71VRCFG規劃軟體使用手冊

71VRCFG規劃軟體使用手冊
Model 71VR1 Paperless Recorder
PC CONFIGURATOR SOFTWARE
Model: 71VRCFG Ver. 3.03
Users Manual
71VRCFG USERS MANUAL EM-7403-C Rev.10
1
CONTENTS
1.INTRODUCTION....................................................................................4
2. BEFORE GETTING STARTED..............................................................5
2.1 GENERAL DESCRIPTIONS...............................................................................................5
2.2 SYSTEM REQUIREMENTS................................................................................................5
2.3 APPLICABLE FIRMWARE VERSION OF 71VR1...............................................................5
3. MAIN DIALOG........................................................................................6
4. INFRARED COMMUNICATION.............................................................7
4.1COP-IRDA...........................................................................................................................7
4.2 SETTING ON THE 71VR1...................................................................................................7
5. COM PORT SETTING............................................................................8
6.CONFIGURATION..................................................................................9
6.1 CREATE AND READ CONFIGURATION............................................................................9
6.1.1 NEW SETTING........................................................................................................9
6.1.2 READ FROM DEVICE.............................................................................................9
6.1.3 READ FROM FILE...................................................................................................9
6.2 CONFIGURATION DIALOG.............................................................................................. 10
6.2.1 GENERAL DESCRIPTIONS.................................................................................. 10
6.2.2 INPUT CHANNEL SETTING DIALOG (71VR1-E001, -E101)................................. 13
6.2.3 INPUT CHANNEL SETTING DIALOG (71VR1-E501)............................................ 15
6.2.4 OUTPUT CHANNEL SETTING DIALOG............................................................... 17
6.2.5 PEN SETTING DIALOG......................................................................................... 18
6.2.6 TRIGGER SETTING DIALOG................................................................................ 19
6.2.7 ANALOG ALARM SETTING DIALOG....................................................................20
6.2.8 DISCRETE ALARM SETTING DIALOG.................................................................21
6.2.9 AUTO VIEW SWITCHING DIALOG (1.4)...............................................................22
6.2.10 FIRMWARE VERSION DIALOG............................................................................23
7. TREND DATA FILE..............................................................................24
7.1
LISTING AND READING FROM FILE...............................................................................24
7.1.1 GENERAL DESCRIPTIONS..................................................................................24
7.1.2 SAVE PATH SETTING............................................................................................24
7.1.3 FILE READING......................................................................................................24
7.2
CSV CONVERSION..........................................................................................................25
7.2.1 GENERAL DESCRIPTIONS..................................................................................25
7.2.2 SAVE PATH SETTING............................................................................................25
7.2.3 FILE SELECTION / CONVERSION.......................................................................26
71VRCFG USERS MANUAL EM-7403-C Rev.10
2
8. ALARM HISTORY................................................................................29
8.1 READING FROM DEVICE................................................................................................29
8.2 READING FROM FILE......................................................................................................29
8.3 SAVE CSV FILE................................................................................................................30
9. VERSION HISTORY.............................................................................32
9.1 Ver. 2.01.............................................................................................................................32
9.2 Ver. 2.02.............................................................................................................................32
9.3 Ver. 3.01.xx.........................................................................................................................32
9.4 Ver. 3.02.xx........................................................................................................................32
9.5Ver.3.03.xx.........................................................................................................................32
71VRCFG USERS MANUAL EM-7403-C Rev.10
3
1.INTRODUCTION
Thank you for choosing M-System’s Paperless Recorder 71VR1.
The Users Manual for model 71VR1 (71VR1-E001/71VR1-E101/71VR1-E501) describes its configurator 71VRCFG’s
software functions, PC environment and operation methods. Please refer to the 71VR1 Users Manual for the detailed
information about the terms used in the manual.
71VRCFG makes it easy and smooth to set parameters to 71VR1. The Trend Data and Alarm History can be exported to CSV files via infrared communication.
Please read this manual carefully to ensure the safe use before getting started.
71VRCFG USERS MANUAL EM-7403-C Rev.10
4
2. BEFORE GETTING STARTED
2.1 GENERAL DESCRIPTIONS
Features and Settings
Available for setting I/O channel, pen, trigger and alarm.
Uploading and displaying a configuration file stored in the 71VR1 to the 71VRCFG.
Downloading a configuration file created on the 71VRCFG to the 71VR1.
Configuration files can be stored in a storage media such as a hard disk.
Creating a Trend Data File
The trend data file (.71VR) can be converted to the CSV format via infrared communication or a memory card.
Creating an Alarm History File
The alarm history file (71VR_Alarm.alm) can be converted to the CSV format via
infrared communication or a memory card.
2.2 SYSTEM REQUIREMENTS
PC
IBM PC/AT or compatible
OS
Windows XP SP3 or later, Windows Vista, Windows 7 Professional
Note: no guarantee for all environments
Screen Area
1024 by 768 pixels or higher
Display Color
65000 colors (16 bits)
USB Port
Use USB port when having infrared communication with 71VR1 via COP-IRDA.
2.3 APPLICABLE FIRMWARE VERSION OF 71VR1
This Users Manual conforms to major version 1, minor version 6.01 or higher of 71VR1-E001 and 71VR1-E101’s
firmware and major version 1, minor version 6.01 or higher of 71VR1-E501’s firmware. Descriptions with the symbols
detailed below correspond to the compatible firmware version.
Refer to the Users Manual of 71VR1 to confirm the firmware version.
SYMBOL
APPLICABLE FIRMWARE VERSION
1.4
1.6
Major version 1, minor version 4.01 or higher
Major version 1, minor version 6.01 or higher
71VRCFG USERS MANUAL EM-7403-C Rev.10
5
3. MAIN DIALOG
Double-clicking the icon of 71VRCFG.exe to start 71VRCFG, the main dialog appears as below.
Configuration
Trend Data File
(.71VR)
New Setting
Create a Configuration file with its initial values.
Reading from Device
Read the Configuration data from 71VR1 via infrared communication.
Reading from File
Read the Configuration file stored in the memory card of 71VR1.
Listing and Reading from File
Acquire a list of Trend Data Files and take out the files you select from
the memory card in 71VR1 via infrared communication.
CSV Conversion
The Trend Data Files which are taken out by the way mentioned
above can be converted to the CSV format.
Reading from Device
Display the Alarm History which is taken out from 71VR1 via infrared
communication. It can be converted to and saved as the CSV format.
Reading from File
Read the Alarm History stored in the memory card of 71VR1. It can
be converted to and saved as the CSV format.
Alarm History
COM Port
Select the COM port you use.
71VRCFG USERS MANUAL EM-7403-C Rev.10
6
4. INFRARED COMMUNICATION
4.1COP-IRDA
Use M-System’s product (Model: COP-IRDA) to communicate with 71VR1 via infrared radiation. Before using COPIRDA, install the driver in your PC. Refer to related driver installation manual for the detailed information.
When the driver is installed correctly, COP-IRDA is assigned to COM port.
max. 20 cm
PC
4.2
IrDA Communication Adaptor
(model: COP-IRDA)
Paperless Recorder
(model: 71VR1)
Remark: Communication can be affected by sunlight,
fluorescent lightings employing inverter technology and so forth.
SETTING
ON
THEif communication
71VR1 is not established.
Try at a shorter
distance
To make 71VRCFG to communicate with 71VR1 via infrared radiation without interference even when plural 71VR1
line up, set only one 71VR1 up for infrared communication. Refer to the related 71VR1 manual for the detailed information.
71VRCFG USERS MANUAL EM-7403-C Rev.10
7
5. COM PORT SETTING
Select COM No. from COM1 to COM20 after COP-IRDA is assigned to COM port.
71VRCFG USERS MANUAL EM-7403-C Rev.10
8
6.CONFIGURATION
6.1 CREATE AND READ CONFIGURATION
6.1.1 NEW SETTING
When creating a Configuration file, select a Device Type as shown below, then the setting dialog with its initial values
is displayed.
• 71VR1-E001
• 71VR1-E101
• 71VR1-E501
6.1.2 READ FROM DEVICE
Set 71VR1 up for infrared communication, click [Read from Device] button, then the Configuration data is read and
the setting dialog is displayed.
6.1.3 READ FROM FILE
After reading the Configuration file stored in the memory card of 71VR1, the Configuration dialog is displayed.
71VRCFG USERS MANUAL EM-7403-C Rev.10
9
6.2 CONFIGURATION DIALOG
6.2.1 GENERAL DESCRIPTIONS
The Configuration dialog is as shown below.
• 71VR1-E001, -E101
• 71VR1-E501
71VRCFG USERS MANUAL EM-7403-C Rev.10
10
[Writing]
ITEM
DESCRIPTION
Writing to Device
Set 71VR1 up for infrared communication, click [Writing to Device] button, then the Configuration data is transferred to 71VR1.
Writing to File
Store the Configuration data into the file, after choosing firmware version of 71VR1.
Note: Use the file name shown below when the file is stored in the memory card in order to
read the file from the memory card inserted in the 71VR1.
\71VR\71VR0000.cfg for 71VR-E001/E101
\71VRU\71VR0000.cfg for 71VR-E501
[System]
ITEM
DESCRIPTION
Device
Device name can be set to max. 16 characters.
It is exported when the Trend Data or the Alarm History is converted to the CSV format.
Decimal
The Decimal setting is for displaying the data on the Trend Display or Digital Display.
Selection range: 0 – 3
Modbus
Set Modbus baud rate.
Selection: 4800bps/9600bps/19200bps/38400bps
Temperature Unit
(Only for 71VR1-E501)
When Channel is set to T/C or RTD, temperature unit setting is required.
Selection: Celsius/Fahrenheit/Kelvin
Temperature unit impacts Analog Channel Range of Input Channel, Upper Limit of Analog
Alarm Zone and Trigger Setting. Therefore, when Temperature Unit is changed, the channels used for T/C or RTD input change to disable.
[Channel]
ITEM
DESCRIPTION
Sample Rate
Set Sample Rate.
Selection: 100ms/200ms/500ms/1s/2s/5s/10s/20s/30s/1min/5min/10min/20min/30min/1 hour
Note: Minimum sample rate of 500 ms is required for T/C or RTD input of 71VR1-E501.
Sample Rate: 20s/30s/1min/5min/10min/20min/30min/1 hour (1.4)
Normal/Demo
Select Normal in the case of application.
When Demo is selected, the Demo graph’s display is available.
Selection: Normal/Demo
Input Setting
Output Setting
Open the Input Channel Setting dialog.
Open the Output Channel Setting dialog.
[Pen]
ITEM
Pen Setting
DESCRIPTION
Open the Pen Setting dialog.
[Trigger]
ITEM
Detect Mode
DESCRIPTION
Select the logic operation for the 3 triggers.
Selection: OR/AND
Pretrigger Sample
Set the Pretrigger Sample number.
Setting range: 0 – 99
Posttrigger Sample
Set the Posttrigger Sample number.
Setting range: 0 – 99
Trigger Setting
Open the Trigger Setting dialog.
71VRCFG USERS MANUAL EM-7403-C Rev.10
11
[Record]
ITEM
DESCRIPTION
Samples per File
Set the Samples per File to split a file.
Setting range: 1000 – 60000
Start Auto Recording
Select the Start Auto Recording mode.
Selection: Start trigger recording/Start recording continuously/Off
[Alarm]
ITEM
DESCRIPTION
Analog Alarm Setting
Open the Analog Alarm Setting dialog.
Discrete Alarm Setting
Open the Discrete Alarm Setting dialog.
[Display]
ITEM
DESCRIPTION
Zero Suppression (1.4)
Set the leading zero suppression in the Digital Display screen when the numeral is less than
9 digits.Selection: Enable (eliminate leading zeros)/Disable (display leading zeros)
Screen Saver (1.6)
Set a desired time to initiate the screen saver.Setting range: NONE /1 min /2 min /5 min /10 min
Auto View Switching (1.4)
Open Auto View Switching dialog.
71VRCFG USERS MANUAL EM-7403-C Rev.10
12
6.2.2 INPUT CHANNEL SETTING DIALOG (71VR1-E001, -E101)
[Analog Input]
ITEM
DESCRIPTION
Input Channel
Select the Input Channel.
Selection: AI1 – AI8
Field Channel
Set the Field Channel to assign to the Input Channel.
71VR1-E001 Selection: Modbus/None
71VR1-E101 Selection: Ai1/Ai2/Modbus/ None
Input Type
Node
Address
Modbus Function (1.4)
Select the Input Type when Ai1 or Ai2 of 71VR1-E101 is selected.
Selection: -10 to +10V / -5 to +5V / -1 to +1V / -20 to +20mA
Set the Node number when Modbus is selected as the Field Channel.
Setting range: 1 – 247
Set the Address when Modbus is selected as the Field Channel.
Setting range: 1 – 9999
Set the Modbus Function when Modbus is selected as the Field Channel.Selection: Read
Holding Register (03)/Read Input Register (04).
Note: Set Read Holding Register(03), only when the 71VR1 communicates with SC200 or SC210.
Range
Set the Range from the left edge value to the right edge value of the trend display.
Input from the terminal block: max. 3 decimal place within each input range.
Setting range: -32768 – 32767
Scale
Set the primary value up to max. 3 decimal place corresponding to the Range.
Setting range: -999999.999 – 999999.999
Engineering Unit
Max. 4 characters
Tag Name
Max. 8 characters
71VRCFG USERS MANUAL EM-7403-C Rev.10
13
[Discrete Input]
ITEM
DESCRIPTION
Input Channel
Select the Input Channel.
Selection: DI1 – DI8
Field Channel
Set the Field Channel to assign to the Input Channel.
Selection: Di1/Di2/Modbus/None
Node
Address
Modbus Function (1.4)
Tag Name
Set the Node number when Modbus is selected as the Field Channel.
Setting range: 1 – 247
Set the Address when Modbus is selected as Field Channel.
Setting range: 1 – 9999
Set the Modbus Function when Modbus is selected as the Field Channel. Selection: Read
Coil Status (01)/Read Input Status (02)
Note: Set Read Coil Status(01), only when the 71VR1 communicates with SC200 or SC210.
Max. 8 characters
71VRCFG USERS MANUAL EM-7403-C Rev.10
14
6.2.3 INPUT CHANNEL SETTING DIALOG (71VR1-E501)
[Analog Input]
ITEM
DESCRIPTION
Input Channel
Set the Input Channel.
Selection: AI1 – AI8
Field Channel
Set the Field Channel to assign to the Input Channel.
Selection: Ai1 / Ai2 / Ai3 / Ai4 / Ai5 / Modbus / None
Sensor Type
For the universal input terminals (Ai3, Ai4, Ai5), the Sensor Type setting is required. For DC
input terminals (Ai1, Ai2), the Sensor Type setting is not available.
Selection: DC / T/C / RTD
• DC
Selection: -10 to +10V / -5 to +5V / -1 to +1V / -20 to +20mA
• TC
Input Type
Selection: K / E / J / T / B / R / S / C / N / U / L / P / PR
• RTD
Selection: Pt100 (JIS’97, IEC) / Pt100 (JIS’89) / JPt100 (JIS’89) / Pt50 (JIS’81) / Ni100 /
Cu10 / Cu50
Node
Address
Modbus Function (1.4)
Set the Node number when Modbus is selected as Field Channel.
Setting range: 1 – 246
Set the Address when Modbus is selected as Field Channel.
Setting range: 1 – 9999
Set the Modbus Function when Modbus is selected as the Field Channel.Selection: Read
Holding Register (03)/Read Input Register (04)
Note: Set Read Holding Register(03), only when the 71VR1 communicates with SC200 or SC210.
Range
Set the Range from the left edge value to the right edge value of the trend display.
Input from the terminal block: within each Input range with max. 3 decimal places
Setting range: -32768 – +32767
Scale
When Modbus or DC input terminal is selected, the Scale setting is required.
Set the primary value up to max. 3 decimal corresponding to the Range.
Setting range: -999999.999 – +999999.999
When T/C or RTD is selected, the Scale setting is not available.
Engineering Unit
Max. 4 characters
Tag Name
Max. 8 characters
CJC
When T/C is selected as the Sensor Type, the CJC setting is required.
Selection: ON/OFF
71VRCFG USERS MANUAL EM-7403-C Rev.10
15
[Discrete Input]
ITEM
DESCRIPTION
Input Channel
Set the Input Channel.
Selection: DI1 – DI8
Field Channel
Set the Field Channel to assign to the Input Channel.
Selection: Di1/Di2/Modbus/None
Node
Address
Modbus Function (1.4)
Tag Name
Set the Node number when Modbus is selected as the Field Channel.
Setting range: 1 – 246
Set the Address when Modbus is selected as the Field Channel.
Setting range: 1 – 9999
Set the Modbus Function when Modbus is selected as the Field Channel.Selection: Read
Holding Register (03)/Read Input Register (04)
Note: Set Read Coil Status(01), only when the 71VR1 communicates with SC200 or SC210.
Max. 8 characters
71VRCFG USERS MANUAL EM-7403-C Rev.10
16
6.2.4 OUTPUT CHANNEL SETTING DIALOG
ITEM
Output Channel
Field Channel
Node
Address
DESCRIPTION
Select the Output Channel.
Selection: DO1 – DO8
Set the Field Channel to assign to the Output Channel.
Selection: Do1/Do2/Modbus/None
Set the Node number when Modbus is selected as the Field Channel.
Setting range: 1 – 247
Note: Setting range 1 – 246 is available for 71VR1-E501.
Set the Address when Modbus is selected as the Field Channel.
Setting range: 1 – 9999
71VRCFG USERS MANUAL EM-7403-C Rev.10
17
6.2.5 PEN SETTING DIALOG
ITEM
DESCRIPTION
Pen
Select the Pen.
Selection: P1 – P16
Input
A list of available channels is displayed.
Selection: AI1 – AI8, DI1 – DI8
Color
Select the Color by using the following Color Menu dialog.
71VRCFG USERS MANUAL EM-7403-C Rev.10
18
6.2.6 TRIGGER SETTING DIALOG
ITEM
Trigger
Condition
Mode
Channel
Level
DESCRIPTION
Select the Trigger.
Selection: T1 – T3
Select the Trigger type.
Selection: DI Edge / DI Level / AI Edge / AI Level / None
Set the Trigger Mode.
When the Condition is set to DI Edge or DI Level, select ON/OFF.
When the Condition is set to AI Edge or AI Level, select UNDER/OVER.
Use the logical channels you set in the Input Channel Setting dialog.
A list of available channels is displayed.
When the Condition is set to AI Edge or AI Level, select AI1 – AI8.
When the Condition is set to DI Edge or DI Level, select DI1 – DI8.
When the Condition is set to AI Edge or AI Level, set the threshold level based on the engineer unit value. Max. 3 decimal place is available.
71VRCFG USERS MANUAL EM-7403-C Rev.10
19
6.2.7 ANALOG ALARM SETTING DIALOG
ITEM
Alarm Menu
Enable/Disable
Partitions
DESCRIPTION
Select an Alarm. An Alarm list of selected channels is displayed.
Selection: AA1 – AA8
To use the selected Alarm, set it to Enable.
Selection: Enable/ Disable
Set the Zones to Partitions.
Selection: 2 – 5
Alarm Name
Max. 10 characters
Upper Limit
Except for the top level Zone, set the Upper Limit to the Engineer Unit value for each Zone.
Max. 3 decimal place is available.
Mode
Alarm Color
Contact Output
Set the Zone property. When the Deadband setting is available, it is shown in the list.
Selection: Normal/Alarm/Deadband
Set the Alarm Color by using the Color Menu dialog.
(For color menu dialog illustration refer to PEN SETTING DIALOG section)
Set the Alarm Contact Output when the Mode is set to the Alarm.
Selection: On/Off
In the case of On, select one from DO1 to DO8. (Unused DOs are not displayed.)
71VRCFG USERS MANUAL EM-7403-C Rev.10
20
6.2.8 DISCRETE ALARM SETTING DIALOG
ITEM
Alarm Menu
Enable/Disable
DESCRIPTION
Select an Alarm. An Alarm list of selected channels is displayed.
Selection: AD1 – AD8
To use the selected Alarm, set it to Enable. Unless, set it to Disable.
Selection: Enable/Disable
Alarm Name
Max. 10 characters
Trigger Mode
Set ON or OFF to the Alarm status.
Selection: ON/OFF
Delay
Alarm Color
Contact Output
Set the sample number as the Delay time applied before judging an Alarm Set/Recover.
Setting range: 0 – 99
Set the Alarm Color by using the Color Menu dialog.
(For color menu dialog illustration refer to PEN SETTING DIALOG section)
Set the Alarm Contact Output.
Selection: On/Off
In the case of On, select from DO1 to DO8. (Unused DOs are not displayed.)
71VRCFG USERS MANUAL EM-7403-C Rev.10
21
6.2.9 AUTO VIEW SWITCHING DIALOG (1.4)
ITEM
Auto View Switching
Waiting Time (s)
DESCRIPTION
Set Disable or Enable for Auto View Switching.Selection: Disable/EnableIn the case of Enable, other items to select for Auto View Switching are available.
Set the time to start Auto View Switching.Setting range: 10 to 180
Interval (s)
Set the time to switch to next view during Auto View Switching.Setting range: 3 to 180
View Order
The number that shows the order of view displayed during Auto View Switching.Selection: 1
to 16
View Type
Select the screen that is displayed during Auto View Switching.Selection: None/Trend/Digital
Page Number
Set the page number of the screen that is displayed during Auto View Switching.Setting
range: 1 to 8.
71VRCFG USERS MANUAL EM-7403-C Rev.10
22
6.2.10 FIRMWARE VERSION DIALOG
When the [Writing to File] button is clicked, the following dialog is displayed.
Select firmware version of the 71VR1 to which a Configuration file is applied. The firmware version initially displayed is different according to the configuration button selected in the main dialog. Refer to the table shown below.
NOTE 1. In order to confirm firmware version, see [SOFTWARE VER] of [SETTING MENU] on 71VR1. For detailed
information refer to the 71VR1 Software Operation Users Manual.
NOTE 2. Firmware version consists of a combination of MAJOR Ver and MINOR Ver. When MAJOR Ver is “1” and
MINOR Ver is “4.01”, firmware version is displayed as “1.4.01”.
BUTTONS IN THE MAIN DIALOG
THE FIRMWARE VERSION INITIALLY DISPLAYED
New Setting
1.4.01 or later
Reading from Device
The firmware version read from 71VR1
Reading from File
The firmware version selected when configuration data is
written into a file
71VRCFG USERS MANUAL EM-7403-C Rev.10
23
7.
TREND DATA FILE
7.1
LISTING AND READING FROM FILE
7.1.1 GENERAL DESCRIPTIONS
When the Trend Data list is taken out from 71VR1, the following dialog is displayed.
7.1.2 SAVE PATH SETTING
Set the Save Path for the received trend file. Click [Save Path Setting] button, set the path in the following dialog
which appears after the button is clicked.
7.1.3 FILE READING
Select a file from the list, click [File Reading] button, the following dialog is displayed and the selected file is transferred. The received file is saved in the path which was set in section 7.1.2.
71VRCFG USERS MANUAL EM-7403-C Rev.10
24
7.2
CSV CONVERSION
7.2.1 GENERAL DESCRIPTIONS
Click [CSV Conversion] button, the following dialog is displayed.
7.2.2 SAVE PATH SETTING
Set the Save Path for the converted file. Click [Save Path Setting] button, set the path in the following dialog which
appears after the button is clicked.
71VRCFG USERS MANUAL EM-7403-C Rev.10
25
7.2.3 FILE SELECTION / CONVERSION
Click [File Selection / Conversion] button, the following dialog is displayed. Select a file you want to convert, click
[Open] button, then the CSV Conversion is started. After the CSV Conversion is finished, the converted file is saved
in the path which was set in section 7.2.2.
[71VR1-E001,-E101]
View on Microsoft Excel of a CVS file created with the 71VRCFG Version 1.xx.
Display Device Name, Sample Rate, Samples per File
Display Tag Name, Engineering Unit
When data is marked in the Trend Display of
71VR1, M is indicated
Display Date, Time, 1/1000 second.
Display sample data
Analog data: Engineering Unit value (max. 3 decimal); Discrete data: 1 (ON), 0(OFF)
71VRCFG USERS MANUAL EM-7403-C Rev.10
26
View on Microsoft Excel of a CVS file created with the 71VRCFG Version 2.xx or later.
Display Device Name, Sample Rate,
Samples per File, Temperature Unit
Display Tag Name, Engineering Unit.
Display Time, 1/1000 second*1.
When data is marked in the Trend Display of
71VR1, M is indicated.
Display sample data.
Analog data: Engineering Unit value (max.3 decimal); Discrete data: 1(ON), 0(OFF)
*1. Opening a CSV file with Microsoft Excel, the display format of the cell which shows the time is modifiable.
E.g.: year/month/day time: minutes:seconds.milliseconds (yyyy/mm/dd hh:mm:ss.000).
71VRCFG USERS MANUAL EM-7403-C Rev.10
27
[71VR1-E501]
View on Microsoft Excel of a CVS file.
Display Device Name, Sample Rate,
Samples per File, Temperature Unit
Display Tag Name, Engineering Unit.
Display Time, 1/1000 second*1.
When data is marked in the Trend Display of
71VR1, M is indicated.
Display sample data.
Analog data: Engineering Unit value (max.3 decimal);
Burnout: “BO”
Discrete data: 1(ON), 0(OFF)
NOTE: The accuracy of T/C or RTD data is based on the Temperature Unit. Refer to the following table for the details.
TEMPERATURE UNIT
ACCURACY
Celsius (C)
1 decimal place
Fahrenheit (F)
Integer
Kelvin (K)
1 decimal place
*1. Opening a CSV file with Microsoft Excel, the display format of the cell which shows the time is modifiable.
E.g.: year/month/day time: minutes:seconds.milliseconds (yyyy/mm/dd hh:mm:ss.000).
71VRCFG USERS MANUAL EM-7403-C Rev.10
28
8. ALARM HISTORY
8.1 READING FROM DEVICE
Click [Reading from Device] button under the Alarm History of the main dialog, the following dialog is displayed after
the Alarm History is read out from 71VR1 via infrared radiation.
8.2 READING FROM FILE
Click [Reading from File] button under the Alarm History of the main dialog. Select and open the file 71VR_Alarm.
alm stored in the memory card to display the Alarm History dialog shown in section 8.1.
71VRCFG USERS MANUAL EM-7403-C Rev.10
29
8.3 SAVE CSV FILE
Click [Save CSV File] button in the Alarm History dialog, the following dialog is displayed.
Click [Save] button to save the CSV file.
View on Microsoft Excel of a CVS file created with the 71VRCFG Version 1.xx.
Display Device Name.
Header is in order of Time, Channel, Tag name, Alarm Name, Mode.
Display the Alarm History
71VRCFG USERS MANUAL EM-7403-C Rev.10
30
View on Microsoft Excel of a CVS file created with the 71VRCFG Version 2.xx or later.
Display Device Name.
Header is in order of Time, Channel, Tag name, Alarm Name, Mode.
Display the Alarm History*1
*1. Opening a CSV file with Microsoft Excel, the display format of the cell which shows the time is modifiable.
E.g.: year/month/day time: minutes:seconds.milliseconds (yyyy/mm/dd hh:mm:ss.000).
71VRCFG USERS MANUAL EM-7403-C Rev.10
31
9. VERSION HISTORY
9.1 Ver. 2.01
The following inconveniences in the previous versions were corrected:
(1) Configuration dialog: “Number of Samples” → “Samples per File”
(2) Temperature unit selection (only for 71VR1-E501): “Temperature Setting” → “Temperature Unit”
(3) Analog Alarm Setting Dialog: “Area” → “Zone”, “On/Off” → “Enable/Disable”
9.2 Ver. 2.02
The following inconvenience in the previous versions was corrected:
The error occurred during 71VR1 reads configuration when analog or discrete alarm is set with all Output Settings
selected to NONE.
9.3 Ver. 3.01.xx
The following new features were incorporated:
(1) “20s/30s/1min./5min./10min./20min./30min/1hour” were added.
(2) [Modbus Function] was added to the Input Channel Setting dialog. (SC200 and SC210 are supported.)
(3) [Display] was added to the Configuration dialog, “Zero Suppression” and “Auto View Switching” were added to
[Display].
(4) Auto View Switching dialog was added.
(5) Version number was changed from xx. xx to xx. xx. xx.
xx. xx. xx
Supplemental number
Minor version
Major version
9.4 Ver. 3.02.xx
The following inconvenience in the previous versions was corrected:
When configuration is stored into a memory card and 71VR1 reads the configuration from the memory card, 71VR1
with major version 1, minor version 0 to 3 fails in reading.
9.5Ver.3.03.xx
Screen Saver setting is added in the Display of Configuraion dialog.
Microsoft and Excel are registered trademark of Microsoft Corporation in this and other countries.
71VRCFG USERS MANUAL EM-7403-C Rev.10
32
Was this manual useful for you? yes no
Thank you for your participation!