❑ KSE- 2 DC ALARM

❑ KSE- 2 DC ALARM
KSE-❑2
INSTRUCTION MANUAL
DC ALARM
KSE-❑2
MODEL
(dial adjustment; dual trip)
BEFORE USE ....
INSTALLATION
Thank you for choosing M-System. Before use, check the
package you received as below.
If you have any problems or questions with the product,
please contact M-System’s Sales Office or representatives.
Detach the yellow clamps located at the top and bottom of
the unit for separating the body
from the base socket.
■ PACKAGE INCLUDES:
Signal conditioner (body + base socket + input resistor) (1)
Input resistor is provided only with current input type.
■ DIN RAIL MOUNTING
Set the base socket so that its
DIN rail adaptor is at the bottom. Position the upper hook
at the rear side of base socket
on the DIN rail and push in the
Spring Loaded
lower. When removing the
DIN Rail Adaptor
socket, push down the DIN rail
adaptor utilizing a screwdriver Shape and size of the base socket
are slightly different with various
(–) and pull.
socket types.
■ MODEL NO.
Check that model No. described on specification label is
exactly what you ordered.
■ INSTRUCTION MANUAL
This manual describes necessary points of caution when you
use this product, installation, connection and basic maintenance procedures.
COMPONENT IDENTIFICATION
Base Socket
Connection Diagram
Label
Specification
Label
Body
K-UNIT
Clamp
(top & bottom)
DIN Rail
35mm wide
■ WALL MOUNTING
Refer to the drawings in the following page.
TERMINAL CONNECTIONS
Connect the unit as in the diagram in the following page or
refer to the connection diagram label on top of the unit.
When an input resistor is provided with the module, attach
it together with input wiring to the input screw terminals.
100
SET1
KSE
Model
50
%
0
Input Resistor
100
50
%
0
SET2
■ FRONT PANEL CONFIGURATION
100
SET1
%
50
0
Hi Setpoint Adj. Dial
Hi Monitor LED
Lo Monitor LED
100
%
50
SET2
Lo Setpoint Adj. Dial
0
P. 1 / 3
EM-3609-B Rev.1
KSE-❑2
DRAWINGS mm (inch)
■DIMENSIONS
CLAMP
(top & bottom)
20
(.79)
7.8 (.31)
DIN RAIL
35mm wide
8
7
6
5
80 (3.15)
80 (3.15)
35.4 (1.39)
4
2–4.5 (.18) dia.
MTG HOLE
25 (.98) deep
9
10 11
11–M3.5
SCREW
50 (1.97)
1
2
40 (1.57)
116 (4.57)
145 (5.71)
3
[3.3 (.13)]
50 (1.97)
•When mounting, no extra space is needed between units.
■CONNECTION DIAGRAM
■TERMINAL ASSIGNMENT
+
INPUT
R
–
*
5
3 HI
6
2 LO
HI OUTPUT
(SET1)
1 COM
8
7
6
4
11 HI
10 LO
5
12 (.47)
INPUT RESISTOR
(model: REM)
LO OUTPUT
(SET2)
9 COM
9
7 U
POWER
10 11
3
1
2
8 V
Input shunt resistor attached
for current input.
*Input shunt resistor attached for current input.
P. 2 / 3
EM-3609-B Rev.1
KSE-❑2
CHECKING
1) Terminal wiring: Check that all cables are correctly
connected according to the connection diagram.
2) Power input voltage: Check voltage across the terminal 7
– 8 with a multimeter.
3) Input: Check that the input signal is within 0 – 100% of
the full-scale.
4) Output load: Check that the output load is 380V AC/
100VA or 125V DC/30W at the maximum (≤0.5A for CE
marking). For use with inductive load, external protection
is recommended.
ALARMp RELAY OPERATIONS
(1–3)ON
Hi Output
(1–2)ON
(9–10)ON
Lo Output
Input
(%)
■ POWER INPUT RATINGS
• Power input ratings are specified by the model number
suffix code. Check the power input voltage for the unit on the
specification label.
AC power: Suffix code K3 : 90 – 132V
Suffix code L3 : 180 – 264V
47 – 66 Hz, approx. 3VA
■ GENERAL
• Before you remove the unit from its base socket or mount it,
turn off the power supply and input signal for safety.
■ ENVIRONMENT
• Indoor use
• When heavy dust or metal particles are present in the air,
install the unit inside proper housing and ventilate it.
• Do not install the unit where it is subjected to continuous
vibration. Do not apply physical impact to the unit.
• Environmental temperature must be within -5 to +55°C (23
to 131°F) with relative humidity within 30 to 90% RH in order
to ensure adequate life span and operation.
(9–11)ON
0
▲
Lo Setpoint
50
▲
Hi Setpoint
100
• Trip operation in power failure: terminals 1 – 2 and 9 – 11 turn ON.
ADJUSTMENT PROCEDURE
■ HOW TO ADJUST ALARM SETPOINTS
Use a signal source and measuring instruments of sufficient
accuracy level. Turn the power supply on and warm up for
more than 10 minutes.
1) Turn the front dial to an approximate position for the
setpoint.
2) Vary simulated input signal around the setpoint and
confirm relay operation and set.
POINTS OF CAUTION
■ CONFORMITY WITH CE/LVD DIRECTIVE
• This equipment is suitable for use in Pollution Degree 2
environment and in Installation Category II, with the maximum operating voltage 300V.
A basic insulation is maintained. Prior to installation, check
that the insulation class of this unit satisfies the system
requirements.
• The equipment must be mounted inside a panel.
• The equipment must be installed such that appropriate
clearance and creepage distances are maintained to conform
to CE requirements. Failure to observe these requirements
may invalidate the CE conformance.
■ WIRING
• Do not install cables (power supply, input and output) close
to noise sources (relay drive cable, high frequency line, etc.).
• Do not bind these cables together with those in which noises
are present. Do not install them in the same duct.
■ AND ....
• The unit is designed to function as soon as power is
supplied, however, a warm up for 10 minutes is required for
satisfying complete performance described in the data sheet.
MAINTENANCE
Regular calibration procedure is explained below:
■ CALIBRATION
Warm up the unit for at least 10 minutes.
• Hi Setpoint
Increase the input signal from a value lower than the setpoint
and check that the trip point remains within the accuracy
described in the data sheet.
• Lo Setpoint
Decrease the input signal from a value higher than the
setpoint and check that the trip point remains within the
accuracy described in the data sheet.
When the trip points are out of tolerance, contact M-System’s
Sales Office or local representatives.
M-SYSTEM WARRANTY
M-System warrants such new M-System product which it manufactures to be free from defects in materials and workmanship during the 36-month period following the date that such
product was originally purchased if such product has been used under normal operating conditions and properly maintained, M-System's sole liability, and purchaser's exclusive remedies,
under this warranty are, at M-System's option, the repair, replacement or refund of the purchase price of any M-System product which is defective under the terms of this warranty. To
submit a claim under this warranty, the purchaser must return, at its expense, the defective M-System product to the below address together with a copy of its original sales invoice.
THIS IS THE ONLY WARRANTY APPLICABLE TO M-SYSTEM PRODUCT AND IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING ANY IMPLIED
WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. M-SYSTEM SHALL HAVE NO LIABILITY FOR CONSEQUENTIAL, INCIDENTAL OR
SPECIAL DAMAGES OF ANY KIND WHATSOEVER.
M-System Co., Ltd., 5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN, Phone: (06) 6659-8201, Fax: (06) 6659-8510, E-mail: [email protected]
P. 3 / 3
EM-3609-B Rev.1