tag
D6
Barcode tag
★
Product certifications(15)
E1
ATEX Flameproof
★
E5
US Explosion-proof, Dust Ignition-proof
★
E6(16)
Canada Explosion-proof, Dust Ignition-proof, Division 2
★
E7
IECEx Flameproof, Dust Ignition-proof
★
I1
ATEX Intrinsic Safety
★
I5
US Intrinsically Safe; Nonincendive
★
I6
Canada Intrinsically Safe
★
I7
IECEx Intrinsic Safety
★
IA
ATEX FISCO Intrinsic Safety (FOUNDATION Fieldbus protocol only)
★
IE
US FISCO Intrinsically Safe (FOUNDATION Fieldbus protocol only)
★
IF
Canada FISCO Intrinsically Safe (FOUNDATION Fieldbus protocol only)
★
IG
IECEx FISCO Intrinsic Safety (FOUNDATION Fieldbus protocol only)
★
K1
ATEX Flameproof, Intrinsic Safety, Type n, Dust
★
K5
US Explosion-proof, Dust Ignition-proof, Intrinsically Safe, Division 2
★
K6(17)
Canada Explosion-proof, Dust Ignition-proof, Intrinsically Safe, Division 2
★
K7
IECEx Flameproof, Dust Ignition-proof, Intrinsic Safety, Type n
★
KA(17)
ATEX and Canada Flameproof, Intrinsically Safe, Division 2
★
EmersonProcess.com/Rosemount
7
Rosemount 3051S High Pressure
December 2015
Table 1. Rosemount 3051S High Static Differential Pressure Transmitter Ordering Information
★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery.
__The Expanded offering is subject to additional delivery lead time.
KB(17)
US and Canada Explosion-proof, Dust Ignition-proof, Intrinsically Safe, Division 2
★
KC
US and ATEX Explosion-proof, Intrinsically Safe, Division 2
★
KD(17)
US, Canada, and ATEX Explosion-proof, Intrinsically Safe
★
KG
US, Canada, ATEX and IECEx FISCO Intrinsic Safety
★
N1
ATEX Type n
★
N7
IECEx Type n
★
ND
ATEX Dust
★
Display type(18)
M5
★
PlantWeb LCD display
M7(11)(17)(19) Remote mount LCD display and interface, PlantWeb housing, no cable, SST bracket
★
M8(11)(20)
Remote mount LCD display and interface, PlantWeb housing, 50 ft. (15 m) cable, SST bracket
★
M9(11)(20)
Remote mount LCD display and interface, PlantWeb housing, 100 ft. (31 m) cable, SST bracket
★
Pressure testing
P1
Hydrostatic testing with certificate
Calibration certification
Q4
★
Calibration certificate
Material traceability certification
Q8
★
Material traceability certification per EN 10204 3.1B
Quality certification for safety
QS(11)(13)
Prior-use certificate of FMEDA Data
★
QT(21)
Safety-certified to IEC 61508 with certificate of FMEDA data
★
Transient protection(20)(22)
T1
★
Transient terminal block
Toolkit performance reports
QZ
★
Remote Seal System Performance Calculation Report
NACE® certificate(20)
Q15
Certificate of Compliance to NACE MR0175/ISO 15156 for wetted materials
★
Q25
Certificate of Compliance to NACE MR0103 for wetted materials
★
Typical model number:
1.
2.
3.
4.
5.
8
3051SHP 1CD6A3N3 H11A1A DA2 B4 M5
For detailed specifications see “Specifications” on page 10.
Materials of Construction comply with metallurgical requirements highlighted within NACE MR0175/ISO 15156 for sour oil field production environments.
Environmental limits apply to certain materials. Consult latest standard for details. Selected materials also conform to NACE MR0103 for sour refining
environments. Order with Q15 or Q25 to receive a NACE certificate.
Isolator diaphragm selection will dictate materials of construction for wetted parts.
Consult factory for available Rosemount 1199 high pressure remote seal options.
“Assemble to” items are specified separately and require a completed model number.
EmersonProcess.com/Rosemount
December 2015
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
20.
21.
22.
Rosemount 3051S High Pressure
Requires PlantWeb housing.
Only intrinsically safe approval codes apply.
Long-Life Power Module must be shipped separately, order Power Module 701PBKKF.
Only available with output code F.
Only available with output code A.
Requires PlantWeb housing and output code A. Includes Hardware Adjustments as standard.
This assembly is included with approval options EP, KP, E1, N1, K1, ND, E4, E7, N7, K7, E2, E3, KA, KC, KD, IA, IB, IE, IF, IG, KG, K2, N3, EM, and KM. It is also included
with transient protection T1.
Not available with housing style codes 00, 01, 2E, 2F, 2G, 2M, 5A, 5J, or 7J.
Transmitter is shipped with 316 SST conduit plug (uninstalled) in place of standard carbon steel conduit plug.
Valid when SuperModule Platform and housing have equivalent approvals.
Not available with M20 or G 1/2 conduit entry size.
Not available with output code F, option code DA2, or option code QT.
Not available with Housing code 7J.
See the 3051S Reference Manual (document number 00809-0100-4801) for cable requirements. Contact an Emerson™ Process Management representative for
additional information.
NACE compliant wetted materials are identified by Footnote 2.
Not available with output code F or X. Not available with housing code 7J.
Not available with Housing code 00, 5A, 5J, or 7J.
EmersonProcess.com/Rosemount
9
Rosemount 3051S High Pressure
December 2015
Specifications
Performance specifications
3051SHP
Warranty(1)
For zero-based spans, reference conditions, silicone oil fill, C-276
isolating diaphragm, coned and threaded process connections,
digital trim values set to equal range points.
Classic models

1-year limited warranty is standard(2)
Conformance to specification (±3σ [Sigma])

Extended 3-year and 5-year limited warranties available if
ordered(3)
Technology leadership, advanced manufacturing techniques,
and statistical process control ensure pressure measurement
specification conformance to ±3σ or better.
Reference accuracy
Ultra models

15-year limited warranty(4)
1.
Stated reference accuracy equations include terminal based
linearity, hysteresis, and repeatability. For FOUNDATION Fieldbus
and wireless devices, use calibrated range in place of span.
2.
3.
4.
Table 2. 3051SHP Differential Pressure Transmitter(1)
Differential
pressure range
Reference accuracy
Range 6
±0.055% of span; Spans less than 10:1,
±[0.005 + 0.01(URL/Span)]% of span
Range 7
±0.055% of span; Spans less than 10:1,
±[0.015 + 0.005 (URL/span)]% of span
Range 8
±0.055% of span; Spans less than 5:1,
±[0.015 + 0.005 (URL/span)]% of span
1.
For transmitters assembled to 1199 remote seals, consult factory.
Process temperature RTD
Total Response Time(1)(2)
100 ms
Dead Time(3)
45 ms
Sensor Update Rate(4)
22 Hz
1.
2.
3.
4.
Table 3. 3051SHP Differential Pressure Transmitter
Differential
pressure
range
Stability
The greater of ±0.185 °F (0.103 °C) or 0.1% of reading per year
(excludes RTD sensor stability)
Ambient temperature effect(1)
Range 6
±0.035% URL + 0.0625% span from 1:1 to 5:1;
±0.070% + 0.125% span from >5:1 to 50:1
Range 7
±0.0125% URL + 0.0625% span from 1:1 to 5:1;
±0.025% + 0.125% span from >5:1 to 100:1
Range 8
±0.0125% URL + 0.0625% span from 1:1 to 5:1;
±0.025% + 0.125% span from >5:1 to 150:1
±0.35% of URL for 10 years
Process temperature
1.
10
For transmitters assembled to 1199 remote seals, consult factory.
For FOUNDATION Fieldbus (output code F), add 52 ms to stated values (not
including segment macro-cycle). For option code DA2, add 45 ms
(nominal) to stated values.
For option code DA2, dead time is 90 milliseconds (nominal).
Does not apply to Wireless (output code X). See “IEC 62591
(WirelessHART)” on page 13 for wireless update rate.
Table 4. 3051SHP Differential Pressure Transmitter
Long term stability
Range 6-8
Dynamic performance
Ambient temperature effect
±0.67 °F (0.37 °C)
Differential
pressure range
Warranty details can be found in Emerson Process Management Terms &
Condition of Sale. Document 63445. Rev G (10/06).
Goods are warranted for twelve (12) months from the date of initial
installation of eighteen (18) months from the date of shipment by seller,
whichever period expires first.
3-year and 5-year warranty apply to date of shipment by seller.
Rosemount Ultra transmitters have a limited warranty of fifteen (15)
years from date of shipment. All other provisions of Emerson Process
Management standard limited warranty remain the same.
Temperature effect calculated per 50 °F (28 °C).
EmersonProcess.com/Rosemount
December 2015
Rosemount 3051S High Pressure
Functional specifications
Process temperature RTD interface
Minimum span = 0.39 °F (0.216 °C) per 50 °F (28 °C)
3051SHP Line pressure effect
(DP measurement only)
Range and sensor limits
Table 5. 3051SHP Differential Pressure Transmitter
LRL
URL
Range 6
-250 inH2O
(-623 mbar)
250 inH2O
(623 mbar)
Differential pressure range
Differential
pressure range
Zero error
Span error
Range 6
±0.1% URL per
1000 psi
±0.3% of reading per
1000 psi
Range 7
-700 inH2O
(-1,74 bar)
700 inH2O
(1,74 bar)
Range 7
±0.1% URL per
1000 psi
±0.2% of reading per
1000 psi
Range 8
-150 psi
(-10,34 bar)
150 psi
(10,34 bar)
Range 8
±0.1% URL per
1000 psi
-1.6% ±0.2% of
reading per 1000 psi
Process temperature RTD interface
LRL
URL
-328 °F (-200 °C)
1562 °F (850 °C)
Mounting position effects
3051SHP Differential Pressure Transmitter
Zero shifts to ±1.25 in H2O (6.22 mbar), which can be zeroed.
Minimum span limits
Span: No effect
Table 6. 3051SHP Differential Pressure Transmitter(1)
Vibration effect
Differential pressure range
Less than ±0.1% of URL when tested per the requirements of
IEC60770-1 field or pipeline with high vibration level (10-60 Hz
0.21 mm displacement peak amplitude/60-2000 Hz 3g).
Range 6
5 inH2O (12,44 mbar)
Range 7
7 inH2O (17,42 mbar)
Range 8
1 psi (68,95 mbar)
For Housing Style codes 1J, 1K, 1L, 2J, and 2M: Less than ±0.1% of
URL when tested per the requirements of IEC60770-1 field with
general application or pipeline with low vibration level (10-60 Hz
0.15 mm displacement peak amplitude/60-500 Hz 2g).
Power supply effect
Less than ±0.005% of calibrated span per volt change in voltage
at the transmitter terminals
Electromagnetic compatibility (EMC)
Meets all relevant requirements of EN 61326.
Transient protection (option T1)
Tested in accordance with IEEE C62.41.2-2002, Location
Category B

6 kV crest (0.5 μs - 100 kHz)

3 kA crest (8 ⫻ 20 microseconds)

6 kV crest (1.2 ⫻ 50 microseconds)
EmersonProcess.com/Rosemount
1.
Limit
For transmitters assembled to 1199 remote seals, consult factory.
Process temperature RTD interface
52 °F (11 °C)
Service
3051SHP (DP only): Liquid, gas, and vapor applications
3051SHP (DP + Temperature): Liquids, saturated steam
4–20 mA HART
Zero and span adjustment
Zero and span values can be set anywhere within the range.
Span must be greater than or equal to the minimum span.
Output
Two-wire 4–20 mA is user-selectable for linear or square root
output. Digital process variable superimposed on 4–20 mA
signal, available to any host that conforms to the HART protocol.
11
Rosemount 3051S High Pressure
Power supply
External power supply required.
 3051S: 10.5 to 42.4 Vdc with no load
 3051S with Advanced HART Diagnostics Suite: 12 to 42.4 Vdc
with no load
Load limitations
Maximum loop resistance is determined by the voltage level of
the external power supply, as described by:
3051SHP
Load (Ohms)
Maximum Loop Resistance = 43.5 * (Power Supply Voltage – 10.5)
Suite includes: Statistical Process Monitoring (SPM), Power
Advisory, Status Log, Variable Log, Advanced Process Alerts,
Service Alerts, and Time Stamp capability.
FOUNDATION Fieldbus
Power supply
External power supply required; transmitters operate on 9.0 to
32.0 Vdc transmitter terminal voltage.
Current draw
1000
17.5 mA for all configurations (including LCD display option)
500
10.5
FOUNDATION Fieldbus parameters
Operating
Region
20
30
Voltage (Vdc)
42.4
The Field Communicator requires a minimum loop resistance of 250Ω
for communication.
3051SHP, 3051SHP with HART Diagnostics (option
code DA2), and 3051SHP with DP + T measurement
Maximum Loop Resistance = 43.5 * (Power Supply Voltage – 12.0)
1322
Load (Ohms)
The Device Dashboard presents the diagnostics in a
graphical, task-based interface that provides single click
access to critical process/device information and descriptive
graphical troubleshooting.
1387
0
1000
500
12.0
Operating
Region
20
30
Voltage (Vdc)
Schedule Entries
14 (max.)
Links
30 (max.)
Virtual Communications Relationships (VCR)
20 (max.)
Standard function blocks
Resource block
•Contains hardware, electronics, and diagnostic information.
Transducer block
•Contains actual sensor measurement data including the
sensor diagnostics and the ability to trim the pressure sensor
or recall factory defaults.
LCD display block
•Configures the local display.
0
42.4
The Field Communicator requires a minimum loop resistance of 250Ω
for communication.
Advanced HART Diagnostics Suite (option code DA2)
Statistical Process Monitoring (SPM) provides statistical data
(standard deviation, mean, coefficient of variation) that can
be used to detect process and process equipment
anomalies, including plugged impulse lines, air entrainment,
pump cavitation, furnace flame instability, distillation
column flooding and more. This diagnostic allows you to
take preventative measures before abnormal process
situations result in unscheduled downtime or rework.
Power Advisory diagnostic pro-actively detects and notifies
you of degraded electrical loop integrity before it can affect
your process operation. Example loop problems that can be
detected include water in the terminal compartment,
corrosion of terminals, improper grounding, and unstable
power supplies.
12
December 2015
2 analog input blocks
•Processes the measurements for input into other function
blocks. The output value is in engineering or custom units
and contains a status indicating measurement quality.
PID block with auto-tune
•Contains all logic to perform PID control in the field
including cascade and feed forward. Auto-tune capability
allows for superior tuning for optimized control
performance.
Backup link active scheduler (LAS)
The transmitter can function as a link active scheduler if the
current link master device fails or is removed from the segment.
Software upgrade in the Field
Software for the 3051S with FOUNDATION Fieldbus is easy to
upgrade in the field using the FOUNDATION Fieldbus “Common
Device Software Download” procedure.
EmersonProcess.com/Rosemount
December 2015
Rosemount 3051S High Pressure
PlantWeb alerts
Fully compensated mass flow block (option code H01)
Enable the full power of the PlantWeb digital architecture by
diagnosing instrumentation issues, communicating advisory,
maintenance, and failure details, and recommending a solution.
Calculates fully compensated mass flow based on differential
pressure with external process pressure and temperature
measurements over the Fieldbus segment. Configuration for the
mass flow calculation is easily accomplished using the
Rosemount Engineering Assistant 5.5.1 software.
Advanced control function block suite (option code A01)
Input selector block
•Selects between inputs and generates an output using
specific selection strategies such as minimum, maximum,
midpoint, average, or first “good.”
Arithmetic block
•Provides pre-defined application-based equations including
flow with partial density compensation, electronic remote
sensors, hydrostatic tank gauging, ratio control and others.
Signal characterizer block
•Characterizes or approximates any function that defines an
input/output relationship by configuring up to twenty X, Y
coordinates. The block interpolates an output value for a
given input value using the curve defined by the configured
coordinates.
Integrator block
•Compares the integrated or accumulated value from one or
two variables to pre-trip and trip limits and generates
discrete output signals when the limits are reached. This
block is useful for calculating total flow, total mass, or
volume over time.
FOUNDATION Fieldbus Diagnostics Suite (option code D01)
Statistical process monitoring (SPM) provides statistical data
(standard deviation and mean) that can be used to detect
process and process equipment anomalies, including plugged
impulse lines, air entrainment, pump cavitation, furnace flame
instability, distillation column flooding, and more. This
diagnostic allows you to take preventative measures before
abnormal process situations result in unscheduled downtime or
rework.
The Device Dashboard presents the diagnostics in a graphical,
task-based interface that provides single click access to critical
process/device information and descriptive graphical
troubleshooting.
Suite includes: statistical process monitoring (SPM) and plugged
impulse line detection (PIL).
IEC 62591 (WirelessHART)
Output splitter block
•Splits the output of one PID or other control block so that the
PID will control two valves or other actuators.
Output
Control selector block
•Selects one of up to three inputs (highest, middle, or lowest)
that are normally connected to the outputs of PID or other
control function blocks.
Radio frequency power output from antenna
Block
Execution time
IEC 62591 (WirelessHART), 2.4 GHz DSSS

External antenna (WK option):
Maximum of 10 mW (10 dBm) EIRP

Extended range, external antenna (WM option):
Maximum of 18 mW (12.5 dBm) EIRP

Remote (WJ option) antenna:
Maximum of 17 mW (12.3 dBm) EIRP

High-gain, remote antenna (WN option):
Maximum of 40 mW (16 dBm) EIRP
Resource
N/A
Transducer
N/A
LCD Display Block
N/A
Analog Input 1, 2
20 milliseconds
PID with Auto-tune
35 milliseconds
Input Selector
20 milliseconds
Arithmetic
20 milliseconds
Signal Characterizer
20 milliseconds
Integrator
20 milliseconds
The optional seven-digit LCD display can display user-selectable
information such as primary variable in engineering units,
percent of range, sensor module temperature, and electronics
temperature. The display updates based on the wireless update
rate.
Output Splitter
20 milliseconds
Update rate
Control Selector
20 milliseconds
User selectable 1 sec. to 60 min.
EmersonProcess.com/Rosemount
Local display
13
Rosemount 3051S High Pressure
December 2015
Power module
Storage
Field replaceable, keyed connection eliminates the risk of
incorrect installation, Intrinsically Safe Lithium-thionyl chloride
Power Module with polybutadine terephthalate (PBT) enclosure.
Ten-year life at one minute update rate.(1)
-50 to 185 °F (-46 to 85 °C)
With LCD display: -40 to 185 °F (-40 to 85 °C)
With wireless output: -40 to 185 °F (-40 to 85 °C)
1.
Reference conditions are 70 °F (21 °C), and routing data for three
additional network devices.
Note: Continuous exposure to ambient temperature limits of
-40 °F or 185 °F (-40 °C or 85 °C) may reduce specified life by less than 20
percent.
Process temperature limits
At atmospheric pressures and above:
Coplanar sensor module
Silicone Fill Sensor(1)
Overpressure limits
1.
Pressure range
Overpressure limit
3051SHP, Static
22,500 psi (1.551 bar)
3051SHP, DP
15,000 psi (1.034 bar)
Maximum working pressure limits
-40 to 250 °F (-40 to 121 °C)
Process temperatures above 185 °F (85 °C) require derating the ambient
limits by a 1.5:1 ratio. For example, for process temperature of 195 °F
(91 °C), new ambient temperature limit is equal to 170 °F (77 °C). This can
be determined as follows:
(195 °F - 185 °F) ⫻ 1.5 = 15 °F,
185 °F - 15 °F = 170 °F
Indication
Optional three-line LCD display
Maximum working pressure is the maximum pressure allowed
for normal transmitter operation. For a differential pressure
transmitter, the maximum working pressure is the static line
pressure under which the transmitter can safely operate. If one
side of the transmitter is exposed to the full static line pressure
due to mis-valving, the transmitter will experience an output
shift and must be re-zeroed. For a gage or absolute pressure
transmitter, the maximum working pressure is the same as the
Upper Range Limit (URL). The maximum working pressure of
transmitters with assemble-to options is limited by the lowest
maximum pressure rating of the individual components.
3051SHP
The maximum working pressure of the 3051SHP is specified in
the model number of the product and is rated up to 15,000 psi
(1.034 bar).
Static pressure limits for the 3051SHP
Operates within specifications between static line pressures of:
0.5 psia to 15,000 psig (0,03 to 1.034,21 bar) for transmitters
with a maximum working pressure of 15,000 psig.
Burst pressure limits
3051SHP: 37,500 psi (2.585 bar)
Temperature limits
Ambient
-40 to 185 °F (-40 to 85 °C)
With LCD display(1): -40 to 175 °F (-40 to 80 °C)
1.
14
LCD display may not be readable and LCD display updates will be slower
at temperatures below -4 °F (-20 °C).
Zero and span adjustment requirements
Zero and span values can be set anywhere within the range
limits stated in Table 5 on page 11. Span must be greater than or
equal to the minimum span stated in Table 6 on page 11.
Humidity limits
0–100% relative humidity
Turn-on time(1)
When power is applied to the transmitter during startup,
performance will be within specification per the time period
described below:
3051S_T: 2 seconds
3051SHP DP: 2 seconds (assumed the same value as 3051S)
3051SHP DP + T: 5 seconds
1.
Does not apply to wireless option code X.
Volumetric displacement
Less than 0.0005 in.3 (0,008 cm3)
Damping
Analog output response time to a step change is user-selectable
from 0 to 60 seconds for one time constant. Software damping
is in addition to sensor module response time.
For 3051SHP DP + T each variable can be individually adjusted.
Transmitter security
Activating the transmitter security function prevents changes to
the transmitter configuration, including local zero and span
adjustments. Security is activated by an internal switch.
EmersonProcess.com/Rosemount
December 2015
Rosemount 3051S High Pressure
Failure mode alarm
Physical specifications
4-20 mA HART (output option code A)
Material selection
If self-diagnostics detect a gross transmitter failure, the analog
signal will be driven offscale to alert the user. Rosemount
standard (default), NAMUR, and custom alarm levels are
available (see Alarm configuration).
High or low alarm signal is software-selectable or
hardware-selectable via the optional switch (option D1).
Alarm configuration
High alarm
Low alarm
Default
≥ 21.75 mA
≤ 3.75 mA
NAMUR(1)
≥ 22.5 mA
≤ 3.6 mA
Custom levels(2)(3)
20.2 - 23.0 mA
3.4 - 3.8 mA
1.
2.
3.
Analog output levels are compliant with NAMUR recommendation NE
43, see option codes C4 or C5.
Low alarm must be 0.1 mA less than low saturation and high alarm must
be 0.1 mA greater than high saturation.
For option code DA2, low alarm custom values are 3.6 - 3.8 mA.
Emerson provides a variety of Rosemount product with various
product options and configurations including materials of
construction that can be expected to perform well in a wide
range of applications. The Rosemount product information
presented is intended as a guide for the purchaser to make an
appropriate selection for the application. It is the purchaser’s
sole responsibility to make a careful analysis of all process
parameters (such as all chemical components, temperature,
pressure, flow rate, abrasives, contaminants, etc.), when
specifying product, materials, options and components for the
particular application. Emerson Process Management is not in a
position to evaluate or guarantee the compatibility of the
process fluid or other process parameters with the product,
options, configuration or materials of construction selected.
Electrical connections
/ –14 NPT, G1/2, and M20 ⫻ 11/2 conduit. HART interface
connections fixed to terminal block for Output code A and X.
1 2
Safety-certified transmitter failure values(1)
Process connections
Device Safety accuracy: ± 2.0% of analog output span (2)
3051SHP
Device Safety response time: 1.5 seconds
Autoclave connection or seals
1.
2.
Does not apply to wireless option code X.
Trip values in the DCS or safety logic solver should be derated by this
device safety accuracy.
Process-wetted parts
Process isolating diaphragms
Coplanar sensor module
Alloy C-276 (UNS N10276)
Non-wetted parts
Electronics housing
Low-copper aluminum alloy or CF-8M (Cast 316 SST)
NEMA® 4X, IP 66, IP 68 (66 ft (20 m) for 168 hours)
Note
IP 68 not available with wireless output.
Coplanar sensor module housing
3051SHP
C-276 module base, CF-3M (Cast 316L SST) upper module
housing
Sensor module fill fluid
Silicone is standard.
Paint for aluminum housing
Polyurethane
EmersonProcess.com/Rosemount
15
Rosemount 3051S High Pressure
Cover O-rings
December 2015
Transmitter option weights
Buna-N
Wireless antenna
External antenna (WK/WM)
PBT/PC integrated omni-directional antenna
1J, 1K, 1L
SST PlantWeb housing
3.5 (1,6)
2J
SST Junction Box housing
3.4 (1,5)
7J
SST Quick Connect
0.4 (0,2)
2A, 2B, 2C
Aluminum Junction Box
housing
1.1 (0,5)
1A, 1B, 1C
Aluminum PlantWeb housing
1.1 (0,5)
LCD display for Aluminum
PlantWeb housing
0.8 (0,4)
LCD display for SST PlantWeb
housing
1.6 (0,7)
SST Mounting Bracket for
Coplanar Flange
1.2 (0,5)
Remote antenna (WN)
Fiberglass omni-directional antenna
Power module
Field replaceable, keyed connection eliminates the risk of
incorrect installation, Intrinsically Safe Lithium-thionyl chloride
power module with PBT enclosure
M5(1)
Shipping weights
B4
Sensor module weights
3051SHP sensor module
1.
4.49 lb (2,04 kg)
3051SHP Transmitter with sensor module
Junction Box housing,
direct process connection
5.64 lb (2,56 kg)
PlantWeb housing,
direct process connection
6.04 lb (2,74 kg)
Wireless PlantWeb housing,
direct process connection
6.64 lb (3,01 kg)
Fully functional transmitter with sensor module, housing, terminal
block, and covers. Does not include LCD display.
Item
Weight in lb. (kg)
Aluminum standard cover
0.4 (0,2)
SST standard cover
1.3 (0,6)
Aluminum display cover
0.7 (0,3)
SST display cover
1.5 (0,7)
Wireless extended cover
0.7 (0,3)
LCD display(1)
0.1 (0,04)
Junction box terminal block
0.2 (0,1)
PlantWeb terminal block
0.2 (0,1)
Power module
0.5 (0,2)
1.
16
Includes LCD display and display cover.
Transmitter component weights
Transmitter weights(1)
1.
Add lb (kg)
Option code Option
Display only
EmersonProcess.com/Rosemount
December 2015
Rosemount 3051S High Pressure
Product Certifications
Rev 1.3
Ordinary Location Certification
Canada
As standard, the transmitter has been examined and tested to
determine that the design meets the basic electrical,
mechanical, and fire protection requirements by a nationally
recognized test laboratory (NRTL) as accredited by the Federal
Occupational Safety and Health Administration (OSHA).
E6
Canada Explosion-proof, Dust Ignition-proof, Division 2
Certificate: 1143113
Standards: CAN/CSA C22.2 No. 0-10, CSA C22.2 No.
25-1966 (R2014), CSA C22.2 No. 30-M1986
(R2012), CSA C22.2 No. 94.2-07, CSA C22.2
No. 213-M1987 (R2013), CAN/CSA-C22.2 No.
61010-1-12, ANSI/ISA 12.27.01-2011
Markings: Class I, Groups B, C, D, -50 °C ≤ Ta ≤ +85 °C;
Class II, Groups E, F, G; Class III; suitable for
Class I, Zone 1, Group IIB+H2, T5; Class I,
Division 2, Groups A, B, C, D; suitable for Class I,
Zone 2, Group IIC, T5; Seal Not Required; Dual
Seal; Type 4X
I6
Canada Intrinsically Safe
Certificate: 1143113
Standards: CAN/CSA C22.2 No. 0-10, AN/CSA-60079-0-11,
CAN/CSA C22.2 No. 60079-11:14, CSA C22.2
No. 94.2-07, ANSI/ISA 12.27.01-2011
Markings: Intrinsically Safe Class I, Division 1; Groups A, B,
C, D; suitable for Class 1, Zone 0, IIC, T3C;
Rosemount drawing 03251-1006; Dual Seal;
Type 4X
I6
Canada FISCO Intrinsically Safe
Certificate: 1143113
Standards: CAN/CSA C22.2 No. 0-10, AN/CSA-60079-0-11,
CAN/CSA C22.2 No. 60079-11:14, CSA C22.2
No. 94.2-07, ANSI/ISA 12.27.01-2011
Markings: Intrinsically Safe Class I, Division 1; Groups A, B,
C, D; suitable for Class 1, Zone 0, IIC, T3C;
Rosemount drawing 03251-1006; Dual Seal;
Type 4X
Installing Equipment in North America
The US National Electrical Code (NEC) and the Canadian
Electrical Code (CEC) permit the use of Division marked
equipment in Zones and Zone marked equipment in Divisions.
The markings must be suitable for the area classification, gas,
and temperature class. This information is clearly defined in the
respective codes.
USA
E5
US Explosionproof, Dust Ignition-proof
Certificate: 1143113
Standards: FM Class 3600 - 2011, FM Class 3615 - 2006,
FM Class 3810 - 2005, UL 1203 5th Ed.,
UL 50E 1st Ed., UL 61010-1 (3rd Edition)
Markings: XP CL I, DIV 1, GP B, C, D;
DIP CL II, DIV 1, GP E, F, G; CL III;
T5(-50 °C ≤ Ta ≤ +85 °C); Seal Not Required;
Type 4X
I5
US Intrinsically Safe; Nonincendive
Certificate: 1143113
Standards: FM Class 3600 - 2011, FM Class 3610 - 2010,
FM Class 3611 - 2004, FM Class 3810 - 2005,
UL 50E 1st Ed., UL 61010-1 (3rd Edition)
Markings: IS CL I,II,III, DIV 1, GP A, B, C, D, E, F, G, T4;
Class 1, Zone 0 AEx ia IIC T4;
NI CL 1, DIV 2, GP A, B, C, D, T5;
Rosemount drawing 03251-1006; Type 4X
IE
US FISCO Intrinsically Safe
Certificate: 1143113
Standards: FM Class 3600 - 2011, FM Class 3610 - 2010,
FM Class 3810 - 2005, UL 50E 1st Ed.,
UL 61010-1 (3rd Edition)
Markings: IS CL I, DIV 1, GP A, B, C, D, T4;
Class 1, Zone 0 AEx ia IIC T4;
Rosemount drawing 03251-1006; Type 4X
EmersonProcess.com/Rosemount
17
Rosemount 3051S High Pressure
December 2015
Dimensional Drawings
Figure 1. PlantWeb Housing
Side view
Front view
5.17
(131,3)
4.20
(106,7)
C
7.70
(195,5)
A
8.25
(209,4)
D
B
A. Digital display cover
B. Bracket mounting holes (5/16-18 UNC, two places)
C. Housing rotation set screw
D. Nameplate
6.71
(170,4)
90.0°
3.53
(89,7)
6.88
(174,8)
4.20
(106,7)
11.16
(283,5)
A
Dimensions are in inches (millimeters).
18
A. Digital display cover
EmersonProcess.com/Rosemount
December 2015
Rosemount 3051S High Pressure
Figure 2. Other Housings
Quick connect
Junction box
1.50
(38,1)
3.45
(87,6)
5.88
(149,2)
6.43
(163,2)
Dimensions are in inches (millimeters).
Figure 3. Remote Meter Option
5.17
(131,3)
5.20
(132,0)
EmersonProcess.com/Rosemount
19
Rosemount 3051S High Pressure
December 2015
Figure 4. High Gain, Remote Mount Antenna (WN Option)
A
20.2 (513)
B
C
D
E
A. Antenna
B. Mounting bracket
C. Lightning arrester
D. 25 ft (7.6 m) cable
E. Min drip loop Ø12-in. (0.3 m)
Dimensions are in inches (millimeters).
20
EmersonProcess.com/Rosemount
December 2015
Rosemount 3051S High Pressure
Figure 5. Traditional Mounting Configurations
Pipe mount
Panel mount
6.400
(162,56)
6.43
(163,2)
2.810
(71,37)
4.94
(125,4)
Dimensions are in inches (millimeters).
Figure 6. Remote Display Mounting Configurations (B4 Bracket)
Pipe mount
Front view
Panel mount
Side view
Side view
2.34
(59,3)
5.17
(131,3)
4.490
(114,04)
8.67
(220,2)
6.15
(156,2)
6.22
(158,1)
4.72
(119,9)
Dimensions are in inches (millimeters).
EmersonProcess.com/Rosemount
21
Rosemount 3051S High Pressure
December 2015
Options
Transmitter options
Tagging (3 options available)
Standard configuration

Standard SST hardware tag is wired to the transmitter. Tag
character height is 0.125-in. (3,18 mm), 56 characters
maximum.

Tag may be permanently stamped on transmitter nameplate
upon request, 56 characters maximum.

Tag may be stored in transmitter memory. Character limit is
dependent on protocol.
Unless otherwise specified, transmitter is shipped as follows:
Engineering units
3051SHP
inH2O (Range 6 and 7)
psi (Range 8)
4 mA(1):
0 (engineering units above)
20 mA(1):
Upper range limit
Output
Linear
External buttons
None
Drain/vent
Specified model code option
LCD display
None
Alarm(1)
High
Software tag
Blank
Damping
0.4 seconds(2)
1.
2.
Not applicable to FOUNDATION Fieldbus or wireless.
For fieldbus protocols, default damping is 1 second.
•HART 4-20mA: 8 characters
•WirelessHART: 32 characters
•FOUNDATION Fieldbus: 32 characters
Commissioning tag(2)
A temporary commissioning tag is attached to all transmitters.
The tag indicates the device ID and allows an area for writing the
location.
Output information
Output range points must be the same unit of measure.
Available units of measure include:
Custom configuration(1)
Pressure
If option code C1 is ordered, the customer may specify the
following data in addition to the standard configuration
parameters.
atm
inH2O @4 °C
g/cm2
psi
mbar
mmH2O
kg/cm2
torr
bar
mmHg
Pa
cmH2O @4 °C(1)
inH20
mmH2O @4 °C
kPa
mH2O @4 °C(1)

Output information

Transmitter information
inHg
ftH20
MPa
ftH2O @60 °F(1)

LCD display configuration
hPa(1)
inH2O @60 °F
kg/m2(1)
cmHg @0 °C(1)
Hardware selectable information
mHg @0 °C(1)
psf(1)

ftH2O @4 °C(1)

Signal selection

Wireless information

Scaled variable

and more
1.
Field configurable only, not available for factory calibration or custom
configuration (option code C1 “Software configuration”).
For 3051SHP, refer to the Rosemount 3051S High Static Pressure
Transmitter Configuration Data Sheet (document number
00806-0100-4851).
1.
22
Not applicable to FOUNDATION Fieldbus protocol.
2.
Only applicable to FOUNDATION Fieldbus.
EmersonProcess.com/Rosemount
December 2015
Rosemount 3051S High Pressure
Display and interface options
M5 Digital Display
• 3-line, 7-digit LCD display
• Direct reading of digital data for higher accuracy
• Displays user-defined flow, level, volume, or pressure
units
• Displays diagnostic messages for local troubleshooting
• 90-degree rotation capability for easy viewing
Configuration buttons
Transmitter will ship with no buttons unless option D1
(hardware adjustments) or DA2 (Advanced HART Diagnostics
Suite) are specified.
The Rosemount Wireless Transmitter is available with a digital
zero button installed with or without the LCD display digital
display.
Transient protection (option code T1)
Tested in accordance with IEEE C62.41.2-2002, Location
Category B
6 kV crest (0.5 μs - 100 kHz)
3 kA crest (8 ⫻ 20 μs)
6 kV crest (1.2 ⫻ 50 μs)
Conduit plug
DO 316 SST Conduit Plug
Single 316 SST conduit plug replaces carbon steel plug
Bracket option
B4
Bracket for 2-in. pipe or panel mounting
• Bracket for mounting of transmitter on 2-in. pipe or
panel
• 316 stainless steel construction with stainless steel
bolts
Other publications
For additional information, go to www.EmersonProcess.com.
EmersonProcess.com/Rosemount
23
Rosemount 3051S High Pressure
Product Data Sheet
00813-0100-4851, Rev AA
December 2015
Global Headquarters
Emerson Process Management
6021 Innovation Blvd.
Shakopee, MN 55379, USA
+1 800 999 9307 or +1 952 906 8888
+1 952 949 7001
[email protected]
North America Regional Office
Emerson Process Management
8200 Market Blvd.
Chanhassen, MN 55317, USA
+1 800 999 9307 or +1 952 906 8888
+1 952 949 7001
[email protected]
Latin America Regional Office
Emerson Process Management
1300 Concord Terrace, Suite 400
Sunrise, FL 33323, USA
+1 954 846 5030
+1 954 846 5121
[email protected]
Europe Regional Office
Emerson Process Management Europe GmbH
Neuhofstrasse 19a P.O. Box 1046
CH 6340 Baar
Switzerland
+41 (0) 41 768 6111
+41 (0) 41 768 6300
[email protected]
Linkedin.com/company/Emerson-Process-Management
Twitter.com/Rosemount_News
Asia Pacific Regional Office
Emerson Process Management Asia Pacific Pte Ltd
1 Pandan Crescent
Singapore 128461
+65 6777 8211
+65 6777 0947
[email protected]
Middle East and Africa Regional Office
Emerson Process Management
Emerson FZE P.O. Box 17033,
Jebel Ali Free Zone - South 2
Dubai, United Arab Emirates
+971 4 8118100
+971 4 8865465
[email protected]
Facebook.com/Rosemount
Youtube.com/user/RosemountMeasurement
Google.com/+RosemountMeasurement
Standard Terms and Conditions of Sale can be found at:
www.Emerson.com/en-us/pages/Terms-of-Use.aspx
The Emerson logo is a trademark and service mark of Emerson Electric Co.
SuperModule, Saturn, PlantWeb, Rosemount, and the Rosemount
logotype are trademarks of Emerson Process Management.
HART and WirelessHART are registered trademarks of the FieldComm
Group.
FOUNDATION Fieldbus is a trademark of the FieldComm Group.
NEMA is a registered trademark and service mark of the National
Electrical Manufacturers Association.
NACE is a registered trademark of NACE International.
All other marks are the property of their respective owners.
© 2015 Emerson Process Management. All rights reserved.