ENTES EPM 07S digital powermeter User manual
Below you will find brief information for digital powermeter EPM 07S. The EPM 07S digital powermeter is a 3-phase device designed for measuring voltage, current, power, energy, and power factor. It features a Modbus communication protocol for data transfer and a user-friendly interface for setting up parameters. Additionally, it provides energy pulse outputs for integration with external systems, demand monitoring, and maximum demand recording.
PDF
Download
Document
Advertisement
Advertisement
DIGITAL POWERMETER DIGITAL POWERMETER EPM-07S EPM-07S EPM-07S DIGITAL POWERMETER FUNCTIONS OF BUTTONS When W led lights,it shows max.power values which are measured instantaneously and it shows total average demand values. Also it is used for moving upwards in the menu. When W led lights,it shows min.power values which are measured instantaneously and it shows total average demand values. Also it is used for moving downwards in the menu. It is used for passing between parameters such as VL-N, VL-L, A, W, VAr, VA, kWh, kVArh, cosj. When it is pressed for 5 seconds, adjustment mode is entered. In the adjustment mode it is used for saving parameters and moving to the sub menu. In the adjustment mode, it is used for entering to the upper menu or it is used to quit from the adjustment mode without saving the values. EPM-07S is a 3-phase digital powermeter and energymeter which measures: -Phase-Neutral voltage (VL-N) -Active Power (W) -Active Energy (kWh) -Phase-Phase voltage (VL-L) -Reactive Power (VAr) -Reactive Energy (kVArh) -Current (A) -Apparent Power (VA) -Cosj These values are displayed by using SET button ( ) First 3 displays show L1, L2 and L3 phase values and the 4th display shows total value of each selected measured value ( V L - N , V L - L , A, W, VAr, VA, kWh, kVArh or Cosj). EPM-07S also measures Maximum Demand, Demand, maximum and minimum values of power. EPM-07S has MODBUS serial interface. When : 1. VL-N led lights 2. VL-L led lights 3. A led lights 4. W led lights 5. VAr led lights 6. VA led lights 7. kWh led lights a-) A-I b-) A-E 8. KVArh led lights a-) r-L b-) r-C 9. Cosj led lights : Phase-Neutral Voltage : Phase-Phase Voltage : Current : Active Power : Reactive Power : Apparent Power : : Imported Active Energy : Exported Active Energy : : Reactive-Inductive Energy : Reactive-Capacitive Energy : Cosj of the network is measured. Current Transformer Ratio Setup In this menu, current transformer ratio is adjusted. Note: If the current transformer is not used between the system and EPM-07S, current transformer ratio is entered as 1. Example: ; If a current transformer which has a ratio of 250/5A is used between the system and EPM-07S; Current transformer ratio is entered as = 250/5 = 50 . Press SET button 5 seconds (Ctr menu is displayed) Operating Principle: Press SET button (The number which is the last digit of second display blinks) EPM-07S displays the energy and power values by multiplying voltage and current ratios by values read from input. So, the displayed values are the real values of the system. By using UP-DOWN buttons enter to the first digit of desired value. Energy Pulse Outputs EPM-07S has 2 Energy Pulse Outputs; Pul1, Pul2. Pul1 (Reactive Energy Pulse Output): A 400msec. pulse output is given, if measured energymeter value increases 1 KVArh. Pul1 is used for Reactive Inductive energy values. Pul2 (Active Energy Pulse Output): A 400msec. pulse output is given, if measured energy meter value increases 1KWh. Pul2 is used for both (Active Import) and (Active Export) energy values. Min. pulse period is 1.6 sec. Press SET button (First number of the third display blinks). If you did not enter the fourth digit correct, you can reentry by pressing the ESC button. 000 By using UP-DOWN buttons, enter to the third digit of desired value. Demand and Maximum Demand Demand is average of power for the demand time. Demand time can be changed between 1-60 minutes. Maximum demand is the max. value of the average power values measured during demand time. If the new average value exceeds the maximum demand value, the new demand value is recorded as maximum demand. Press SET button (The number which is in the middle of the third display blinks. If you did not enter the third digit correct, you can reentry by pressing the ESC button. By using UP-DOWN buttons, enter to the second digit of desired value Watching of Min.,Max. and Demand Values: Min. and Max. values are defined for Active Power (W),reactive power (VAr) and apparent power (VA). Demand values are defined for total active power (SW),total reactive power (SVAr) and total apparent power (SVA). When these power values are displayed, if UP button is pressed, maximum demand values for total active / reactive / apparent power are displayed. If DOWN button is pressed demand values for total active / reactive / apparent power are displayed. If measured instant value is smaller than min. value which was stored before, it is stored as new min. value. If measured instant value is greater than max. value which was stored before, it is stored as new max. value. Demand value is the smallest value of the measured values in demand time. If the smallest value of the measured values (for example 15 minutes) in demand time is greater than the demand value which was stored before, it is stored as new demand value. When one of defined parameters is displayed, if UP/DOWN button is pressed, min., max or demand values are displayed. When an undefined parameter is displayed, if UP/DOWN button is pressed, instant value is continued to display. For example when power factor is displayed, instant values are continued to display because min., max. and demand values are undefined for this parameter. Press SET button (The number which is the last digit of third display blinks). If you did not enter the second digit correct, you can reenter by pressing the ESC button By using UP-DOWN buttons, enter to the last digit of desired value. Press set button,Ctr is displayed. (Data is entered but is not activated yet. For activating the new data, please follow the below steps). Press ESC button one by one until (SAU SEt yES) appears at the display. Press SET button when (SAU SEt yES) appears at the display. When SAU SEt yES appears at the display,If you push ESC button or choose no option instead of yES option by using UP-DOWN buttons, new data will be cancelled and previous value will be activated. Phase Monitoring leds Voltage Transformer Ratio Setup In this menu, voltage transformer ratio is adjusted. Phase Monitoring Display Kilo led Note: If the voltage transformer is not used between the system and EPM-07S, voltage transformer ratio is entered as 1. Example: ; If a voltage transformer which has a ratio of 34.5KV/100V is used between the system and EPM-07S; Voltage transformer ratio is entered as = 34500/100 = 345 Mega led Up Press SET button for 5 seconds (Ctr menu is displayed) Set Total (S) Monitoring / Demand Display A3552/Rev.1 8 Esc Down By using UP-DOWN buttons, find the Utr menu. 1 Press SET button (The number which is the last digit of second display blinks) DIGITAL POWERMETER DIGITAL POWERMETER EPM-07S EPM-07S Press SET button for 5 seconds (Ctr menu is displayed) By using UP-DOWN buttons, enter to the fourth digit of desired value. Press SET button (The number which is in the middle of the third display blinks. If you did not enter the third digit correct, you can reenter by pressing the ESC button. EPM-07S PC CONNECTION By using the UP-DOWN buttons find the CLr dE or En menu. Press SET button (First number of the third display blinks). If you did not enter the fourth digit correct, you can reenter by pressing the ESC button. By using UP-DOWN buttons, enter to the third digit of desired value. Press SET button.(CLr dE no menu is displayed) 31 DEVICES CAN BE CONNECTED AT THE SAME LINE MAX. 1200 mt. By using the UP-DOWN buttons ; If you want to delete the values choose yEs, if not choose no. 000 B A Press ESC button. By using UP-DOWN buttons, enter to the second digit of desired value User password Setup: Press SET button (The number which is the last digit of third display blinks). If you did not enter the second digit correct, you can reenter by pressing the ESC button In this menu user password is defined and activated. You must define and activate a 4 digit user password for preventing device settings from the illegal usage. There are 2 sub menus under the Pýn menu. This menu is used for changing the user password . Note: Factory default value for user password is 1234 For changing the user password; In the measurement mode ; Press SET button, Utr is displayed. (Data is entered but is not activated yet. For activating the new data, please follow the below steps.) Press ESC button one by one until (SAU SEt yES) appears at the display. Bu using UP-DOWN buttons, find Pýn menu. A GND By using the UP-DOWN buttons, find Pýn CHg menu. In this menu,demand time is adjusted . ... EPM-07S -31 Press SET button (Pýn ACt menu is displayed.) Demand Time Setup: TR B A GND TR B EPM-07S -2 A GND 9 PIN CONNECTOR EPM-07S -1 000 U P TO 2 4 7 D E V I C E S C A N B E C O N N E C T E D AT T H E S A M E L I N E B Y U S I N G R E P E AT E R . Press SET button for 5 seconds (Ctr menu is displayed) Press SET button By using UP-DOWN buttons, find the dt menu. By using UP-DOWN-SET button, enter the old password By using UP-DOWN buttons, enter to the first digit of desired value TR B Press SET button for 5 seconds (Ctr menu is displayed) Press SET button when (SAU SEt yES) appears at the display. When SAU SEt yES appears at the display,If you press ESC button or choose no option instead of yES option by using UP-DOWN buttons, new data will be cancelled and previous value will be activated. PC GND Changing of User Password: By using UP-DOWN buttons, enter to the last digit of desired value. Press SET button (The number which is in the middle of the third display blinks.) RS485/RS232 CONVERTER Press SET button. (CLr dE is displayed) MAX. 1200 mt. MAX. 1200 mt. B A GND By using UP-DOWN-SET button, enter the new password 000 By using UP-DOWN-SET button, reenter the new password. Press SET button, Pýn CHg is displayed. (Data is entered but is not activated yet. For activating the new data, please follow the below steps). Press ESC button one by one until (SAU SEt yES) appears at the display. Press SET button (The number which is the last digit of third display blinks). If you did not enter the second digit correct, you can reenter by pressing the ESC button. Press SET button when (SAU SEt yES) appears at the display. When SAU SEt yES appears at the display,If you push ESC button or choose no option instead of yES option by using UP-DOWN buttons, you quit from adjustment menu without saving new settings and device continues to work with previous settings. By using UP-DOWN buttons, enter to the second digit of desired value. Press set button, dt is displayed. (Data is entered but is not activated yet. For activating the new data, please follow the below steps). Activating the user password: TRB A GND ... EPM-07S -247 ... EPM-07S -31 EPM-07S -2 EPM-07S -1 REPEATER This menu is used for activating the user password. After the user password is activated for entering to the menus; while the instant values are observed, user password is required When the button is pressed for 5 seconds. If the wrong user password is entered user can not enter to the menus. Note: Factory default value of user password is 1234 For activating the user password, In the measurement mode ; Press SET button for 5 seconds. Press ESC button one by one until (SAU SEt yES) appears at the display. Press SET button when (SAU SEt yES) appears at the display. When SAU SEt yES appears at the display,If you press ESC button or choose no option instead of yES option by using UP-DOWN buttons, you quit from adjustment menu without saving new settings and device continues to work with previous settings. Monitoring and Reseting of minimum and maximum values: In this menu, min. values, max. value or energy counters are reset. It saves the instantaneously measured min. and max. values of EPM-07S into its memory. Please kindly look at to the section of FUNCTIONS OF BUTTONS for min. and max. values. Note: Informations which are saved to the memory are not affected from the electricity interruptions. In the CLr dE or En menu ; when you choose and quit from all menus, if you confirm the changes,min. and max. values of all parameters or values of energy counters are reset at the same time.For reseting the values of min. and max. or energy counter;In the measurement mode. By using UP-DOWN buttons, find Pýn menu. Press SET button (Pýn ACt menu is displayed.) Press SET button (The number which is the last digit of second display blinks) 2 RS485/RS232 CONVERTER 000 7 PC CONNECTOR (DB9) DIGITAL POWERMETER DIGITAL POWERMETER EPM-07S EPM-07S PR 19 Box Connection Diagram L1 K L2 k L K l L k L3 K l L k N 1 2 IL1 3 4 L1 K L2 k 5 IL2 ( 12-48V DC ) InC In1 In2 L3 IL3 1 L2 8 Pul 2 N 10 L3 9 Pul C Auxiliary Supply 11 4 6 5 IL3 IL2 Max: 30 VDC ( 12-48V DC ) InC In1 In2 L2 8 L1 7 GND A B TR Auxiliary Supply L1 N N 10 L3 9 3 Phase neutral Press ESC button one by one until (SAU SEt yES) appears 11 Press SET button when (SAU SEt yES) appears at the display. When SAU SEt yES appears at the display,If you press ESC button or choose no option instead of yES option by using UP-DOWN buttons, you quit from adjustment menu without saving new settings and device continues to work with previous settings. Parity Setting: Parity can be set as NO, ODD or EVEN. Press SET button (The number which is the last digit of third display blinks). If you did not enter the third digit correct, you can reenter by pressing the ESC button) Pul 2 Voltage Measuring Input 12 Press SET button for saving the new value. By using UP-DOWN buttons, enter to the third digit of desired value RS485 19 20 21 22 13 14 15 16 17 18 Pul 1 1A L1 7 3 By using UP-DOWN buttons, adjust the desired value. Press SET button (First number of the third display blinks). If you did not enter the first digit correct, you can reenter by pressing the ESC button Press SET button (The number which is in the middle of the third display blinks. If you did not enter the third digit correct, you can reenter by pressing the ESC button) By using UP-DOWN buttons, enter to the last digit of desired value. 12 1A + _ Pul 1 2 IL1 By using UP-DOWN buttons, enter to the first digit of desired value. By using UP-DOWN buttons, enter to the second digit of desired value. Current Measuring Input GND A B TR Voltage Measuring Input l 6 RS485 19 20 21 22 13 14 15 16 17 18 L k + _ Pul C K l l Current Measuring Input Max: 30 VDC L L1 N 000 By using UP-DOWN buttons, find By using UP-DOWN buttons adjust the desired value. Press SET button for saving the new value. Press ESC button one by one until (SAU SEt yES) appears Press SET button when (SAU SEt yES) appears at the display. When SAU SEt yES appears at the display, if you press ESC button or choose no option instead of yES option by using UP-DOWN buttons, new data will be cancelled and previous value will be activated. L1 K L2 k L K l L k L3 K l L k 1 IL1 2 3 4 5 IL2 L1 K L2 k K l 1 ( 12-48V DC ) InC In1 In2 13 14 15 16 17 18 + _ Pul 1 L3 9 N 10 Auxiliary Supply 11 4 5 IL2 Max: 30 VDC Pul 2 1A L2 8 3 Pul C ( 12-48V DC ) InC In1 In2 Pul 1 L1 7 L1 N L2 8 3 Phase without neutral T IL3 By using UP-DOWN buttons, find L3 9 N 10 menu. 3 Phase without neutral current input with Aron wiring configuration CRCH CRCL T Available Modbus Function: Auxiliary Supply By using UP-DOWN buttons adjust the desired value. 12 ESC 03H READ HOLD REGISTERS 06H PRESET SINGLE REGISTER 10H PRESET MULTIPLE REGISTERS Press SET button for saving the new value. L1 N Press ESC button one by one until (SAU SEt yES) appears Read Hold (03) function is used for reading measured values and transformers ratio. Registers can be read are between 0-49. For example to read phase1 voltage; 001 01 03 00 00 00 01 84 0A Press SET button when (SAU SEt yES) appears at the display. When SAU SEt yES appears at the display, If you press ESC button or choose no option instead of yES option by using UP-DOWN buttons, you quit from adjustment menu without saving new settings and device continues to work with previous settings. 002 01 Device adres 03 Function 00 MSB adres 00 LSB adres 00 Register number MSB 01 Register number LSB 84 CRC MSB 0A CRC LSB Preset Single Register (06) function is used to set transformer ratio or for clearing one of min.,max., Demand values. Baud Rate Setting Baud Rate can be set as a value of 1200,2400,4800,9600,19200, 38400 bps Press SET button for 5 sec. By using UP-DOWN buttons, find Press SET button again. 6 DATA NX8BIT CRC is a error check method by using MODBUS RTU protocol and consists of 2 bytes. Press SET button again. GND A B TR 11 FUNCTION 8 BIT ADDRESS 8 BIT The T times corresponds to a time in which data must not be exchanged on the communication bus to allow the connected devices to recognize the end of one message and the beginning of another. This time must be at least 3.5 characters at the selected baud rate. Adress range (1-247 ) is address of the connected device. The data field contains data sent to the slave by master or data sent to master by slave. Pul 2 Voltage Measuring Input 12 Standart MODBUS RTU message is shown below. Press SET button for 5 seconds 6 RS485 19 20 21 22 13 14 15 16 17 18 MODBUS RTU PROTOCOL Parameter Settings Device Address Setting Current Measuring Input RS485 19 20 21 22 GND A B TR Voltage Measuring Input L1 7 IL1 2 1A Pul C l 6 + _ Max: 30 VDC L k IL3 IMPORTANT NOTE : In order communicate with ENTES MPR-SWsoftware baudrate value must be set as 38400 bps and parity must be selected as no EPM-07S has MODBUS RTU communication protocol which is optical isolated. All measured parameters can be saved to the computer.Transformer ratios and communication parameters can be set. Saved demand and energy values can be reset. l L3 Current Measuring Input Press SET button when (SAU SEt yES) appears at the display. When SAU SEt yES appears at the display,If you press ESC button or choose no option instead of yES option by using UP-DOWN buttons, you quit from adjustment menu without saving new settings and device continues to work with previous settings. Serial Communication L menu. Press SET button again. Press SET button, Pýn ACt oF is displayed (Data is entered but is not activated yet. For activating the new data, please follow the below steps) Press ESC button one by one until (SAU SEt yES) appears at the display. 3 Phase without neutral current input with Aron wiring configuration ESC Press SET button for 5 seconds ESC Current transformers ratio can be set 1-2000, voltage transformer ratio can be set 1-2000 min.,Max. and Demand values can be only clear. If sent value is outside of this range device responds with an error message. menu 9 600 3 DIGITAL POWERMETER DIGITAL POWERMETER EPM-07S 01 10 00 41 00 02 04 00 C8 00 64 84 8F 01 Device Address 10 Function 00 MSB adres 41 LSB adres 00 Register number MSB 02 Register number LSB 04 Byte count 00 Data MSB C8 Data LSB 00 Data MSB 64 Data LSB 84 CRC MSB 8F CRC LSB 01 Device Address 06 Function 00 MSB adres 42 LSB adres 00 Data MSB 64 Data LSB D8 CRC MSB 35 CRC LSB The Parameters are sent in 16bit Hexadecimal format. For Example, 230V voltage will be sent as 00E6H. Cosj values shall be divided to 100. 0.98 Cosj will be sent as 0062H. While Cosj is a negative value the MSB bit will be sent as 1. Energy values are sent in 8 bytes (in decimal). 1234567891234,567kWh = 12 34 56 78 91 23 45 67 / 1000 Specifications for data cable ; - 24 AWG or thicker - Less than 100 ohm/ km - Nominal characteristic impedance at 100 kHz of 100 ohms - Less than 60 pF/m mutual capacitance (between two wires in a pair) - Less than 120 pF/m mutual pair capacitance ( the capacitance between one wire and all others connected to earth). - Twisted Pair ADDRESS(HEX) FORMAT UNIT 0 00 int V L1 VOLTAGE 1 01 int V L2 VOLTAGE 2 02 int V L3 VOLTAGE 3 03 int V L1-2 VOLTAGE 4 04 int V L2-3 VOLTAGE 5 05 int V L3-1 VOLTAGE 6 06 int A L1 CURRENT 7 07 int A L2 CURRENT 8 08 int A L3 CURRENT 9 09 int W L1 ACTIVE POWER 10 0A int W L2 ACTIVE POWER 11 0B int W L3 ACTIVE POWER 12 0C int W TOTAL ACTIVE POWER 13 0D int VAr 14 0E int VAr L2 REACTIVE POWER 15 0F int VAr L3 REACTIVE POWER 16 10 int VAr TOTAL REACTIVE POWER 17 11 int VA L1 APPARENT POWER 18 12 int VA L2 APPARENT POWER 19 13 int VA L3 APPARENT POWER 20 14 int VA TOTAL APPARENT POWER 21 15 - L1 COS 22 16 - L2 COS 23 17 - L3 COS 24 18 25 19 int W ACTIVE DEMAND 26 1A int VAr REACTIVE DEMAND 27 1B int VA APPARENT DEMAND 28 1C int W ACTIVE MAX. DEMAND 29 1D int VAr REACTIVE MAX. DEMAND 30 1E int VA APPARENT MAX. DEMAND 31 1F int W L1 MAX. ACTIVE POWER 32 20 int W L1 MIN. ACTIVE POWER 33 21 int W L2 MAX. ACTIVE POWER 34 22 int W L2 MIN. ACTIVE POWER MPR-SW Software is designed for use with EPM-07S device and analyze its measurement values. MPR-SW is able to view realtime measurements and parameters on a PC screen. The software records all parameters and values into a database for future graphical analysis. The Graphical Analysis is designed flexible for view past records in hour,day and month periods. Inductive/Reactive and Capacitive/Reactive values can be viewed on the main window. Energy reports can also be viewed between specific dates. You may change setup parameters using the MPR-SW Software: Set Transformer ratios, Reset Energy and Demand values and change the device address up to 247. MPR-SW can communicate with multiple (max. 247) EPM-07S devices. MPR-SW Software Setup Insert the Setup CD into the CD-ROM drive. Browse the CD by double clicking My Computer and CD-Rom icons. Run Setup.EXE by double clicking its icon or use the START menu button and choose Run. Write d:\setup.exe into the text box opened below.The setup program will install the software to your computer. AVERAGE COS 23 int W 24 int W L3 MIN. ACTIVE POWER 25 int VAr L1 MAX. REACTIVE POWER 38 26 int VAr L1 MIN. REACTIVE POWER 39 27 int VAr L2 MAX. REACTIVE POWER 40 28 int VAr L2 MIN. REACTIVE POWER 41 29 int VAr L3 MAX. REACTIVE POWER Run The MPR-SW Program : The setup software will install the MPR-SW-1/SW-2 Software under C:\Program files\Entes directory. You may browse and run it Please use the softwares own EXIT buttons while quitting the menu or the Main Window. L3 MAX. ACTIVE POWER 2A int VAr L3 MIN. REACTIVE POWER 43 2B int VA L1 MAX. APPARENT POWER 44 2C int VA L1 MIN. APPARENT POWER 45 2D int VA 46 2E int VA L2 MIN. APPARENT POWER 47 2F int VA L3 MAX. APPARENT POWER 48 30 int VA 49 31 50 32 51 33 52 34 kWh 53 35 kWh 54 36 kWh 55 37 kWh 56 38 kWh 57 39 kVArh 58 3A kVArh 59 3B kVArh 60 3C kVArh 61 3D kVArh 62 3E kVArh 63 3F kVArh 64 40 kVArh 65 41 - VOLTAGE TRANSFORMER RATIO 66 42 - CURRENT TRANSFORMER RATIO 67 43 sec. DEMAND TIME 68 44 69 45 70 46 71 47 PARITY 72 48 PASSWORD 73 49 PASSWORD ACTIVATION The area Measurements on The Control Panel IMPORTANT NOTICE: Wall PRECAUTIONS FOR INSTALLATION AND SAFE USE L2 MAX. APPARENT POWER L3 MIN. APPARENT POWER Clicking the START button on the main window, starts the real time analysis of EPM-07S device values. SETTINGS button is for setting up communication parameters (Adress, Parity, Baud Rate) between the PC and EPM-07S device. Both side parameters should be the same for correct data transmission. There are CLEAR ENERGY and CLEAR DEMAND buttons for resetting those values. Transformer ratio is able to setup with the TRANS.RATIOS button on the main menu. IMPORT ACTIVE ENERGY EXPORT ACTIVE ENERGY Failure to follow those instructions will result in death or serious injury. - Disconnect all power before working on equipment.. - When the device is connected to the network, do not remove the front panel. - Do not try to clean the device with solvent or the like.Only clean with dry cloth. - Verify correct terminal connections when wiring. - Electrical equipment should be serviced only by your component seller. - No responsibility is assured by manufacturer or any of its subsidiaries for any consequences arising out of the use of this material. - Only for rack panel mounting. 92mm Type 19 50mm Dimensions 79.3mm 70mm IMPORT REACTIVE ENERGY EXPORT REACTIVE ENERGY DIGITAL INPUTS ADDRESS bps 79.3mm 70mm 90mm 42 MPR-SW serial Interface Software L1 REACTIVE POWER 37 : Please look at the back labels on the device Operating frequency (f) : 50/60 Hz Auxiliary supply Power Consumption : < 4 VA Measuring Input Power Consumption : < 1VA VIn : 10-300VAC 50/60Hz. (L-N) : 10-500VAC 50/60Hz. (L-L) IIn : 0.05 - 5.5 A~ Measuring Range : 0...999 M(W,VAr,VA) : 999999999.999 kWh,kVArh Measuring Category : CAT III Class : 1±1digit [(%10-%110) xFull Scale] Voltage Transformer Ratio : 1 ... 2000 Current Transformer Ratio : 1 ... 2000 Demand Time : 1-60 min. (programmable) Serial Interface : MODBUS RTU (RS 485) : Optically Isolated, programmable : Baud Rate 1200-38400 bps : Address 1-247 : No , odd ,even Parity Pulse Output : NPN Transistor Switch Period : Min. 1,6 Sec. (400 msec pulse width) Operation Current : Max. 50 mA Operation Voltage : 5.....24 V DC, max. 30 VDC Input : 12...48 V DC Ambient Temprature : -5°C; +50°C Display : Red LED Display Dimensions : PR-19 Equipment Protection Class : Double Insulation-Class II ( ) Box Protection Class : IP 40 Box Material : Non-flammable Installation : Panel Mounted (PR-16, PR-19) Rail Mounted (PK-26) Wire Thickness(for terminal block) : 2.5 mm2 Weight : 0.45 kg (PR-19, PK-26) 0.8 kg (PR-16) Installation Category : Class III Slave device (EPM-07S) sends error message when receive any missing query. Error codes are given below. 01 ILLEGAL FUNCTION : If any message except given above is used, then 01 error messages will be sent. 02 ILLEGAL DATA ADDRESS : EPM-07S uses registers between 0 and 57. If any message is been sent out of this range, then 02 error message will be sent. 03 ILLEGAL DATA VALUE : If any different value is been set for dedicated Transformer values and nonzero for demand value, then error message 03 will be sent. DESCRIPTION 36 Operating Voltage (Un) 96mm 35 - TECHNICAL DATA The Graphic menu, shows records and values for past 1 year period on a graphical interface. Users are able to choose the statistics period, hourly,daily and monthly from the window shown below. ERROR CODES Preset Multiple Register(10H) is used to set more then one register at same time. NO Graphic Button and Statistics : 90mm Setting CT to 100, Ut to 20,0 ; 01 06 00 42 00 64 D8 35 92mm Setting CT to 100; EPM-07S BAUD 4 5 96mm ">
Advertisement
Key features
- 3-phase power measurement
- Modbus RTU communication
- Energy pulse outputs
- Demand monitoring
- Maximum demand recording
- User-friendly interface
Frequently asked questions
The EPM 07S is a digital powermeter designed for measuring voltage, current, power, energy, and power factor in a three-phase electrical system.
The EPM 07S utilizes the Modbus RTU protocol for communication with a computer via an RS-485 serial interface.
The EPM 07S has two energy pulse outputs: Pul1 for reactive energy and Pul2 for active energy. Pul1 is used for reactive inductive energy values, and Pul2 is used for both active import and export energy values.
The demand time can be programmed between 1 and 60 minutes using the 'dt' menu, which allows you to customize the averaging period for power measurements.
Yes, the EPM 07S provides options to clear energy and demand values through the 'Clr dE' and 'En' menus, respectively.