Thermon TESH Heat Tracing Cable

Thermon TESH Heat Tracing Cable
TESH TM
Series Constant Watt Heating Cable
Product Specifications
Application . . .
Long Line Temperature Maintenance or Freeze Protection TESH series resistance constant Watt heating cables
are used where circuit lengths exceed the limitations of
parallel resistance heating cables. TESH withstands the temperature exposures associated with steam purging.
1
2
3
The series circuitry of TESH provides consistent Watt-permetre power output along the entire length of the cable
with no voltage drop. A glassceramic tape layer adds additional protection to the heating cable and a fluoropolymer
overjacket provides chemical resistance while maintaining
maximum flexibility. The construction of the cable meets the
7 Joule impact test per EN50019.
4
5
TESH cables are approved for use in ordinary (nonclassified) areas and Catagories 2 and 3 ATEX classified areas.
Ratings . . .
Maximum Watt density.............................................. 25 W/m
Maximum supply voltage............................................750 Vac
Maximum continuous exposure temperature
Power-off................................................................. 260°C
Minimum installation temperature................................. -60°C
Minimum bend radius.......................................5 x cable O.D.
T-rating1 .................................................................... T2 to T6
(using the principles of stabilized design or limiters)2
Stabilised Design . . .
Construction . . .
1
2
3
4
5
Heating Conductor
Fluoropolymer Dielectric Insulation
Glassceramic Tape
Nickel-Plated Copper Braid (BN)
Fluoropolymer Overjacket
Certification/Approval . . .
The Watt density limitation for TESH cables is directly related to the desired maintain temperature. Thermon is able to
ensure the T-rating based on a stabilised design that enables
series constant Watt heating cables to operate in hazardous
areas without limiting thermostats. TESH cable output and Trating are dependent upon supply voltage, cable resistance,
temperature conditions as well as additional variables.
Contact Thermon for design assistance.
European Organisation for Electrotechnical
Standardisation
Hazardous (Classified) Locations
II 2 G EEx e IIC T2 to T6 LCIE 05 ATEX 6135
TESH has additional hazardous area approvals
including:
• GGTN • Kazakhstan
Basic Accessories3 . . .
Power Connection: TESH cables typically require nonheating terminations at each end of the circuit before connecting to power. Contact Thermon for complete information.
Notes . . .
1. T-rating per internationally recognised testing agency guidelines.
2. Thermon heating cables are approved for the listed T-ratings using the stabilised
design method. This enables the cable to operate in hazardous areas without limiting thermostats. The T-rating may be determined using CompuTrace® Electric Heat
Tracing Design Software or contact Thermon for design assistance.
Product Features . . .
• Withstands continuous flamibility testing
according to IEC 60332-1: 1993
• Allows cable to be installed at temperatures
to -60°C
THERMON . . . The Heat Tracing Specialists®
www.thermon.com
European Headquarters
Boezemweg 25
2641 KG Pijnacker
PO Box 205
2640 AE Pijnacker
The Netherlands
Phone: +31 (0) 15-36 15 370
Facsimile: +31 (0) 15-36 15 379
•
•
•
•
Corporate
Tel: +44Headquarters
(0)191 490 1547
100
Dr. 477
PO Box
609
Fax:Thermon
+44 (0)191
5371
San
Marcos,
TX 78667-0609
U.S.A.
Email:
[email protected]
Phone:
+1 512-396-5801
Facsimile: +1 512-396-3627
Website:
www.heattracing.co.uk
www.thorneanderrick.co.uk
•
•
•
TESH TM
Series Constant Watt Heating Cable
Product Specifications
Available Cables . . .
Resistance
Ohm/m
at 20°C
Circuit Breaker Sizing and Type . . .
Conductor Max. Cable Length1
Cable
Size
m (with 30 mA earth- Diameter
mm2
fault protection)
mm
TESH 2.9
0.0029
6.00
1435
7.0
TESH 4.4
0.0044
4.00
1525
6.3
TESH 7
0.0072
2.50
1855
5.5
TESH 10
0.010
1.79
1775
5.1
TESH 11.7
0.0117
1.50
2025
4.9
TESH 15
0.015
1.20
2090
4.7
TESH 17.8
0.0178
1.00
2275
4.6
TESH 25
0.025
1.11
2525
4.6
TESH 31.5
0.0315
1.60
2400
4.9
TESH 50
0.050
1.02
2335
4.7
TESH 65
0.065
0.75
1890
4.4
TESH 80
0.080
1.21
2190
4.3
TESH 100
0.100
1.50
2025
4.9
TESH 150
0.150
1.02
2335
4.6
TESH 200
0.200
0.75
2605
4.4
TESH 320
0.320
0.92
2420
4.5
TESH 380
0.380
0.79
2555
4.4
TESH 480
0.480
0.64
2765
4.3
TESH 600
0.600
0.49
3010
4.2
TESH 700
0.700
0.43
3155
4.1
TESH 810
0.810
0.62
2780
4.3
TESH 1000
1.000
0.49
3010
4.2
TESH 1440
1.440
0.34
3395
4.1
TESH 1750
1.750
0.29
3615
4.1
TESH 2000
2.000
0.55
2900
4.2
TESH 3000
3.000
0.34
3395
4.1
TESH 8000
8.000
0.14
4455
3.8
Maximum circuit lengths for TESH heating cables will be a
function of cable resistance, circuit length and operating
voltage. Circuit length, breaker sizing and earth-fault protection should be based on applicable local codes.
Earth-fault protection of equipment should be provided for
each branch circuit supplying electric heating equipment.
Note . . .
1. Longer circuit lengths are possible based on earth-fault protection with higher earthfault ratings; contact Thermon.
Form TEP0070U-1205 © Thermon Manufacturing Co. Printed in U.S.A. Information subject to change.