Quick facts
►► Enables internal communication between the Super
WISE (Gateway) and room units (thermostats)
►► Manages 60 rooms per Super WISE Router
►► Used mainly in ventilation systems without zone
dampers
►► Can be centrally located in plant rooms or out in the
system
1
Super WISE Router
Technical description
Operation
The Super WISE Router is a communication unit designed
for internal communication between gateway (Super
WISE) and room level (WISE/CONDUCTOR)
Addressing and commissioning the system is made easier
by employing a logical tree structure, which automatically
puts the incorporated products on the correct level (via
Modbus Forwarding). In small ventilation systems where
zone control is not required, the Super WISE Router is
needed as a communication unit for the room controllers.
The Super WISE Router has no functions of its own, apart
from mediating communication between room level and
Super WISE.
For detailed information about the system design, see
also the product datasheet on Super WISE.
Super WISE (Optimisation of the pressure
in air handling units/Gateway/Web page)
Zone level
(CONTROL D/
Super WISE Router)
Mb1
Mb2
12
on
off
Room level
(WISE/CONDUCTOR)
Figure 1. Super WISE Router supersedes zone products in smaller ventilation systems, without requirement for zone control.
Zone level: blue line. Room level: red line.
2
Swegon reserves the right to alter specifications.
2012-06-08
www.swegon.com
Super WISE Router
Project Design
Connections
The Super WISE Router is well suited for use in smaller
ventilation systems in which zone control is not required,
for example a system involving one ventilation unit per
storey, or in a smaller building. Several Super WISE Routers can be subject to supervision of the same Super WISE
if it is desirable to divide room supervision into several
parts.
Commissioning
The Super WISE Router normally does not need to be
commissioned; requires only to be assigned a Modbus ID.
The Modbus ID is set to 1 on delivery, and is adjustable
via the hand-held thermostat (CONDUCTOR RU or TUNE
Control). For further information about addressing, see
the WISE Project Manual.
Installation
The Super WISE Router can be mounted directly on a wall,
in plant rooms or out in the system.
Normally only the power supply and communication for
internal Modbus communication between Super WISE
and room products are connected.
Connect to wiring terminals 5, 6 and 7 (Modbus loop 1)
on the Super WISE as well as 1, 2 and 3 (Modbus loop
2) on the room products. Connect the 24 V AC supply
voltage to terminals 23 and 24; see the wiring instructions
below.
Terminations Table
Pos. 1 Passive termination. Used when the product is
placed first or last on the loop and there is one
termination like Position 2 at the other end.
Pos. 2 Termination via internal pull-up resistor to
ensure correct 0 level. One of the loop ends
must be terminated in this way.
Pos. 3 Non-terminated. This setting is used on all units
that are not placed first or last on the loop.
Connection to room product,
Wiring terminals 1, 2 and 2
Connection to the Super WISE or
Router 2, 3 etc. Wiring terminals 5, 6 and 7



24 V AC

















Figure 2. Wiring diagram for the Super WISE Router
Swegon reserves the right to alter specifications.
2012-06-08
www.swegon.com
3
Super WISE Router



Super WISE Router
AWG24
A→5
B→6
C→7
Figure 3. Router for connection to the Super WISE.
4
Swegon reserves the right to alter specifications.
2012-06-08
www.swegon.com
Super WISE Router
Technical data
Designation: Super WISE Router
Storage temperature: -40 to + 80 ºC
Ordering key
Product
Operating temperature: -20 to + 50 ºC
Degree of protection: IP 32
IP 55 (with enclosure)
Dimensions: 121 × 193 × 44 mm
Power supply: 24 V AC ±10 %
Power consumption: 4.5 VA
Internal connections unit
Super WISE Router a
1 = Without enclosure
2 = With enclosure
Mounting: Mounting holes in enclosure or
to DIN rail
Connections: Wiring terminal for 2.5 mm² multicore cable
Data communication Modbus RTU
Wireless
communication: 433 MHz band radio modem with room thermostat
Modular contact: RJ12 6-pole for connecting up
to the room unit (thermostat)
Super WISE Router
Figure 4. Super WISE Router
Figure 5. Super WISE Router with enclosure
Swegon reserves the right to alter specifications.
2012-06-08
www.swegon.com
5
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertisement