- Home
- Domestic appliances
- Climate control
- Split-system air conditioners
- Sharp
- AF-S 50CX
- Service manual
- 44 Pages
SHARP AF-S 50CX, 55CX, 60CX air conditioner SERVICE MANUAL
The AF-S50CX, AF-S55CX and AF-S60CX are window air conditioners that offer a variety of features, including: Cooling, fan-only operation, timer functions, and Energy Saver mode. The units are easy to operate and come with a remote control for added convenience.
advertisement
Assistant Bot
Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.
AF-S50CX
AF-S55CX
AF-S60CX
SERVICE MANUAL
S3207AFS06CX/
AIR CONDITIONER
AF-S50CX
AF-S55CX
MODELS
AF-S60CX
In the interests of user-safety (Required by safety regulations in some countries) the set should be restored to its original condition and only parts identical to those specified should be used.
TABLE OF CONTENTS
Page
SPECIFICATIONS ................................................................................................................................................ 2
EXTERNAL DIMENSIONS ................................................................................................................................... 4
HOW TO OPERATE ............................................................................................................................................. 5
INSTALLATIOIN INSTRUCTIONS ...................................................................................................................... 13
DISASSEMBLING PROCEDURE ....................................................................................................................... 16
HOW TO REPAIR REFRIGERATION ................................................................................................................ 20
ELECTRICAL COMPONENT TEST .................................................................................................................... 23
MICROCOMPUTER CONTROL SYSTEM .......................................................................................................... 24
TROUBLESHOOTING GUIDE ............................................................................................................................ 28
COOLING LOAD ESTIMATE FORM ................................................................................................................... 33
RUNNING CONDITION ....................................................................................................................................... 35
PACKING AND ACCESSORIES ......................................................................................................................... 36
REPLACEMENT PARTS LIST ............................................................................................................................ 37
SHARP CORPORATION
1
This document has been published to be used for after sales service only.
The contents are subject to change without notice.
AF-S50CX
AF-S55CX
AF-S60CX
SPECIFICATIONS
Models
Cooling capacity
Moisture removal
BTU/h
Pints/h
AF-S50CX, AF-S55CX
5000
1.2
AF-S60CX
6000
1.5
ELECTRICAL DATA
Phase
Rared frequency
Rated voltage
Rated current
Rated input
Power factor
EER
Hz
Volts
Amps
Watts
%
BTU/Wh
Single
60
115
4.2
455
94
11.0
5.2
545
91
11.0
COMPRESSOR
Type
Model, Motor output
(Hermetically sealed rotary type)
39R121AA-C4P, 390W 39R141AA-04P, 460W
REFRIGERANT SYSTEM
Evaporator
Condenser
Louver fin, Grooved tube, 7mm, Hair pin
Louver fin, Grooved tube, 7mm, Hair pin
Control O.D. x I.D. x Length x Q'ty(mm) 2.7 x 1.1 x 600 x 1 2.7 x 1.2 x 700 x 1
(Capillary tube)
Refrigerant volume R-22(OZ)
(Factory change)
11.1
11.8
NET DIMENSIONS
Width Height Depth
Net Weight inches(mm) 17-23/32(450) x 14-9/16(370) x 14-7/8(378) lbs 47 48
GROSS DIMENSIONS
Width Height Depth
Gross Weight inches(mm) 20-7/8(530) x 18-1/8(460) x 18-3/8(467) lbs 53 54
FAN SYSTEM
Indoor side(Evaporator)
Outdoor side(Condenser)
Air flow rate(indoor side) CFM
Centrifugal fan
Propeller fan
High / Med / Low
195 / 175 / 150
OTHERS
Safety devices
Air filter
Power cord length
Power plug type ft
Compressor: Overload relay
Fan motor: Internal thermal protector
Polypropylene net
6.0
125V, 10A
2
ELECTRICAL PARTS
Models
Running capacitor
Fan capacitor
Thermistor
Fan motor
Overload relay
AF-S50CX, AF-S55CX
250V-35
µ
F
250V-6
µ
F
15k
Ω
at 78˚F
OBM-2016K1
(MLA998)
B210-130-241A
AF-S60CX
250V-25
µ
F
B200-130-141E
WIRING DIAGRAM
POWER SUPPLY CORD
115V 60Hz
NON RIBBED
GR
IN
OUT
OVERLOAD
PROTECTOR
3A 125V
BK
FU1
MRY CONTROL
BOARD UNIT
NR
C1
RIBBED
COMPRESSOR
MOTOR
C
RUNNING
CAPACITOR
250V 35
µ
F
R
RE
BK
S
WH
BL
FAN MOTOR
CAPACITOR
250V 6
µ
F
BL BK
GY
RE
OR
WH
GY
8
7
1
3
5
1 2 3 6 5 4
BL BK GY RE OR WH
CONNECTOR
H M L
FAN MOTOR
THERMAL
PROTECTOR EARTH
BCN1
BK M.C
A.C
GR
TR
CNR1
CNR2
CNR3
RY1
RY2
RY3
CN1
BCN2
BCN3
WIRE COLOR
BK
BL
RE
WH
GR
GY
OR
: BLACK
: BLUE
: RED
: WHITE
: GREEN
: GRAY
: ORANGE
THERMISTOR
(ROOM TEMP)
YELLOW
CN2
CN3
TH1
DISPLAY
BOARD
UNIT
Figure W-1. Wiring diagram for AF-S50CX, AF-S55CX
POWER SUPPLY CORD
115V 60Hz
NON RIBBED
GR
IN
OUT
OVERLOAD
PROTECTOR
3A 125V
BK
FU1
MRY CONTROL
BOARD UNIT
NR
C1
RIBBED
COMPRESSOR
MOTOR
C
RUNNING
CAPACITOR
250V 25
µ
F
R
RE
BK
S
WH
FAN MOTOR
CAPACITOR
250V 6
µ
F
BL BK
BL
BK
GY
RE
OR
WH
GY
1 2 3 6 5 4
BL BK
CONNECTOR
GY RE OR WH
H M L
BCN1
FAN MOTOR
THERMAL
PROTECTOR EARTH
M.C
A.C
GR
1
3
5
8
7
TR
CNR1
CNR2
CNR3
RY1
RY2
RY3
CN1
BCN2
BCN3
WIRE COLOR
BK
BL
RE
WH
GR
GY
OR
: BLACK
: BLUE
: RED
: WHITE
: GREEN
: GRAY
: ORANGE
THERMISTOR
(ROOM TEMP)
YELLOW
CN2
CN3
DISPLAY
BOARD
UNIT
TH1
Figure W-2. Wiring diagram for AF-S60CX
3
AF-S50CX
AF-S55CX
AF-S60CX
AF-S50CX
AF-S55CX
AF-S60CX
EXTERNAL DIMENSIONS
.
17-23/32"
33-7/16" (full opened)
21-21/32" (full closed)
4-1/8"
15-1/4"
Fig. E-1
4
HOW TO OPERATE
PARTS NAMES
UNIT
3
4 5
2
1
6
11
7
8
9
10
1 Front Cabinet
2 Air Inlet (Indoor Side)
3 Horizontal Louvers
4 Vertical Louvers
5 Air Outlet (Indoor Side)
6 Control Panel
7 Rear Cabinet
8 Air Inlet (Outdoor side)
9 Filter (Pull the filter handle to the right to remove.)
0 Filter Handle q Power Cord
CONTROL PANEL
AF-S50CX, S60CX
2 1
3
COOL / FAN TEMP
SELECTOR
F hr
POWER
ON/OFF
TIMER
ON/OFF
ENERGY
SAVER
11
10
4 5 6 7 8 9
1 Receiver window for remote control signal
2 Display
3 SELECTOR indicator
4 SELECTOR pad
5 TEMPERATURE setting pad
----
Lower temp.
----
Raise temp.
AF-S55CX
2 1
3
COOL / FAN TEMP
SELECTOR
F hr
POWER
ON/OFF
TIMER
ON/OFF
ENERGY
SAVER
11
10
4 5 6 7 8 9
6 TIMER ON/OFF pad
7 TIMER indicator
8 ENERGY SAVER pad
9 ENERGY SAVER indicator
0 POWER ON/OFF pad q POWER indicator
5
AF-S50CX
AF-S55CX
AF-S60CX
AF-S50CX
AF-S55CX
AF-S60CX
COOLING OPERATION
SELECTOR indicator
POWER indicator
COOL / FAN TEMP
SELECTOR
F hr
POWER
ON/OFF
TIMER
ON/OFF
ENERGY
SAVER
1 Touch POWER ON/OFF pad.
• The unit is preset at 74
°
F and HIGH
COOL. This will show in the display when the power is first turned on.
• POWER indicator and SELECTOR indicator (COOL) will light.
2
To turn off the unit, touch POWER
ON/OFF pad again
.
• POWER indicator and SELECTOR indicator will go off.
POWER ON/OFF pad
TO CHANGE TEMPERATURE SETTING
F hr
POWER
ON/OFF
During cooling operation
Touch the TEMPERATURE setting pad to adjust the temperature setting.
COOL / FAN TEMP
SELECTOR
TIMER
ON/OFF
ENERGY
SAVER
TEMPERATURE setting pad
---
Lower temp.
---
Raise temp.
• Temperature can be set within the range of 64
°
F to 86
°
F.
• Display will change as you touch the pad.
NOTE:
•
The latest temperature setting will be memorized and will appear on the display the next time the unit is turned on.
• In cases of power outages or when the unit is disconnected; when the power is restored or the unit is plugged in, the unit and display will return to the preset conditions of 74
°
F and HIGH
COOL. The unit will not automatically turn back on. The user must touch POWER ON/OFF to resume opertion.
6
TO CHANGE FAN SPEED AND OPERATION MODE
SELECTOR indicator
COOL / FAN TEMP
SELECTOR
F hr
POWER
ON/OFF
TIMER
ON/OFF
ENERGY
SAVER
During operation
Touch SELECTOR pad and select the operation mode and fan speed.
• SELECTOR indicator and display will light in order as you touch.
HIGH COOL MED COOL LOW COOL
LOW FAN MED FAN HIGH FAN
SELECTOR pad
AF-S50CX
AF-S55CX
AF-S60CX
NOTES ON OPERATION MODE:
MODE SELECTOR DISPLAY
HIGH COOL COOL
MED COOL COOL
LOW COOL COOL
HIGH FAN FAN
MED FAN
LOW FAN
FAN
FAN
Cooling operation with high fan speed.
Cooling operation with medium fan speed.
Cooling operation with low fan speed.
Fan only operation with high fan speed.
Fan only operation with medium fan speed.
Fan only operation with low fan speed.
• The latest operation mode will be memorized and the selector indicator and display will light when the unit is turned on.
• In fan only operation, the temperature display will go off.
• When the SELECTOR is changed to fan only operation from cooling operation, it will take 5 seconds for the compressor to stop.
7
AF-S50CX
AF-S55CX
AF-S60CX
ENERGY SAVER
During normal operation, the thermostat automatically controls cooling and the fan runs continuously.
When the ENERGY SAVER is selected, the thermostat automatically controls cooling and the fan automatically stops when the compressor is not operating. (Fan will stop 30 seconds after the compressor stops. After the fan stops, the fan is programmed to rotate for approx. 2 minutes to detect room temperature. This will occur within a 20 min time span.)
ENERGY SAVER indicator
1
During cooling operation
Touch ENERGY SAVER pad.
• ENERGY SAVER indicator will light.
F hr
POWER
ON/OFF
COOL / FAN TEMP
SELECTOR
TIMER
ON/OFF
ENERGY
SAVER
2
To cancel, touch ENERGY SAVER pad again.
• ENERGY SAVER indicator will go off.
ENERGY SAVER pad
NOTE: ENERGY SAVER cannot be set during fan only (HIGH FAN, MED FAN, LOW FAN) operation.
TO CHANGE AIR FLOW DIRECTION
The horizontal louvers are used to adjust the UP / DOWN direction of air flow, and the vertical louvers are used to adjust the LEFT / RIGHT direction of air flow for uniform and efficient cooling of the room.
Horizontal louvers Vertical louvers
Adjust UP/DOWN air flow Adjust LEFT/RIGHT air flow
Lever
8
ON TIMER OPERATION
• This unit has a built-in timer that can be programmed to start the unit up to 12 hours in advance.
You can set the timer to start in increments of 30 minutes (0.5 hours) up to 9.5 hours in advance of the start time, or in 1 hour increments from 10 to 12 hours in advance of the start time.
• The unit will start automatically according to your setting.
SELECTOR indicator
F hr
POWER
ON/OFF
When the unit is not operating
1 Touch the TIMER ON/OFF pad to set the delayed start time.
• The time setting will change as you touch the pad. The display will change as follows;
COOL / FAN TEMP
SELECTOR
TIMER
ON/OFF
ENERGY
SAVER
TIMER ON/OFF pad
TIMER indicator
(If you wish to start the operation
6 hours and 30 minutes later, set the delay time as shown above.)
Preset(0.5h)
Previous setting
0.5h
1.0h
1.5h
10h
CL(cancel) 12h 11h
• The timer will be set, 5 seconds after the
TIMER ON/OFF pad is touched for the last time.
• SELECTOR indicator and TIMER indicator will light.
• The time display will count down the remaining time.
• The unit will start when the set time expires.
The temperature setting will be displayed.
TO CANCEL THE TIMER SETTING
Touch the TIMER ON/OFF pad again after the timer is set, or press the TIMER ON/OFF pad until CL(cancel) appears on the display.
NOTES FOR TIMER SETTING AND OPERATION:
• After setting the TIMER, change the temperature and fan speed settings as shown on pages 11 and 12. When the temperature is set in the timer mode, the temperature will show in the display for 5 seconds and then return to the time display.
• The last setting used will be memorized and will appear on the display the next time you operate the unit with the TIMER function.
• If a power failure occurs while the ON or OFF TIMER is set, the TIMER memory will be cancelled and will not resume even after power is reinstated. The unit will not automatically start.
• OFF TIMER OPERATION can also be set with the REMOTE CONTROL.
AF-S50CX
AF-S55CX
AF-S60CX
9
AF-S50CX
AF-S55CX
AF-S60CX
OFF TIMER OPERATION
• This unit has a built-in timer that can be programmed to shut the unit off up to 12 hours in advance.
You can set the timer to stop in increments of 30 minutes (0.5 hours) up to 9.5 hours in advance of the stop time, or in 1 hour increments from 10 to 12 hours in advance of the stop time.
• The unit will stop automatically according to your setting.
F hr
POWER
ON/OFF
When the unit is operating
1 Touch the TIMER ON/OFF pad to set the delayed stop time.
• The time setting will change as you touch the pad. The display will change as follows;
COOL / FAN TEMP
SELECTOR
TIMER
ON/OFF
ENERGY
SAVER
TIMER ON/OFF pad
TIMER indicator
(If you wish to stop the operation
10 hours later, set the delay time as shown above.)
Preset(0.5h)
Previous setting
0.5h
1.0h
1.5h
10h
CL(cancel) 12h 11h
• The timer will be set, 5 seconds after the
TIMER ON/OFF pad is touched for the last time.
• TIMER indicator will light.
• The time display will count down the remaining time.
• The unit will stop when the set time expires.
All indicators and displays will go out.
TO CANCEL THE TIMER SETTING
Touch the TIMER ON/OFF pad again after the timer is set or, press the TIMER ON/OFF pad until
CL(cancel) appears on the display.
10
USING THE REMOTE CONTROL
INSTALLING BATTERIES
Use two size-AAA (R03) batteries.
1
Remove the battery compartment cover.
2 Insert the batteries in the compartment, making sure the and polarities are properly aligned.
Battery compartment cover
Replace the cover.
3
NOTES:
• The battery life is approximately one year with normal use.
• When you replace the batteries, always use two new ones of the same type.
• If the remote control does not operate normally after replacing the batteries, take out the batteries and replace them again after 30 seconds.
• If you will not be using the unit for a long time, remove the batteries from the remote control.
ATTACHING THE REMOTE CONTROL HOOK
• Remove the backing from the remote control hook.
• Attach the hook onto the left side of the unit's front cabinet.
• To prevent loss, hook the remote control on the front cabinet when not in use.
Rear Cabinet
Front Cabinet
Remote control hook
HOW TO USE THE REMOTE CONTROL
Point the remote control towards the unit's receiver window and press the desired button. A beep will sound when the unit receives the signal.
• Make sure no objects, such as curtains, block the receiver window.
• The remote control operates from up to 20 feet (6 meters) away.
• The beep will also sound when each pad on the control panel is touched.
CAUTION:
• Do not expose the receiver window to direct sunlight. This can adversely affect its operation. In such case, close the curtains to block the sunlight.
• Use of a fluorescent lamp in the same room may interfere with the transmission of the signal.
• The unit may be affected by signals emitted from the remote control of a television, VCR or other equipment used in the same room.
• Do not leave the remote control exposed to direct sunlight or near a heater. Protect the remote control from moisture and shock which can discolor or damage it.
AF-S50CX
AF-S55CX
AF-S60CX
11
AF-S50CX
AF-S55CX
AF-S60CX
OPERATING WITH THE REMOTE CONTROL
TRANSMITTER
POWER
ON/OFF
POWER ON/OFF button
Push to start or stop the operation.
TEMP.
TEMP.
SELECTOR
SET TIMER/OFF
TEMP.
TEMP.
---
Raise temp. setting 1
°
F at a time.
---
Lower temp. setting 1
°
F at a time.
SELECTOR button
Push to change fan speed and operation mode.
Fan speed and operation mode selections are shown to the right.
SET TIMER/OFF button
Push to set delay "OFF" timer during operation.
HIGH COOL
MED COOL
LOW COOL
HIGH FAN
MED FAN
LOW FAN
• The time setting will change as you push the button. The display will change as follows;
Preset(0.5h)
Previous setting
0.5h
1.0h
1.5h
10h
CL(cancel) 12h 11h
• The last OFF time setting is memorized by the unit and will appear on the display when the button is pushed.
• The timer will be set, 5 seconds after the SET TIMER/OFF button is pushed for the last time.
• If you wish to cancel the timer, push the SET TIMER/OFF button again after the time is set or, push the SET TIMER/OFF button until CL (cancel) appears on the display. A double beep will sound when the timer is cancelled.
• The "ON" TIMER cannot be set with the remote control.
It can only be activated by the TIMER ON/OFF pad on the unit's control panel ( See page 9 ).
To change temperature setting when ON/OFF timer is in use
1. Push a TEMPERATURE setting button.
The current set temperature will be recalled on the unit's display.
2. Use the TEMPERATURE setting buttons to set the new temperature.
The new set temperature will show on the display for 5 seconds and return to the time display.
12
INSTALLATION INSTRUCTIONS
ACCESSORIES
9
10
7
8
5
6
11
No.
1
2
3
4
Accessories
Right closure assembly
Left closure assembly
Window sash foam seal
Window sash foam seal
(adhesive type)
Bottom gasket
Screws (L=1", 25.4mm)
Screws (L=
13
/
32
", 10mm)
Base pan angle
Remote control
Battery
Remote control hook
1
2
1
6
2
1
7
Q'ty
1
1
1
1
9
7
2
3
4
6
6
8
10
2
SUGGESTED TOOLS
1. Screw driver (medium size Phillips)
2. Tape measure or ruler
3. Knife or scissors
7
11
1
2
5
AF-S50CX
AF-S55CX
AF-S60CX
13
AF-S50CX
AF-S55CX
AF-S60CX
INSTALLATION
WARNING: Make sure the unit is turned off and unplugged before working.
Sash
1 Cut the window sash foam seal (adhesive type) to the proper length and attach it to the underside of the window sash.
Jamb
Window sash foam seal
(adhesive type)
Sill
2 Insert the right closure assembly and the left closure assembly into the top angle and the bottom channels.
Secure the right and left closure to the cabinet with six of the provided screws.
(L= 13 /
32
", 10mm) Closure assembly
3 Open the window sash and place the air conditioner on the sill.
Balance the unit on the sill and close the window sash securely behind the top angle.
WARNING:
At this step, make sure the unit is inclined approximately 1 cm ( 3 /
8
") to the back.
If the unit is not properly inclined, the water collected in the bottom tray during operation will not drain properly and may flow into the room where the air conditioner is installed.
unit sill incline backwards approximately
1cm ( 3 /
8
")
4 Insert the bottom gasket into the space between the window sill and the bottom of the unit to seal outside air.
If there is space between the bottom channel and the sill, fill the gap with a thin board or other hard filler.
Bottom gasket
14
Closure assembly
(Left) 5 Insert the closure assemblies on both sides into the rails of the jamb.
Jamb
(Left)
Closure assembly
(Left)
6 Loosen screws on both sides of the cabinet, then hang the base pan angle on and secure the screws again.
Sill
Indoor side
Indoor side
1/2 inches
(13mm)
Stool
7 Secure the base pan angle to the sill by using the hole of the front side on the angle with one screw. (L=1", 25.4mm)
8 Secure the top angle of the unit and the top of the closure assemblies to the sash with three of the provided screws. (L=1",
25.4mm)
And secure the bottom of the closure assemblies to the sill with two of the provided screws. (L=1", 25.4mm)
9 Cut the window sash foam seal to the proper length and seal the opening between the top of the inside window sash and the outside window sash.
Window sash foam seal
15
Top angle
AF-S50CX
AF-S55CX
AF-S60CX
AF-S50CX
AF-S55CX
AF-S60CX
DISASSEMBLING PROCEDURE
CAUTION: DISCONNECT THE ROOM AIR CONDITIONER FROM THE POWER SUPPLY BEFORE ANY SERVICE
1. Unscrew the 2 screws holding the front panel on each side.
5. Remove the control panel.
2. Remove the front panel by pulling the front panel at the lower corner toward you about one inch. Next lift up and pull it toward you.
6. Unscrew the 5 screws.
3 screws are holding the control box at the top and right side.
1 screw is holding the power supply cord.
1 screw each screw on the evaporator.
3. Unscrew the 9 screws holding the cabinet.
2 screws are on each side.
4 screws are on back side.
3 screws are on top side.
7. Take off the fan motor connector.
8. Unscrew the 1 screw holding the compressor cord.
4. Remove the thermistor holder.
16
9. Cut the wire fixing band, slide the control box rightward and remove.
SLIDE
AF-S50CX
AF-S55CX
AF-S60CX
13. Unscrew the 3 screws holding the condenser shround.
And remove the condenser shround.
10. Unfasten the one nut at the top of the compressor holding the terminal cover. Then remove the wiring connector of the compressor cord.
14. Unscrew the 5 screws. 2 screws are holding the evaporator on each side. 3 screws are holding the bulkhead to the base pan on each side and back side.
11. Unscrew the 6 screws holding the condenser.
2 screws are on right side.
2 screws are on left side.
2 screws are on back side.
And remove the condenser from the unit.
15. Lift up and take out the bulkhead.
12. Unfasten the nut holding the propeller fan by rotating it counter-clockise. And remove the propeller fan.
16. Unscrew the 2 screws holding the orifice.
17
AF-S50CX
AF-S55CX
AF-S60CX
17. Unscrew the 1 screw holding the centrifugal fan.
18. Remove the caseing.
19. Unscrew the 4 screws holding fan motor.
18
AF-S50CX
AF-S55CX
AF-S60CX
DISASSEMBLING THE CONTROL BOX
1. Unscrew the 2 screws holding the control box cover.
CAUTION:
DISCHARGE THE FAN MOTOR CAPACITOR AND
RUNNING CAPACITOR BEFORE TOUCHING
THOSE CAPACITORS OR OTHER COMPONENTS
OR WIRING.
5. Unscrew the 1 power supply cord grounding screw.
Unscrew the earth screw. Unscrew the 1 screw holding the capacitor clamp.
2. Unscrew the 3 screws holding the printed wiring board.
6. Detach each connector by using long-noise pliers.
3. Cut the wire fixing bands holding the fan motor lead wires, the compressor cord and the power supply cord.
7. Unscrew the 2 screws holding the transformer.
4. Unscrew the 1 screw holding the fan motor capacitor.
8. Remove the control board with unhooking the 2 spacers.
19
AF-S50CX
AF-S55CX
AF-S60CX
HOW TO REPAIR REFRIGERATION
Before sealed system work can be preformed a refrigerant recovery EPA and LOCALLY approved certification is required, additionally, EPA and LOCALLY approved refrigerant recovery equipment is required.
SEALED SYSTEM REPAIR
Sealed system repairs should be properly diagnosed before entering into a repair of the system.
It is important to follow proper procedures when doing a system repair for safety reasons and that the repair will result in a restoration of the system to proper factory standards.
SAFETY REMINDERS
1) Do not heat any system component with an open flame for any reason.
2) Do not solder until you are sure that all refrigerant has been removed from the system.
3) Do not heat the charging cylinder with an open flame. Use warm water only and do not exceed 125˚F(not too hot to keep your hand in.)
4) Do not over fill any charging cylinders, as they could explode when over filled.
5) Use proper wrenches.
6) Use safety goggles when working with refrigerants.
7) Keep a fire extinguisher within easy reach.
8) Watch flame direction when soldering so as not to burn clothing, wiring or other components.
9) Solder in a well ventilated area. If a high concentration of freon is present, an open flame will create phosgene gas which can be harmful.
GOOD FIT
PROPER
JOINT FIT
CLEARANCE
0.01" TO 0.03"
PROPER SOLDERING
Joint clearances should be maintained so that the brazing alloy will flow between the closely mated surfaces rather than forming large fillets.
This films make the strongest joints, capillary attraction also work best with close tolerance.
The best clearance is between 0.01" to 0.03" , the amount of lap will be approximately 3/8" depending on the swaging tool used. (Figure 1.)
POOR FIT
Joint Clearance.
Figure 1
CLEANING TUBING
To make a sound, leak tight joint, the brazing alloy when raised to brazing temperature, must wet and flow freely over the entire surface of the tubing in the joint area.
To assure this, the tubing surfaces must be free of all dirt, grease, oil and oxides otherwise the alloy will not wet and flow properly over any surface with these elements present. Cleaning can be done with an abrasive cloth or steel wool. Never blow into the tubing because this will introduce a lot of moisture into the system. Open tubing joints should be covered if exposed for long periods of time.
EMERY CLOTH
KEEP TUBE IN
DOWNWARD POSITION
Cleaning Tubing.
Figure 2
20
PROPER FLUXING
Flux is necessary when using silver solder; it is not required when using silfos on copper to copper joints.
To do a good job the flux should cover the tube surface completely. Be careful not to introduce any flux inside the tubing.
Fluxing should be done after the tubing is mated together and just before brazing is done. Do not allow it to dry out.
When brazing, the flux should become entirely liquid and clear, like water. The temperature will be at 1100˚F and only a little more heat will allow the alloy to flow freely into the joint.
3/8"
SILVER ALLOY
INNER CONE
TORCH STEM
Directing Torch Flame to Copper Tubing.
Figure 3
HEATING THE TUBING
Direct the torch flame so that the larger tube receives most of the heat. Silver solder flows at 1200˚F and silfos flows at
1300˚F.
Heat all around the tubing.
The flame is composed of two cones, a smaller inner cone
(pale blue) in calor and a much larger outer cone. The hottest part of the flame is at the tip of the inner cone. The flame should be directed at the joint with the tip of the cone just touching the surface of the tubing. Figure 3 and 4.
OUTER CONE
HOTTEST PART
OF FLAME
INNER CONE
TORCH STEM
AF-S50CX
AF-S55CX
AF-S60CX
Composition of Torch Flame.
Figure 4
DEHYDRATING SEALED SYSTEM
Many servicers feel that since air conditioners run with evaporator temperatures above 33˚F, moisture will not present a problem. Nothing is further from the truth. Oxygen in moisture plus the heat produced during compression will react with the refrigerant oil to produce harmful acids in the system which will break down motor winding insulation, create sludge and pit component parts, reducing efficiency of the air conditioner and shortening the life of compressors.
There it becomes mandatory that good dehydrating practices be adhered to at all times.
Proper hook up procedures as shown in Figure 5 must be used in order to pull and good vacuum from the system.
The use of a good vacuum pump is very important so that the boiling point of any water in the system will be lowered to a point where it will vaporize and be expelled from the system in the form of vapour.
21
AF-S50CX
AF-S55CX
AF-S60CX
Type of evacuation methods
1. Piston Type Compressor No good.
System parts must be above 110˚F.
2. Rotary Vacuum Pump Disavantages.
Low CFMC. 4 oil gets dirty.
3. Single State Vacuum Pump will not clean oil.
Oil must be changed often.
4. Two Stage Vacuum Pump will reach 50 microns.
First stage is below atmospheric pressure.
Moisture is removed into second stage which works up to atmospheric pressure thus keeping oil clean.
Manometer cannot be read to 1/2 mm. Micron gauge reads from 25,400 microns to 0.
TO RELATED SERVICE
VALVE OR PROCESS
TUBES OF THE UNIT.
ELECTRIC
VACUUM
GAUGE
LARGE DIAMETER
BRAIDED VACUUM
HOSES
HIGH VACUUM
MANIFOLD
DIAL-CHARGE
CHARGING CYLINDER
LOW SIDE
GAUGE
HIGH SIDE
GAUGE
Hook up for Evacuation and charging
HIGH VACUUM PUMP
Figure 5
It becomes clear that good equipment and maintained properly must be used in order to remove air and moisture from the system.
When a vacuum of 1,000 to 500 microns is reached, block off the vacuum pump from the system.
This is done by closing the value between the pump and system. If the micron gauge does not increase above 1,000, the system is free of moisture and no leak exists. If the micron gauge increases to higher levels moisture or a leak exists.
LEAKS
Several methods are used to detect leaks in systems.
Electronic Leak Detectors are very sensitive and are able to detect leaks down to 1/2 ounce per year.
A good electronic leak detector is generally far better in locating very small leaks.
Halide Torch be sure the room is free from refrigerant vapours. Watch the flame for the slightest change in calor.
A very faint green indicates a small leak. The flame will be unmistakably changed to green or purple when large leaks are encountered. To simplify leak detection pressurize the system to approximately 75 lbs.
Some leaks can be located by a visual inspection of the system components and solder joints and if oil is found at any given location it generally is a sign that a leak exists at that point due to the fact that flame does carry oil with it travels through the system.
Soap Bubbles
Liquid detergents can sometimes assist in finding small leaks by brushing detergent on the suspect area and watching for bubbles. Before applying detergent be sure that the system is pressurized.
Tap line devices are permissible for diagnosis only they are not suitable when evacuating the system. After the diagnosis has been made they must be removed so that the system will be restored to a hermeticly sealed condition.
22
AF-S50CX
AF-S55CX
AF-S60CX
ELECTRICAL COMPONENT TEST
RUNNING CAPACITOR AND FAN CAPACITOR
CAUTION: DISCHARGE THE RUNNING CAPACITOR AND FAN CAPACITOR BEFORE TOUCHING CAPACITOR
OR WIRING.
(1) Discharge capacitor by shorting terminals.
(2) Take the wires off the capacitor terminals.
(3) Set the selector switch of a volt-ohm-meter (or a tester) on the resistance range.
(4) Connect the probes to the capacitor terminals and watch the indicator swing.
The indicator does not swing at all ..... Open.
The indicator swings but does not return ..... Shorted.
The indicator swings, then returns a moment later ..... Good.
FAN CAPACITOR RUNNING CAPACITOR
INSULATION TEST
Check the resistance between the terminals and case.
Reading must be more than 10M
Ω
at DC 500V.
OVERLOAD RELAY
Check continuity between terminals with volt-ohm-meter.
INSULATION TEST
Check resistance between terminals and the relay case.
Reading must be more than 10M
Ω
at DC 500V.
COMPRESSOR
(1) Take the wires off compressor terminals.
(2) Set selector switch of volt-ohm-meter on the resistance range.
(3) Put the probes on the terminals of the compressor and check continuity between each terminal.
INSULATION TEST
Check the resistance between the terminals and the copper tube.
Reading must be more than 10M
Ω
at DC 500V.
23
AF-S50CX
AF-S55CX
AF-S60CX
MICROCOMPUTER CONTROL SYSTEM
1. Temperature control characteristic
1-1 COOL operation
In the “COOL” mode, the thermostat circuit is controlled by two thermostat lines (C1, C2).
86
84
C1
C2
3. Fan speed
Fan speeds are given by the fan motor, “H”, “M” and
“L”, which are available in the following operation mode.
Table Y-1
Selector
HIGH COOL
MED COOL
LOW COOL
HIGH FAN
MED FAN
LOW FAN
Fan motor
H
M
L
H
M
L
64
62
64
Preset temperature (
°
F)
("THERMO" switch)
Figure Y-1
86
2. Operation mode
2-1 COOL operation
The compressor turns on or off, at thermostat lines C1 and C2. The fan motor is also controlled with the compressor.
States 1 & 3 : Compressor ON
States 2 : Compressor OFF
3
C1
1
2
Room temperature transition
Preset temperature (
°
C)
Figure Y-2
2-2 FAN ONLY operation
The fan motor always turns on.
C2
4. 12-hours timer
4-1 OFF-TIMER operation
Set the delay timer during operation.
The unit will turn off automatically according to your setting. Timer duration can be set by 0.5 hours to maximum 12 hours. Up to 9.5 hours, you can set by 0.5
hours increments and from 10 to 12 hours, by 1 hour increment.
If you touch button “POWER ON/OFF” during OFF-
TIMER operation, then the unit turns off and OFF-
TIMER operation is cancelled.
4-2 ON-TIMER operation
Set the delay timer when unit is not operating.
The unit will turn on automatically according to your setting. Timer duration can be set by 0.5 hours to maximum 12 hours. Up to 9.5 hours, you can set by
0.5 hours increments and from 10 to 12 hours, by 1 hour increment.
If you touch button “POWER ON/OFF” during ON-
TIMER operation, then the unit turns on and ON-TIMER operation is cancelled.
ON-TIME and OFF-TIME display will count down the remaining time.
from 0.5 to 9.5 ..... 0.5 hours from 10 to 12 ....... 1 hour
5. Energy saver
During normal operation, the thermostat automatically controls cooling and the fan runs continuously whenever the air conditioner is in operation.
When the ENERGY SAVER is set, the thermostat automatically controls cooling and the fan automatically stop when compressor is not operating. (Fan will stop in 30 seconds after the compressor stops.)
ON
Compressor
OFF
ON
Fan
OFF
30 seconds
Figure Y-3
24
T(˚C)
8
9
10
11
12
6
7
2
3
0
1
4
5
17
18
19
20
13
14
15
16
AF-S50CX
AF-S55CX
AF-S60CX
6. Safety start
When you turn the air conditioner OFF and restart again soon, wait at least 3 minutes before the cooling operation starts.
7. Test mode
Keep pushing both buttons “POWER ON/OFF” and “ " ” and supply the power, the system will go to the test mode.
In this mode, the output operation is switched by pushing buttons. Normal outputs are shown in Table Y-2.
For selfdiagnosis check mode
Table Y-2
No. PUSH KEY (SWITCH)
0
1
PLUG IN the power supply cord while pushing power ON/OFF key and (down) key.
SELECTOR <SW3>
2
5
6
3
4
<SW6>
<SW5>
TIMER <SW2>
ENERGY SAVER <SW1>
ON/OFF <SW4>
BEPP
SOUND
LED1
2 8.8
FAN
HIGH
<LED2>
FAN
MID
<LED3>
ON ON
FAN
LOW
<LED4>
LED LIGHTING
COOL
<LED9>
FAN
<LED5>
TIMER
<LED7>
ENERGY
SAVER
<LED8>
POWER
ON/OFF
<LED6>
FAN
OUTPUT
COMP
OUTPUT
CHECK ITEM and REMARK
ON ON O N O N O N O N O F F O F F LED ALL ON
1
1
1
1
1
1
OFF
01
02
03
04
05
OFF
OFF
2 )
ON
OFF
OFF
ON
OFF OFF OFF O F F O F F O F F O F F
OFF
3 )
OFF
4 )
OFF O F F O F F O F F 1 )
OFF OFF ON O F F O F F O N O F F
ON OFF OFF O N O F F O F F O N
OFF ON OFF O F F O N O F F O F F
OFF OFF ON O F F O F F O N O F F
7 POWER ON/OFF by REMOTE CONTROL 1 05
OFF
OFF OFF OFF
8 POWER SUPPLY OFF
1 ) I f t h e r m i s t o r i s n o r m a l ( n e t h e r s h o r t n o r o p e n ) , L E D i s O N .
2 ) W h e n A / D ( R 4 2 ) b i t 7 = 1 , L E D i s O N .
2 ) W h e n A / D ( R 4 2 ) b i t 6 = 1 , L E D i s O N .
2 ) W h e n A / D ( R 4 2 ) b i t 5 = 1 , L E D i s O N .
OFF O F F O F F O F F O F F
OFF OFF OFF OFF O F F O F F O F F O F F
L O W
MIDDLE
O F F
O F F
H I G H
O F F
L O W
H I G H
MIDDLE
O F F
O F F
LED ALL OFF
FAN CHECK
O F F
O F F
O N COMPRESSOR CHECK
O F F
O F F
REMOTE CONTROL CHECK
Table Y-3
T(˚F)
42.8
44.6
46.4
48.2
50.0
51.8
53.6
32.0
33.8
35.6
37.4
39.2
41.0
55.4
57.2
59.0
60.8
62.8
64.4
66.2
68.0
36.44
34.68
33.02
31.45
29.96
28.55
27.22
R(k
Ω
)
49.33
46.86
44.53
42.33
40.25
38.29
25.96
24.76
23.62
22.56
21.52
20.55
19.63
18.76
V(volts)
1.46
1.51
1.56
1.61
1.67
1.72
1.78
1.17
1.21
1.26
1.31
1.36
1.41
1.83
1.89
1.94
2.00
2.05
2.11
2.17
2.22
V ....... Input the voltage of microcomputer (No. 10-port).
T(˚C)
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
T(˚F)
69.8
71.6
73.4
75.2
77.0
78.8
80.6
82.4
84.2
86.0
87.8
89.6
91.4
93.2
95.0
96.8
98.6
100.4
102.2
104.0
12.07
11.57
11.09
10.63
10.19
9.78
9.38
9.00
R(k
Ω
)
17.93
17.14
16.39
15.68
15.00
14.36
13.74
13.16
12.60
8.64
8.30
7.97
2.98
3.03
3.08
3.13
3.17
3.22
3.27
2.61
2.66
2.71
2.77
2.82
2.87
2.93
V(volts)
2.28
2.33
2.39
2.44
2.50
2.55
25
AF-S50CX
AF-S55CX
AF-S60CX
R18
R17
R16
R15
R14
R13
R12
R11
SW6
SW5
SW4
SW3
SW2
SW1
E/SAVER
TIMER
SELECTOR
POWER
UP-KEY
QWN-KEY
D13
D12
D11
D10
D15
D14
10K
R24
R6
10K
R7
10K
F
µ
R5
10K
16V 10 C19
1000P 50V
C15
C16
10K
R28
TMP47C443N
26
WH
GR
RE
GY
BK
BL
OR
RE
WH
BK
BL
GY
GREEN
FAN MOTOR
DPWBFA244JBKZ
(AF-S55CX)
QPWBFB438JBZZ
(AF-S55CX)
DPWBFA278JBKZ QPWBFB475JBZZ
R15
AF-S50CX
AF-S55CX
AF-S60CX
BCN2
DPWBFA278JBKZ
DPWBFA244JBKZ
(AF-S55CX)
QPWBFB475JBZZ
QPWBFB438JBZZ
(AF-S55CX)
Printed Wiring Board
27
AF-S50CX
AF-S55CX
AF-S60CX
No cooling
(Operation not at all.)
TROUBLESHOOTING GUIDE
Measure the power supply voltage at receptacle.
under 100V
120V(over 100V) The house fuse or circuit breaker open ?
open
Is it proper current capacity of the house fuse or the circuit breaker ?
not open.
Ask the power supply company for check.
Change the house fuse and the circuit breaker turn on.
Is it sufficient current capacity of power equipment ?
Is it small wiring for power supply equipment ?
sufficient insufficient
Ask the power supply company for check.
Is plug disconnecting ?
connecting disconnecting
Connect plug properly.
Check the power supply cord.
imperfect contact
OK Change the power supply cord.
Check the fuse on PWB ass'y.
open
OK Change the fuse on PWB ass'y.
Measure the secondary voltage of transformer.
over 14V(AC) under 14V(AC)
Measure the voltage between
-12V and GND on PWB ass'y.
OK(12V, DC)
Measure the voltage between
-5V and GND on PWB ass'y.
NG
NG
OK(5V, DC) Change PWB ass'y.
If unit operate, dose the house fuse or the circuit breaker open ?
NO
YES
Measure the insulation resistance of compressor.
OK(over 10M
Ω
)
NG(under 10M
Ω
)
Change the compressor.
Measure the insulation resistance of fan motor.
OK(over 10M
Ω
)
NG(under 10M
Ω
)
Change the fan motor.
Can the Compressor operate ?
can't operate can operate Change the compressor.
Checking complete.
28
No cooling
(Fan operate but the compressor doesn't operate.)
Measure the power supply voltage at receptacle.
Is it sufficient current capacity of power equipment ?
Is it small wiring for power supply equipment ?
under 100V
120V(over 100V)
Ask the power supply company for check.
insufficient
Ask the power supply company for check.
sufficient
Measure the current in compressor circuit.
current
Check the overload relay.
OK no current imperfect contact
Change the overload relay.
Check the running capacitor.
OK
NG
Change the running capacitor.
Check the overload relay.
short open
Change the overload relay.
Is the connector disconnecting ?
connecting disconnecting
Connect properly.
Check the compressor relay.(MRY on PWB)
OK
NG
Change PWB ass'y.
Check the thermister.
OK
NG
Change the thermistor.
Measure the resistance of compressor coil.
OK
NG
Change the compressor.
Is there high heat source near the unit.
there isn't there is
Remove the high heat source or stop.
Is the outdoor temperature too high ?
under 43ûC over 43ûC
Avoid sun light and ventilate well for outdoor heat exchanger.
Check the outdoor heat exchanger.
not dirty dirty
Clean them with steam cleaner or another method.
Can the compressor operate ?
can operate can't operate
Change the compressor.
Checking complete.
Checking method for the compressor relay.
(MRY on PWB)
Turn off the power supply.
Measure the resistance of its coil.
NG
OK(160
Ω
at 20ûC)
Turn on the power supplty as operating the compressor.
Measure the voltage to its coil.
OK(12V, DC)
NG
OK NG
29
AF-S50CX
AF-S55CX
AF-S60CX
AF-S50CX
AF-S55CX
AF-S60CX
No cooling
(The compressor operate but the fan motor doesn't operate) crack at the solder part
Repair with over solder.
Check BNC1 on PWB ass'y
OK disconnecting the connector
Connect the connector properly.
Check the fan motor
capacitor.
OK
NG
Change the fan motor capacitor
Measure the resistance of compressor coil.
OK
NG
Change the fan motor.
Is the fan locked ?
locked
Is the fan touched to another parts ?
no touch
Change the fan motor.
touch
Change fan or another parts, or adjust.
Checking complete
The compressor doesn't turn off.
Check the thermister connector.
OK disconnecting
Connect the connector properly.
Check the thermister resistance.
OK
NG
Change the thermister.
Check the compressor relay.
OK
NG
Change PWB ass'y.
Checking complete.
Checking method for the compressor relay.
(MRY and PWB)
Turn off the power supply.
Measure the contact resistance.
open
OK short
NG
30
AF-S50CX
AF-S55CX
AF-S60CX
Insufficient cooling(Both compressor and compressor operate)
Check the temperature setting.
OK too high
Set the lower temperature.
dirty
Check the air filter.
not dirty
Clean the air filter.
Is there high heat source or any object restricting heat radiation near the unit.
there isn't there is
Remove the high heat source or stop.
Check doors and windows.
close open
Doors and windows must be kept closed.
Check the outdoor and indoor heat exchanger.
not dirty dirty
Clean them with steam cleaner or another method.
Calculate heat load wit using
Cooling load estimate form.
OK
Check rotating direction of centrifugal fan.(to clockwise)
OK
Check changing fan speed properly.
OK
Undersized air conditioner
NG
NG
Change unit to proper sized air conditioner.
Check the fan motor connector.
NG
OK
Measure the resistance of fan motor coil.
OK
NG
Change the fan motor.
Connect properly.
Is the outdoor temperature too high ?
under 40ûC over 40ûC
Avoid sun light and ventilate well for outdoor heat exchanger.
Check the thermister.
OK
NG
Change the thermister.
Measure temperature difference between inlet and outlet air at indoor.
over 10ûC under 10ûC
Is frost sticking to capillary tube ?
Or is indoor heat exchanger no cold ?
NO
YES
Is the refrigerant leaked ?
NO
The capillary tube restrict, and change the capillary tube.
YES
Repair leakage and recharge
the refrigerant.
Measure the emperature difference between discharge tube and suction tube.
No temperature difference temperature difference
The compressor is defective.
Change the compressor.
Checking complete.
31
AF-S50CX
AF-S55CX
AF-S60CX
Excessive vibration or Abnormal noise
At fan only mode,
Excessive vibration
or Abnormal noise
NO
YES
Check the air filter not dirty dirty
Clean the air filter.
Check rotating direction of centrifugal fan.(to clockwise)
OK
NG
Check the fan motor connector.
OK
Measure the resistance of fan motor coil.
OK
NG
NG
Change the fan motor.
Connect properly.
Is the fan deformed or broken.
OK deform or broken
Change the fan
Is loosened screw and nut fixing fan ?
OK loosened
Tighten up.
Is each screws loosened ?
OK
Checking complete loosen
Tighten up
Is pipe touching to another parts.
OK touching
Repair with adjusting shape of pipes.
Check mounting of compressor.
OK
NG
Repair mounting or change compressor cushion.
Check compressor noise and vibration.
OK too big
Change compressor.
Checking complete
32
AF-S50CX
AF-S55CX
AF-S60CX
COOLING LOAD ESTIMATE FORM
INSTRUCTIONS FOR USING COOLING LOAD ESTIMATE FORM FOR ROOM AIR CONDITIONERS
(AHAM PUB. NO. RAC-1)
A. This cooling load estimate form is suitable for estimating the cooling load for comfort air conditioning installations which do not require specific conditions of inside temperature and humidity.
B. The form is based on an outside design temperature of 95˚F dry bulb and 75˚F wet bulb. It can be used for areas in the continental United States having other outside design temperature by applying a correction factor for the particular locality as determined from the map.
C. The form includes "day" factors for calculating cooling loads in rooms where daytime comfort (such as living rooms, offices, etc.).
D. The numbers of the following paragraphs refer to the correspondingly numbered item on the form:
1. Multiply the square feet of window area for each exposure by the applicable factor. The window area is the area of the wall opening in which the window is installed. For windows shaded by inside shades or venetian blinds, use the factor for "Inside Shades". For windows shades by outside awnings or by both outside awnings and inside shades (or venetian blinds), use the factor for "Outside Awnings". "Single Glass" includes all types of single thickness windows, and "Double Glass" includes sealed air space types, storm windows, and glass block. Only one number should be entered in the right-hand column for item 1, and this number should represent only the exposure with the largest load.
2. Multiply the total square feet of all windows in the room by the applicable factor.
3a. Multiply the total length (linear feet) of all walls exposed to the outside by the applicable factor. Doors should be considered as being part of the wall. Outside walls facing due north should be calculated separately from outside walls facing other directions. Walls which are permanently shaded by adjacent structures should be considered as being "North Exposure". Do not consider trees and shrubbery as providing permanent shading. An insulated frame wall or a masonry wall 8 inches or less in thickness is considered "Light Construction". An insulated frame wall or a masonry wall over 8 inches in thickness is considered "Heavy Construction".
3b. Multiply the total length (linear feet) of all inside walls between the space to be conditioned and any unconditioned spaces by the given factor. Do not include inside walls which separate other air conditioned rooms.
4. Multiply the total square feet of roof or ceiling area by the factor given for the type of construction most nearly describing the particular application. (Use one line only.)
5. Multiply the total square feet of floor area by the factor given. Disregard this item if the floor is directly on the ground or over a basement.
6. Multiply the number of people who normally occupy the space to be air conditioned by the factory given. Use a minimum of 2 people.
7. Determine the total number of watts for lights and electrical equipment, except the air conditioner itself, that will be in use when the room air conditioning is operating. Multiply the total wattage by the factor given.
8. Multiply the total width (linear feet) of any doors or arches which are continually open to an unconditioned space by the applicable factor.
NOTE: Where the width of the doors or arches is more than 5 feet, the actual load may exceed the calculated value. In such cases, both adjoining rooms should be considered as a single large room, and the room air conditioner unit or units should be selected according to a calculation made on this new basis.
9. Total the loads estimated for the foregoing 8 items.
10. Multiply the sub total obtained in item 9 by the proper correction factor, selected from the map, for the particular locality. The result is the total estimated design cooling load in BTU per hour.
E. For best results a room air conditioner unit or units having a cooling capacity rating (determined in accordance with the NEMA Standards Publication for Room Air Conditioners, CN 1-1960) as close as possible to the estimated load should be selected. In general, a greatly oversized unit which would operate intermittently will be much less satisfactory than one which is slightly undersized and which would operate more nearly continuously.
F. Intermittent loads such as kitchen and laundry equipment are not included in this form.
33
AF-S50CX
AF-S55CX
AF-S60CX
HEAT GAIN FROM
1. WINDOWS: Heat gain from sun.
Northeast
Southeast
South
Southwest
Southeast
West
Northwest
North
QUANTITY
FACTORS
DAY
BTU/Hr
(Quantity x Factor) sq ft sq ft sq ft sq ft sq ft sq ft sq ft
No
Shades
60
80
75
75
110
150
120
0
Inside
Shades
25
40
30
35
45
65
50
0
Outside
Shades
20
25
20
20
30
45
35
0
(Area a
Factor)
Use only the largest load
Use only
only
These factors are for single glass only. For glass block, multiply the above factors by 0.5: for double-glass or storm windows, multiply the above factors by 0.8.
2. WINDOWS: Heat gain by conduction.
(Total of all windows)
Single glass
Double glass or glass block
3. WALLS: (Based on linear feet of wall.) a. Outside walls
Noth exposure
Other than North exposure b. Inside Walls (between conditioned
and unconditioned spaces only)
4. ROOF OR CEILING: (Use one only.) a. Roof, uninsulated b. Roof, 1 inch or more insulation c. Ceiling, occupied space above.
d. Ceiling, insulated with attic space
above e. Ceiling, uninsulated, with attic space
above
5. FLOOR: (Disregard if floor is directly
on ground or over basement.)
6. NUMBER OF PEOPLE:
7. LIGHTS AND ELECTRICAL
EQUIPMENT IN USE
8. DOORS AND ARCHES
CONTINUOUSLY OPENED TO
UNCONDITIONED SPACE:
(Linear feet of width.)
9. SUB-TOTAL
10. TOTAL COOLING LOAD:
(BTU per hour to be used for selection
of room air conditioner(s).) watts x x x x x ft
(Item 9) x sq ft sq ft sq ft sq ft sq ft sq ft sq ft sq ft ft ft ft
Light Construction
30
60
19
8
3
5
12
3
600
14
7
30
Heavy Construction
20
30
3
300 x x x x x
(Factor from Map) =
FARGO
EUGENE
SACRAMENT
FRESNO
RENO
LAS VEGAS
PHOENIX
PUEBLO
WICHITA
GREEN BAY
ROCHESTER
BIRMINGHAM
COLUMBIA
ATLANTA
ALBANY
NEW HAVEN
SAN ANTONIO
34
RUNNING CONDITION
Note:
1. Select mode of the Running Condition of a Room Air Conditioner.
SELECTOR .................................................................................................... HIGH COOL
THERMOSTAT .............................................................................................. 64˚F
2. Data of Performance Curve is measured between 40%RH and 70%RH.
If you measure the Room Air Conditioner above or below this rating, the data may miss the range of the performance curve.
3. Outlet air temp. is influenced by the method of measurement. Measurement examples are shown.
4. Use power input data when checking the Running Condition.
AF-S50CX
AF-S55CX
AF-S60CX
600
500
400
300
6
5
4
3
30
(86)
20
(68)
10
(50)
25
(77)
RUNNING CONDITION FOR
MODEL AF-S50CX / AF-S55CX
PERFORMANCE CURVE
30
(86)
35
(95)
Outside air temp.˚C (˚F)
40%RH
70%RH
40%RH
700
600
5
70%RH
70%RH
40%RH
40
(104)
4
30
(86)
20
(68)
10
(50)
25
(77)
500
400
7
6
RUNNING CONDITION FOR
MODEL AF-S60CX
PERFORMANCE CURVE
30
(86)
35
(95)
Outside air temp.˚C (˚F)
40%RH
70%RH
40%RH
70%RH
70%RH
40%RH
40
(104)
35
AF-S50CX
AF-S55CX
AF-S60CX
PACKING AND ACCESSORIES
TOP PAD ASSEMBLY (DPADBA004JBFZ)
Top pad L
Top pad R
4
5
6
3
Front side
6
5
Accessories
Operation manual
Window sash foam seal
Window sash seal
Bottom gasket
Screws
Base pan angle
Right closure assembly
Left closure assembly
Remote control
Battery
Remote control hook
Packing case
SPAKCA996JBEZ: AF-S50CX
SPAKCB050JBEZ: AF-S55CX
SPAKCA997JBEZ: AF-S60CX
"Front side" mark
2
Enegry card
TLAB-C213JBEZ: AF-S50CX
TLAB-C270JBEZ: AF-S55CX
TLAB-C214JBEZ: AF-S60CX
Protect
(SSAKHA009JBEZ)
Energy star label
(TLAB-C277JBRZ)
Power supply cord
1
Bottom pad assembly
(CPADBA046JBKZ)
Detail is assembling
Energy card
36
1-19
1-19
1-19
1-20
1-20
1-20
1-21
1-22
1-22
1-22
1-15
1-16
1-16
1-16
1-17
1-17
1-17
1-18
1-18
1-18
1- 7
1- 8
1- 9
1-10
1-11
1-12
1-13
1-14
1-15
1-15
1- 1
1- 2
1- 3
1- 4
1- 5
1- 5
1- 5
1- 6
1- 6
1- 6
1-28
1-28
1-29
1-30
1-31
1-32
1-33
1-34
1-35
1-35
1-35
1-23
1-23
1-23
1-24
1-25
1-26
1-27
1-27
1-27
1-28
REF. NO.
2- 1
2- 2
2- 3
2- 4
2- 5
2- 6
REPLACEMENT PARTS LIST
PART NO.
DESCRIPTION
CABINET AND UNIT PARTS
DCHS-A441JBTA Base pan ass’y
CCAB-A316JBKZ Cabinet ass’y
LANG-A503JBTA Top inst. angle
PSEL-C357JBEZ Cabinet insulator
HPNLCA802JBFA Control panel [AF-S50CX]
HPNLCA802JBFA Control panel [AF-S60CX]
HPNLCA802JBFB Control panel [AF-S55CX]
HPNLCA811JBEA Key sheet [AF-S50CX]
HPNLCA811JBEA Key sheet [AF-S60CX]
HPNLCA810JBEA Key sheet [AF-S55CX]
PKESPA091JBFZ Condenser shroud
PSEL-C351JBEZ Condenser indulator
NFANPA106JBFZ Propeller fan
CMOTLA998JBEZ Fan motor
PSEL-A828JBE0 Motor insulator
PSKR-A239JBFA Bulkhead
PKESSA067JBFZ Caseing
NFANSA027JBF0 Centrifugal fan
PKESSA066JBFA Orifice [AF-S50CX]
PKESSA066JBFA Orifice [AF-S60CX]
PKESSA066JBFB Orifice [AF-S55CX]
MLOV-A321JBFA Vertical louver A [AF-S50CX]
MLOV-A321JBFA Vertical louver A [AF-S60CX]
MLOV-A321JBFB Vertical louver A [AF-S55CX]
MLOV-A322JBFA Vertical louver B [AF-S50CX]
MLOV-A322JBFA Vertical louver B [AF-S60CX]
MLOV-A322JBFB Vertical louver B [AF-S55CX]
MJNTPA089JBFA Louver joint [AF-S50CX]
MJNTPA089JBFA Louver joint [AF-S60CX]
MJNTPA089JBFB Louver joint [AF-S55CX]
MLOV-A323JBFA Horizontal louver [AF-S50CX]
MLOV-A323JBFA Horizontal louver [AF-S60CX]
MLOV-A323JBFB Horizontal louver [AF-S55CX]
MJNTPA090JBFA Louver link [AF-S50CX]
MJNTPA090JBFA Louver link [AF-S60CX]
MJNTPA090JBFB Louver link [AF-S55CX]
MSPR-A148JBEZ Louver spring
GWAKPA150JBFA Front panel [AF-S50CX]
GWAKPA150JBFA Front panel [AF-S60CX]
GWAKPA150JBFB Front panel [AF-S55CX]
PFILMA162JBEA Air filter [AF-S50CX]
PFILMA162JBEA Air filter [AF-S60CX]
PFILMA162JBEB Air filter [AF-S55CX]
PSEL-C254JBEZ Tube insulator
LHLDW0364JBE0 Wire holder
LHLDW0366JBE0 Wire holder
TSPC-E073JBRZ Name badge [AF-S50CX]
TSPC-E140JBRZ Name badge [AF-S55CX]
TSPC-E074JBRZ Name badge [AF-S60CX]
TLAB-C213JBEZ Energy card [AF-S50CX]
TLAB-C270JBEZ Energy card [AF-S55CX]
TLAB-C214JBEZ Energy card [AF-S60CX]
TLABBA110JBRA Sharp badge
TLABKA564JBE0 Number card
TLABMA326JBRZ Feature card
LBND-A042JBE0 Wire fixing band
TLAB-C277JBRZ Energy star label
DSKR-A126JBKZ Bulkhead ass'y
DKES-A029JBKZ Orifice ass'y [AF-S50CX]
DKES-A029JBKZ Orifice ass'y [AF-S60CX]
DKES-A030JBKZ Orifice ass'y [AF-S55CX]
CONTROL BOX PARTS
DPLT-A057JBWZ Cont. box cover ass’y
DPLT-A058JBWZ Cont. box angle ass’y
LBNDKA104JBWZ Capacitor clamp
QACC-A260JBZZ Power supply cord
RH-HXA006JBZZ Thermistor
QW-VZC561JBE0 Lead wire
37
AF-S50CX
AF-S55CX
AF-S60CX
1
1
1
1
1
1
Q'TY CODE
1
2
1
1
1
4
4
4
1
1
3
3
1
1
1
1
1
1
1
3
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
1
1
AC
AF
AV
AV
AV
AC
AC
AC
AC
AC
AC
AC
AC
AC
AC
AR
AC
AC
AC
AC
AX
AH
AU
AH
AH
AS
AC
AR
BK
AB
AE
AE
AS
AS
AN
BA
BB
AP
AE
AE
AC
AB
AW
AW
AW
AV
AC
AC
AB
AC
AE
AA
AC
AC
AC
AC
AK
AK
AK
AC
AA
AH
AM
AG
AS
AK
AD
4- 9
4-10
4-11
4-12
4-13
4-14
4-15
4-16
4-17
4-18
4-19
4- 1
4- 2
4- 3
4- 4
4- 5
4- 6
4- 7
4- 8
3- 7
3- 8
3- 8
3- 8
3- 9
3-10
3-10
3-10
3-11
3-12
3- 1
3- 1
3- 1
3- 2
3- 3
3- 4
3- 5
3- 6
3- 6
3- 6
3- 7
3- 7
3-13
3-14
3-14
3-15
3-15
3-16
3-17
3-17
3-17
3-18
AF-S50CX
AF-S55CX
AF-S60CX
REF. NO.
2-10
2-11
2-12
2-13
2-14
2-15
2-16
2-17
2- 7
2- 8
2- 8
2- 8
2- 9
2- 9
2- 9
2-10
2-10
PART NO.
DESCRIPTION
RC-HZA256JBE0 Fan motor capacitor
RC-HZA136JBZ0 Running capacitor [AF-S50CX]
RC-HZA136JBZ0 Running capacitor [AF-S55CX]
RC-HZA393JBE0 Running capacitor [AF-S60CX]
TLABCB587JBRZ Wiring diagram [AF-S50CX]
TLABCB587JBRZ Wiring diagram [AF-S55CX]
TLABCB582JBRZ Wiring diagram [AF-S60CX]
DPWBFA278JBKZ Control board unit [AF-S50CX]
DPWBFA278JBKZ Control board unit [AF-S60CX]
DPWBFA244JBKZ Control board unit [AF-S55CX]
PSPA-A158JBZZ PWB Spacer
PSPA-A159JBZZ PWB Spacer
QFS-AA048JBE0 Fuse
LBND-A042JBE0 Wire fixing band
QW-IZA038JBZZ Comp. wiring
PPLT-A299JBEZ Insulator sheet
PPLT-A301JBEZ Insulator sheet
CYCLE PARTS
PCMPRA364JBEZ Compressor [AF-S50CX]
PCMPRA364JBEZ Compressor [AF-S55CX]
PCMPRA362JBEZ Compressor [AF-S60CX]
GLEG-A103JBE0 Compressor cushion
PPIPCF683JB1Z Discharge tube
PCON-A485JBEZ Condenser
PPIPCF491JB1Z Lead tube
DCPY-A274JBKZ Capillary tube ass’y [AF-S50CX]
DCPY-A274JBKZ Capillary tube ass’y [AF-S55CX]
DCPY-A273JBKZ Capillary tube ass’y [AF-S60CX]
PEVA-A454JBEZ Evaporator [AF-S50CX]
PEVA-A454JBEZ Evaporator [AF-S55CX]
PEVA-A461JBEZ Evaporator [AF-S60CX]
CPIP-A028JBKZ Suction tube ass’y [AF-S50CX]
CPIP-A028JBKZ Suction tube ass’y [AF-S55CX]
CPIP-A029JBKZ Suction tube ass’y [AF-S60CX]
PSEL-B160JBE0 Terminal gasket
RHOG-A201JBZZ Overload relay [AF-S50CX]
RHOG-A201JBZZ Overload relay [AF-S55CX]
RHOG-A200JBZZ Overload relay [AF-S60CX]
MSPR-A114JBE0 Protector spring
PCOV-A371JBE0 Terminal cover
PSEL-B161JBE0 Gasket washer
PGUM-A113JBE0 Damper rubber [AF-S50CX]
PGUM-A113JBE0 Damper rubber [AF-S55CX]
LBND-A046JBE0 Wire fixing band [AF-S50CX]
LBND-A046JBE0 Wire fixing band [AF-S55CX]
LHLD-A315JBF0 Thermistor holder
PSEL-C250JBEZ Evaporator insulator [AF-S50CX]
PSEL-C250JBEZ Evaporator insulator [AF-S55CX]
PSEL-C289JBEZ Evaporator insulator [AF-S60CX]
LBND-A042JBE0 Wire fixing band
ACCESSORY PARTS
TINSEA326JBRZ Operation manual
LANGAA011JBFE Left closure frame
LANGAA012JBFE Right closure frame
PPLTPA016JBFB Closure
PSEL-A931JBE0 Window insulator
PSEL-A932JBE0 Window insulator
PSEL-C251JBEZ Window insulator
TCAD-A351JBEZ Consummer card
DX-BZA016JBK0 Screws kit
SSAKAA018YDE0 Bag
XCTSD40P10000 Tapping screw
XMPSD40P25000 Wood screw
LANGAA030JBTA Base pan angle
CRMC-A526JBEZ Remote control
LHLD-A389JBFB Controller holder
SPADBA163JBEZ Card board
SSAKHA009JBEZ Bag
UBATUA027JBE0 Battery pack
CFZK-C019JBKZ Closure ass’y
38
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
3
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
6
7
2
2
1
1
1
1
1
1
1
Q'TY CODE
1
2
1
1
3
1
1
1
1
1
1
1
1
1
1
1
1
BF
AD
AD
AB
AC
AS
AG
AA
AB
AB
AA
BL
BL
AM
AU
AU
AW
AU
AU
AU
AF
AF
BM
AV
AV
AX
AH
AR
AR
AV
BD
BD
BZ
BZ
BZ
AG
AM
BQ
AF
AE
AB
AB
AC
AC
AH
AH
AH
AE
AE
AT
AC
AC
AC
AE
BB
AW
AB
AA
AA
AD
AC
AH
AH
AK
AH
AE
AC
AB
REF. NO.
6- 1
6- 2
6- 3
6- 4
6- 5
6- 6
6- 7
6- 8
6- 9
6-10
6-11
6-12
6-13
6-14
6-15
5- 1
5- 2
5- 3
5- 3
5- 3
5- 4
5- 5
5- 6
PART NO.
DESCRIPTION
PACKING PARTS
DPADBA004JBFZ Top pad ass’y
CPADBA046JBKZ Bottom pad ass’y
SPAKCA996JBEZ Packing case [AF-S50CX]
SPAKCB050JBEZ Packing case [AF-S55CX]
SPAKCA997JBEZ Packing case [AF-S60CX]
SSAKHA245YDE0 Protect
SSAKAA053YDE0 Bag
TLABMA331JBRZ Color label [AF-S55CX]
XTTSD40P20000 Tapping screw
XCTWJ40P16000 Tapping screw
XTTSD40P14000 Tapping screw
XTTSD40P12000 Tapping screw
XHTSD40P10000 Tap tight screw
XHTSD40P08000 Tap tight screw
XTPSD40P08000 Tapping screw
LX-BZA236JBE0 Special screw
LX-CZA038WRE0 Special screw
LX-HZA001JBE0 Special screw
LX-BZA140JBE0 Special screw
XBPSD40P12J00 Machine screw
LX-NZA074JBE0 Special nut
LX-NZA148JBE0 Frange nut
LX-NZA026JBE0 Special nut
SCREWS AND NUTS
4
3
1
4
1
4
2
7
14
6
2
2
1
1
3
AF-S50CX
AF-S55CX
AF-S60CX
Q'TY CODE
1
1
1
1
1
1
1
1
AH
AN
AP
AR
AP
AB
AB
AH
AA
AA
AC
AA
AB
AA
AA
AA
AA
AA
AB
AB
AB
AD
AC
HOW TO ORDER REPLACEMENT PARTS
To have your order filled prompty and correctly, please furnish the following information.
1. MODEL NUMBER 2. REF. NO.
3. PART NO.
4. DESCRIPTION
39
A
AF-S50CX
AF-S55CX
AF-S60CX
1 2
CABINET PARTS
4-9 4-16
4-17
4-10
4-11
4-12
4-3
3
4-19
B
4-14
4-8
4-1
4-5
4-7
4-6
4-15
4-18
4-13
6-4
C
6-10
4-4
6-5
4-2
4
6-11
1-4
6-1
6-5
1-34
1-10
1-11
6-1
6-13
1-9
6-4
1-3
5
6-4
1-8
5-3
6-9
6
6-11
1-2
A
6-9
B
C
D
1-12
1-26
6-4
1-7 1-30
D
5-1
E
1-13
1-32
1-24
1-26
6-3
1-25
5-6
[AF-S55CX only]
2-4
5-2
5-4
E
1-35 5-5
1-14
1-17
1-21
1-19
6-8
F F
1-16
1-20
1-18
6-3 1-15
6-4
1-29
G
1-22
6-2
1-33
1-28
6-3
1-23 6-3
1-1
6-4
G
1-31
6-2
1-27
H H
1 2 3 4 5 6
40
A
1 2
CONTROL BOX PARTS
3
1-6
B
1-5
C
2-17
6-7
2-10
6-7
6-12
6-6
D
E
2-5
2-10
2-16
6-4
2-3
2-8
6-5
4
2-6
2-13
F
6-6
5
2-12
G
2-14
6-6
2-1
6
AF-S50CX
AF-S55CX
AF-S60CX
A
B
C
2-2
2-11
2-7
6-5
D
E
2-4
F
2-9
6-4
G
H
1 2 3
41
4 5 6
H
A
AF-S50CX
AF-S55CX
AF-S60CX
1
CYCLE PARTS
2
B
C
D
6-3
E
F
3-16
3-17
3-7
6-5
3 4 5 6
A
6-14
3-13
3-12
3-11
3-10
3-9
3-4
6-15
3-3
2-15
B
C
3-8
3-1
3-5
3-6
3-15
[AF-S50CX/S55CX, only]
3-14
[AF-S50CX/S55CX, only]
D
E
3-18
6-15
3-2
F
G G
H
1 2 3
42
4 5 6
H
43
AF-S50CX
AF-S55CX
AF-S60CX
AF-S50CX
AF-S55CX
AF-S60CX
COPYRIGHT © 2002 BY SHARP CORPORATION
ALL RIGHTS RESERVED.
No part of this publication may be reproduced, stored in retrieval systems, or transmitted in any form or by any means, electronic, mechanical, photocopying, recording, or otherwise, without prior written permission of the publisher.
44 ’02 SHARP CORP. (3S0.85E) Printed in U.S.A.
advertisement
Key Features
- Cooling operation
- Fan only operation
- Timer functions
- Energy Saver mode
- Remote control
- Easy to operate
Frequently Answers and Questions
How do I set the timer on my air conditioner?
What is the Energy Saver mode?
How do I change the fan speed on my air conditioner?
How do I adjust the air flow direction?
Related manuals
advertisement
Table of contents
- 2 SPECIFICATIONS
- 4 EXTERNAL DIMENSIONS
- 5 HOW TO OPERATE
- 13 INSTALLATIOIN INSTRUCTIONS
- 16 DISASSEMBLING PROCEDURE
- 20 HOW TO REPAIR REFRIGERATION
- 23 ELECTRICAL COMPONENT TEST
- 24 MICROCOMPUTER CONTROL SYSTEM
- 28 TROUBLESHOOTING GUIDE
- 33 COOLING LOAD ESTIMATE FORM
- 35 RUNNING CONDITION
- 36 PACKING AND ACCESSORIES
- 37 REPLACEMENT PARTS LIST