6. FAULT FINDING
The following table provides a list of possible faults related to the sensor together with possible causes and remedies.
F a u l t
Sensor reads non zero all the time
Sensor reads non zero when no gas is present
Sensor reads low when gas is applied
Sensor reads high when gas is applied
Sensor reads zero when gas is applied
11
Quick Start Guide
MAN0622 Issue 01 January 03
2106M0523
SENSEPOINT HT
COMBUSTIBLE GAS SENSOR
Sensepoint HT
Combustible Gas Sensor
C a u s e / R e m e d y
Gas could be present, ensure there is no combustible gas in the atmosphere.
Adjust the control system zero setting.
Adjust the control system span setting.
Adjust the control system span setting.
1. Check the wiring.
2. Check that the protective disc has been removed from the filter housing.
3. Check that the filter is not dirty/obstructed.
4. Replace the sensor if poisoning is suspected.
total environmental solutions
7. CERTIFICATION
The following BASEEFA certification information is imprinted on adjacent faces in two separate blocks on the hexagonal part of the sensor body.
Manufacturer’s trademark & address
Product name
Identification number of ATEX notified body
CE mark
- conforms to all applicable European directives
Year of manufacture/ serial number
Certification number
Explosion protection mark and equipment group & category
Certification code
Caution
Certified ambient temperature range
12
1. INTRODUCTION
The Sensepoint High Temperature (HT) Combustible Gas Sensor is a sealed disposable sensor for the detection of flammable gases. It must be fitted into a suitably approved Exe or Exd high temperature junction box (e.g. Feel Flameproof
Enclosures) fitted with an approved cable gland for external wiring (e.g. Peppers
Cable Glands, Series A3LF or CR3 CROLOCK Series).
The sensor features a Filter Housing that retains a stainless steel mesh filter. It employs a catalytic pellistor sensor device which is used as part of a bridge measuring circuit.
Sensepoint HT is certified for hazardous areas to EN50014/EN50018 and is protected against water and dust ingress to IP66/67. The sensor is available in
M20, M25 and 3/4 NPT thread versions. The sensor accepts accessories from a specified range (see Accessories & Spare Parts).
Information notices
The types of information notices used throughout this handbook are as follows:
WARNINGS
Indicates hazardous or unsafe practice that could result in severe injury or death to personnel.
Caution: Indicates hazardous or unsafe practice which could result in minor injury to personnel, or product or property damage.
Note Provides useful/helpful/additional information.
If more information outside the scope of this technical handbook is required please contact Honeywell Analytics.
Associated Documents
Sensepoint Gas Sensors Technical Handbook Part No: 2106M0502
1
D i m e n s i o n s :
Operating temperature range:
Operating humidity range:
Operating pressure range:
W a r m u p it m e :
V o tl a g e r a n g e :
Power consumption:
S i g n a l o u t p u :t
Calibration flow rate:
P o i s o n i n g :
Expected operating life:
I P r a it n g :
C E :
ATEX Certification:
8. SPECIFICATIONS
S e e d i a section.
g r a m i n I n s t a ll a it o n
-40°C to +150°C.
20% to 90% RH continuous.
10% to 99% RH intermittent - non condensing.
75 to 110 k Pa.
L e s s t h a n 1 0 m i n u t e s .
2 .
9 V t o 3 .
5 V b ir d g e ( a t 2 0 0 m A ) .
700mW.
m V b ir d g e .
Recommended between 1 and
1.5 l/min.
T h e s e n s i n g e l e m e n t s m a y become inactive after extensive exposure to silicones, halogenated hydrocarbons, heavy metals or sulphur compounds.
5 years.
I P 6 5 s t a n d a r d ; I P 6
Weather Protection.
6 / 6 7 w ti h
T h e s e n s o r c o m p il e s relevant CE directives.
w ti h
II 2G EEx d II C T3
Tamb -40 o C to +150 o C
Baseefa02ATEX0242X
13
2. SAFETY
WARNINGS
1. This unit is intended for use at a normal, or reduced, levels of atmospheric oxygen and pressure only, i.e. less than 21% oxygen and less than 1.1 bar. Oxygen deficient atmospheres (less than
10%V/V) may suppress the sensor output.
2. Refer to local or national regulations relative to installation at the site. For Europe see EN50073 and EN60079-14.
3. Operators should be fully aware of the action to be taken if the gas concentration exceeds the alarm level.
4. Installation should consider not only the best placing for gas leakage related to potential leak points, gas characteristics and ventilation, but also where the potential of mechanical damage is minimized or avoided.
5. Only assessed for ATEX for ignition hazards.
CAUTIONS
1. Atmospheres above 100% LEL may suppress the sensor reading.
2. Do not modify or alter the sensor construction as essential safety requirements may be invalidated.
3. Install using suitably approved and certified Exe or Exd high temperature junction box, connectors and glands.
4. Dispose of in accordance with local disposal regulations.
Materials used - Stainless Steel.
2
9. ACCESSORIES & SPARE PARTS
D e s c r i p t i o n
Complete replacement sensor:
•
•
•
M
M
3 /
2
2
4
0
5 v e v
N P e
T r r s s i i v o n o n e r s i o n
S t a i n l e s s s t e e l if tl e r
F i tl e r H o u s i n g
High Temperature Junction Box
High Temperature Weather Protection
14
P a r t N u m b e r
2
2
2
1
1
1
0
0
0
6
6 B
6
B
B
2
2 3 1 1
2
3
3
1
1
0
2
0 0 7 8 0 F 0 0 1 8
0 0 7 8 0 C 0 0 3 8
2052D0001
00780-A-0076
MEMBERS OF THE ZELLWEGER ANALYTICS DIVISION
UK AND INTERNATIONAL
ENQUIRIES
Zellweger Analytics Ltd
Hatch Pond House
4 Stinsford Road
Nuffield Estate
Poole
Dorset
BH17 0RZ, UK
Tel:
Fax:
Email:
+44 (0)1202 676161
+44 (0)1202 678011 [email protected]
FRANCE
Zellweger Analytics France SA
Les Fermes Californiennes
62 avenue de l’Europe
Emerainville
77436 MARNE LA VALLEE
CEDEX 2
France
Tel:
Fax:
33 (1) 60 95 45 46
33 (1) 60 95 45 50
ASIA PACIFIC
Zellweger Analytics Ltd
Asia Pacific Regional Office
1 Scotts Road
#25-04 Shaw Centre
Singapore 228208
Tel:
Fax:
+65 6862 7701
+65 6862 3858
GERMANY
Zellweger Analytics GmbH
Sollner Strasse 65b
D-81479 Munchen
Germany
Tel:
Fax:
Email:
+49 89 791 920
+49 89 791 9243 [email protected]
NETHERLANDS
Zellweger Analytics BV
Postbus 157
NL-3740
AD Baarn
Tel:
Fax:
+31 (0)355435646
+31 (0)355435929
Email: [email protected]
SPAIN
Zellweger Analytics SA
Avda Remolar 31
08820 El Prat de Llobregat
Barcelona
Spain
Tel:
Fax:
Email:
+34 93 379 9611
+34 93 379 8551 [email protected]
Life Safety Distribution AG
BELGIUM
Zellweger Analytics NV
Leuvensesteenweg 392a
Chee de Louvain
Fax: +41 (0)44 943 4398
B-1932 Zaventem
Belgium
Tel:
Fax:
Email:
Sunrise, FL 33325
+32 27140311
+32 27140344 [email protected]
USA
Tel: +1 954 514 2700
Toll free: +1 800 538 0363
Fax: +1 954 514 2784 [email protected]
ITALY
Zellweger Analytics srl
Via F. Primaticcio 168
1-20147 Milano
Italy
Tel:
Fax:
Email:
+39 0248 3391
+39 0248 3023 14 [email protected]
MIDDLE EAST
Zellweger Analytics Limited
PO Box 52196
Dubai UAE
Tel:
Fax:
+971 4 3458 338
+971 4 3458 778
Email:[email protected]
USA
Zellweger Analytics, Inc.
5089 Bristol Industrial Way
Suite B & C
Buford, Georgia 30518
USA
Tel: +1 770 831 4800
Toll Free: +1 800 535 0606
Fax: +1 678 546 1954
Email: [email protected]
Asia Pacific
Honeywell Analytics Asia Pacific
#508, Kolon Science Valley (1)
187-10 Guro-Dong, Guro-Gu
Seoul, 152-050
Korea
Tel: +82 (0)2 2025 0307
Fax: +82 (0)2 2025 0329 [email protected]
Please Note:
While every effort has been made to ensure accuracy in this publication, no responsibility can be accepted for errors or omissions. Data may change, as well as legislation, and you are strongly advised to obtain copies of the most recently
This publication is not intended to form the basis of a contract, and the company reserves the right of a contract.
to amend the design and specification of the instruments without notice.
www.honeywell.com
Issue 1 12/2005
H_MAN0622Z_ 2106M0523_EMEA
07-07
© 2007 Honeywell Analytics A company of the Zellweger Luwa Group
3. INSTALLATION
The Sensepoint HT Combustible Gas Sensor must be fitted into a suitably approved Exe or Exd high temperature junction box fitted with an approved cable gland for external wiring. The sensor requires a
200mA current supply, nominal 3V, derived from a suitable control card.
Only a qualified installation engineer should install the sensor.
Install the sensor in a location free from direct heat sources and fit it so that it either points downwards or horizontally. It is not recommended that the sensor points upwards. See the Sensepoint Gas Sensors
Technical Handbook for installation in forced air conditions.
1. Isolate all associated power supplies and ensure that they remain
OFF during the installation procedure. Ensure a gas free atmosphere.
2. Install the high temperature junction box.
See the manufacturer’s instructions.
3. Remove the junction box lid.
4. Fit the Sensepoint HT sensor to the junction box.
Ensure that the junction box thread and the sensor thread are compatible. Push the sensor wires through the cable entry in the junction box and screw the sensor body firmly home into the entry.
Lock the sensor in place with a suitable lock-nut.
5. Connect the sensor wiring to the junction box terminal strip.
See the subsequent wiring diagram. Use multicore cable, three wire minimum, of conductor size 2.5mm
2 max.
6. Fit a suitable gland to the box, secure the control system cable and connect the field wiring to the terminal strip.
See the subsequent wiring diagram.
7. Refit the junction box lid.
8. Unscrew the filter housing from the sensor body and remove the filter from the filter housing.
Discard the filter housing with protective disc. The filter housing material cannot withstand high temperatures.
3
CALIBRATION
To calibrate the Sensepoint HT sensor carry out the following procedure:
1. Obtain the star rating for both the test gas and the gas to be detected from Table 1 .
2. Use the values in Table 2 to obtain the required meter setting when a 50% LEL test gas is applied to the detector.
If a sensor is to be used to detect a gas other than that for which it was calibrated, the required correction factor may be obtained from
Table 3 . The meter reading should be multiplied by this number in order to obtain the true gas concentration.
Important Notes:
1. Since combustible sensors require oxygen for correct operation, a mixture of gas in air should be used for calibration purposes.
2. Assuming an average sensor performance, the sensitivity information in Tables 1 to 3 is normally accurate to ± 20%.
Table 1 Star Rating of Gases
Gas
Acetone
Ammonia
Benzene
Butane 4*
Diethyl ether 4*
Ethane 6*
Ethanol 5*
Ethyl acetate 3*
Ethylene 5*
Star Rating Gas
4*
7*
3*
Hexane
Hydrogen
Methane
Octane
Propan-2-ol
Propane
3*
4*
5*
Styrene 2*
Tetra hydrafuran 4*
Xylene 2*
Star Rating
3*
6*
6*
S e n s o r w i r i n g
Green
Brown
Blue
White
INSTALLATION
C o n t r o l s y s t e wiring m if e l d
Earth
Sensitive (S)
Non-Sensitive (NS)
Common
Note: In addition to the sensor's integral earth conductor, earth equipotential bonding may be maintained via the sensor rear mounting thread if required.
9. If the sensor is installed:
• indoors - discard the filter.
• outdoors - fit the previously removed filter (if required) to the High Temperature Weather Protection accessory
(Part No: 00780-A-0076) and fit the accessory to the sensor.
Fit the seal supplied with the Weather Protection accessory to the sensor body. Screw the accessory firmly onto the sensor until it seats against the sensor body hexagon.
10. Power-up the system and check for correct operation.
4
CALIBRATION
Table 2 Meter Settings
4*
3*
2*
1*
8*
7*
6*
5*
* Calibration
Gas
-
-
-
* Rating of Gas to be Detected
8* 7* 6* 5* 4* 3* 2* 1*
50 62 76 95 -
40 50 61 76 96 -
-
33 41 50 62 78 98 -
-
-
26 33 40 50 63 79 100 -
21 26 32 40 50 63 80 -
-
-
-
-
-
21 26 32 40 50 64 81
25 31 39 50 64
25 31 39 50
Note: These settings must only be used with a calibration gas concentration of 50% LEL. All data at standard temperature and pressure.
Example
1. The target gas to be detected is Butane.
The calibration gas available is Methane (50% LEL).
2. Look up the star rating for each gas from Table 1:
Butane = 4* Methane = 6*
3. Check the meter settings for 50% LEL calibration gas from Table 2.
The reading is 78%.
4. The control card should therefore be set to 78%.
This gives an accurate reading for Butane, using 50% LEL Methane as a calibration gas.
125mm
58mm
42mm
INSTALLATION
High Temperature
Junction Box
Exe/Exd gland
Threads available:
M20, M25, 3/4 NPT
Certification data (on adjacent faces)
38mm across flats
Sensepoint
Temperature
High
Combustible
Gas Sensor 0-100%LEL
Filter
Filter Housing
4. CALIBRATION
Sensors should be calibrated at concentrations representative of those to be measured. It is always recommended that Sensepoint HT is calibrated with the target gas it is to detect. If this is not possible, then cross calibration can be used.
For calibration in fast flow conditions see the Sensepoint Gas Sensors
Technical Handbook.
Prior to calibration, allow the sensor to warm up for approximately
10 minutes. Re-calibration should only be attempted by qualified service personnel.
1. Zero the control system with no gas present on the sensor.
If combustible gas is suspected to be in the vicinity of Sensepoint HT flow clean air over the sensor using a flow housing (see below).
2. Fit a flow housing and connect a cylinder of either air, for a zero, or a known concentration of gas in air, at approximately the alarm point (e.g. 50% LEL), to the flow housing.
3. Pass the gas through the flow housing at a flow rate of approximately 1 litre to 1.5 litre/min.
4. Allow the sensor to stabilise.
5. When gassing with air, adjust the control card to indicate zero.
6. For span, the control card should be adjusted to indicate the concentration of the target gas being applied.
Remove the flow housing and the gas supply.
Cross Calibration Procedure
When calibrating the Sensepoint HT sensor with a gas which is different to the gas/vapour to be detected, the following cross calibration procedure should be followed.
Table 1 lists gases according to the reaction they produce at the detector.
An eight star (8*) gas produces the highest output while a one star (1*) gas produces the lowest output. (These are not applicable at ppm levels.)
5
CALIBRATION
Table 3 Meter Multiplication Factors
Unit calibrated to detect
5*
4*
3*
2*
1*
8*
7*
6*
8* 7*
Unit used to detect
6* 5* 4* 3* 2* 1*
1.00 1.24 1.52 1.89 2.37 2.98 3.78 4.83
0.81 1.00 1.23 1.53 1.92 2.40 3.05 3.90
0.66 0.81 1.00 1.24 1.56 1.96 2.49 3.17
0.53 0.66 0.80 1.00 1.25 1.58 2.00 2.55
0.42 0.52 0.64 0.80 1.00 1.26 1.60 2.03
0.34 0.42 0.51 0.64 0.80 1.00 1.27 1.62
0.26 0.33 0.40 0.50 0.63 0.79 1.00 1.28
0.21 0.26 0.32 0.39 0.49 0.62 0.78 1.00
6
5. MAINTENANCE
Only a qualified installation engineer should service the sensor. Ensure power is off before carrying out any maintenance procedures.
The only maintenance required is sensor replacement and filter changing
(if fitted to an accessory). To replace the complete sensor refer to the
Sensepoint Gas Sensors Technical Handbook. To replace the filter carry out the following procedure:
1. Remove the High Temperature Weather Protection accessory.
2. Remove the old filter and replace with a fresh filter.
3. Replace the Weather Protection accessory.
Ensure the Weather Protection seal is in place. Screw the accessory firmly onto the sensor until it seats against the sensor body hexagon.
7 8 9 10
Thank you for reading this data sheet.
For pricing or for further information, please contact us at our UK Office, using the details below.
UK Office
Keison Products,
P.O. Box 2124, Chelmsford, Essex, CM1 3UP, England.
Tel: +44 (0)1245 600560
Fax: +44 (0)1245 808399
Email:
Please note - Product designs and specifications are subject to change without notice. The user is responsible for determining the suitability of this product.