- Home
- Domestic appliances
- Large home appliances
- Water heaters & boilers
- Viessmann
- VITOPEND
- User manual
Viessmann VITODENS Operating Instructions Manual
Add to my manuals
36 Pages
Viessmann VITODENS: The compact, energy-efficient gas condensing boiler for heating your home and providing hot water. With its user-friendly control unit, the Vitotronic 100, you can easily adjust and monitor your heating system to ensure maximum comfort and energy savings. The VITODENS is equipped with a variety of features to meet your individual needs, including:
-
Automatic modulation: Continuously adjusts the boiler's output to match the heating demand, reducing energy consumption and lowering your heating bills.
-
Load-dependent control: Ensures that the boiler only operates when necessary, further saving energy and extending the lifespan of the boiler.
advertisement
Operating instructions
for the system user
VIESMANN
Heating system with the Vitotronic 100 control unit, type HC1B for constant temperature operation
VITODENS
VITOPEND
5592 683 GB 1/2011
Please keep safe.
2
Safety instructions
For your safety
Please follow these safety instructions closely to prevent accidents and material losses.
Safety instructions explained
Danger
This symbol warns against the risk of injury.
!
Please note
This symbol warns against the risk of material losses and environmental pollution.
Note
Details identified by the word "Note" contain additional information.
Target group
These operating instructions are for the heating system user.
This appliance is not designed to be used by persons (including children) with limited physical, sensory or mental capacities, or lacking experience and/or knowledge, unless they are supervised by a person responsible for their safety, or have received instructions from such a person as to how to use the appliance.
!
Please note
Children should be supervised.
Ensure that children never play with the appliance.
Danger
Incorrectly executed work on the heating system can lead to lifethreatening accidents.
■ Work on gas installations must only be carried out by a registered gas fitter.
■ Work on electrical equipment must only be carried out by a qualified electrician.
If you smell gas
Danger
Escaping gas can lead to explosions which may result in serious injury.
■ Do not smoke. Prevent naked flames and sparks. Do not switch lights or electrical appliances on or off.
■ Close the gas shut-off valve.
■ Open windows and doors.
■ Remove all people from the danger zone.
■ Notify your gas or electricity supplier and your local heating contractor from outside the building.
■ Shut off the electricity supply to the building from a safe place
(outside the building).
Safety instructions
For your safety
(cont.)
If you smell flue gas
Danger
Flue gas can lead to life-threatening poisoning.
■ Shut down the heating system.
■ Ventilate the boiler room.
■ Close all doors in the living space.
In case of fire
Danger
Fire creates the risk of burning and explosions.
■ Shut down the heating system.
■ Close the shut-off valves of the fuel lines.
■ Use a tested fire extinguisher, class ABC.
Boiler room requirements
!
Please note
Incorrect ambient conditions can lead to damage to the heating system and put the safe operation at risk.
■ Ensure ambient temperatures above 0 ºC and below 35 ºC.
■ Prevent air contamination by halogenated hydrocarbons
(e.g. as contained in paints, solvents or cleaning fluids) and excessive dust (e.g. through grinding/polishing work).
■ Avoid continuously high humidity levels (e.g. through frequent drying of washing).
■ Never close existing ventilation apertures.
Auxiliary components, spare and wearing parts
!
Please note
Components which are not tested with the heating system may lead to damage to the heating system, or may affect their various functions.
Installation or replacement work must only be carried out by qualified personnel.
3
Index
Index
■ Without frost protection monitoring (shutdown)................................................ 11
Setting the heating program (DHW heating)........................................................ 14
4
Index
Index
(cont.)
Maintenance........................................................................................................ 28
5
Introductory information
Commissioning
The commissioning and matching of the control unit to local conditions and building characteristics, as well as instructing the user in the operation of the system, must be carried out by your heating contractor.
As the user of new combustion equipment, you may be obliged to notify your local flue gas inspector of the installation
[check local regulations]. Your local flue gas inspector will also inform you [where appropriate] about work he may be required to carry out on your combustion equipment (e.g. regular checks, cleaning).
Your system is preset at the factory
The control unit is factory-set to " for central heating and DHW heating.
"
Your heating system is therefore ready for use:
Central heating
■ The rooms are heated in accordance with the settings on your control unit and room temperature control unit.
■ Your heating contractor can make further settings for you during commissioning.
You can change any settings individually at any time to suit your requirements (see chapter "Central heating").
DHW heating
■ The DHW is heated to 50 °C.
■ Your heating contractor can make further settings for you during commissioning.
You can change any settings individually at any time to suit your requirements (see chapter "DHW heating").
Frost protection
■ Your boiler and DHW cylinder are protected against frost.
Power failure
■ All data is saved if there is a power failure.
6
Introductory information
Terminology
To provide you with a better understanding of the functions of your control unit, the appendix contains the chapter "Ter-
Tips on saving energy
Utilise the setting options on the control unit and the room temperature control unit:
■ Never overheat your rooms. Every degree by which the room temperature is reduced saves up to 6 % on heating costs.
Never set your room temperature
higher than 20 °C (see page 12).
■ Never set the DHW temperature too
■ Select the heating program that meets your current requirements:
– In the summer, if you do not want to heat any rooms but require hot water, select the " " heating pro-
– If you do not want to heat any rooms and require no hot water for a prolonged period of time, select the
" " heating program (see
Further recommendations:
■ Correct ventilation/airing.
Briefly open windows fully and at the same time close the thermostatic radiator valves.
■ Close roller shutters (if installed) at dusk.
■ Set thermostatic valves correctly.
■ Never cover radiators or thermostatic valves.
■ Controlled DHW consumption: A shower generally uses less energy than a full bath.
7
8
Operation
Controls
You can change the settings for your heating system centrally at the programming unit of the control unit.
If you have a room temperature control unit installed in your rooms, you can also change the settings on the room temperature control unit.
Room temperature control unit operating instructions
Note
The programming unit can be placed in a wall mounting base. This is available as an accessory. Ask your heating contractor for more information.
s
4 8
°C
A
Takes you one step back in the menu
Cursor keys
To scroll in the menu or set values
OK Enables you to confirm your selections or setting
No function
Enables you to call up the menu for settings and scanning
Operation
How to use the controls
Standard display
4 8
°C
Press . This takes you to the menu for settings and scanning.
Symbols
These symbols are not always displayed, but appear subject to the system version and the operating state. Flashing displays indicate that modifications can be made.
Menu
Central heating
DHW heating
Information
Emissions test mode
Additional settings
Heating program
Frost protection monitoring
(standby mode)
DHW heating
Central heating and DHW heating
COMF Comfort mode for DHW heating
ECO
Without comfort mode for DHW heating
Messages
Service message
The service interval has expired
Fault message
Fault message for burner
Displays
Temperature
Frost protection monitoring
Central heating
Heating circuit pump running
Cylinder primary pump running
In conjunction with a solar thermal system:
Solar circuit pump is running
Burner running
Standard factory setting
9
Start-up/shutdown
Starting the heating system
A B C D s
4 8
°C
A
0
1 2 3
4 bar
E
A Fault indicator (red)
B ON indicator (green)
C Reset button
1. Check the heating system pressure at the pressure gauge. The system pressure is too low if the indicator points to the area below 1.0 bar. In this case, top up with water or notify your local heating contractor.
2. For open flue operation:
Check that the ventilation apertures of the installation room are open and unrestricted.
Note
With open flue operation, the combustion air is drawn from the installation room.
3. Open the gas shut-off valve.
Note
Ask your heating contractor to explain the positioning and handling of these components.
10
D ON/OFF switch
E Pressure gauge
4. Switch ON the power supply, e.g. at a separate MCB/fuse or a mains isolator.
5. Turn the ON/OFF switch " " ON.
After a short time, the standard display appears and the green ON indicator illuminates. Your heating system and room temperature control unit are now ready for operation.
Start-up/shutdown
Shutting down the heating system
With frost protection monitoring
Select heating program " " for frost protection monitoring (standby mode).
Terminating heating program " "
Select another heating program.
Press the following keys:
Press the following keys:
1.
for settings; " " flashes.
1.
for settings; " " flashes.
2. OK to confirm; " " flashes.
2. OK to confirm; " " flashes.
3. OK to confirm; " " flashes.
3. OK to confirm; " " flashes.
4.
until " " flashes.
5. OK to confirm; frost protection monitoring is activated.
■ No central heating.
■ No DHW heating.
■ Frost protection for the boiler and the
DHW cylinder is enabled.
4.
until " " flashes: The rooms are heated and DHW is provided.
or until " " flashes: DHW is heated but central heating is not active.
Note
The circulation pumps are briefly started every 24 hours to prevent them from seizing up.
5. OK to confirm; the selected heating program is activated.
Without frost protection monitoring (shutdown)
1. Switch the ON/OFF switch " "
OFF.
2. Close the gas shut-off valve.
Note
Ask your heating contractor to explain the positioning and handling of these components.
3. Isolate the heating system from its main power supply, e.g. at a separate
MCB/fuse or a mains isolator.
4. Where outside temperatures of below 3 °C are anticipated, please take suitable measures to protect the heating system against frost. If necessary, contact your heating contractor.
11
Central heating
Required settings for central heating
If you want central heating, check the following points:
■ Have you set the required room temperature?
Room temperature control unit operating instructions
■ Have you set the heating flow temperature at a sufficiently high level?
For settings, see the next chapter.
■ Have you set the correct heating program?
and
Room temperature control unit operating instructions
■ Have you set the required time program?
Room temperature control unit operating instructions
Setting the heating flow temperature
Set the heating flow temperature sufficiently high so the required room temperature can be achieved.
Factory setting: 74 °C
Press the following keys:
1.
for settings; " " flashes.
2. OK to confirm; " " flashes.
3.
for boiler water temperature;
" " flashes.
4. OK to confirm; the selected temperature value flashes.
5. / for the required boiler water temperature.
6. OK to confirm; the new temperature value is saved.
Setting the heating program (central heating)
Factory setting: " " for central heating and DHW heating (winter mode).
Press the following keys:
1.
for settings; " " flashes.
2. OK to confirm; "
3. OK to confirm.
" flashes.
4. / until " " flashes.
5. OK to confirm; the rooms are heated and DHW is provided.
12
Stopping the central heating
You do not want to heat any rooms but you want to heat the DHW.
Press the following keys:
1.
for settings; " " flashes.
2. OK to confirm; "
3. OK to confirm; "
" flashes.
" flashes.
4.
until " " flashes.
5. OK to confirm; the central heating is deactivated and DHW is heated
(summer mode).
You do not want to heat any rooms or
DHW.
Press the following keys:
1.
for settings; " " flashes.
2. OK to confirm; "
3. OK to confirm; "
" flashes.
" flashes.
4.
until " " flashes.
5. OK to confirm; the central heating and DHW heating are deactivated, frost protection monitoring is activated (standby mode).
Central heating
13
DHW heating
Required settings (DHW heating)
If you want DHW heating, check the following points:
■ Have you set the required DHW temperature?
For settings, see the next chapter.
■ Have you set the correct heating program?
Setting the DHW temperature
1.
2.
Factory setting: 50 °C
Press the following keys: for settings; " for " ".
" flashes.
3. OK to confirm; temperature value flashes.
4. / for required DHW temperature.
5. OK to confirm; the new temperature value is saved.
Setting the heating program (DHW heating)
Factory setting: " " for central heating and DHW heating (winter mode).
Press the following keys:
1.
for settings; " " flashes.
2. OK to confirm; "
3. OK to confirm; "
" flashes.
" flashes.
4. / until " " flashes for DHW heating (summer mode, no central heating) or until " " flashes for central heating and DHW heating (winter mode).
5. OK to confirm; the selected heating program is activated.
14
DHW heating
Stopping the DHW heating
You do not want DHW, but do want to heat the rooms.
Press the following keys:
1.
for settings; " " flashes.
2. OK to confirm; " " flashes.
3. OK to confirm; " " flashes.
4.
until " " flashes.
5. OK to confirm; the rooms are heated and DHW is provided
(winter mode).
6.
7.
for settings; " for " ".
" flashes.
8. OK to confirm; temperature value flashes.
9.
to 10 °C.
10. OK to confirm; the new temperature value is saved.
You do not want to have DHW or heat your rooms.
Press the following keys:
1.
for settings; " " flashes.
2. OK to confirm; " " flashes.
3. OK to confirm; " " flashes.
4.
until " " flashes.
5. OK to confirm; DHW heating and central heating are stopped, frost protection monitoring is activated (standby mode).
Comfort function (if available)
With the comfort function you can preheat the water volume in the plate heat exchanger to the selected DHW temperature. This makes DHW available immediately.
Press the following keys:
1.
for settings; " " flashes.
2.
for " ".
3. OK to confirm, "COMF ECO" flashes.
4. OK to confirm; "ECO" flashes.
5.
for "COMF".
6. OK to confirm; the comfort function is activated.
15
DHW heating
Comfort function (if available)
(cont.)
1.
2.
Ending the comfort function
Press the following keys: for settings; " for " ".
" flashes.
3. OK to confirm, "COMF ECO" flashes.
4. OK to confirm; "COMF" flashes.
5.
for "ECO".
6. OK to confirm; the comfort function is terminated.
16
Further adjustments
Setting the temperature unit (°C/°F)
1.
2.
Factory setting: °C
Press the following keys: for settings; " " flashes.
for " ".
3. OK to confirm; " " flashes.
4. / for required temperature unit
("°C" or "°F").
5. OK to confirm; the new temperature unit is saved.
Restoring factory settings
You can simultaneously reset all changed values to the factory settings.
Press the following keys:
1.
for settings; " " flashes.
2.
for " ".
3. OK to confirm; " " flashes.
4. OK to confirm; the factory setting is reinstated.
Factory settings:
■ Heating program: "
■ Temperature unit: °C
"
■ Boiler water temperature: 74 °C
■ DHW temperature: 50 °C
17
18
Scanning
Scanning information
2.
for " ".
3. OK to confirm.
6. OK to confirm; the value is reset.
Subject to the connected components and settings made, you can scan current temperatures and operating conditions.
Press the following keys:
1.
for settings; " " flashes.
Example:
On the display, you can see the number
"3" which shows the boiler water temperature. The current boiler water temperature is 65 °C.
¸
3 6 5
°C
4. / for the required information.
5. OK to confirm; if you want to reset the value to "0" (see following table), " " flashes.
Note
The scan mode terminates automatically after 30 min or if you press .
3
5
The information appears in the following sequence:
Display Explanation Notes
0 0 Boiler number Displayed only on multi boiler systems.
1
5
□
15 °C Outside temperature Displayed only if an outside temperature sensor is connected.
65 °C Boiler water temperature --
50 °C DHW temperature Displayed only if a DHW cylinder is connected.
45 °C DHW temperature with solar operation
Displayed only if a solar thermal system is connected.
53
54
6
50 °C Temperature sensor / Displayed only if the Viessmann solar control module is available and a third temperature sensor has been connected.
50 °C Temperature sensor aÖ Displayed only if the Viessmann
70 °C Collector temperature solar control module is available and a fourth temperature sensor has been connected.
Displayed only if a solar thermal system is connected.
Scanning
Scanning information
(cont.)
Display
1
0 0 1 4 2 5
6
7
8
2 6 3 5 7 2
0 3 0 5 2 9
3
5
9
Burner starts
0 0 1 4 1 7 h Solar circuit pump hours run
0 0 0 5 0 6 h Hours run, output 22
0 0 0 5 0 6 Pump starts, output 22
0 0 2 8 5 0 h
Explanation
Burner hours run
Pump starts, solar circuit pump
Solar yield in kWh
Notes
Number of hours run (only approximate values).
The hours run can be reset to "0" by pressing "D".
The number of burner starts can be reset to "0" by pressing "D".
Displayed only if a Viessmann solar control module is installed.
The hours run can be reset to "0" by pressing "D".
Displayed only if a Viessmann solar control module is installed.
The pump starts can be reset to
"0" by pressing "D".
Displayed only if the Viessmann solar control module is available and a second circulation pump has been connected.
The hours run can be reset to "0" by pressing "D".
Displayed only if the Viessmann solar control module is available and a second circulation pump has been connected.
The pump starts can be reset to
"0" by pressing "D".
Displayed only if a Viessmann solar control module is installed.
The solar energy can be reset to
"0" by pressing "D".
Scanning the service messages
Your heating contractor can set a service interval. For example, burner service after 2500 hours run or service after 12 months.
If your heating system is due for a service, the symbol " " flashes on the display and the expired service interval is shown.
19
Scanning
Scanning the service messages
(cont.)
Example:
Service display with the service interval of 2500 hours run by the burner:
ë
2 5 0 0 h
Service display with the service interval of 12 months:
1
ë u
2
Notify your local heating contractor and acknowledge the service message by pressing OK.
Note
If the service can only be carried out at a later point in time, the service message will reappear after 7 days.
Calling up an acknowledged service message
Press OK for approx. 4 s.
20
Scanning fault messages
If any faults have occurred in your heating system, the symbol " " flashes on the display and the fault code is shown.
In addition, the red fault indicator flashes
Example:
Fault code shown: "50"
ã
1 5 0
1. Notify your heating contractor of the fault code. This enables the heating contractor to be better prepared for the service call and may save additional travelling costs.
Scanning fault messages
(cont.)
2. Acknowledge the fault message with
OK. The symbol " " no longer flashes.
Note
■ If you have connected up signalling equipment (e.g. an alarm) for fault messages, this is deactivated when the fault message is acknowledged.
■ If the fault can only be fixed at a later point in time, the fault message will reappear the following day.
Calling up an acknowledged fault message
Press OK for approx. 4 s.
Note
If there are several fault messages, you can scan these in sequence by pressing
/ .
Scanning
21
22
Multi boiler systems
Special considerations for multi boiler systems
In systems with several boilers (multi boiler systems), each boiler is equipped with its own control unit. These control units are regulated by a higher control unit. Make the required settings (e.g.
room temperature) at the higher control unit.
Operating instructions of the higher control unit
Boiler number
In multi boiler systems, each boiler control unit indicates the boiler number on the standard display.
Example:
Boiler number "3"
Heating program
■ " " for frost protection monitoring
(standby mode):
By selecting the heating program " " you individually shut down the respective boiler.
Boiler frost protection monitoring is active.
■ " " for DHW heating (summer mode):
You cannot change the " " heating program.
Room temperature/boiler water temperature
You cannot select either room temperature or boiler water temperature.
3
4 8
°C
Boiler number "3" has been blocked by the higher control unit.
3 0
Emissions test mode
Emissions test mode
Emissions test mode should only be activated by your flue gas inspector during the annual inspection.
Press the following keys:
1.
for settings; " " flashes.
2.
for " ".
3. OK to confirm; "ON" flashes.
4. OK to confirm; "ON" is shown constantly.
Stopping emissions test mode
Press the following keys:
1.
for settings; " " flashes.
2.
for " ".
3. OK to confirm; "OFF" flashes.
4. OK to confirm.
Note
Emissions test mode also ends automatically after 30 min.
23
What to do if...
Rooms are too cold
Cause
The heating system is off.
Control unit or room temperature control unit incorrectly adjusted.
Remedy
■ Switch the ON/OFF switch " " ON
■ Switch ON the mains isolator, if installed (outside the boiler room).
■ Reset the MCB in the power distribution board (main domestic MCB).
Check settings and correct if required:
■ " " has to be adjusted (see
■ Room temperature or boiler water tem-
■ Time program
Only when operating with DHW heating:
DHW priority is enabled (" " is displayed).
No fuel.
Symbol " " is shown on the display.
Symbol " " is shown on the display.
Room temperature control unit operating instructions
Wait until the DHW cylinder has been heated up (" " symbol extinguishes).
In the case of operation with an instantaneous water heater, stop DHW draw-off.
With LPG:
Check the fuel reserves and re-order if required.
With natural gas:
Open the gas shut-off valve. If necessary, check with your gas supply utility.
Press "R" (see diagram on page 10).
Acknowledge the fault message with OK
Notify your heating contractor of the fault code if the fault reoccurs.
Notify your heating contractor of the fault code.
Acknowledge the fault message with OK
24
What to do if...
Rooms are too hot
Cause
Control unit or room temperature control unit incorrectly adjusted.
Remedy
Check settings and correct if required:
■ Room temperature or boiler water tem-
■ Time program
Room temperature control unit operating instructions
The " " symbol is shown on the display. Notify your heating contractor of the fault code.
Acknowledge the fault message with OK
There is no hot water
Cause
The heating system is off.
Control unit incorrectly adjusted.
No fuel.
Remedy
■ Switch the ON/OFF switch " " (see
■ Switch ON the mains isolator, if installed (outside the boiler room).
■ Reset the MCB in the power distribution board (main domestic MCB).
Check settings and correct if required:
■ DHW heating must be enabled (see
■ DHW temperature (see page 14).
With LPG:
Check the fuel reserves and re-order if required.
With natural gas:
Open the gas shut-off valve. If necessary, check with your gas supply utility.
25
What to do if...
There is no hot water
(cont.)
Cause
The " " symbol is shown on the display.
The " " symbol is shown on the display.
Remedy
Press "R" (see diagram on page 10).
Acknowledge the fault message with OK
Notify your heating contractor of the fault code if the fault reoccurs.
Notify your heating contractor of the fault code.
Acknowledge the fault message with OK
The DHW is too hot
Cause Remedy
The control unit is incorrectly adjusted.
Check and correct the DHW temperature
"ã" flashes on the display
Cause
Heating system fault.
Remedy
Notify your heating contractor of the fault code.
Acknowledge the fault message with OK
"E" flashes on the display
Cause
Heating system fault.
Remedy
Press "R" (see diagram on page 10).
Acknowledge the fault message with OK
Notify your heating contractor of the fault code if the fault reoccurs.
26
What to do if...
"ë" flashes on the display
Cause
The time for a service, as specified by your heating contractor, has arrived.
Remedy
Notify your local heating contractor and acknowledge the service message with
27
Maintenance
Maintenance
Cleaning
All equipment can be cleaned with a commercially available domestic cleaning agent (non-scouring).
Inspection and maintenance
Inspection and maintenance of your heating system is prescribed by the
Energy Savings Order and DIN 4755,
DVGW-TRGI 2008 and DIN 1988-8.
Regular maintenance ensures troublefree, energy efficient, environmentally responsible and safe heating. Your heating system must be serviced by an authorised contractor at least every
2 years. For this, we strongly advise you to arrange an inspection and maintenance contract with your local heating contractor.
Boiler
Increasing boiler contamination raises the flue gas temperature and thereby increases energy losses. All boilers should therefore be cleaned annually.
DHW cylinder (if installed)
The DIN 1988-8 and EN 806 specify that maintenance and cleaning should be carried out no later than two years after commissioning and thereafter as required.
Only a qualified heating contractor should clean the inside of a DHW cylinder and the DHW connections.
You can clean the front of the programming unit with a microfibre cloth.
Refill any water treatment equipment
(e.g. a lock or injection system) in good time, if such equipment is installed in the cold water supply of the DHW cylinder.
In this connection, observe the manufacturer's instructions.
Additionally for a Vitocell 100:
We recommend that the correct function of the sacrificial anode is checked annually by your heating contractor.
The anode function can be checked without interrupting the system operation.
The heating contractor will check the earth current with an anode tester.
Safety valve (DHW cylinder)
The safety valve function should be checked every six months by venting, either by the system user or the local heating contractor. The valve seat may become contaminated (see the valve manufacturer's instructions).
Potable water filter (if installed)
To maintain high hygiene standards, proceed as follows:
■ Replace filter element on non-back flushing filters every six months (visual inspection every two months).
■ On back flushing filters, back flush every two months.
28
Terminology
Constant temperature operation
In constant temperature operation, the heating water is constantly heated to the selected boiler water temperature.
Heating program
The heating program determines whether you heat your rooms and DHW, or only heat DHW, or whether you shut down your heating system with frost protection monitoring.
You can select the following heating programs:
■ "
"
The rooms are heated and DHW is provided (winter mode).
■ " "
DHW is provided but there is no central heating (summer mode).
■ " "
Frost protection for the boiler and
DHW cylinder is active, no central heating, no DHW heating (standby mode).
Note
A heating program for central heating without DHW heating is not available. If rooms are to be heated, hot water is generally also required (winter mode).
If you still only want central heating, select the " " heating program and set the DHW temperature to 10 °C (see
page 15). This means that you will not
heat DHW unnecessarily but the DHW cylinder is protected against frost.
Heating circuit
A heating circuit is a sealed circuit between the boiler and radiators, in which the heating water circulates.
Heating circuit pump
Circulation pump for the circulation of the heating water in the heating circuit.
Actual temperature
Current temperature at the time of the scan; e.g. actual DHW temperature.
Boiler water temperature
See "Constant temperature operation".
Open flue operation
The combustion air is drawn from the room where the boiler is installed.
Balanced flue operation
The combustion air is drawn from outside the building.
Safety valve
A safety device that must be installed by your heating contractor in the cold water pipe. The safety valve opens automatically to prevent excess pressure in the
DHW cylinder.
Set temperature
Default temperature that should be reached; e.g. set DHW temperature.
29
Terminology
(cont.)
Summer mode
Heating program " ".
At warmer times of the year, i.e. when the rooms do not have to be heated, you can stop heating mode. The boiler remains enabled for DHW heating.
Cylinder primary pump
Circulation pump for heating the DHW in the DHW cylinder.
Potable water filter
A device that removes solids from the water. The potable water filter is installed in the cold water pipe upstream of the
DHW cylinder or the instantaneous water heater.
30
Keyword index
Keyword index
A
Actual temperature.............................29
Additional settings
■ Symbol..............................................9
B
Balanced flue operation.....................29
Boiler number.....................................22
Boiler water temperature
■ Setting............................................12
Burner
■ Symbol..............................................9
C
Central heating
■ Factory setting..................................6
■ Heating mode symbol.......................9
■ Heating program.............................12
■ Heating program symbol..................9
■ Required settings............................12
■ Room temperature..........................12
■ Stopping.........................................13
■ Symbol menu....................................9
Cleaning.............................................28
Cleaning information..........................28
Cold rooms.........................................24
Comfort function
■ Activating........................................15
■ Ending............................................16
Comfort mode
■ Symbol..............................................9
Commissioning..............................6, 10
Constant temperature operation........29
Controls................................................8
Cylinder primary pump
■ Symbol..............................................9
D
DHW heating........................................6
■ DHW temperature...........................14
■ Factory setting..................................6
■ Heating program.............................14
■ Required settings............................14
■ Stopping.........................................15
■ Symbol..............................................9
DHW temperature
■ Setting............................................14
E
Emissions test mode
■ Symbol..............................................9
Ending
■ DHW heating..................................15
Energy saving function.......................16
F
Factory setting.....................................6
■ Symbol..............................................9
Fault
■ ã..............................................24, 26
■ E..............................................24, 26
Fault indicator....................................10
Fault message
■ Acknowledging...............................20
■ Calling up (acknowledged).............21
■ Scanning.........................................20
■ Symbol..............................................9
Filter...................................................30
Frost protection
■ Factory setting..................................6
Frost protection monitoring
■ Heating program symbol..................9
■ Symbol..............................................9
H
Heating
■ Without DHW heating.....................15
Heating and hot water..........................6
Heating circuit....................................29
31
Keyword index
Keyword index
(cont.)
Heating circuit pump
■ Symbol..............................................9
Heating flow temperature...................12
Heating mode
■ Setting............................................12
Heating only.......................................15
Heating operation
■ Constant temperature.....................29
Heating program
■ DHW heating..................................14
■ For central heating..........................12
■ Multi boiler system..........................22
■ Symbol..............................................9
Heating system
■ Shutting down.................................11
■ Starting...........................................10
Hot water............................................26
How to use the controls.......................9
I
Information
■ Scanning.........................................18
■ Symbol..............................................9
Inspection...........................................28
M
Maintenance......................................28
Maintenance contract.........................28
Menu....................................................9
Multi boiler systems
■ Boiler number.................................22
■ Boiler water temperature................22
■ Heating program.............................22
■ Room temperature..........................22
■ Special considerations....................22
N
No hot water.......................................25
Notice of completion............................6
O
ON/OFF switch............................10, 11
ON indicator.......................................10
32
Open flue operation...........................29
Operation.............................................8
■ Controls............................................8
■ How to use the controls....................9
P
Potable water filter.............................30
Power failure........................................6
Pressure display................................10
Pressure gauge..................................10
Programming unit.................................8
Pump
■ Cylinder..........................................30
■ Heating circuit.................................29
R
Remote control.....................................8
Reset
■ Symbol..............................................9
Resetting burner starts.......................18
Resetting data....................................18
Resetting fuel consumption................18
Resetting hours run............................18
Restoring factory settings..................17
Rooms too cold..................................24
Rooms too warm................................25
Room temperature
■ Setting............................................12
■ With room temperature control unit 12
Room temperature control unit............8
S
Safety valve.......................................29
Saving energy
■ Tips...................................................7
Scan
■ Fault message................................20
■ Information......................................18
■ Operating conditions.......................18
■ Service message............................19
■ Temperatures.................................18
Scanning operating conditions...........18
Scanning the actual temperature.......18
Keyword index
Keyword index
(cont.)
Service
■ ë....................................................27
Service interval hours run
■ Symbol..............................................9
Service message
■ Acknowledging...............................19
■ Calling up (acknowledged).............20
■ Scanning.........................................19
■ Symbol..............................................9
Set temperature.................................29
Settings
■ For central heating..........................12
■ For DHW heating............................14
Shutdown...........................................11
Shutting down
■ Heating system with frost protection monitoring.......................................11
■ Heating system without frost protection monitoring................................11
Shutting down the heating system.....11
Standard display..................................9
Standard settings...............................17
Standby mode
■ Symbol..............................................9
Starting
■ Comfort function.............................15
■ Energy saving function...................16
■ Frost protection monitoring.............11
■ Heating system...............................10
■ Standby mode..........................11, 13
■ Summer mode................................13
Starting the appliance........................10
Stopping
■ Central heating...............................13
■ DHW heating..................................15
Summer mode.......................13, 29, 30
Symbols...............................................9
T
Temperature
■ Actual temperature.........................29
■ Boiler water.....................................29
■ DHW...............................................14
■ Multi boiler system..........................22
■ Room temperature..........................12
■ Scanning.........................................18
■ Set temperature..............................29
■ Symbol..............................................9
Temperature unit................................17
Terminology.......................................29
Test mode..........................................23
Troubleshooting
■ ........................................................24
W
Warm rooms......................................25
Water too cold....................................25
Water too hot.....................................26
Where to find the controls....................8
Winter mode.......................................29
33
34
35
Your contact
Contact your local contractor if you have any questions regarding the maintenance and repair of your system. You may, for example, find local contractors on the internet under www.viessmann.com.
Viessmann Werke GmbH&Co KG
D-35107 Allendorf
Telephone: +49 6452 70-0
Fax: +49 6452 70-2780 www.viessmann.com
Viessmann Limited
Hortonwood 30, Telford
Shropshire, TF1 7YP, GB
Telephone: +44 1952 675000
Fax: +44 1952 675040
E-mail: [email protected]
36
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement
Table of contents
- 10 Starting the heating system
- 11 Shutting down the heating system
- 11 ■ With frost protection monitoring
- 11 ■ Without frost protection monitoring (shutdown)
- 12 Required settings for central heating
- 12 Setting the heating flow temperature
- 12 Setting the heating program (central heating)
- 13 Stopping the central heating
- 14 Required settings (DHW heating)
- 14 Setting the DHW temperature
- 14 Setting the heating program (DHW heating)
- 15 Stopping the DHW heating
- 15 Comfort function (if available)
- 17 Setting the temperature unit (°C/°F)
- 17 Restoring factory settings
- 18 Scanning information
- 19 Scanning the service messages
- 20 Scanning fault messages
- 22 Special considerations for multi boiler systems
- 23 Emissions test mode
- 24 Rooms are too cold
- 25 Rooms are too hot
- 25 There is no hot water
- 26 The DHW is too hot
- 26 "ã" flashes on the display
- 26 "E" flashes on the display
- 27 "ë" flashes on the display
- 28 Maintenance
- 31 Keyword index