3RT14 Contactors for Switching Resistive Loads (AC-1)
3-pole, 140 ... 690 A
■ Overview
The accessories for the 3RT10 contactors can also be used
here.
AC and DC operation (size S3)
UC operation (AC/DC) (sizes S6 to S12)
For more detailed descriptions about the sizes S3 to S12, see
"3RT10 Contactors, 3-pole, 3 to 250 kW."
IEC 60947, EN 60947 (VDE 0660)
3
The contactors are suitable for use in any climate. They are finger-safe according to EN 50274.
3RT14 contactors are used for switching resistive loads (AC-1)
or as contactors, for example for variable-speed operating
mechanisms that normally only have to carry the current.
■ Selection and ordering data
Size
Rated data AC-1,
Tu: 40 °C
Rated control DT Screw terminals
supply voltage
Us
OperaRatings of AC loads
tional cur- (p.f. = 0.95) at
rent Ie
Order No.
Up to
690 V
230 V 400 V 500 V 690 V
A
kW
kW
kW
kW
PU
(UNIT,
SET, M)
PS*
PG
Weight
per PU
approx.
Price
per PU
V
kg
For screw and snap-on mounting onto TH 35 and TH 75 standard
mounting rail
AC operation
S3
140
53
92
115
159
AC 24, 50 Hz B
AC 110, 50 Hz B
AC 230, 50 Hz }
3RT14 46-1AB00
3RT14 46-1AF00
3RT14 46-1AP00
1
1
1
1 unit
1 unit
1 unit
101
101
101
1.850
1.850
1.850
}
B
3RT14 46-1BB40
3RT14 46-1BM40
1
1
1 unit
1 unit
101
101
2.800
2.800
DC operation · DC solenoid system
S3
140
53
92
115
159
DC 24
DC 220
3RT14 46-1A. .0
* You can order this quantity or a multiple thereof.
3/50
Siemens LV 1 · 2010
© Siemens AG 2010
3RT, 3RH, 3TB, 3TC, 3TH, 3TK Contactors for Special Applications
3RT14 Contactors for Switching Resistive Loads (AC-1)
3-pole, 140 ... 690 A
AC/DC operation (40 Hz to 60 Hz, DC)
Auxiliary and control conductors: screw terminals
Withdrawable coils
Integrated coil circuit (Varistor)
Main conductors: busbar connections
Size
Rated data AC-1,
Tu: 40 °C
AuxilRated
DT Screw terminals
iary
control
contacts supply
voltage Us
Opera- Ratings of AC loads
tional
(p.f. = 0.95) at
current
Ie
Order No.
PS*
PG
Weight
per PU
approx.
Price
per PU
3
Version
PU
(UNIT,
SET,
M)
Up to
690 V
230 V 400 V 500 V 690 V
A
kW
kW
kW
kW
NO NC V
kg
Conventional operating mechanisms
S6
275
105
180
225
310
2
2
110 ... 127 }
220 ... 240 }
3RT14 56-6AF36
3RT14 56-6AP36
1
1
1 unit 101
1 unit 101
3.360
3.360
S10
400
151
263
329
454
2
2
110 ... 127 }
220 ... 240 }
3RT14 66-6AF36
3RT14 66-6AP36
1
1
1 unit 101
1 unit 101
6.600
6.600
S12
690
261
454
568
783
2
2
110 ... 127 A
220 ... 240 }
3RT14 76-6AF36
3RT14 76-6AP36
1
1
1 unit 101
1 unit 101
10.500
10.500
3RT14 6.
Solid-state operating mechanisms · for 24 V DC PLC output
S6
275
105
180
225
310
2
2
96 ... 127 B
200 ... 277 A
3RT14 56-6NF36
3RT14 56-6NP36
1
1
1 unit 101
1 unit 101
3.400
3.400
S10
400
151
263
329
454
2
2
96 ... 127 B
200 ... 277 A
3RT14 66-6NF36
3RT14 66-6NP36
1
1
1 unit 101
1 unit 101
6.600
6.600
S12
690
261
454
568
783
2
2
96 ... 127 B
200 ... 277 A
3RT14 76-6NF36
3RT14 76-6NP36
1
1
1 unit 101
1 unit 101
10.500
10.500
4.200
4.200
Solid-state operating mechanisms · for 24 V DC PLC output/PLC relay output, with remaining lifetime indicator (RLT)
S6
275
105
180
225
310
1
1
96 ... 127 B
200 ... 277 B
3RT14 56-6PF35
3RT14 56-6PP35
1
1
1 unit 101
1 unit 101
S10
400
151
263
329
454
1
1
200 ... 277 B
3RT14 66-6PP35
1
1 unit 101
5.700
S12
690
261
454
568
783
1
1
200 ... 277 B
3RT14 76-6PP35
1
1 unit 101
10.500
3.100
3.100
Solid-state operating mechanisms · with AS-Interface and
remaining lifetime indicator (RLT)
S6
275
105
180
225
310
1
1
96 ... 127 B
200 ... 277 B
3RT14 56-6QF35
3RT14 56-6QP35
1
1
1 unit 101
1 unit 101
S10
400
151
263
329
454
1
1
200 ... 277 B
3RT14 66-6QP35
1
1 unit 101
5.700
S12
690
261
454
568
783
1
1
200 ... 277 B
3RT14 76-6QP35
1
1 unit 101
10.500
For other voltages see page 3/26.
For accessories, see page 3/102.
For spare parts, see page 3/115.
* You can order this quantity or a multiple thereof.
Siemens LV 1 · 2010
3/51
© Siemens AG 2010
3RT, 3RH, 3TB, 3TC, 3TH, 3TK Contactors for Special Applications
3RT13 Contactors for Switching Resistive Loads (AC-1)
4-pole, 4 NO, 18 ... 140 A
■ Overview
The accessories for the 3-pole SIRIUS contactors can also be
used for the 4-pole versions.
AC and DC operation
EN 60947-4-1 (VDE 0660 Part 102).
The contactors are suitable for use in any climate. They are finger-safe according to EN 50274.
The contactors are also suitable for switching mixed loads in distribution systems (e. g. for supplying heaters, lamps, motors, PC
power supply units) with p.f. > 0.8 according to IEC 60947-4-1,
test conditions for utilization category AC-1.
3
■ Selection and ordering data
AC operation, 4 NO contacts
PU (UNIT, SET, M)= 1
PS*
= 1 unit
PG
= 101
3RT13 1.-1A.00
3RT13 2.-1A.00
Rated data AC-1,
Tu: 40/60 °C
Rated control
supply voltage Us
DT Screw terminals
Operational cur- Ratings of AC loads
rent Ie
(p.f. = 0.95) at 50 Hz
and
Order No.
Weight DT Cage Clamp
per PU
terminals
approx.
Price
per PU
Order No.
Weight
per PU
approx.
Price
per PU
400 V
A
kW
V AC
kg
kg
For screw and snap-on mounting onto TH 35 standard mounting rail
Size S001)
18 / 16
12 / 11
24, 50/60 Hz
110, 50/60 Hz
230, 50/60 Hz
}
}
}
3RT13 16-1AB00
3RT13 16-1AF00
3RT13 16-1AP00
0.200 B
0.200 B
0.200 B
3RT13 16-2AB00
3RT13 16-2AF00
3RT13 16-2AP00
0.200
0.200
0.200
22 / 20
14.5 / 13
24, 50/60 Hz
110, 50/60 Hz
230, 50/60 Hz
}
}
}
3RT13 17-1AB00
3RT13 17-1AF00
3RT13 17-1AP00
0.200 B
0.200 B
0.200 B
3RT13 17-2AB00
3RT13 17-2AF00
3RT13 17-2AP00
0.200
0.200
0.200
35 / 302)
22 / 20
24, 50 Hz
110, 50 Hz
230, 50 Hz
}
}
}
3RT13 25-1AB00
3RT13 25-1AF00
3RT13 25-1AP00
0.400
0.400
0.400
----
40 / 352)
26 / 23
24, 50 Hz
110, 50 Hz
230, 50 Hz
}
}
}
3RT13 26-1AB00
3RT13 26-1AF00
3RT13 26-1AP00
0.400
0.400
0.400
----
39 / 36
24, 50 Hz
110, 50 Hz
230, 50 Hz
B
B
}
3RT13 36-1AB00
3RT13 36-1AF00
3RT13 36-1AP00
0.990
0.990
0.990
----
110 / 100
72 / 66
24, 50 Hz
110, 50 Hz
230, 50 Hz
B
B
}
3RT13 44-1AB00
3RT13 44-1AF00
3RT13 44-1AP00
2.200
2.200
2.200
----
140 / 120
92 / 79
24, 50 Hz
110, 50 Hz
230, 50 Hz
B
B
}
3RT13 46-1AB00
3RT13 46-1AF00
3RT13 46-1AP00
2.200
2.200
2.200
----
Size S0
Size S2
60 / 55
Size S3
Size S00:
Snap-on auxiliary switch blocks according to EN 50005.
Sizes S0 to S3:
Snap-on auxiliary switch blocks according to EN 50012 and EN 50005
(for S0 max. 2 auxiliary contacts) (for more information see Accessories on page 3/97).
For other voltages see page 3/26.
For accessories, see page 3/102.
For spare parts, see page 3/115.
1)
For size S00: Coil operating range
at 50 Hz: 0.8 ... 1.1 x Us,
at 60 Hz: 0.85 ... 1.1 x Us.
2)
Minimum conductor cross-section 10 mm².
* You can order this quantity or a multiple thereof.
3/52
Siemens LV 1 · 2010
© Siemens AG 2010
3RT, 3RH, 3TB, 3TC, 3TH, 3TK Contactors for Special Applications
3RT13 Contactors for Switching Resistive Loads (AC-1)
4-pole, 4 NO, 18 ... 140 A
DC operation · DC solenoid system, 4 NO contacts
3
PU (UNIT, SET, M)= 1
PS*
= 1 unit
PG
= 101
3RT13 1.-2B. .0
3RT13 36-1. . .0
Rated data AC-1,
Tu: 40/60 °C
Rated control
supply voltage Us
3RT13 4.-1. . .0
DT Screw terminals
Operational cur- Ratings of AC loads
rent Ie
(p.f. = 0.95) at 50 Hz
and
Order No.
Weight DT Cage Clamp
per PU
terminals
approx.
Price
per PU
Order No.
Weight
per PU
approx.
Price
per PU
400 V
A
kW
V DC
kg
kg
For screw and snap-on mounting onto TH 35 standard mounting rail
Size S00
18 / 16
12 / 11
24
220
}
B
3RT13 16-1BB40
3RT13 16-1BM40
0.250 }
0.250 B
3RT13 16-2BB40
3RT13 16-2BM40
0.250
0.250
22 / 20
14.5 / 13
24
220
}
B
3RT13 17-1BB40
3RT13 17-1BM40
0.250 A
0.250 B
3RT13 17-2BB40
3RT13 17-2BM40
0.250
0.250
35 / 301)
22 / 20
24
220
}
B
3RT13 25-1BB40
3RT13 25-1BM40
0.630
0.630
---
40 / 351)
26 / 23
24
220
}
B
3RT13 26-1BB40
3RT13 26-1BM40
0.630
0.630
---
39 / 36
24
220
}
B
3RT13 36-1BB40
3RT13 36-1BM40
1.600
1.600
---
110 / 100
72 / 66
24
220
B
B
3RT13 44-1BB40
3RT13 44-1BM40
3.200
3.200
---
140 / 120
92 / 79
24
220
B
B
3RT13 46-1BB40
3RT13 46-1BM40
3.200
3.200
---
Size S0
Size S2
60 / 55
Size S3
Size S00:
Snap-on auxiliary switch blocks according to EN 50005.
Sizes S0 to S3:
Snap-on auxiliary switch blocks according to EN 50012 and EN 50005
(for S0 max. 2 auxiliary contacts) (for more information see Accessories on page 3/97).
For other voltages see page 3/26.
For accessories, see page 3/102.
For spare parts, see page 3/115.
1)
Minimum conductor cross-section 10 mm².
* You can order this quantity or a multiple thereof.
Siemens LV 1 · 2010
3/53
© Siemens AG 2010
3RT, 3RH, 3TB, 3TC, 3TH, 3TK Contactors for Special Applications
3TK1 Contactors for Switching Resistive Loads (AC-1)
4-pole, 4 NO, 200 ... 1000 A
■ Overview
EN 60947-4-1 (VDE 0660 Part 102).
The contactors also comply with the requirements of
NFC 63-110 and NFC 20–040.
3
The contactors are suitable for use in any climate. They are finger-safe according to EN 50274. Terminal covers may have to be
fitted onto the connecting bars, depending on the configuration
with other devices.
Solenoid coils for 3TK10 to 3TK13 contactors: as withdrawable
coils.
Surge suppression
Control circuit
Solenoid coils for 3TK1 contactors: can be retrofitted with RC
elements.
The contactors are also suitable for switching mixed loads in distribution systems (e. g. for supplying heaters, lamps, motors, PC
power supply units) with p.f. > 0.8 according to IEC 60947-4-1,
test conditions for utilization category AC-1.
■ Selection and ordering data
Screw terminals
Screw fixing
3TK13
Rated data AC-1
Auxiliary con- Rated control supply
tacts
voltage Us
Operational
current Ie
up to 690 V
(at 40 °C)
Ratings of AC loads
(p.f. = 0.95) at
Version
A
kW
DT Screw terminals
Order No.
PU
(UNIT,
SET, M)
PS*
PG
Weight
per PU
approx.
Price
per PU
230 V 400 V 690 V 1000 V
kW
kW
kW
NO
NC
V AC
kg
AC operation
200
75
130
225
205
2
2
220 ... 230, 50 Hz
230 ... 240, 50 Hz
110/120, 50/60 Hz
24, 50 Hz
B
D
D
D
3TK10 42-0AP0
3TK10 42-0AU0
3TK10 42-0AF0
3TK10 42-0AB0
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
4.400
4.400
4.400
4.400
250
90
165
280
200
2
2
220 ... 230, 50 Hz
230 ... 240, 50 Hz
110/120, 50/60 Hz
24, 50 Hz
B
D
D
D
3TK11 42-0AP0
3TK11 42-0AU0
3TK11 42-0AF0
3TK11 42-0AB0
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
4.700
4.700
4.700
4.700
300
110
195
340
325
2
2
220 ... 230, 50 Hz
230 ... 240, 50 Hz
110/120, 50/60 Hz
24, 50 Hz
B
D
D
D
3TK12 42-0AP0
3TK12 42-0AU0
3TK12 42-0AF0
3TK12 42-0AB0
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
7.200
7.200
7.200
7.200
350
130
230
395
370
2
2
220 ... 230, 50 Hz
230 ... 240, 50 Hz
110/120, 50/60 Hz
24, 50 Hz
B
D
D
D
3TK13 42-0AP0
3TK13 42-0AU0
3TK13 42-0AF0
3TK13 42-0AB0
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
7.200
7.200
7.200
7.200
550
205
360
620
510
2
2
220 ... 230, 50 Hz1)
230 ... 240, 50 Hz
110/120, 50/60 Hz
B
D
D
3TK14 42-0AP0
3TK14 42-0AU0
3TK14 42-0AF0
1
1
1
1 unit
1 unit
1 unit
101
101
101
19.000
19.000
19.000
800
300
525
905
575
2
2
220 ... 230, 50 Hz1)
230 ... 240, 50 Hz
110/120, 50/60 Hz
B
D
D
3TK15 42-0AP0
3TK15 42-0AU0
3TK15 42-0AF0
1
1
1
1 unit
1 unit
1 unit
101
101
101
19.000
19.000
19.000
1000
375
655
1135
--
2
2
220 ... 230, 50 Hz1)
230 ... 240, 50 Hz
110/120 50/60 Hz
B
D
D
3TK17 42-0AP0
3TK17 42-0AU0
3TK17 42-0AF0
1
1
1
1 unit
1 unit
1 unit
101
101
101
20.100
20.100
20.100
For accessories see page 3/120 onwards.
For spare parts, see page 3/128 onwards.
1)
At 60 Hz: 240 V.
* You can order this quantity or a multiple thereof.
3/54
Siemens LV 1 · 2010
© Siemens AG 2010
3RT, 3RH, 3TB, 3TC, 3TH, 3TK Contactors for Special Applications
3TK20 Contactors
4-pole, 4 kW
■ Overview
■ Application
The main area of application for the 3TK2 contactors with flat
connectors is in household equipment. These contactors are
also suitable for simple electric controllers. No auxiliary switch
blocks can be retrofitted.
AC and DC operation
IEC 60947 (VDE 0660).
The contactors are suitable for use in any climate.
The contactors with screw terminals are finger-safe according to
EN 50274.
3
The contactors are available in versions with screw terminals,
6.3 mm plug-in terminals and solder pin connections for soldering in printed circuit boards.
■ Selection and ordering data
Size 00
AC-1: operational current Ie = 16 A (at 55 °C)
Rated data
Utilization categories AC-2 and AC-3
Main contacts
DT Order No.
Operational Ratings of induction motors at Version
current Ie
50 Hz and
At 400/
380 V
230/
400/
500 V 690/
220 V 380 V
660 V
A
kW
kW
kW
kW
NO
2.4
4
4
4
PU
(UNIT,
SET, M)
PS*
PG
NC
Weight
per PU
approx.
kg
Contactors with screw terminals ·
for screw and snap-on mounting onto TH 35 standard mounting rail
AC operation
9
Price €
per PU
Screw terminals
4
3
2
-1
2
C
C
C
3TK20 40-0AP0
3TK20 31-0AP0
3TK20 22-0AP0
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.190
0.190
0.190
4
3
2
-1
2
C
C
C
3TK20 40-0BB4
3TK20 31-0BB4
3TK20 22-0BB4
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.210
0.210
0.210
DC operation · DC solenoid system
9
2.4
4
4
4
3TK20. .-0. . .
Contactors with 6.3 mm x 0.8 mm·flat connectors
for screw and snap-on mounting onto TH 35 standard mounting rail
AC operation
9
2.4
4
4
--
Flat connectors
4
3
2
-1
2
C
C
C
3TK20 40-3AP0
3TK20 31-3AP0
3TK20 22-3AP0
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.170
0.170
0.170
4
3
2
-1
2
C
C
C
3TK20 40-3BB4
3TK20 31-3BB4
3TK20 22-3BB4
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.190
0.190
0.190
4
3
2
-1
2
C
C
C
3TK20 40-7AP0
3TK20 31-7AP0
3TK20 22-7AP0
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.170
0.170
0.170
4
3
2
-1
2
C
C
C
3TK20 40-7BB4
3TK20 31-7BB4
3TK20 22-7BB4
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.190
0.190
0.190
DC operation · DC solenoid system
9
2.4
4
4
--
3TK20. .-3. . .
Contactors with 6.3 mm x 0.8 mm flat connectors
for screw fixing (diagonal)
AC operation
9
2.4
4
4
--
DC operation · DC solenoid system
9
2.4
4
4
--
3TK20. .-7. . .
Contactors with solder pin connections for printed circuit boards1)
for screw fixing (diagonal)
AC operation
9
2.4
4
4
--
Solder pin connections
4
3
2
-1
2
C
C
C
3TK20 40-6AP0
3TK20 31-6AP0
3TK20 22-6AP0
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.170
0.170
0.170
4
3
2
-1
2
C
C
C
3TK20 40-6BB4
3TK20 31-6BB4
3TK20 22-6BB4
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.190
0.190
0.190
DC operation · DC solenoid system
3TK20. .-6. . .
9
2.4
4
4
--
For accessories, see page 3/123.
1)
Operating range at AC-1
220 V: 0.85 to 1.15 x Us; lower operating range limit according to
IEC 60947.
* You can order this quantity or a multiple thereof.
Siemens LV 1 · 2010
3/55
© Siemens AG 2010
3RT, 3RH, 3TB, 3TC, 3TH, 3TK Contactors for Special Applications
3TK20 Contactors
4-pole, 4 kW
Rated control supply voltages
(the 10th and 11th position of the order number must be
changed)
Contactor type
3TK20
Rated control supply voltage Us
AC operation
3
Solenoid coils for AC 50 and 60 Hz
50 Hz
60 Hz
230/220 V AC
276 V AC
P01)
DC operation
24 V DC
1)
B4
Operating range at 220 V:
0.85 to 1.15 x Us; lower operating range limit according to IEC 60947.
Please inquire about other voltages.
3/56
Siemens LV 1 · 2010
© Siemens AG 2010
3RT, 3RH, 3TB, 3TC, 3TH, 3TK Contactors for Special Applications
3RT15 Contactors
4-pole, 2 NO + 2 NC, 4 ... 18.5 kW
■ Overview
The contactors are suitable for use in any climate. They are finger-safe according to EN 50274.
AC and DC operation
EN 60947-4-1 (VDE 0660 Part 102).
The accessories for the 3-pole SIRIUS contactors can also be
used for the 4-pole versions.
■ Selection and ordering data
AC and DC operation, 2 NO contacts + 2 NC contacts1)
3
PU (UNIT, SET, M)= 1
PS*
= 1 unit
PG
= 101
3RT15 1.-1. . . .
3RT15 1.-2. . . .
Rated data
AC-2/AC-3,
Tu: Up to 60 °C
AC-1,
Tu: 40/60 °C
Operational
current Ie
Ratings of induction Operational
motors at 50 Hz
current Ie
and
At 400 V
400 V
A
kW
A
Rated control
supply voltage
Us
3RT15 26-1. . . .
DT Screw terminals
Order No.
Weight DT Cage Clamp
per PU
terminals
approx.
Price
per PU
V
Order No.
Weight
per PU
approx.
Price
per PU
kg
kg
For screw and snap-on mounting onto TH 35 standard mounting rail
AC operation
Size S00 2)
9
4
18 / 16
24, 50/60 Hz
110, 50/60 Hz
230, 50/60 Hz
B
B
}
3RT15 16-1AB00
3RT15 16-1AF00
3RT15 16-1AP00
0.200 B
0.200 B
0.200 B
3RT15 16-2AB00
3RT15 16-2AF00
3RT15 16-2AP00
0.200
0.200
0.200
12
5.5
22 / 20
24, 50/60 Hz
110, 50/60 Hz
230, 50/60 Hz
A
}
}
3RT15 17-1AB00
3RT15 17-1AF00
3RT15 17-1AP00
0.200 B
0.200 B
0.200 }
3RT15 17-2AB00
3RT15 17-2AF00
3RT15 17-2AP00
0.200
0.200
0.200
11
40 / 35 3)
24, 50 Hz
110, 50 Hz
230, 50 Hz
B
B
}
3RT15 26-1AB00
3RT15 26-1AF00
3RT15 26-1AP00
0.400
0.400
0.400
----
18.5
55 / 50
24, 50 Hz
110, 50 Hz
230, 50 Hz
B
B
}
3RT15 35-1AB00
3RT15 35-1AF00
3RT15 35-1AP00
1.000
1.000
1.000
----
Size S0
25
Size S2
40
DC operation · DC solenoid system
Size S00
9
4
18 / 16
DC 24
DC 220
}
B
3RT15 16-1BB40
3RT15 16-1BM40
0.260 }
0.260 B
3RT15 16-2BB40
3RT15 16-2BM40
0.260
0.260
12
5.5
22 / 20
DC 24
DC 220
}
B
3RT15 17-1BB40
3RT15 17-1BM40
0.260 B
0.260 B
3RT15 17-2BB40
3RT15 17-2BM40
0.260
0.260
11
40 / 35 3)
DC 24
DC 220
}
B
3RT15 26-1BB40
3RT15 26-1BM40
0.630
0.630
---
18.5
55 / 50
DC 24
DC 220
}
B
3RT15 35-1BB40
3RT15 35-1BM40
1.590
1.590
---
Size S0
20
Size S2
40
Size S00: Snap-on auxiliary switch blocks according to EN 50005.
Sizes S0 to S3: Snap-on auxiliary switch blocks according to EN 50012 and EN 50005
(for S0 max. 2 auxiliary contacts) (for more information see Accessories on page 3/97).
For other voltages see page 3/26.
For accessories, see page 3/102.
For spare parts, see page 3/115.
1)
Single device for pole reversal; not suitable for reversing duty.
2)
For size S00: Coil operating range
at 50 Hz: 0.8 ... 1.1 x Us
at 60 Hz: 0.85 ... 1.1 x Us.
3)
Required conductor cross-section: 10 mm².
* You can order this quantity or a multiple thereof.
Siemens LV 1 · 2010
3/57
© Siemens AG 2010
3RT, 3RH, 3TB, 3TC, 3TH, 3TK Contactors for Special Applications
3RT16 Capacitor Contactors
12.5 ... 50 kvar
■ Overview
The contactors are suitable for use in any climate. They are finger-safe according to EN 50274.
The auxiliary switch block which is snapped onto the capacitor
contactor contains the three leading NO contacts and in the
case of S00 one standard NC contact and in the case of S0 and
S3 one standard NO contact, which is unassigned. Size S00 also
contains another unassigned NO contact in the basic unit.
The 3RT16 capacitor contactors are special version of the size
S00 to S3 SIRIUS contactors. The capacitors are precharged by
means of the mounted leading NO contacts and resistors; only
then do the main contacts close.
In addition, a 2-pole auxiliary switch block can be mounted laterally on the 3RT16 47 capacitor contactors (2 NO, 2 NC or 1 NO
+ 1 NC versions); type 3RH19 21-1EA. .. The fitting of auxiliary
switches for 3RT16 17 and 3RT16 27 is not expandable.
This prevents disturbances in the network and welding of the
contactors.
Capacitor switching capacity of the basic 3RT10 contactor version (see note on Technical Information on page 3/1).
AC operation
3
IEC 60947, EN 60947 (VDE 0660).
Only discharged capacitors are permitted to be switched on
with capacitor contactors.
■ Selection and ordering data
AC operation
Screw terminals
3RT16 17-1A.03
3RT16 27-1A.01
Utilization category AC-6b
Switching of AC capacitors for an
ambient temperature of 60 °C1)
Auxiliary
contacts,
unassigned
Capacitor rating at
operational voltage 50/60 Hz
Version
At 230 V
At 400 V
At 525 V
At 690 V
kvar
kvar
kvar
kvar
NO
3RT16 47-1A.01
Rated control
DT Screw terminals
supply voltage Us2)
Order No.
NC
V AC
PU
(UNIT,
SET, M)
PS*
PG
Weight
per PU
approx.
Price
per PU
kg
Hz
For screw and snap-on mounting onto TH 35 standard mounting rail
Size S00
3 … 7.5
5 … 12.5
7.5 … 15
10 … 21
1
1
24
110
230
50 / 60
B
B
}
3RT16 17-1AB03
3RT16 17-1AF03
3RT16 17-1AP03
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.280
0.280
0.280
6 … 25
7.8 … 30
10 … 42
1
--
24
110
230
50
B
B
}
3RT16 27-1AB01
3RT16 27-1AF01
3RT16 27-1AP01
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.440
0.440
0.440
5 … 50
7.5 … 60
10 … 84
1
--
24
110
230
50
B
B
}
3RT16 47-1AB01
3RT16 47-1AF01
3RT16 47-1AP01
1
1
1
1 unit
1 unit
1 unit
101
101
101
2.040
2.040
2.040
Size S03)
3.5 … 15
Size S3
3.5 … 30
For other voltages see page 3/26.
For accessories, see page 3/104.
1)
For size S3: 55 °C.
2)
Operating range: 0.85 ... 1.1 x Us.
3)
For conductor cross-sections > 6 mm2
use 3RV19 25-5AB terminals (2 units).
* You can order this quantity or a multiple thereof.
3/58
Siemens LV 1 · 2010
© Siemens AG 2010
3RT, 3RH, 3TB, 3TC, 3TH, 3TK Contactors for Special Applications
Contactors with Extended Operating Range 0.7 ... 1.25 x Us, for Railway Applications
3RH11 contactor relays
■ Overview
3RH11 22-2K.40-0LA0
DC operation
IEC 60947-4-1, EN 60947-4-1 (VDE 0660, Part 102), for requirements according to IEC 60077-1 and IEC 60077-2.
The contactor relays are finger-safe according to EN 50274. The
size S00 contactor relays have Cage Clamp connections for all
terminals.
The DC solenoid systems of the contactor relays are modified (to
holding excitation) by means of a series resistor.
The size S00 contactor relays are supplied prewired with a plugon module containing the series resistor. The varistor is integrated. A 4-pole auxiliary switch block (according to EN 50005)
can be fitted additionally.
The permissible ambient temperature for operation of the contactor relays (across the full coil operating range) is -40 °C to
+70 °C.
Uninterrupted duty at temperatures > +60 °C reduces the mechanical endurance, the current carrying capacity of the conducting paths and the switching frequency.
At ambient temperatures up to 70°C, the size S00 contactor relays are allowed to be mounted side by side.
3RH11 22-2K.40:
These contactor relays have an extended operating range from
0.7 to 1.25 x Us; the coils are fitted with varistors as standard. An
additional series resistor is not required. Please note:
No auxiliary switch block can be mounted on size S00.
■ Application
Mounting
For operation in installations which are subject both to considerable variations in the control voltage and to high ambient temperatures, e. g. railway applications under extreme climatic conditions, rolling mills, etc.
A clearance of 10 mm is required for side-by-side mounting at
ambient temperatures > 60 °C ≤ 70 °C.
Control and auxiliary circuits
The solenoid coils of the contactor relays have an extended coil
operating range from 0.7 to 1.25 x Us and are fitted as standard
with varistors to provide protection against overvoltage. The
opening delay is consequently 2 to 5 ms longer than for standard
contactors.
■ Selection and ordering data
DC operation · DC solenoid system
Cage Clamp terminals
For screw and snap-on mounting onto standard mounting rail
Solenoid coil fitted with varistor
3RH11 22-2K.40
3RH11 22-2K.40-0LA0
Rated operational current
Ie/AC-15/AC-14
Tu: 70 °C at
Contacts
Rated control supply
voltage Us
DT Cage Clamp terminals
Version
230 V
400 V
500 V
690 V
A
A
A
A
NO
Order No.
NC
V DC
PU
(UNIT,
SET, M)
PS*
PG
Weight
per PU
approx.
Price
per PU
kg
3RH11 contactor relays
Size S00
Cage Clamp terminals for all connections
6
3
2
1
2
21)
24 2)
110 2)
}
A
3RH11 22-2KB40
3RH11 22-2KF40
1
1
1 unit
1 unit
101
101
0.260
0.260
6
3
2
1
2
13)
24
110
A
A
3RH11 22-2KB40-0LA0
3RH11 22-2KF40-0LA0
1
1
1 unit
1 unit
101
101
0.290
0.290
1)
It is not possible to mount an auxiliary switch block. A clearance of 10 mm
is required for side-by-side mounting at ambient temperatures > 60 °C.
2)
Version without series resistor.
3)
One 4-pole auxiliary switch block according to EN 50005 can be mounted;
no distance required up to 70 °C.
* You can order this quantity or a multiple thereof.
Siemens LV 1 · 2010
3/59
3
Mounting
Ambient temperature
© Siemens AG 2010
3RT, 3RH, 3TB, 3TC, 3TH, 3TK Contactors for Special Applications
Contactors with Extended Operating Range 0.7 ... 1.25 x Us , for Railway Applications
3TH4 contactor relays
■ Overview
■ Application
For operation in plants which are subject both to considerable
variations in the control voltage and to high ambient temperatures, e. g. in railway applications.
DC operation
EN 60947-4-1.
For requirements according to IEC 60077-1 and IEC 60077-2.
The contactors are finger-safe according to EN 50274. Terminal
covers may have to be fitted onto the connecting bars, depending on the configuration with other devices.
3
Ambient temperature
The permissible ambient temperature for operation of the contactors (across the full operating range of the solenoid coil) is 50 to +70 °C. Uninterrupted duty at temperatures < -25 °C and
> +55 °C reduces the mechanical endurance, the current-carrying capacity of the conducting paths and the switching frequency.
Control and auxiliary circuits
The solenoid coils of the contactors have an extended coil operating range from 0.7 to 1.25 x Us and are fitted as standard with
varistors to provide protection against overvoltage. The opening
delay is consequently 2 to 5 ms longer than for standard contactors.
At ambient temperatures > 55 °C, a distance of 10 mm must be
observed if contactor relays and size 1 and 2 contactors are
mounted side by side. There is no need to reduce the technical
specifications.
■ Selection and ordering data
For screw and snap-on mounting onto 35 mm standard mounting rail
Solenoid coil fitted with varistor
3TH4
Contacts Rated operational current
Ie/AC-15/AC-14
Number
230 V
400 V
500 V
690 V
A
A
A
A
Contacts1)
Ident. No.
acc. to
EN 50011
Rated control
supply voltage
Us
DT Screw terminals
Version
Order No.
PU
(UNIT,
SET, M)
PS*
PG
Weight
per PU
approx.
Price
per PU
NO NC V DC
kg
3TH42 contactor relays · DC operation · DC solenoid system
8
10
6
4
2
44E
4
4
24
110
}
}
3TH42 44-0LB4
3TH42 44-0LF4
1
1
1 unit
1 unit
101
101
0.670
0.670
53E
5
3
24
110
D
}
3TH42 53-0LB4
3TH42 53-0LF4
1
1
1 unit
1 unit
101
101
0.670
0.670
62E
6
2
24
110
}
}
3TH42 62-0LB4
3TH42 62-0LF4
1
1
1 unit
1 unit
101
101
0.670
0.670
For accessories, see page 3/125.
1)
Contacts not extendable.
* You can order this quantity or a multiple thereof.
3/60
Siemens LV 1 · 2010
© Siemens AG 2010
3RT, 3RH, 3TB, 3TC, 3TH, 3TK Contactors for Special Applications
Contactors with Extended Operating Range 0.7 ... 1.25 x Us, for Railway Applications
3RT10 motor contactors, 5.5 ... 45 kW
DC operation
IEC 60947-4-1, EN 60947-4-1,
for requirements according to IEC 60077-1 and IEC 60077-2.
The contactors are finger-safe according to EN 50274 (exception: series resistors S0 to S3). The contactors are available with
both Cage Clamp and screw connection. The size S00 contactors have Cage Clamp terminals for all connections. The auxiliary conductor and coil terminals of sizes S0 to S3 are all Cage
Clamp terminals.
Control and auxiliary circuits
Contactors are available with:
• Conventional coils (sizes S00 and S0 only)
• Coils with series resistor
• Coils with solid-state control unit
Ambient temperature
The permissible ambient temperature for operation of the contactors (across the full coil operating range) is -40 °C to +70 °C.
Uninterrupted duty at temperatures > +60 °C reduces the mechanical endurance, the current carrying capacity of the conducting paths and the switching frequency.
■ Application
For operation in installations which are subject both to considerable variations in the control voltage and to high ambient temperatures, e. g. railway applications under extreme climatic conditions, rolling mills, etc.
■ More information
Control and auxiliary circuits
The solenoid coils of the contactors have an extended coil operating range from 0.7 to 1.25 x Us and are fitted as standard with
varistors to provide protection against overvoltage. The opening
delay is consequently 2 to 5 ms longer than for standard contactors.
3RT10 . .-2K.42-0LA0,
3RT10 . .-3K.44-0LA0
The DC solenoid systems of the contactors are modified (to
holding excitation) by means of a series resistor.
Auxiliary switches
The size S00 contactors are supplied prewired with a plug-on
module containing the series resistor. The varistor is integrated.
A 4-pole auxiliary switch block (according to EN 50005) can be
fitted additionally.
Mounting
At ambient temperatures up to 70°C, the size S00 contactors
and contactor relays are allowed to be mounted side by side.
The resistor module of the size S0 to S3 contactors must be
mounted to the left of the contactor owing to the prefabricated
connecting cables.
Dimensions
Attaching resistors increases the width of contactor sizes S0 to
S3 (see note on Dimensional Drawings, page 3/1).
3RT10 17-2K.4.,
3RT10 2.-3K.40
3
■ Overview
These contactor relays have an extended operating range from
0.7 to 1.25 x Us; the coils are fitted with varistors as standard. An
additional series resistor is not required.
Please note:
• Size S00: It is not possible to mount an auxiliary switch block.
• Size S0: Up to two single-pole auxiliary switch blocks can be
mounted.
Mounting
A clearance of 10 mm is required for side-by-side mounting at
ambient temperatures > 60 °C ≤ 70 °C.
3RT10 contactors with contactor control unit, extended operating range
3RT10 . .-.X.40-0LA2
They are supplied as complete units with a built-on contactor
control unit.
Control and auxiliary circuits
The contactors are energized via upstream control electronics
which ensure the coil operating range of 0.7 to 1.25 x Us at an
ambient temperature of 70 °C.
A varistor is integrated for damping opening surges in the coil.
The opening delay is consequently 2 to 5 ms longer than for
standard contactors.
The possibility of mounting auxiliary switches is the same as that
for equivalent standard contactors.
Mounting
At ambient temperatures up to 70 °C, sizes S0 to S3 of these
contactor versions are allowed to be mounted side by side.
Dimensions
Because of the built-on contactor control unit, the height of the
size S0 to S3 contactors increases by up to 34 mm (see note on
Dimensional Drawings, page 3/1).
The size S0 to S3 contactors are equipped on the front with an
auxiliary switch block with 2 NO + 2 NC contacts. The separate
series resistor, which is attached laterally next to the contactor
on the 35 mm standard mounting rail, is fitted with connecting
cables for mounting onto contactors. A circuit diagram showing
the terminals is stuck onto each contactor. One NC of the auxiliary contacts is required for the series resistor function. The selection and ordering data shows the number of additional, unassigned auxiliary contacts. It is only possible to extend the
number of auxiliary contacts with size S00.
Siemens LV 1 · 2010
3/61
© Siemens AG 2010
3RT, 3RH, 3TB, 3TC, 3TH, 3TK Contactors for Special Applications
Contactors with Extended Operating Range 0.7 ... 1.25 x Us , for Railway Applications
3RT10 motor contactors, 5.5 ... 45 kW
■ Selection and ordering data
3
DC operation · DC solenoid system
Cage Clamp terminals
For screw and snap-on mounting onto standard mounting rail
Solenoid coil fitted with varistor
3RT10 17-2K.4.-0LA0
3RT10 2.-3K.40
Rated data
AC-2 and AC-3
Tu: 70 °C
Auxiliary contacts
Operational current Ie
at
Version
Ratings of
induction motors at
400 V
230 V 400 V 500 V 690 V
A
kW
kW
kW
kW
NO
3RT10 3.-3K.44-0LA0
Rated control sup- DT Cage Clamp terminals
ply voltage Us
Order No.
NC
V DC
PU
(UNIT,
SET, M)
PS*
PG
Weight
per PU
approx.
Price
per PU
kg
3RT10 contactors for switching motors
Size S00
Cage Clamp terminals for all connections
12
3
5.5
5.5
5.5
11)
--
243)
110 3)
}
B
3RT10 17-2KB41
3RT10 17-2KF41
1
1
1 unit
1 unit
101
101
0.260
0.260
12
3
5.5
5.5
5.5
--
11)
243)
1103)
}
B
3RT10 17-2KB42
3RT10 17-2KF42
1
1
1 unit
1 unit
101
101
0.260
0.260
12
3
5.5
5.5
5.5
--
12)
24
110
A
B
3RT10 17-2KB42-0LA0
3RT10 17-2KF42-0LA0
1
1
1 unit
1 unit
101
101
0.280
0.280
Size S0
Cage Clamp terminals for coil terminals and auxiliary contacts
17
4
7.5
10
11
--
--4)
243)
1103)
}
B
3RT10 25-3KB40
3RT10 25-3KF40
1
1
1 unit
1 unit
101
101
0.600
0.600
25
5.5
11
11
11
--
--4)
243)
1103)
}
B
3RT10 26-3KB40
3RT10 26-3KF40
1
1
1 unit
1 unit
101
101
0.600
0.600
17
4
7.5
10
11
2
15)
24
110
B
B
3RT10 25-3KB44-0LA0
3RT10 25-3KF44-0LA0
1
1
1 unit
1 unit
101
101
0.760
0.760
25
5.5
11
11
11
2
15)
24
110
B
B
3RT10 26-3KB44-0LA0
3RT10 26-3KF44-0LA0
1
1
1 unit
1 unit
101
101
0.760
0.760
Size S2
Cage Clamp terminals for coil terminals and auxiliary contacts
32
7.5
15
18.5
18.5
2
15)
24
110
B
B
3RT10 34-3KB44-0LA0
3RT10 34-3KF44-0LA0
1
1
1 unit
1 unit
101
101
1.670
1.670
40
11
18.5
22
22
2
15)
24
110
B
B
3RT10 35-3KB44-0LA0
3RT10 35-3KF44-0LA0
1
1
1 unit
1 unit
101
101
1.670
1.670
50
15
22
30
22
2
15)
24
110
B
B
3RT10 36-3KB44-0LA0
3RT10 36-3KF44-0LA0
1
1
1 unit
1 unit
101
101
1.670
1.670
Size S3
Cage Clamp terminals for coil terminals and auxiliary contacts
65
18.5
30
37
43
2
15)
24
110
B
B
3RT10 44-3KB44-0LA0
3RT10 44-3KF44-0LA0
1
1
1 unit
1 unit
101
101
3.100
3.100
80
22
37
45
55
2
15)
24
110
B
B
3RT10 45-3KB44-0LA0
3RT10 45-3KF44-0LA0
1
1
1 unit
1 unit
101
101
3.100
3.100
2
15)
24
110
B
B
3RT10 46-3KB44-0LA0
3RT10 46-3KF44-0LA0
1
1
1 unit
1 unit
101
101
3.100
3.100
95
22
45
55
55
For spare parts, see page 3/103.
1)
It is not possible to mount an auxiliary switch block. A clearance of 10 mm
is required for side-by-side mounting at ambient temperatures > 60 °C.
2)
One 4-pole auxiliary switch block according to EN 50005 can be mounted;
no distance required up to 70 °C.
3)
Version without series resistor.
4)
Up to two single-pole auxiliary switch blocks can be mounted. A clearance
of 10 mm is required for side-by-side mounting at ambient temperatures
> 60 °C.
5)
The number of auxiliary contacts cannot be increased; no clearance
required up to 70 °C.
* You can order this quantity or a multiple thereof.
3/62
Siemens LV 1 · 2010
© Siemens AG 2010
3RT, 3RH, 3TB, 3TC, 3TH, 3TK Contactors for Special Applications
Contactors with Extended Operating Range 0.7 ... 1.25 x Us, for Railway Applications
3RT10 motor contactors, 5.5 ... 45 kW
DC operation · DC solenoid system
For screw and snap-on mounting onto standard mounting rail
Contactor control unit
Solenoid coil fitted with varistor
3
PU (UNIT, SET, M)= 1
PS*
= 1 unit
PG
= 101
3RT10 . .-3X.40-0LA2
Rated data
AC-2 and AC-3
Tu: Up to 70 °C
Auxiliary
contacts1)
Rated operational
current Ie
up to
Ident.
No.
Power of
induction
motors at
50 Hz
400 V
400 V
A
kW
Rated control DT Screw terminals
supply voltage Us
Version
Order No.
Weight DT Cage Clamp terminals
per PU
for coil terminals
approx.
Price
per PU
Order No.
Weight
per PU
approx.
Price
per PU
kg
NO NC V DC
kg
For screw and snap-on mounting onto TH 35 standard mounting rail
Size S0
17
7.5
---
---
---
24
110
C
B
3RT10 25-1XB40-0LA2
3RT10 25-1XF40-0LA2
0.640 B
0.640 B
3RT10 25-3XB40-0LA2
3RT10 25-3XF40-0LA2
0.640
0.640
25
11
---
---
---
24
110
B
B
3RT10 26-1XB40-0LA2
3RT10 26-1XF40-0LA2
0.640 B
0.640 B
3RT10 26-3XB40-0LA2
3RT10 26-3XF40-0LA2
0.640
0.640
32
15
---
---
---
24
110
B
B
3RT10 34-1XB40-0LA2
3RT10 34-1XF40-0LA2
1.500 C
1.500 B
3RT10 34-3XB40-0LA2
3RT10 34-3XF40-0LA2
1.500
1.500
40
18.5
---
---
---
24
110
B
B
3RT10 35-1XB40-0LA2
3RT10 35-1XF40-0LA2
1.500 C
1.500 B
3RT10 35-3XB40-0LA2
3RT10 35-3XF40-0LA2
1.500
1.500
50
22
---
---
---
24
110
B
B
3RT10 36-1XB40-0LA2
3RT10 36-1XF40-0LA2
1.500 B
1.500 B
3RT10 36-3XB40-0LA2
3RT10 36-3XF40-0LA2
1.500
1.500
Size S2
For screw and snap-on mounting onto TH 35 and TH 75 standard mounting rail
Size S3
65
30
---
---
---
24
110
B
B
3RT10 44-1XB40-0LA2
3RT10 44-1XF40-0LA2
2.900 B
2.900 B
3RT10 44-3XB40-0LA2
3RT10 44-3XF40-0LA2
2.900
2.900
80
37
---
---
---
24
110
B
B
3RT10 45-1XB40-0LA2
3RT10 45-1XF40-0LA2
2.900 B
2.900 B
3RT10 45-3XB40-0LA2
3RT10 45-3XF40-0LA2
2.900
2.900
95
45
---
---
---
24
110
B
B
3RT10 46-1XB40-0LA2
3RT10 46-1XF40-0LA2
2.900 B
2.900 B
3RT10 46-3XB40-0LA2
3RT10 46-3XF40-0LA2
2.900
2.900
1)
Auxiliary switch blocks mountable as standard contactors.
* You can order this quantity or a multiple thereof.
Siemens LV 1 · 2010
3/63
© Siemens AG 2010
3RT, 3RH, 3TB, 3TC, 3TH, 3TK Contactors for Special Applications
Contactors with Extended Operating Range 0.7 ... 1.25 x Us , for Railway Applications
3TB5 motor contactors, 55 ... 200 kW
3TB52 to 3TB56, the series resistor must be attached separately
next to the contactors.
■ Overview
EN 60947-4-1.
One NC of the auxiliary contacts is required for the series resistor
function. The selection and ordering data show the number of
additional, unassigned auxiliary contacts. It is not possible to extend the number of auxiliary contacts.
For requirements according to IEC 60077-1 and IEC 60077-2.
The contactors are finger-safe according to EN 50274. Terminal
covers may have to be fitted onto the connecting bars, depending on the configuration with other devices.
Reversing contactors
With the 3TB52 to 3TB56 contactors, the series resistor must be
connected using an additional K2 reversing contactor (3RT13
17-1F.40). This contactor is automatically included in the scope
of supply in the same packaging as the contactor.
3
All specifications and technical specifications not mentioned
here are identical to those of the standard 3TB contactors.
Ambient temperature
The permissible ambient temperature for operation of the contactors (across the full operating range of the solenoid coil) is 50 to +70 °C. Uninterrupted duty at temperatures < -25 °C and
> +55 °C reduces the mechanical endurance, the current-carrying capacity of the conducting paths and the switching frequency.
Dimensions
Attaching resistors and varistors increases the width of the contactors (see note on Dimensional Drawings, page 3/1).
■ Application
At ambient temperatures > 55 °C, a distance of 10 mm must be
observed if contactor relays and size 1 and 2 contactors are
mounted side by side. There is no need to reduce the technical
specifications.
For operation in plants which are subject both to considerable
variations in the control voltage and to high ambient temperatures, e. g. in railway applications.
Series resistor
Control and auxiliary circuits
The DC solenoid systems of the 3TB contactors must be modified (to hold-in coil) by means of a series resistor. This series resistor is supplied separately packed with the contactors.
The solenoid coils of the contactors have an extended coil operating range from 0.7 to 1.25 x Us and are fitted as standard with
varistors to provide protection against overvoltage. The opening
delay is consequently 2 to 5 ms longer than for standard contactors.
With types 3TB50, the series resistor must be attached onto the
right-hand side of the auxiliary switch block by means of the enclosed mounting parts and sets of links provided. With types
■ Selection and ordering data
3TB50 to 3TB56 contactors
For screw fixing
Solenoid coil fitted with varistor
Size
Rated data
AC-2 and AC-3
Auxiliary
contacts1)
OperaRatings of
tional cur- induction motors
rent Ie at at
Version
400 V
230 V 400 V 500 V 690 V
A
kW
kW
kW
kW
Rated control
supply voltage
Us
DT Screw terminals
Order No.
NO
NC
V DC
PU
(UNIT,
SET, M)
PS*
PG
Weight
per PU
approx.
Price
per PU
kg
Contactors for switching AC voltage
DC operation · DC solenoid system
6
110
37
55
75
90
2
1
24
110
D
D
3TB50 17-0LB4
3TB50 17-0LF4
1
1
1 unit
1 unit
101
101
6.600
6.600
8
170
55
90
110
132
2
1
24
110
D
D
3TB52 17-0LB4
3TB52 17-0LF4
1
1
1 unit
1 unit
101
101
9.300
9.300
10
250
75
132
160
200
2
1
24
110
D
D
3TB54 17-0LB4
3TB54 17-0LF4
1
1
1 unit
1 unit
101
101
16.800
16.800
12
400
115
200
255
355
2
1
110
D
3TB56 17-0LF4
1
1 unit
101
19.800
1)
The number of auxiliary contacts cannot be increased.
* You can order this quantity or a multiple thereof.
3/64
Siemens LV 1 · 2010
© Siemens AG 2010
3RT, 3RH, 3TB, 3TC, 3TH, 3TK Contactors for Special Applications
Contactors with Extended Operating Range 0.7 ... 1.25 x Us, for Railway Applications
3TC contactors for switching DC voltage,
2-pole
EN 60947-4-1.
For requirements according to IEC 60077-1 and IEC 60077-2.
The contactors are finger-safe according to EN 50274 (exception: series resistor). Terminal covers may have to be fitted onto
the connecting bars, depending on the configuration with other
devices.
All specifications and technical specifications not mentioned
here are identical to those of the standard 3TC contactors.
Ambient temperature
The permissible ambient temperature for operation of the contactors (across the full operating range of the solenoid coil) is 50 to +70 °C. Uninterrupted duty at temperatures < -25 °C and
> +55 °C reduces the mechanical endurance, the current-carrying capacity of the conducting paths and the switching frequency.
At ambient temperatures > 55 °C, a distance of 10 mm must be
observed if contactor relays and size 1 and 2 contactors are
mounted side by side. There is no need to reduce the technical
specifications.
closed mounting parts and sets of links provided, while in the
case of the 3TC44 it must be mounted and wired between the
contactor poles. With types 3TC52 and 3TC56, the series resistor must be attached separately next to the contactors.
One NC of the auxiliary contacts is required for the series resistor
function. The selection and ordering data show the number of
additional, unassigned auxiliary contacts. It is not possible to extend the number of auxiliary contacts.
Reversing contactors
With the 3TC52 and 3TC56 contactors, the series resistor must
be connected using an additional K2 reversing contactor
(3RT13 17-1F.40). This contactor is automatically included in the
scope of supply in the same packaging as the contactor.
Dimensions
Attaching resistors and varistors increases the width of the contactors (see note on Dimensional Drawings, page 3/1).
■ Application
For operation in plants which are subject both to considerable
variations in the control voltage and to high ambient temperatures, e. g. in railway applications.
Series resistor
Control and auxiliary circuits
The DC solenoid systems of the 3TC contactors must be modified (to hold-in coil) by means of a series resistor. This series resistor is supplied separately packed with the contactors.
The solenoid coils of the contactors have an extended coil operating range from 0.7 to 1.25 x Us and are fitted as standard with
varistors to provide protection against overvoltage. The opening
delay is consequently 2 to 5 ms longer than for standard contactors.
With types 3TC48, the series resistor must be attached onto the
right-hand side of the auxiliary switch block by means of the en-
■ Selection and ordering data
3TC44: for screw and snap-on mounting onto 35 mm standard mounting rail
3TC48 to 3TC56: For screw fixing
Solenoid coil fitted with varistor
3TC48
Size
Utilization
categories
Rated op- Rated power
erational of loads
current Ie at
at
AuxilRated control DT Screw terminals
iary
supply voltcontacts age Us
1)
Version
750 V
220 V 440 V 600 V 750 V
A
kW
kW
PU
(UNIT,
SET,
M)
Order No.
kW
kW
NO NC V DC
PS*
PG
Weight
per PU
approx.
Price
per PU
kg
Contactors for switching DC voltage
DC operation · DC solenoid system
2
DC-1
DC-3/DC-5
32
7.5
7
5
14
9
19.2
9
24
4
2
1
24
110
B
C
3TC44 17-0LB4
3TC44 17-0LF4
1
1
1 unit
1 unit
101
101
1.380
1.380
4
DC-1
DC-3/DC-5
75
75
16.5
13
33
27
45
38
56
45
2
1
24
110
C
C
3TC48 17-0LB4
3TC48 17-0LF4
1
1
1 unit
1 unit
101
101
4.900
4.900
8
DC-1
DC-3/DC-5
170
170
48
41
97
82
132
110
165
110
2
1
24
110
C
C
3TC52 17-0LB4
3TC52 17-0LF4
1
1
1 unit
1 unit
101
101
10.800
10.800
12
DC-1
DC-3/DC-5
400
400
88
70
176
140
240
200
300
250
2
1
24
110
C
D
3TC56 17-0LB4
3TC56 17-0LF4
1
1
1 unit
1 unit
101
101
19.500
19.500
1)
The number of auxiliary contacts cannot be increased.
* You can order this quantity or a multiple thereof.
Siemens LV 1 · 2010
3/65
3
■ Overview
© Siemens AG 2010
3RT, 3RH, 3TB, 3TC, 3TH, 3TK Contactors for Special Applications
3TC Contactors for Switching DC Voltage
1- and 2-pole, 32 ... 400 A
■ Overview
■ Application
3TC4 and 3TC5
EN 60947-4-1 (VDE 0660 Part 102).
The contactors are finger-safe according to EN 50274.
3
Terminal covers may have to be fitted onto the connecting bars,
depending on the configuration with other devices.
The DC motor ratings given in the tables are applicable to the
DC-3 and DC-5 utilization categories with two-pole switching of
the load or with the two conducting paths of the contactor connected in series.
One contactor conducting path can switch full power up to
220 V. The ratings for higher voltages are available on request.
3TC7
EN 60947-4-1 (VDE 0660 Part 102).
The contactors are suitable for use in any climate. They are suitable for switching and controlling DC motors as well as all other
DC loads. The electromagnetic excitation is designed for a particularly wide coil operating range.
It is between 0.7 or 0.8 to 1.2 × Us.
3TC74 contactors can be used at up to 750 V/400 A and 50 Hz
in AC-1 operation.
3/66
Siemens LV 1 · 2010
The contactors are suitable for switching and controlling DC motors as well as all other DC circuits.
A version with an especially large coil operating range is available for operation in electrically driven vehicles and in switchgear with significant fluctuations in the actuating voltage (see
page 3/65).
© Siemens AG 2010
3RT, 3RH, 3TB, 3TC, 3TH, 3TK Contactors for Special Applications
3TC Contactors for Switching DC Voltage
1- and 2-pole, 32 ... 400 A
■ Selection and ordering data
Size
3TC48
3
3TC44
Rated data DC-3 and DC-51)
Operational current Ie3)
Ratings of
DC motors at
A
kW
Auxiliary
contacts2)
Rated control DT Screw terminals
supply voltage
Us
110 V 220 V 440 V 600 V 750 V Version
kW
kW
kW
kW
NO
NC
Order No.
PU
(UNIT,
SET,
M)
PS*
PG
Weight
per PU
approx.
Price
per PU
V
kg
3TC44 to 3TC56 two-pole contactors
DC operation
Screw and snap-on mounting onto TH 35 standard mounting rail
2
32
2.5
5
9
9
4
2
2
24 DC
110 DC
220 DC
}
}
}
3TC44 17-0AB4
3TC44 17-0AF4
3TC44 17-0AM4
1
1
1
1 unit
1 unit
1 unit
101
101
101
1.100
1.100
1.100
Screw fixing
4
75
6.5
13
27
38
45
2
2
24 DC
110 DC
220 DC
A
A
A
3TC48 17-0AB4
3TC48 17-0AF4
3TC48 17-0AM4
1
1
1
1 unit
1 unit
1 unit
101
101
101
4.700
4.700
4.700
8
2204)
20
41
82
110
110
2
2
24 DC
110 DC
220 DC
C
C
C
3TC52 17-0AB4
3TC52 17-0AF4
3TC52 17-0AM4
1
1
1
1 unit
1 unit
1 unit
101
101
101
10.800
10.800
10.800
12
400
35
70
140
200
250
2
2
24 DC
110 DC
220 DC
C
C
C
3TC56 17-0AB4
3TC56 17-0AF4
3TC56 17-0AM4
1
1
1
1 unit
1 unit
1 unit
101
101
101
19.500
19.500
19.500
AC operation, 50 Hz
Screw and snap-on mounting onto TH 35 standard mounting rail
2
32
2.5
5
9
9
4
2
2
220/230 AC5)
110/110 AC
}
}
3TC44 17-0BP0
3TC44 17-0BF0
1
1
1 unit
1 unit
101
101
0.700
0.700
Screw fixing
4
75
6.5
13
27
38
45
2
2
220/230 AC5)
110 AC
A
C
3TC48 17-0BP0
3TC48 17-0BF0
1
1
1 unit
1 unit
101
101
3.500
3.500
8
2204)
20
41
82
110
110
2
2
220/230 AC5)
110 AC
A
C
3TC52 17-0BP0
3TC52 17-0BF0
1
1
1 unit
1 unit
101
101
7.200
7.200
12
400
35
70
140
200
250
2
2
220/230 AC5)
110 AC
C
C
3TC56 17-0BP0
3TC56 17-0BF0
1
1
1 unit
1 unit
101
101
14.500
14.500
For more rated control supply voltages Us, see page 3/68.
1)
For the permissible load for utilization category DC-1, see note on Technical Information on page 3/1.
2)
The fitting of auxiliary switches cannot be altered on DC-operated contactors.
3)
The following rated operational currents are permitted for reversing duty
with 3TC44 to 3TC56 contactors:
Contactor Rated operational voltage
110 V, 220 V 440 V
Type
3TC44
3TC48
3TC52
3TC56
32 A
75 A
170 A
400 A
7A
75 A
170 A
400 A
4)
At > 600 V: Ie = 170 A.
5)
Operating range at 220 V: 0.85 to 1.15 x Us.
* You can order this quantity or a multiple thereof.
Siemens LV 1 · 2010
3/67
© Siemens AG 2010
3RT, 3RH, 3TB, 3TC, 3TH, 3TK Contactors for Special Applications
3TC Contactors for Switching DC Voltage
1- and 2-pole, 32 ... 400 A
3TC78
3
3TC74
Size
Rated data
DC-3 and DC-51)
AuxilRated coniary
trol supply
contacts voltage Us
2)
Operational
current
Ie
Ratings of
DC motors at
Version
A
kW
DT Screw terminals
Order No.
110 V 220 V 440 V 600 V 750 V 1200 V 1500 V
kW
kW
kW
kW
kW
kW
PU
(UNIT,
SET,
M)
PS*
PG
Weight
per PU
approx.
Price
per PU
kg
NO NC V
3TC74 1-pole contactors · Operational voltage up to 750 V
DC operation
12
400
35
70
140
200
250
--
--
4
4
24 DC
110 DC
C
C
3TC74 14-0EB
3TC74 14-0EF
1
1
1 unit
1 unit
101
101
10.800
10.800
70
140
200
250
--
--
4
4
230/220 AC3) C
3TC74 14-1CM
1
1 unit
101
10.800
AC operation, 50 Hz
12
400
35
3TC78 2-pole contactors · Operational voltage up to 1500 V
DC operation
12
400
35
70
140
200
250
400
500
4
4
24 DC
110 DC
C
C
3TC78 14-0EB
3TC78 14-0EF
1
1
1 unit
1 unit
101
101
22.500
22.500
70
140
200
250
400
500
4
4
230/220 AC3) C
3TC78 14-1CM
1
1 unit
101
23.800
AC operation, 50 Hz
12
400
35
For more rated control supply voltages Us see below.
For spare parts, see page 3/130.
1)
For the permissible load for utilization category DC-1, see note on Technical Information on page 3/1.
2)
The fitting of auxiliary switches cannot be altered on DC-operated contactors.
3)
Upper operating range limit at 230 V: 1.14 x Us.
Rated control supply voltages (the 10th and 11th position of the order number must be changed)
Contactor type
Rated control supply voltage Us
3TC44
3TC48
3TC52/56
3TC74/78
24 V AC
110 V AC
B0
F0
B0
F0
-F0
---
230/220 V AC
240 V AC
P01)
P01)
P01)
U0
U0
--
M2)
--
24 V AC
110 V AC
120 V AC
C2
G2
K2
----
----
----
220 V AC
230 V AC
N2
L2
---
---
---
24 V DC
48 V DC
60 V DC
B4
W4
E4
B4
W4
E4
B4
---
B
---
110 V DC
125 V DC
220 V DC
F4
G4
M4
F4
G4
M4
F4
-M4
F
-M
230 V DC
P4
P4
--
--
AC operation
Solenoid coils for 50 Hz
AC operation
Solenoid coils for 50/60 Hz
DC operation
1)
Operating range at 220 V or 380 V: 0.85 to 1.15 × Us;
lower operating range limit according to IEC 60947.
2)
Upper operating range limit at 230 V: 1.14 × Us.
* You can order this quantity or a multiple thereof.