SPEC_UIS-WCB2

SPEC_UIS-WCB2
UniStream™ Uni-I/O™ Modules
Technical Specifications
UIS-WCB2
This guide provides specifications for Unitronics’ Uni-I/O™ Wide module UIS-WCB2. This module
comprises:






10 Digital inputs, 24VDC, sink/source,
including 2 High speed counter input channels (1) (2)
2 x Analog inputs, 0÷10V / 0÷20mA, 14 bits
2 x Temperature inputs, RTD / Thermocouple
8 x Transistor outputs, source
2 x Transistor outputs, sink
including 2 High speed PWM output channels (1) (3)
2 x Analog outputs, 0÷10V / -10÷10V / 0÷20mA / 4÷20mA, 13/14 bits
Uni-I/O Wide modules are compatible with UniStream™ Programmable Logic Controllers. They may be
either snapped onto the back of a UniStream™ HMI Panel next to a CPU-for-Panel to create an all-inone PLC + HMI controller, or installed on a standard DIN Rail using a Local Expansion Adapter.
Installation Guides are available in the Unitronics Technical Library at www.unitronics.com.
Power Supply
Nominal operating voltage
24VDC
Operating voltage
20.4 – 28.8VDC
Maximum current
consumption
[email protected]
Isolation
None
Digital Inputs
Number of inputs
10
Type
Sink or Source
Isolation voltage
Input to bus
500VAC for 1 minute
Input to input
None
Input to power supply
500VAC for 1 minute
Nominal voltage
24VDC @ 6mA
Input voltage
Sink/Source
On state: 15-30VDC, 4mA min.
Off state: 0-5VDC, 1mA max.
Nominal impedance
4kΩ
Filter
Settable between 1 to 32ms
High speed inputs
(1) (2)
Frequency / Period
Pulse/Direction mode: 10kHz max. / 100s min.
(tp in the Pulse/Dir Mode figure below)
Quadrature mode: 5kHz max. / 200s min.
(tp in the Quadrature Mode figure below)
Pulse width
40s min. for each state (tw in the figures below)
Cable
Shielded twisted pair
Unitronics
1
09/15
UniStream™
Quadrature Mode
Pulse/Direction mode
Analog Inputs
Number of inputs
2
Input range
Input Type
Nominal Values
Over-range Values *
0 ÷ 10VDC
0 ≤ Vin ≤ 10VDC
10 < Vin ≤ 10.15VDC
0 ÷ 20mA
0 ≤ in ≤ 20mA
20 < in ≤ 20.3mA
(4) (5)
* Overflow
boundary.
Absolute maximum rating
(6)
is declared when an input value exceeds the Over-range
±30V (Voltage), ±30mA (Current)
Isolation voltage
Input to bus
500VAC for 1 minute
Input to input
None
Input to temperature
inputs
None
Input to power supply
500VAC for 1 minute
Conversion method
Delta-sigma
Resolution
14 bits
Accuracy
±0.2% / ±0.5% of full scale (Voltage)
(25°C / -20°C to 55°C)
±0.2% / ±0.3% of full scale (Current)
Input impedence
492kΩ (Voltage), 30Ω (Current)
Noise rejection
10Hz, 50Hz, 60Hz, 400Hz
Unitronics
2
UIS-WCB2
Technical Specifications
Step response
(7)
Smoothing
(0 to 100% of final value)
Update time
(7)
Cable
Diagnostics
Noise Rejection Frequency
400Hz
60Hz
50Hz
10Hz
None
251.6 ms
411.6 ms
491.6 ms
2411.6 ms
Weak
503.2 ms
823.2 ms
983.2 ms
4823.2 ms
Medium
1006.4 ms
1646.4 ms
1966.4 ms
9646.4 ms
Strong
2012.7 ms
3292.7 ms
3932.7 ms
19292.7 ms
Noise Rejection Frequency
Update Time
400Hz
251.6 ms
60Hz
411.6 ms
50Hz
491.6 ms
10Hz
2411.6 ms
Shielded twisted pair
(6)
Analog input overflow
Temperature Inputs
Number of inputs
2
Sensor Type
RTD (4, 3 and 2 wire(8)),
Themocouple
Input range
(9)
Input type
Nominal values
Over/Under-range
Values *
RTD
PT100
0.00385
0.00392
0.00391
-200°C ≤ T ≤ 850°C
(-328°F ≤ T ≤ 1,562°F)
Under-range:
-220°C ≤ T < -200°C
(-364°F ≤ T < -328°F)
RTD
NI100
0.00618
-100°C ≤ T ≤ 260°C
(-148°F ≤ T ≤ 500°F)
Over-range:
850°C < T ≤ 860°C
(1,562°F < T ≤ 1,580°F)
Under-range:
-150°C ≤ T < -100°C
(-238°F ≤ T < -148°F)
Over-range:
260°C < T ≤ 270°C
(500°F < T ≤ 518°F)
RTD
NI120
0.00672
-80°C ≤ T ≤ 260°C
(-112°F ≤ T ≤ 500°F)
Under-range:
-130°C ≤ T < -80°C
(-202°F ≤ T < -112°F)
Over-range:
260°C < T ≤ 270°C
(500°F < T ≤ 518°F)
RTD
NI100
0.00617
-60°C ≤ T ≤ 180°C
(-76°F ≤ T ≤ 356°F)
Under-range:
-104°C ≤ T < -60°C
(-219°F ≤ T < -76°F)
Over-range:
180°C < T ≤ 210°C
(356°F < T ≤ 410°F)
Unitronics
3
09/15
UniStream™
Thermocouple
type J
-200°C ≤ T ≤ 1,200°C
(-328°F ≤ T ≤ 2,192°F)
Under-range:
-210°C ≤ T < -200°C
(-346°F ≤ T < -328°F)
Over-range:
1,200°C < T ≤ 1,250°C
(2,192°F < T ≤ 2,282°F)
Thermocouple
type K
-200°C ≤ T ≤ 1,372°C
(-328°F ≤ T ≤ 2,501.6°F)
Under-range:
-270°C ≤ T < -200°C
(-454°F ≤ T < -328°F)
Over-range:
1,372°C < T ≤ 1,400°C
(2,501.6°F < T ≤ 2,552°F)
Thermocouple
type T
-200°C ≤ T ≤ 400°C
(-328°F ≤ T ≤ 752°F)
Under-range:
-270°C ≤ T < -200°C
(-454°F ≤ T <-328°F)
Over-range:
400°C < T ≤ 430°C
(752°F < T ≤ 806°F)
Thermocouple
type E
-200°C ≤ T ≤ 1,000°C
(-328°F ≤ T ≤ 1,832°F)
Under-range:
-270°C ≤ T < -200°C
(-454°F ≤ T < -328°F)
Over-range:
1,000°C < T ≤ 1,010°C
(1,832°F < T ≤ 1,850°F)
Thermocouple
type R
0°C ≤ T ≤ 1,768°C
(32°F ≤ T ≤ 3,214.4°F)
Under-range:
-50°C ≤ T < 0°C
(-58°F ≤ T < 32°F)
Over-range:
1,768°C < T ≤ 1,800°C
(3,214.4°F < T ≤ 3,272°F)
Thermocouple
type S
0°C ≤ T ≤ 1,768°C
(32°F ≤ T ≤ 3,214.4°F)
Under-range:
-50°C ≤ T < 0°C
(-58°F ≤ T < 32°F)
Over-range:
1,768°C < T ≤ 1,800°C
(3,214.4°F < T ≤ 3,272°F)
Thermocouple
type B
200°C ≤ T ≤ 1,820°C
(392°F ≤ T ≤ 3,308°F)
Under-range:
100°C ≤ T < 200°C
(212°F ≤ T < 392°F)
Over-range:
1,820°C < T ≤ 1,870°C
(3,308°F < T ≤ 3,398°F)
Thermocouple
type N
-210°C ≤ T ≤ 1,300°C
(-346°F ≤ T ≤ 2,372°F)
Under range:
-270°C ≤ T < -210°C
(-454°F ≤ T < -346°F)
Over-range:
1,300°C < T ≤ 1,350°C
(2,372°F < T ≤ 2,462°F)
Unitronics
4
UIS-WCB2
Technical Specifications
Thermocouple
type C
10°C ≤ T ≤ 2,315°C
(50°F ≤ T ≤ 4,199°F)
Under-range:
0°C ≤ T < 10 °C
(32°F ≤ T < 50°F)
Over-range:
2,315°C < T ≤ 2,370°C
(4,199°F < T ≤ 4,298°F)
Resistance
0Ω ≤ R ≤ 390Ω
390Ω < R ≤ 395.85Ω
mV
-70mV ≤ V ≤ 70mV
Under-range:
-71.05mV ≤ V < -70mV
Over-range:
70mV ≤ V < 71.05mV
* Overflow or Underflow
is declared when an input value exceeds the
Over-range or Under-range boundaries respectively.
(6)
Absolute maximum rating
±36 V
Isolation voltage
Input to bus
500 VAC for 1 minute
Input to input
None
Input to analog inputs
None
Input to power supply
500 VAC for 1 minute
Conversion method
Delta-sigma
Resolution
Temperature – 0.1°C (0.1°F)
(10)
Resistance – 14 bits
mV – 13 bits plus sign
Accuracy
Input type
(25°C / -20°C to 55°C)
RTD, all types
Accuracy
± 0.5°C / ± 1.0°C (± 0.9°F / ± 1.8°F)
Thermocouple type J
Noise rejection
Step response
± 0.4°C / ± 0.7°C (± 0.72°F / ± 1.26°F)
Thermocouple type K
(11)
± 0.5°C / ± 1.0°C (± 0.9°F / ± 1.8°F)
Thermocouple type T
(11)
± 0.6°C / ± 1.2°C (± 1.08°F / ± 2.16°F)
Thermocouple type E
(11)
± 0.4°C / ± 0.8°C (± 0.72°F / ± 1.44°F)
Thermocouple type R
(11)
± 1.2°C / ± 2.4°C (± 2.16°F / ± 4.32°F)
Thermocouple type S
(11)
± 1.2°C / ± 2.4°C (± 2.16°F / ± 4.32°F)
Thermocouple type B
(11)
± 2.0°C / ± 3.8°C (± 3.46°F / ± 6.84°F)
Thermocouple type N
(11)
± 1.0°C / ± 1.5°C (± 1.8°F / ± 2.7°F)
Thermocouple type C
(11)
± 0.8°C / ± 2.0°C (±1.44°F / ± 3.46°F)
Resistance
± 0.05% / ± 0.1% of full scale
mV
± 0.05% / ± 0.1% of full scale
10Hz, 50 Hz, 60 Hz, 400 Hz
(7)
Smoothing
(0 to 100% of final value)
Unitronics
(11)
Noise Rejection Frequency
400Hz
60Hz
50Hz
10Hz
None
251.6 ms
411.6 ms
491.6 ms
2411.6 ms
Weak
503.2 ms
823.2 ms
983.2 ms
4823.2 ms
Medium
1006.4 ms
1646.4 ms
1966.4 ms
9646.4 ms
Strong
2012.7 ms
3292.7 ms
3932.7 ms
19292.7 ms
5
09/15
UniStream™
Update time
(7)
Thermocouple
Cold junction error
Update Time
400Hz
251.6 ms
60Hz
411.6 ms
50Hz
491.6 ms
10Hz
2411.6 ms
±1.5°C (±2.7°F)
(11)
Cable
Diagnostics
Noise Rejection Frequency
Shielded, see installation guide for details
(6)
Input Overflow or Underflow, sensor connection fault
(12)
Source Transistor Outputs
Number of outputs
Output type
8 (O2 to O9)
Transistor, Source (pnp)
Isolation voltage
Output to bus
500VAC for 1 minute
Output to output
None
Outputs power supply
to bus
Outputs power supply
to output
Current
500VAC for 1 minute
Voltage
See Source Transistor Outputs Power Supply specfication
ON state voltage drop
0.5V maximum
OFF state leakage current
10µA maximum
Switching times
Turn-on/off: 80s max. (Load resistance < 4kΩ(
Short-circuit protection
Yes
None
0.5A maximum per output
Source Transistor Outputs Power Supply
Nominal operating voltage
24VDC
Operating voltage
20.4 – 28.8VDC
Maximum current
consumption
[email protected]
Current consumption does not include load current
Unitronics
6
UIS-WCB2
Technical Specifications
Sink Transistor Outputs
Number of outputs
2 (O0 and O1)
Output type
Transistor, Sink
Isolation
None
Current
50mA max. per output
Voltage
Nominal: 24VDC
Range: 3.5V to 28.8VDC
On state voltage drop
1V max
Off state leakage current
10µA max
Short circuit protection
None
Switching times
Turn-on: 0.4s max. (470Ω and 4kΩ load)
Turn-off: 1.1s max. (470Ω load), 3.4s max. )4kΩ load(
High speed outputs
(1) (3)
PWM Frequency
6Hz min.
250kHz max. (470Ω load)
100kHz max. )4kΩ load(
Cable
Shielded twisted pair
Analog Outputs
Number of outputs
Output range
(14)
2
Output Type
Nominal Values
Over/Under-range Values *
0 ÷ 10VDC
0 ≤ Vout ≤ 10VDC
10 < Vout ≤ 10.15VDC
-10 ÷ 10VDC
-10 ≤ Vout ≤ 10VDC
-10.15  Vout < -10VDC
10 < Vout ≤ 10.15VDC
0 ÷ 20mA
0 ≤ out ≤ 20mA
20 ≤ out ≤ 20.3mA
4 ÷ 20mA
4 ≤ out ≤ 20mA
20 ≤ out ≤ 20.3mA
* Overflow or Underflow is declared when an output value exceeds the
Over-range or Under-range boundaries respectively.
Isolation
None
Resolution
0 ÷ 10VDC – 14 bit
-10 ÷ 10VDC – 13 bit + sign
0 ÷ 20mA – 13 bit
4 ÷ 20mA – 13 bit
Accuracy
±0.3% / ±0.5% of full scale (Voltage)
(25°C /-20°C to 55°C)
±0.5% / ±0.7% of full scale (Current)
Load impedance
Voltage – 2kΩ minimum
Current – 600Ω maximum
Settling time
0 ÷ 10VDC – 1.8ms (2kΩ resistive load), 3.7ms (2kΩ + 1uF load)
(95% of new value)
-10 ÷ 10VDC – 3ms (2kΩ resistive load), 5.5ms (2kΩ + 1uF load)
0 ÷ 20mA and 4 ÷ 20mA – 1.7ms (600Ω load), 1.7ms (600Ω + 10mH
load)
Short circuit protection
(voltage mode)
Yes (no indication)
Cable
Shielded twisted pair
Unitronics
7
09/15
Diagnostics
UniStream™
(6)
Current – Open circuit indication
Supply level – Normal / Low or missing
IO/COM Bus
Bus maximum current
consumption
110mA
LED Indications
Digital Input LEDs
Green
Input state
Analog Input LEDs
Red
On: Input value is in Overflow
Temperature Input LEDs
Red
On: Input value is in Overflow, Underflow, or a
connection fault occurs
Relay and Transistor
Output LEDs
Green
Output state
Analog Output LEDs
Red
On: Open Circuit (when set to Current mode)
Status LED
A triple color LED. Indications are as follows:
Color
Green
Green/Red
Red
Orange
LED State
Status
On
Operating normally
Slow blink
Boot
Rapid blink
OS initialization
Slow blink
Configuration mismatch
Slow blink
No IO exchange
Rapid blink
Communication error
Rapid blink
OS Upgrade
Environmental
Protection
IP20, NEMA1
Operating temperature
-20°C to 55°C (-4°F to 131°F)
Storage temperature
-30°C to 70°C (-22°F to 158°F)
Relative Humidity (RH)
5% to 95% (non-condensing)
Operating Altitude
2,000m (6,562 ft)
Shock
IEC 60068-2-27, 15G, 11ms duration
Vibration
IEC 60068-2-6, 5Hz to 8.4Hz, 3.5mm constant amplitude, 8.4Hz to 150Hz,
1G acceleration.
Dimensions
Weight
0.250 kg (0.551 lb)
Size
Identical for all models, as shown in the images below
Unitronics
8
UIS-WCB2
Technical Specifications
Top View
Side View
Front View
Notes
1.
2.
3.
4.
5.
The UIS-WCB1 utilizes two high speed blocks that can each be assigned either to the inputs or to
the outputs.
Four of the digital inputs may be configured to function either as normal, or as high speed digital
inputs, that can receive high speed pulse signals from up to two sensors or shaft encoders.
The two transistor outputs may be configured to function either as normal, or as high speed PWM
outputs.
The 4-20mA input option is implemented using 0-20mA input range.
The UIS-WCB1 analog inputs measure values that are slightly higher than the nominal input range
(Input Over-range).
Note that when the input overflow occurs, it is indicated in the corresponding I/O Status tag while
the input value is registered as the maximum permissible value. For example, if the specified input
Unitronics
9
09/15
UniStream™
range is 0 ÷ 10V, the Over-range values can reach up to 10.15V, and any input voltage higher than
that will still register as 10.15V while the Overflow system tag is turned on.
6.
7.
8.
9.
See LED Indications Table for description of the relevant indications. Note that the diagnostics
results are also indicated in the system tags and can be observed through the UniApps™ or the
online state of the UniLogic™.
Step response and update time are independent of the number of channels that are used.
The UIS-WCB1 inherently supports 3-wire sensors.
4-wire sensors may be connected by utilizing 3 of the sensor wires; in-order to achieve the
specified performance, all sensor wires shall be of identical type and length just as with a 3-wire
sensor connection.
2-wire sensors may also be connected; performance in this case will degrade because of the wires`
resistance.
Refer to the UIS-WCB1 installation guide for detailed installation instructions.
The UIS-WCB1 temperature inputs measure values that are slightly higher or lower than the
nominal input range (Input Over/Under-range respectively).
Note that when input Overflow, Underflow or a connection fault occurs, it is indicated in the
corresponding I/O Status tag (refer to the UniLogic™ help for details) as well as by the respective
input LED (see LED Indications), while the input value is registered as follows:
Fault Type
Registered Value in the Input Tag
Overflow
32,767
Underflow
-32,767
Connection fault
-32,768
10. For temperature measurement, the value is represented in 0.1° units. For example, a temperature
of 12.3° is represented as 123 at the Value tag.
11. The overall accuracy for thermocouples is a combination of the per-sensor specified accuracy and
the thermocouple cold junction error specification.
The module requires at least 30 minutes of warm-up in order to meet the accuracy specifications.
12. Sensor connection fault check is active by default for temperature, resistance and mV
measurements. This may interfere with some test equipment like RTD, thermocouple, resistance
and voltage simulators and thus may induce reading errors or cause malfunction of the test
equipment and/or the UIS-WCB1.
In order to interoperate correctly with such equipment, you may set the Disable Fault Detection I/O
tag. This will disable connection fault check for all inputs.
Note that when this tag is set, the UIS-WCB1 will not check, or report, connection faults; thus, the
reading in such case is unpredictable.
13. Life expectancy of the relay contacts depends on the application that they are used in. The
product’s installation guide provides procedures for using the contacts with long cables or with
inductive loads.
14. The UIS-WCB1 analog outputs are able to output values that are slightly higher or lower (if
applicable) than the nominal output range (Output Over/Under-range respectively).
The information in this document reflects products at the date of printing. Unitronics reserves the right, subject to all applicable laws, at any time, at its sole
discretion, and without notice, to discontinue or change the features, designs, materials and other specifications of its products, and to either permanently or
temporarily withdraw any of the forgoing from the market.
All information in this document is provided "as is" without warranty of any kind, either expressed or implied, including but not limited to any implied warranties
of merchantability, fitness for a particular purpose, or non-infringement. Unitronics assumes no responsibility for errors or omissions in the information
presented in this document. In no event shall Unitronics be liable for any special, incidental, indirect or consequential damages of any kind, or any damages
whatsoever arising out of or in connection with the use or performance of this information.
The tradenames, trademarks, logos and service marks presented in this document, including their design, are the property of Unitronics (1989) (R"G) Ltd. or