Installation instruction
www.contura.eu
C i50
GB
82
CERTIFICATE
DECLARATION OF PERFORMANCE
No. Ci50-CPR-150821-SE-1
PRODUCT
Product type
Type designation
Manufacturing number
Intended area of use
Fuel
MANUFACTURER
Name
Address
CHECKS
According to AVCP
European standard
Test institute
Insert lit with solid biofuels
Contura i50
See rating plate on the insert
Heating of rooms in residential buildings
Wood
NIBE AB / Contura
Box 134, Skulptörvägen 10
SE-285 23 Markaryd, Sweden
System 3
EN 13229:2001/AC:2006, EN-13229:2001/A2:2004/AC:2007
Rein-Ruhr Feuerstätten Prüfstelle, NB 1625, has checked declared performance and issued test report no. RRF-29 15 4067
DECLARED PERFORMANCE
Essential characteristics
Reaction to fire
Minimum distance to combustible material
Risk of falling embers
Emissions from combustion
Surface temperatures
Cleaning options
Mechanical durability
Emissions of hazardous substances
Nominal output
Efficiency
Flue gas temperature in connector at nominal output
Performance Harmonised technical specification
A1 WT
150 mm to rear
700 mm to side
According to the given conditions in the installation instructions.
Approved
CO 0.08%
NOx 96 mg/m 3
OGC 69 mg/m 3
PM 23 mg/m 3
Approved
Approved
Approved
Approved
8 kW
80%
334°C
EN 13229:2001/AC:2006,
EN-13229:2001/A2:2004/AC:2007
The undersigned is responsible for the manufacture and conformity with the declared performance.
Niklas Gunnarsson,
Business area manager NIBE STOVES
Markaryd, August 21, 2015
CONTENTS
GB
83
A warm welcome to Contura.
A warm welcome to the Contura family. We hope you will get a great deal of pleasure from your new insert.
As a new owner of a Contura insert, you have secured a product with timeless design and long service life.
Contura also has a combustion process that is both environmentally friendly and efficient, for the best heat production.
Read through these installation instructions carefully before installation. Read how to best light your stove in the lighting instructions.
List of Contents
Technical specifications
Important dimensions
Prior to installation
Recessing the insert
84
85
85
96
NOTE:
Report the installation of a stove to your local authority.
The owner of the house is personally responsible for ensuring compliance with the mandatory safety requirements and must have the installation approved by a qualified inspector. Your local chimney sweep must also be informed about the installation as this will affect the routines for regular chimney-sweeping services.
WARNING!
The insert becomes very hot
During operation, certain surfaces of the insert become very hot and can cause burn injuries if touched. Also, take heed of the strong heat radiated through the door glass. Placing flammable material closer than the safe distance indicated may cause a fire. Smoulder combustion can cause quick gas ignition with the risk of damage to property and personal injury.
GB
84
FACTS
Technical specifications
Model i50
Output 6-11 kW
Nominal output 8 kW
Efficiency 80%
Weight (kg)
Width (mm)
Depth (mm)
Height (mm)
160
765
485
(with Thermotte)
1465
Connector diameter Ø150 mm ext.
General
This manual contains instructions about how to assemble and install the Contura i50. To ensure the function and safety of the insert, we recommend that installation is carried out by an authorised technician.
Our Contura agents can recommend a suitable installer; information regarding our agents is available at www.contura.eu
Instructions for lighting are also supplied with the insert. Read them carefully and keep them safe for future use.
Structural support
Check that floor joists have the sufficient load capacity for the insert, chimney and construction parts that are used when recessing.
Floor plate
If the floor under the stove is flammable, it must be protected by a non-flammable material e.g. natural stone, concrete or at least 0.7 mm thick metal. The floor in front of the hearth opening must be protected against any falling embers using non-flammable material that covers an area at least 300 mm all around. A toughened glass hearth plate is available as an accessory.
Application to local authority
Before installing a stove or erecting a chimney, it is necessary for you to make an application for permission to your local authority. Ask your local authority for advice regarding regulations and the application.
Important dimensions
765
140
240
670
Prior to installation
Opening sidelights
IMPORTANT DIMENSIONS / PRIOR TO INSTALLATION
GB
85
C i50
485
190
420
270
70 260
GB
86
PRIOR TO INSTALLATION
Remove the loose parts from the firebox.
The insert is secured to the pallet by the two rails, remove the screws and remove the angle brackets. Reinstall the screws on the legs before moving the insert from the pallet.
10 mm
3 mm
!
Check wire routing and remove the transport locking devices!
PRIOR TO INSTALLATION
GB
87
10 mm
GB
88
PRIOR TO INSTALLATION
Function check
Perform a function check on the Insert as follows:
Use the adjustable feet to level the insert. Check that the door can be opened and closed.
Check that the damper knob can be moved back and forth to the max and min marks.
!
The door runners are lubricated at the factory, with special grease that can withstand high temperatures.
This type of grease is usually difficult to find on the market and we recommend contacting a Contura dealer to order this special grease when lubricating the runners.
Installing the fi rebox cladding
1 2
3 4
PRIOR TO INSTALLATION
GB
89
5 6
GB
90
PRIOR TO INSTALLATION
7 8
9 10
PRIOR TO INSTALLATION
GB
91
11
Installing heat defl ector
PH2
10
CHROME
No. 7
10
10 mm
GB
92
OPTION
Installing Powerstone
Option
!
Install the Powerstone blocks as illustrated.
• With combustion air hose as option –
now install according to separate instructions.
• With recessing frame as option –
now install according to separate instructions.
Installation
Ensure that the installation meets national and regional regulations. The installation must be approved by an authorized inspection body.
Supply of combustion air must be provided. Combustion air can be provided directly via a duct from outside, or indirectly via a vent in the outer wall of the room where the stove is placed. The amount of combustion air that is used for combustion is approx.
25 m 3 /h.
Some installation alternatives are shown below. The air duct connection on the stove has an external diameter of Ø100 mm.
!
Turn the connector to ensure an air supply!
In hot areas, the duct should be insulated with 30 mm mineral wool covered with a moisture inhibitor (aluminium tape). It is important that the lead-in, between the pipe and the wall (or floor), is sealed using jointing compound.
A 1 m length of condensation-insulated ducting for combustion air is available as an accessory.
HK
HK
HK
INSTALLATION
GB
93
HK
GB
94
CHIMNEY / SELF-CLOSING DOOR
Chimney
The insert is approved and must be connected to a chimney dimensioned for at least 350°C, the external connection diameter is Ø150 mm.
The insert requires a draft in the chimney of at least –12 Pa. The draft is affected both by the length and area of the chimney, and by how well sealed it is. Carefully check that the chimney is sealed and that there is no leakage around soot hatches and flue connections.
Note that a flue with sharp bends and horizontal routing reduces the draught in the chimney. The maximum horizontal flue is 1 m, on the condition that the vertical flue length is at least 5 m. It must be possible to sweep the full length of the flue and the soot hatches must be easily accessible.
If two fireplaces are connected to the same chimney flue, the stove must be equipped with self-closing door.
Rearward connection
For the rearward connection it is recommended to use a 45°+45° angle with soot hatch and with the centre 235 mm above the connector.
It is important that sweeping can be carried out through convection grates or a hatch in the surround.
Self-closing door
(ONLY APPLIES TO GERMANY)
The insert can be supplied with a self-closing door. Fold out the three tabs on the counterweight pack. Lift out the two weights that are positioned slightly higher up. Remove the two side panels and install the two panels enclosed instead, see images on the next page. Check the function, if necessary further weight can be removed. Fold in the three tabs again to keep the counterweights in place.
1 2
3
B
A
4
B
5
A
SELF-CLOSING DOOR
GB
95
GB
96 RECESSING THE INSERT
Recessing the insert
When recessing the insert, adjacent walls that are not classed as fire walls or are considered unsuitable for heat loads must be protected by non-combustible material according to the specification below.
All joints on the non-combustible material must be sealed using the manufacture’s recommended method. The area between the insert and the recess must be ventilated according to the specification/dimension diagrams on page 98.
When connecting a steel flue, please refer to the particular manufacturer's installation instructions. Observe the safety distance to combustible material required by the steel flue Heat radiation from the door is strong and because of this combustible material must not be placed closer than 1.5 m in front of the door.
When recessing, building material must not be in direct contact with the insert due to the thermal expansion of the insert.
Note that building regulations apply regarding the area below and in front of the insert, see section ”Hearth plate”.
Material requirements
The building material must not be combustible.
The thermal conductivity coefficient
λ
must be a maximum of
0.14 W/mK.
The thickness of the building material must always be at least
100 mm.
In cases where the building material’s insulation properties are given as a U-Value, this must be a maximum of 1.4 W/ m²K.
List of suitable materials:
Aerated concrete
λ
=0.12-0.14
Vermiculite
λ
=0.12-0.14
Calcium silicate
λ
= 0.09
Sealing
The recess must not go all the way up to the ceiling, leave an air gap of at least 20 mm closest to the ceiling. The recess must be sealed off above the convection exhaust. The seal must be 100 mm above the convection exhaust’s upper edge and must be made of 100 mm non-flammable material according to the material requirements above. Use heat-resistant silicone, for example, between the seal and chimney.
Convection air
The convection air ventilates the surround, cools the insert and transports the hot air out into the room. The effective cross section area on the air intake and exhaust must not be less than the stated values. The air intake must be positioned somewhere between floor level and the bottom of the insert, at the front or on the sides of the recess. The vent must be positioned above the insert’s highest point at the front or to the sides of the recess.
If the air intake respectively the vent is positioned on the sides, the areas for the left respectively right sides must be the same size to ensure that the insert is evenly cooled.
The distance from the exhausts on the sides to the combustible wall behind must be 100 mm.
Observe the minimum distance up to the ceiling (see diagram on page 98).
Convection air in: 600 cm²
Convection air out: 600 cm²
If the convection outlets are directed upwards the following applies
- the recess must be free-standing or placed against a non-combustible wall.
- the distance from the air outlet to combustible roof must be at least 750 mm.
!
Service
Access to the damper and counterweight must be ensured via doors or ventilation grilles in the surround.
100
20
Recess example
550
!
max 100
The dimensions are the minimum dimensions, unless otherwise stated.
Wall of combustible material
Chimney breast
(I 20 min 2300)
(I 10 min 2100)
20
100
20
RECESSING THE INSERT
GB
97
Wall of non-combustible material that is not in contact with combustible material and therefore has no minimum thickness requirement.
Wall of non-combustible material, made
100
700
* The distance from the exhausts on the sides to the combustible wall behind must be 100 mm.
Final inspection of the installation
It is extremely important that the installation is inspected by an authorised inspection body before the stove is used. Also read the "Lighting instructions" before lighting for the first time.
GB
98 RECESSING THE INSERT
Area out 600 cm 2 2
Area out 600 cm 2
2
100
50
Area in 600 cm 2
100
50
Area in 600 cm 2
Area ut 600 cm 2
Area out 600 cm 2 2
Area in 600 cm 2
50
100
Can be excluded if the chimney breast behind is approved and meets full safety requirements according to the authorized inspection body.
Area in 600 cm 2
100
!
Always observe the safety distances to combustible material required by a steel flue
50
!
The dimensions are the minimum dimensions, unless otherwise stated.
811267 IAV SE-EX Ci50-2
2015-08-31
NIBE AB · Box 134 · 285 23 · Markaryd · Sweden www.contura.eu
Contura reserves the right to change dimensions and procedures described in these instructions at any time without special notice. The current edition can be downloaded from www.contura.eu