3103
Isolated repeater
3103
– Isolation and 1:1 conversion of standard current signals
– Slimline housing of 6 mm
– Response time < 7 ms
– Low cost
– Simple - no setup needed
Application
• Isolation and 1:1 conversion of standard current signals.
• Galvanic separation of analog current signals.
• Elimination of ground loops and measurement of floating
signals.
• A competitive choice in terms of both price and technology for
galvanic isolation of current signals to SCADA systems or
PLC equipment.
• Installation in ATEX Ex zone 2 / IECEx Zone 2 / FM division
2.
• Suitable for environments with high vibration stress, e.g.
ships.
Connections
Technical characteristics
• The input is protected against overvoltage and polarity error.
• Factory-calibrated measurement ranges.
• Inputs and outputs are floating and galvanically separated.
This page is automatically generated on the basis of information provided on www.prelectronics.com and affiliated websites. It is provided to you as a service and for information
purpose only. While we have attempted to maintain the information as accurately as possible, the page may contain errors or omissions for which we disclaim any and all liability
Environmental Conditions
Specifications range.......................................
Storage temperature......................................
Calibration temperature.................................
Relative humidity............................................
Protection degree...........................................
Installation in..................................................
Output specifications
-25°C to +70°C
-40°C to +85°C
20...28°C
< 95% RH (non-cond.)
IP20
Pollution degree 2 &
measurement / overvoltage
cat. II
Mechanical specifications
Dimensions (HxWxD).....................................
Weight approx................................................
DIN rail type...................................................
Wire size........................................................
113 x 6.1 x 115 mm
70 g
DIN EN 60715/35 mm
0.13 x 2.5 mm2 / AWG 26...12
stranded wire
Screw terminal torque.................................... 0.5 Nm
Vibration: 2...25 Hz........................................ ±1.6 mm
Vibration: 25...100 Hz.................................... ±4 g
Common specifications
Supply
Supply voltage............................................... 16.8...31.2 VDC
Isolation voltage
Isolation voltage, test /
working........................................................... 2.5 kVAC / 300 VAC
(reinforced)
Zone 2 / Div. 2................................................ 250 VAC
Current output
Signal range...................................................
Load (max.)....................................................
Load stability..................................................
Current limit....................................................
0...20.5 mA (span)
23 mA/600 Ω
≤0.01% of span / 100 Ω
≤ 28 mA
*of span.......................................................... = 0...20 mA
Observed authority requirements
EMC............................................................... 2004/108/EC
LVD................................................................ 2006/95/EC
RoHS.............................................................. 2011/65/EU
Approvals
ATEX 94/9/EC................................................ KEMA 10ATEX0147 X, II 3 G
Ex nA IIC T4 Gc
IECEx............................................................. KEM 10.0068X
FM.................................................................. 3041043-C
UL................................................................... UL 61010-1
DNV Marine.................................................... Stand. f. Certific. No. 2.4
GL.................................................................. V1-7-2
EAC................................................................ TR-CU 020/2011
EAC Ex TR-CU 012/2011.............................. RU C-DK.GB08.V.00410
CCOE............................................................. P337347/1
Response time
Response time (0...90%, 100...10%)............. < 7 ms
Max. power consumption...............................
Internal consumption......................................
Signal / noise ratio.........................................
Accuracy........................................................
0.8 W
0.4 W (typ.) / 0.65 W (max.)
> 60 dB
Better than 0.05% of selected
range
Temperature coefficient................................. < ±0.01% of span / °C
EMC immunity influence................................ < ±0.5% of span
Extended EMC immunity: NAMUR
NE 21, A criterion, burst................................. < ±1% of span
Input specifications
Current input
Measurement range....................................... 0...20.5 mA
Functional range............................................ 0...23 mA
Input voltage drop.......................................... < 1.5 VDC
3103-040716