SVF SIGNAL TRANSMITTER BEFORE USE .... MODEL

SVF SIGNAL TRANSMITTER BEFORE USE .... MODEL
SVF
INSTRUCTION MANUAL
SIGNAL TRANSMITTER
BEFORE USE ....
Thank you for choosing M-System. Before use, check the
package you received as below.
If you have any problems or questions with the product,
please contact M-System's Sales Office or representatives.
■ PACKAGE INCLUDES:
Signal conditioner (body + base socket + input resistor) ..... (1)
The resistor is provided only with current input type.
■ MODEL NO.
Check that model No. described on specification label is
exactly what you ordered.
■ INSTRUCTION MANUAL
This manual describes necessary points of caution when you
use this product, installation, connection and basic maintenance procedures.
POINTS OF CAUTION
■ CONFORMITY WITH EC DIRECTIVES
• This equipment is suitable for use in Pollution Degree 2
environment and in Installation Category II, with the maximum operating voltage 300V.
Basic insulation is maintained between the input and output.
Prior to installation, check that the insulation class of this
unit satisfies the system requirements.
• Altitude up to 2000 meters
• The equipment must be mounted inside a panel.
• The equipment must be installed such that appropriate
clearance and creepage distances are maintained to conform
to CE requirements. Failure to observe these requirements
may invalidate the CE conformance.
• Insert noise filters for the signal input and output connected to the unit. TDK Model ZCAT 3035-1330 or equivalent is recommended.
• The actual installation environments such as panel configurations, connected devices, connected wires, may affect
the protection level of this unit when it is integrated in a
panel system. The user may have to review the CE requirements in regard to the whole system and employ additional
protective measures to ensure the CE conformity.
■ POWER INPUT RATINGS
• Operational range & power consumption: Check the power
rating for the unit on the specification label.
AC ratings: Rating ±10%, 50/60 ±2 Hz, approx. 2VA
DC ratings: Rating ±10%, approx. 2W
SVF
MODEL
(high speed response; isolated)
• Environmental temperature must be within -5 to +60°C (23
to 140°F) with relative humidity within 30 to 90% RH in order
to ensure adequate life span and operation.
■ WIRING
• Do not install cables (power supply, input and output) close
to noise sources (relay drive cable, high frequency line, etc.).
• Do not bind these cables together with those in which noises
are present. Do not install them in the same duct.
■ AND ....
• The unit is designed to function as soon as power is
supplied, however, a warm up for 10 minutes is required for
satisfying complete performance described in the data sheet.
COMPONENT IDENTIFICATION
Body
Base Socket
Connection
Diagram Label
Front Cover
Input Resistor
Specification
Label
■ HOW TO OPEN THE FRONT COVER:
Position your finger on the hook at the top of front cover and
pull.
The shape of base socket may be different
for some models.
■ FRONT PANEL CONFIGURATIONS
■ UNPLUGGING THE UNIT
• Before you remove the unit from its base socket or mount it,
turn off the power supply and input signal for safety.
Zero Adj.
■ ENVIRONMENT
• When heavy dust or metal particles are present in the air,
install the unit inside proper housing and ventilate it.
• Do not install the unit where it is subjected to continuous
vibration. Do not apply physical impact to the unit.
Front Cover (open)
Span Adj.
P. 1 / 3
EM-1313 Rev.3
SVF
INSTALLATION
Detach the yellow clamps located at the top and bottom of the
unit for separating the body from the base socket.
■ DIN RAIL MOUNTING
Set the base socket so that its
DIN rail adaptor is at the bottom. Position the upper hook
at the rear side of base socket
on the DIN rail and push in
the lower. When removing the
socket, push down the DIN rail
adaptor utilizing a screwdriver
(–) and pull.
Clamp
(top & bottom)
DIN Rail
35mm wide
Spring Loaded
DIN Rail Adaptor
■ WALL MOUNTING
Refer to the drawings in the Shape and size of the base socket
are slightly different with various
following page.
socket types.
TERMINAL CONNECTIONS
Connect the unit as in the diagram below or refer to the connection diagram label on top of the unit.
When an input resistor is provided with the module, attach it together with input wiring to the input screw terminals.
■ DIMENSIONS mm (inch)
CLAMP
(top & bottom)
20
(.79)
7.8 (.31)
5
4
3
7
8
1
2
2–4.5 (.18) dia.
MTG HOLE
15 (.59) deep
8–M3.5
SCREW
50 (1.97)
6
80 (3.15)
80 (3.15)
35.4 (1.39)
DIN RAIL
35mm wide
107 (4.21)
127 (5)
40 (1.57)
[3.3 (.13)]
50 (1.97)
•When mounting, no extra space is needed between units.
■ TERMINAL ASSIGNMENTS mm (inch)
■ CONNECTION DIAGRAM
–
R
*
3
1 +
4
2 –
OUTPUT
7 U(+)
6
5
4
3
7
8
1
2
POWER
8 V(–)
12 (.47)
+
SIGNAL
SOURCE
INPUT RESISTOR
(model: REM)
*Input shunt resistor attached for current input.
Remark: The SVF, due to its fast-response design, does not
eliminate noises included in the input signal. Use shielded
twisted-pair cable for preventing them.
Input shunt resistor attached
for current input.
P. 2 / 3
EM-1313 Rev.3
SVF
CHECKING
1) Terminal wiring: Check that all cables are correctly
connected according to the connection diagram.
2) Power input voltage: Check voltage across the terminal 7
– 8 with a multimeter.
3) Input: Check that the input signal is within 0 – 100% of
the full-scale.
4) Output: Check that the load resistance meets the described specifications.
ADJUSTMENT PROCEDURE
This unit is calibrated at the factory to meet the ordered
specifications, therefore you usually do not need any calibration.
For matching the signal to a receiving instrument or in case
of regular calibration, adjust the output as explained in the
following.
■ HOW TO CALIBRATE THE OUTPUT SIGNAL
Use a signal source and measuring instruments of sufficient
accuracy level. Turn the power supply on and warm up for
more than 10 minutes.
1) ZERO: Apply 0% input and adjust output to 0%.
2) SPAN: Apply 100% input and adjust output to 100%.
3) Check ZERO adjustment again with 0% input.
4) When ZERO value is changed, repeat the above procedure
1) – 3).
MAINTENANCE
Regular calibration procedure is explained below:
■ CALIBRATION
Warm up the unit for at least 10 minutes. Apply 0%, 25%,
50%, 75% and 100% input signal. Check that the output
signal for the respective input signal remains within accuracy described in the data sheet. When the output is out of
tolerance, recalibrate the unit according to the "ADJUSTMENT PROCEDURE" explained earlier.
M-SYSTEM WARRANTY
M-System warrants such new M-System product which it manufactures to be free from defects in materials and workmanship during the 36-month period following the date that such
product was originally purchased if such product has been used under normal operating conditions and properly maintained, M-System's sole liability, and purchaser's exclusive remedies,
under this warranty are, at M-System's option, the repair, replacement or refund of the purchase price of any M-System product which is defective under the terms of this warranty. To
submit a claim under this warranty, the purchaser must return, at its expense, the defective M-System product to the below address together with a copy of its original sales invoice.
THIS IS THE ONLY WARRANTY APPLICABLE TO M-SYSTEM PRODUCT AND IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING ANY IMPLIED
WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. M-SYSTEM SHALL HAVE NO LIABILITY FOR CONSEQUENTIAL, INCIDENTAL OR
SPECIAL DAMAGES OF ANY KIND WHATSOEVER.
M-System Co., Ltd., 5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN, Phone: (06) 6659-8201, Fax: (06) 6659-8510, E-mail: [email protected]
P. 3 / 3
EM-1313 Rev.3
Was this manual useful for you? yes no
Thank you for your participation!