ClimateMaster EarthPure R410A Guide
Add to my manuals8 Pages
ClimateMaster EarthPure R410A is a non-chlorine based (HFC) refrigerant, that with R407c and R134a, is considered the future of all refrigerants used worldwide. It has higher efficiencies, higher operating pressures, and requires POE oil in compressors. In some systems it can result in smaller heat exchangers with the same performance. It has low global warming potential and zero ozone depletion (0.39/0.0). ClimateMaster EarthPure R410A is a near azeotropic mixture of R32-50% and R125-50%, and has a temperature glide of 0.2°F.
advertisement
EarthPure
EarthPure R410a
Application and Service Guide
Release: 03/29/04
EarthPure
EarthPure Application and Service Guide
Although the bulk of this manual will be information regarding EarthPure R410a, R407c will also be discussed.
Consult the ClimateMaster Tech 1 service guide for a more detailed descriptions of the general procedures.
EarthPure R410a Overview
R410a is a non-chlorine based (HFC) refrigerant, that with R407c and R134a, is seen as the future of all refrigerants used worldwide. R410a characteristics compared to R22 are:
• Binary and near azeotropic mixture of R32-50% and R125-50%
• Higher effi ciencies
• Higher operating pressures
• Requires POE oil in compressors
• In some systems can result in smaller heat exchangers with the same performance
• Low global warming potential and zero ozone depletion (0.39/0.0)
• Temperature glide of 0.2°F
• Containers are “Rose” colored utilize a more traditional table with only one pressure column as shown in Table 2.
What is “Fractionation”?
Many of the newer refrigerants are a blend of two or more other refrigerants. At various conditions these components can separate and change the ratio of the original mixture and in effect change the total performance of the remaining blend. Therefore it is recommended to use the refrigerant in liquid form, insuring that all of the components are handled together in the proper blend.
R407c Overview
R407a is a non-chlorine based (HFC) refrigerant. R407c characteristics compared to R22 are:
• Ternary and near azeotropic mixture of R32-23%,
R125-25%, R134a-52%
• Slightly lower effi ciencies
• Nearly equal operating pressures
• Requires POE oil in compressors
• Considered a near drop-in replacement for R22
• Low global warming potential and zero ozone depletion (0.34/0.0)
• Temperature glide of 10°F
• Containers are “Medium Brown” colored
What is “Glide”?
Pure compounds like CFC-R12 boil and condense at exactly the same temperature for a given pressure. Nearazeotropic blends are not pure compounds but a blend of compounds. These compounds will have a temperature glide or range of temperatures in which the blend will boil or condense. In these situations, for example R407c, a chart listing a bubble and dew point will be used as the pressure/temperature chart since it has a glide of 10°F.
The bubble point is used for subcooling calculations and the dew point is used for superheat calculations as in
Table 1. R410a has a very small glide (0.2°F) and acts as a single component refrigerant. Therefore R410a can
100
105
110
115
120
125
130
135
80
85
90
95
60
65
70
75
140
145
150
40
45
50
55
20
25
30
35
0
5
10
15
° F
-15
-10
-5
Table 1. R407c Pressure/Temperature Chart
R407c
129.2
140.9
153.2
166.2
180.0
194.6
209.9
226.0
57.8
64.8
72.4
80.4
89.0
98.1
107.9
118.2
243.0
260.8
279.5
299.0
319.6
341.0
363.4
386.9
411.3
436.8
Bubble
Pressure
Dew
Pressure
(for subcooling) for (superheat) psig
17.2
21.0
25.1
29.5
34.4
39.6
45.2
51.3
psig
9.2
12.3
15.7
63.0
70.6
78.7
87.4
96.7
106.6
117.1
128.4
19.4
23.4
27.8
32.6
37.8
43.4
49.4
56.0
265.3
285.0
305.8
327.6
350.5
374.6
399.8
140.4
153.1
166.5
180.8
195.9
211.9
228.7
246.5
Page 2
Table 2. R410a Pressure/Temperature Chart
R410a
Pressure psig
340.6
365.1
390.9
418.0
446.5
476.5
508.0
541.2
576.0
612.8
185.1
201.0
217.8
235.6
254.5
274.3
295.3
317.4
87.5
97.2
107.5
118.5
130.2
142.7
156.0
170.1
31.3
36.5
42.2
48.4
55.1
62.4
70.2
78.5
° F
105
110
115
120
125
130
135
140
145
150
85
90
95
100
65
70
75
80
45
50
55
60
25
30
35
40
5
10
15
20
-15
-10
-5
0
Component Considerations for R410a
Compressor
Wall thickness has increased with the increase of operating pressures of R410a. The internal pressure relief valve setting has been increased from 375-450 psig for R22 to
550-625 psig for R410a. Although the discharge pressure is higher in R410a the discharge temperature should be lower due its higher vapor heat capacity. Desuperheating hot water generators must be designed around this lower hot gas temperatures as well. High pressure switches will now open at 600 psig ±10 psig and reset at 450 ±10 psig.
The compressor oil must be polyolester (POE) based.
Mineral oils should never be used. POE oils also absorb
EarthPure Application and Service Guide moisture very easily. For this reason any compressor using POE oil should only be exposed to ambient air for short periods of time during manufacture or service. See the service section of this manual for more information.
Condenser/Evaporator Heat Exchangers
The heat exchangers must be designed to have a working pressure above the 600 psig level. In some cases this can mean a thicker wall.
Filter Driers
Liquid fi lter driers must have working pressure of no less than 600 psig and be approved for use with R410a. A
100% molecular sieve with no activated Alumina is recommended for maximum moisture removal. It is always required to install a new fi lter drier whenever the system is opened.
Suction line fi lter driers should only be used after a burn out and should be removed after an appropriate clean-up time.
Thermostatic Expansion Valves
R410a metering devices are about 15% smaller than R22 devices. The selective charge used in the bulb must be matched for R410a operation, therefore a txv must be designed for R410A use. Metering devices for R22 and
R410a are NOT interchangeable.
Refrigerant Tubing
There are no general changes to the tubing other than the working pressure increase to 600 psig. Generally the lower refrigerant fl ow rate of R410a versus R22 does not result in any pipe diameter changes.
Polyolester Oils
POE oils are very hygroscopic. That is to say they readily absorb moisture and hold it. For this reason POE oils should be limited in their exposure to ambient air during manufacture or service. The lubricant should be exposed to ambient air for no more than 15 minutes. Always store
POE oil in glass or metal containers. Pumps are recommended to move the oil from containers to the refrigeration system. If the system is under a vacuum, break the vacuum with the refrigerant or dry nitrogen. It is never recommended to break the vacuum with air. Liquid line fi lter driers should be used to remove any moisture in the system. Charging system may also contain a replaceable fi lter drier for improved moisture removal. In summary:
• POE oil is hygroscopic and will readily absorb moisture
• Never store POE oil in plastic containers. Always use metal or glass
• Use a pump to transfer POE lubricants
• Use an approved POE lubricant. They arenʼt all interchangeable
Page 3
EarthPure Application and Service Guide
Figure 1. PPM of Water Absorbed Over Time
PPM of
Water
POE: Continues to absorb moisture
Mineral Oils: Max water absorption, excess separates
24 hrs Time
• A vacuum pump will not adequately remove moisture from the POE lubricants. Use a fi lter drier and replace whenever the system is opened.
• POEʼs can be irritating to the skin
• POEʼs can damage some roofi ng membrane materials
• POEʼs are better solvents than mineral oils
• Leave POE Refrigerant circuits open no more than
15 minutes
Approved POE Oils for Copeland R410a and R407c compressors are:
• Copeland Ultra 22CC
• Copeland 3MA (scroll compressors only)
• Mobil EAL Arctic 22CC
• ICI (Virginia KMP) Emkarate RL32CF
• Thermal Zone 22CC
Service Tools
It is recommended that a separate R410a tool set be employed to avoid the problem of mixing refrigerants on the job site.
Gauge Manifold Sets
A specifi c gauge set for use with R410a is required.
These will allow pressure measurements to 800 psig on the high side and 250 psig on the low side. Hoses will have a service rating of 800 psig.
Vacuum Pump
A 500 micron evacuation will not be suffi cient to separate moisture from POE oil in R410a systems. It is for this reason that an R410a approved liquid line fi lter drier should be installed everytime the system is opened.
Leak Detectors
An approved leak detector for HFC refrigerants can be used in R410a systems. Older R22 leak detectors and Halide torch leak detectors can not be used in R410a service.
Never use a mixture of air and R410a to leak check. As a mixture it may become fl ammable at pressures above amtospheric. Nitrogen and trace R410a or nitrogen alone can be safely used for leak testing in R410a systems. Six approved leak detector types for alternative refrigerants are:
• Non-selective detectors
• Halogen specifi c
• Compound specifi c
• Infrared based
• Flourescent dyes
• Ultrasonic
Active Recovery Equipment (Self-Contained)
Due to the increased pressure of R410a, recovery equipment has been redesigned to handle these higher pressures. Recovery equipment rated for R410a must be used.
Recovery cylinders must have a service pressure rating of
400 psig (DOT 4BA 400 and DOT 4BW 400 are acceptable). DO NOT USE STANDARD DOT RECOVERY
OR STORAGE CYLINDERS WITH A 300 PSIG RAT-
ING WITH R410A!
Other Service Tools
Other service tools such as the micron gauge and vacuum pump are adequate for both R22 and R410a service.
Service Procedures
Leak Detection
If an R410a system develops a leak, the technician does not have to recover the the remaining refrigerant from the system before topping-off the system. Because R410a is close to being an azeotropic blend, it behaves like a pure compound or single component refrigerant. The technician can use the existing refrigerant in the system after leaks have occurred. There is no signifi cant change in the refrigerant composition during multiple leaks and recharges. However the service technician must remember that when adding R410a to the system, it must come out of the charging cylinder as a liquid to avoid fractionation and for optimum system performance. If the refrigeration system has lost its complete charge, the system should be leak checked, repaired, liquid line fi lter drier replaced and evacuated below 500 microns. A digital scale or a calibrated charging cylinder designed for the greater pressures of R410a should then be used to recharge R410a back into the system.
The Refrigerant Recycling Regulations Section 608 of the Clean Air Act states that the technician must fi nd and repair substantial leaks of systems with 50 lbs. or more of refrigerant. Substantial leaks are defi ned as:
Page 4
• 35% annual leak rate of commercial and industrial refrigeration
• 15% annual leak rate comfort cooling chillers and all other equipment
R407c Considerations
R407c equipment for leak detection are the same as
R410a. However, the technician CANNOT use the existing refrigerant in the system after leaks have occurred.
There can be a signifi cant change in the refrigerant composition during multiple leaks and recharges. Unit should be recharged using the ClimateMaster's recommended charge. However the service technician must remember that when adding R407c to the system, it must come out of the charging cylinder as a liquid to avoid fractionation and for optimum system performance
Refrigerant Recovery
Use an R410a approved recovery device. Due to the increased pressure of R410a, recovery equipment has been redesigned to handle these higher pressures. Recovery equipment rated for R410a must be used. Recovery cylinders must have a service pressure rating of 400 psig
(DOT 4BA 400 and DOT 4BW 400 are acceptable). DO
NOT USE STANDARD DOT RECOVERY OR STOR-
AGE CYLINDERS WITH A 300 PSIG RATING WITH
R410A! As stated earlier, a specifi c gauge set for use with
R410a is required. These will allow pressure measurements to 800 psig on the high side and 250 psig on the low side. Hoses will have a service rating 800 psig.
R407c storage tanks do not need the higher pressure ratings.
Figure 2. Triple Vacuum Procedure
EarthPure Application and Service Guide
Evacuation
ClimateMaster recommends two evacuation methods, the deep vacuum method and the “Triple Vac” method.
The Deep Vacuum Method
The deep vacuum method requires a vacuum pump capable of at least a 500 micron vacuum and a micron gauge capable of measuring this vacuum. The deep vacuum method is the most positive way of assuring a system is free of air and moisture and is the recommended method by ClimateMaster.
Triple Vacuum Method
The triple vac method should only be used when the vac pump is not capable of pulling a 500 micron vacuum.
Note: Warranty labor allowance may not cover the
complete service time with this method. See Figure 2.
Figure 3. Vacuum and Time the following is the Triple Vac procedure.
1. The unit should be evacuated to at least 29.72 in.
Hg.
2. Break the vacuum with dry nitrogen and wait 1 hour.
3. Evacuate until at least 29.72 in. Hg. is reached and then continue for 15 minutes.
4. Break the vacuum with dry nitrogen and wait 1 hour.
5. Evacuate until at least 29.72 in. Hg. is reached and then continue for 20 minutes.
6. Isolate and Turn Vac Pump Off and wait. Vac measurement should stay low and not rise above 29.5 other wise leak or moisture still remains in system.
Refrigerant Charging
An undercharged txv unit can be identifi ed by:
• Low evaporating pressure
• High superheat
• Low subcooling
Page 5
EarthPure Application and Service Guide
An overcharged txv unit can be identifi ed by:
• High subcooling
• High head pressures
Even though R410a has a very small fractionation potential it cannot be ignored completely when charging.
To avoid fractionation. charging of a system with R410a should be done with LIQUID from the tank to maintain optimum system performance. To insure that the proper blend of refrigerant be used, it is important that liquid only be removed from the storage tank. Some cylinders use dip tubes which allow liquid to be extracted from the cylinder. These can be identifi ed as recovery tanks with yellow tops and gray bottom and have a dual liquid and vapor valve assembly. Storage tanks without dip tubes will need to be tipped upside down in order for liquid to be removed. Once the liquid is removed from the storage cylinder, it can be charged into the system in the vapor state as long as all of the refrigerant is used from the charging cylinder. Liquid charging can be accomplished by using:
• A throttling valve (Figure 3) to insure the liquid vaporizes as it enters the suction line of the unit.
• Τ he gauge set as a throttling device and restrict liquid from fl ooding the compressor during charging.
Recharging should always be accomplished by using the nameplate charge. When this is not possible, charging using the subcooling method can be done using the following procedure. This method requires accurate gauges and a digital strap-on temperature meter.
1. Operate system for 10 minutes to stabilize.
2. Insure that the unit has proper water and air fl ow and the air fi lter is clean.
3. Attach gauges to discharge port and record the saturation temperature at this pressure using a pressure/temperature chart for R410a.
4. Measure the liquid line (LL) temperature (between aircoil and txv in heating and between coax and txv in cooling).
5. Subtract the LL temperature from the saturation pressure to fi nd the subcooling. Consult Table 4 for appropriate values.
6. If the subcooling is too low add 2-4 oz., or too high, remove 2-4 oz. Typical values are shown in
Table 4.
Superheat can be calculated similarly. This method also requires accurate gauges and a digital strap-on thermometer. Operate system for 10 minutes to stabilize.
2. Insure that the unit has proper water and air fl ow and the air fi lter is clean.
3. Attach gauges to suction port and record the saturation temperature at this pressure using a pressure/ temperature chart for R410a.
Table 4. Tranquility Typical Pressure and Temperatures (TT*064 Shown)
TT*064 Full Load Cooling - without HWG active Full Load Heating - without HWG active
Entering
Water
30
50
70
90
110
Water
Flow GPM
15.0
7.5
11.3
15.0
7.5
11.3
15.0
7.5
11.3
15.0
7.5
11.3
15.0
7.5
11.3
Suction
Pressure
PSIG
117-127
116-126
115-125
128-138
126-136
125-135
135-145
134-144
133-143
139-149
138-148
138-148
144-154
143-153
142-152
Discharge
Pressure
PSIG
170-190
143-163
135-155
238-258
222-242
205-225
315-335
296-316
276-296
408-428
386-406
364-384
515-535
493-513
469-489
Super-heat
15-20
10-15
10-15
10-15
8-13
8-13
8-13
27-32
28-33
29-34
16-21
21-26
26-31
10-15
12-17
Subcooling
11-16
15-20
13-18
11-16
14-19
13-18
12-17
15-20
13-18
12-17
14-19
13-18
12-17
14-19
13-18
HWG should be disabled for accurate chart comparison
*Based on Nominal 400 cfm per ton airflow and 70°F EAT ° F EA cooling
**Cooling air and water numbers can vary greatly with changes in humidity
Subcooling is based upon the head pressure at compressor service port
Page 6
Water
Temp Rise
F
18.2-20.2
12.6-14.6
7-9
20.5-22.5
14.9-16.9
9.2-11.2
21-23
15.5-17.5
10-12
20.1-22.1
14.8-16.8
9.5-11.5
19-21
14-16
9-11
Temp
Drop F DB
22-28
21-27
21-27
21-27
20-26
20-26
20-26
17-23
17-23
17-23
21-27
21-27
21-27
22-28
22-28
Suction
Pressure
PSIG
66-76
69-79
72-82
90-100
95-105
99-109
115-125
120-130
126-136
157-167
161-171
166-176
Discharge
Pressure
PSIG
282-302
285-305
289-309
310-330
313-333
316-336
337-357
341-361
345-365
390-410
394-414
398-418
Super-heat
10-16
10-16
10-16
11-17
11-17
11-17
12-18
12-18
12-18
15-20
15-20
15-20
Subcooling
9-14
9-14
10-15
12-17
12-17
12-17
14-19
14-19
15-20
14-19
14-19
15-20
Water
Temp Drop
F
8-10
6-8
4-6
11.3-13.3
8.5-10.5
5.7-7.7
14-16
10.6-12.6
7.3-9.3
18.2-20.2
13.9-15.9
9.6-11.6
Temp
Rise F DB
19-25
19-25
20-26
24-30
25-31
26-32
28-35
29-36
30-37
37-45
38-46
39-47
4. Measure the suction line temperature just prior to entering the compressor.
5. Subtract the saturation temperature from the suction temperature to fi nd the superheat. Consult Table
4 for appropriate values.
6. If the superheat is too high then unit might still be undercharged. Txv's will mask overcharging in the superheat value by closing off the txv port and reducing the refrigerant fl ow. Therefore superheat CAN-
NOT be used to identify an overcharged unit. Typical values are shown in Table 4.
Brazing
Always use dry nitrogen when brazing and wrap all components with damp rags to reduce heat damage. Never unbraze a liquid line fi lter drier. Unbrazing a liquid line fi lter drier can release acids and contaminants back into the system.
R407C Considerations
Since R407c can fractionate, it should always be charged using liquid into the suction line at low enough rates to allow vaporization before it enters the compressor. The same procedure can be used for both R410a and R407c as long as proper respect is given to the fractionation problem. R407c pressure temperature chart requires the bubble column for subcooling calculations and the dew point column for superheat calculations.
System Cleanup After a Burnout
Some compressor electrical failures can cause the motor to burn and produce byproducts such as sludge and acid and contaminate the system. Test the oil for acid using a
POE oil acid test kit to determine severity. If burnout is severe enugh, the system must be cleaned before replacement compressor is installed. Burnouts can be classifi ed as mild and severe.
A mild burnout will have little to no characteristic odor.
Compressor oil is clear to slightly discolored. An acid test of the oil will be negative. The liquid line fi lter drier should be replaced along with the compressor.
A severe burnout will have a strong, pungent rotten egg odor. Compressor oil will be dark and evidence of burning may be present in tubing connected to the compressor.
An acid test of the compressor oil will be positive. Follow these additional steps:
1. TXV must be cleaned or replaced.
2. Drain any trapped oil from the accumulator (if present)
3. Replace liquid line fi lter drier.
4. After system is reassembled, install suction line fi lter drier (between compressor and accumulator if present).
EarthPure Application and Service Guide
5. Operate system for 10 hours. Monitor pressure drop across driers. If pressure drop exceeds 3 psi replace driers. Be sure to purge system with dry nitrogen when replacing driers. If suction line drier must be replaced retest pressure drop after additional
10 hours of operation. After 10 hrs. of operation remove suction line fi lter drier and replace liquid line fi lter drier. Never leave a suction line fi lter drier in the system for more than 72 hrs actual time.
Hot Water Generator Applications
The higher effi ciency but lower heat capacity of refrigerant R410a results in a lower hot water generator (HWG) capacity. At times the units hot gas temperature may even be lower than the entering hot water. For this reason, special controls are needed to turn off the HWG pump to avoid removing heat from the water heater (reverse of the the intended process) and causing excessive energy use in the water heater. The Tranquility series has these controls built in and will generally shut off the pump with hot gas temperatures below 125°F.
MSDS Overview-EarthPure R410a
Consult the MSDS sheet for details.
Toxicity – R410a is low toxicity
Flammability – DOT considers R410a non-fl ammable
Combustibility – At pressures above one atmosphere, mixtures of air and R410a can become combustible.
Ingestion – If ingestion does occur, induce vomiting and seek medical attention.
Skin and eye contact – Avoid contact with skin and promptly fl ush eyes and skin with clean lukewarm water if contact is made. POE oils can cause skin irritation.
Therefore gloves should be worn when handling POE lubricants. Promptly fl ush eyes and skin with clean lukewarm water if contact is made)
Inhalation – Inhaling high concentrations of refrigerant vapors can have a narcotic effect. A feeling of intoxication, dizziness loss of coordination and slurred speech are symptoms. Cardiac irregularities, unconsciousness, and ultimate death can result from breathing this concentration. If any of these symptoms become evident, move to fresh air and seek medical help immediately.
Refrigerant Decomposition – When refrigerants are exposed to high temperatures from open fl ames or heater elements, decomposition occurs. Decomposition produces toxic and irritating compounds, such as hydrogen fl uoride with HFCʼs. The acidic vapors produced are dangerous and the area should be evacuated and ventilated.
Page 7
Safety Overview
ASHRAE Standard 15 details safety precautions when handling refrigerants in commercial systems and should be read and understood. Refrigerants are especially dangerous in confi ned spaces.
• R410a has a much higher pressure (60%) associated with its operation and therefore has the potential for serious accidents.
• Use an R410a approved recovery device. Recovery cylinders must have a service pressure rating of 400 psig (DOT 4BA 400 and DOT 4BW 400 are acceptable). DO NOT USE STANDARD DOT
RECOVERY OR STORAGE CYLINDERS WITH A
300 PSIG RATING WITH R410A! NEVER LET A
CYLINDER GET ABOVE 125°F!
• The color code for R410A cylinders is “Rose” and
R407c is “Chocolate Brown”.
• A 410a specifi c gauge set is required. These will allow pressure measurements to 800 psig on the high side and 250 psig on the low side. Hoses will have a service rating 800 psig.
• Do not mix air and R410a. the resulting mixture can be fl ammable above atmospheric pressure.
• Do not mix R410a and other refrigerants. Gauges, manifold, and hoses should be evacuated after each use. Dedicated equipment for R410a will go a long way toward eliminating this concern.
• Consult the MSDS sheet for details on toxicity, fl ammability, ingestion limits etc.
• Exposure is the same as R22 – 40 hour work week.
*97B0036N01*
97B0036N01
7300 S.W. 44th Street
Oklahoma City, OK 73179
Phone: 405-745-6000
Fax: 405-745-6058 www.climatemaster.com
ClimateMaster works continually to improve its products. As a result, the design and specifi cations of each product at the time for order may be changed without notice and may not be as described herein. Please contact ClimateMasterʼs Customer Service Department at 1-405-745-6000 for specifi c information on the current design and spec i fi ca tions. Statements and other in for ma tion contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMasterʼs opinion or com men da tion of its products.
© ClimateMaster, Inc. 2004 Release: 03/29/04
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project