Actuator/Valve Specification
Section 230900 – INSTRUMENTATION AND CONTROL FOR HVAC
2.16 CONTROL VALVES
A. Manufacturer:
1. Manufactured, brand labeled or distributed by BELIMO.
PART 1 – GENERAL
The following addition should be made to 1.2.B.
1.2
SUMMARY
B. Related Sections include the following:
3. Division 23 Section “Hydronic Piping” for requirements for piping
packages for control valves.
The following replaces the noted specification sections, except as noted.
01/12 - Subject to change. © Belimo Aircontrols (USA), Inc.
2.15 ACTUATORS
A. Electronic Actuators:
1. Manufactured, brand labeled or distributed by BELIMO.
2. Size for torque required for damper seal at load conditions.
3. Coupling: V-bolt dual nut clamp with a V-shaped, toothed cradle.
4. Mounting: Actuators shall be capable of being mechanically and
electrically paralleled to increase torque if required.
5. Overload protected electronically throughout rotation.
6. Fail-Safe Operation: Mechanical, spring-return mechanism.
[Electronic fail safe shall incorporate a visual indication of the
fail safe status on the face of the actuator. The power fail
position shall be field adjustable between 0 to 100% in 10°
increments. The electronic fail safe shall have a 2 sec [0-10
sec] <Insert Timing between 0-10 sec>] operational delay.]
Choose electronic fail safe option when specifying pressure
independent valves (2-1/2” through 6”).
7. Power Requirements: 24 [120] [230] V ac, maximum 10 VA [22
VA] at 24-V ac or 8 W at 24-V dc.
Choose 22 VA is selecting electronic fail safe option in 2.15.A.6.
(above).
8. Proportional Actuators shall be fully programmable through an
EEPROM without the use of actuator mounted switches
9. Temperature Rating: -22 to +122ºF -30 to +50ºC [-58 to +122ºF
-50 to +50ºC]
10. Housing: Minimum requirement NEMA type 2 (4/4X) / IP54 (IP67)
mounted in any orientation. .
11. Agency Listings: ISO 9001, cULus, CE or CSA
12. The manufacturer shall warrant all components for a period of 5
years from the date of production, with the first two years
unconditional.
B. Control Valve Actuators:
1. Size for valve close off at 100 percent of total system (head)
pressure for two-way valves and three-way diverting valves; and
100 percent of total system (pump) head differential pressure for
three-way mixing valves. [Combination of actuator and trim
shall provide minimum close-off pressure rating of [100 psid]
[200 psid] <Insert Close-Off Rating>.]
Choose optional close-off pressure rating statement for higher (greater
than 100psid) requirements.
2. Coupling: directly couple and mount to valve stem, shaft ISO-style
direct-coupled mounting pad.
3. Shall meet all the requirements of 2.15.A. Electronic Actuators.
Specifier must include section 2.15.A Electronic Actuators when using
this section.
C. Control Valves:
1. Factory fabricated of type, body material, and pressure class
based on maximum pressure and temperature rating of piping
system, unless otherwise indicated.
2. Sizing:
a. Two-Position: Line size or size using a pressure differential of
1 psi.
b. Two-Way Modulating: [3 psid] 5 psid or twice the load pressure
drop, whichever is more.
c. Three-Way Modulating: Twice the load pressure drop, but not
more than [3 psid] 5 psid.
[2. Sizing (steam):
a. Two-Position: Line size or sized using 10% of inlet
gauge pressure.
b. Modulating: 15 PSIG or less inlet steam pressure, the
pressure drop shall be 80% of inlet gauge pressure.
Higher than 15 PSIG inlet steam pressure the pressure
drop shall be 42% of the inlet absolute pressure.]
Choose this option when specifying steam valves.
3. The control valve assembly shall be provided and delivered from a
single manufacturer as a complete assembly.
B. Industrial Actuators (ONLY TO BE USED WITH 2.16.I Butterfly Valves
– Resilient Seat and 2.16.J Butterfly Valves – High Performance.)
1. Manufactured, brand labeled or distributed by BELIMO.
2. The combination of valve and actuator shall meet the close-off
requirements as specified in Section 2.16.H – Butterfly Valves.
3. Coupling: ISO 5211 mounting standards.
4. Overload Protection: A self resetting thermal switch embedded in
the motor.
5. Manual Override: Actuator shall be equipped with a hand wheel or
shaft for manual override to permit operation of the actuator in the
event of an electrical power failure
6. Power Requirements: 24VAC [120VAC] [230VAC] 1 pH.
7. Auxiliary Switches: 2 SPDT rated 3A at 250 VAC.
8. Temperature Rating: -22 to +150ºF. -30 to +65ºC.
9. Housing: Minimum requirement NEMA type 4X/ IP67 with an
industrial quality coating. Actuator shall have an internal heater to
prevent condensation within the housing. A visual indication
beacon shall indicate position status of the device.
10. Agency Listing: ISO, CE, CSA
11. The manufacturer shall warrant for 2 years from the date of
production.
800-543-9038 USA
866-805-7089 CANADA
D. The manufacturer shall warrant all components for a period of 5
years from the date of production, with the first two years
unconditional (except as noted).
E. Pressure Independent Control Valves
1. NPS 2 and Smaller: Forged brass body rated at no less than 400
PSI, chrome plated brass ball and stem, female NPT union ends,
dual EPDM lubricated O-rings and a brass or TEFZEL
characterizing disc.
2. NPS 2-1/2 through 6: GG25 cast iron body according to ANSI
Class 125, standard class B, stainless steel ball and blowout proof
stem, flange to match ANSI 125 with a dual EPDM O-ring packing
design, PTFE seats, and a stainless steel flow characterizing disc.
3. Accuracy: The control valves shall accurately control the flow from
0 to 100% full rated flow with an operating pressure differential
range of 5 to 50 PSI differential across the valve with a valve body
accuracy of +/- 5% variance due to differential pressure fluctuation
or +/- 10% total assembly error incorporating differential pressure
fluctuation, .manufacturing tolerances and valve hysteresis
4. Flow Characteristics: Equal percentage characteristics.
Remember to modify 2.15.A.6 to incorporate electronic fail-safe option
for 2-1/2” through 6” Pressure Independent Valves, where fail safe
applications are required.
203-791-8396 LATIN AMERICA/CARIBBEAN
1
Actuator/Valve Specification
When choosing pressure independent control valves, specifier must
include the revisions to 232113 for elimination of the balancing valve
installation. Modify 230593 to eliminate the individual balancing of
each coil/valve combination when installing pressure independent
valves. 230953 is also modified for selected testing and verification of
the PI Valves installed.
F. Characterized Control Valves:
SPECIFYING PRESSURE INDEPENDENT CONTROL VALVES REQUIRE
THE FOLLOWING ADDITIONS TO SECTIONS 232113 AND 230593.
To be inserted into Section 232113 – HYDRONIC PIPING
2.6
CONTROL VALVES
K. Calibrated Balancing Valves and Automatic Flow-Control Valves shall
not be used on equipment where pressure independent control
valves are installed.
To be inserted into Section 230593 – TESTING, ADJUSTING, AND
BALANCING FOR HVAC
3.11 PROCEDURE FOR HYDRONIC SYSTEMS
H. Systems installed with pressure independent control valves shall not
require terminal level hydronic system balancing. [Total system flow
shall be verified to be within +/-10% of system design.] [ [10%]
[20%] [25%] <Insert Percentage> of the total installed product
shall be randomly checked for individual conformance. Exact
locations of tested product to be coordinated with the design
engineer. Any individual adjustments for the pressure
independent valve assembly (valve and actuator combination)
for field conditions shall be performed using the pressure
independent control valve manufacturer’s documented
procedure following the guidelines of the National Environmental
Balancing Bureau (NEBB) and the Testing Adjusting Balancing
Bureau (TABB)]
800-543-9038 USA
2
866-805-7089 CANADA
1. NPS 2 and Smaller: Nickel-plated forged brass body rated at no
less than 400 psi, stainless steel ball and blowout proof stem,
female NPT end fittings, with a dual EPDM O-ring packing design,
fiberglass reinforced Teflon seats, and a TEFZEL flow
characterizing disc. [NPS ¾” and Smaller for Terminal Units:
Nickel plated forged brass body rated at no less than 600 psi,
chrome plated brass ball and blowout proof stem, female NPT
end fittings, with a dual EPDM O-Ring packing design,
fiberglass reinforced Teflon seats, and a TEFZEL flow
characterizing disc.]
Choose option when specifying smaller terminal unit characterized
control valves ½” and ¾” only.
2. NPS 2-1/2 through 3: GG25 cast iron body according to ANSI
Class 125, standard class B, stainless steel ball and blowout proof
stem, flange to match ANSI 125 with a dual EPDM O-ring package
design, PTFE seats, and a stainless steel flow characterizing disc.
3. [NPS 1 and Smaller: Nickel-plated forged brass body rated at
no less than 600 psi, stainless steel ball and blowout proof
stem, female NPT end fittings, with a dual EPDM O-ring
packing design, fiberglass reinforced PTFE Teflon seats, and a
PTFE Teflon flow characterizing disc.
a. Flow Characteristics: Equal percentage characteristics.]
Choose option when specifying for steam applications.
4. NPS 2” and smaller characterized control valves for individual coil
control shall be provided as part of a pipe package supplied by the
valve manufacturer. The supply side of the coil shall contain a
strainer/shut-off ball valve/drain [an integrated isolation ball valve/
manual air vent] with a P/T port. The return side of the coil shall
contain a union fitting with a P/T port, characterized control valve,
an integrated manual balancing valve/union/isolation ball valve/
manual air vent with P/T port. Shut-off valves as an integrated part
of the characterized control valve are prohibited. [For 3-way
installations, supply an integrated 100% port isolation valve/
manual air vent with a P/T port for field installation in the
bypass of the circuit.] . [A [12”] [24”] flexible hose set shall be
provided for each coil supply and return connection for all
pipe packages.]
5. Six-way Control Valves shall have the following characteristics:
a. NPS ½” and ¾”: Nickel plated forged brass body rated at no
less than 600 psi, dual chrome plated brass ball and blowout
proof stems, and female NPT end fittings. Each three-way
portion of the 6-way valve body shall have EPDM O-Ring
packing design, fiberglass reinforced Teflon seats, and a
TEFZEL flow characterizing disc.
b. The six-way control valve shall be controlled by a rotary actuator
for managing two media in a switching application. The valve
shall be closed to flow at mid-rotation.
6. Globe valves shall have the following characteristics:
a. NPS 2 and Smaller: ANSI Class 250 bronze body, stainless
steel stem, brass plug, bronze seat, and a TFE packing.
b. NPS 2-1/2 and Larger: ANSI Class 125 [250] cast iron body,
stainless steel stem, bronze plug, bronze seat, and a TFE V-ring
packing.
c. Flow Characteristics: Two-way valves shall have equal
percentage characteristics; three-way valves shall have linear
characteristics.
d. Two- and three-way globe valves shall be used only if
characterized control valves do not fit the sizing criteria or
application.
[Steam system globe valves shall have the following
characteristics:
e. NPS 2 and Smaller: ANSI Class 250 bronze body; stainless
steel seat, stem and plug; and a TFE packing.
f. NPS 2-1/2 and Larger: ANSI Class 125 [250] cast iron body;
stainless steel seat, stem and plug; and a TFE V-ring packing.
203-791-8396 LATIN AMERICA/CARIBBEAN
01/12 - Subject to change. © Belimo Aircontrols (USA), Inc.
5. All actuators shall be capable of being electronically programmed
in the field by use of external computer software or a dedicated
handheld tool for the adjustment of flow. Programming using
actuator mounted switches or multi-turn actuators are not
acceptable. [Actuators for 3-wire floating (tri-state) on ½” – 1”
pressure independent control valves shall fail in place and
have a mechanical device inserted between the valve and the
actuator for the adjustment of flow.] [Actuators for twoposition ½’-1” pressure independent control valves shall fail
in place and have a mechanical device inserted between the
valve and the actuator for the adjustment of flow.] [Actuators
shall be provided with an auxiliary switch.]
Option for two-position or floating control actuator (non-programmable)
for small, unitary (1/2” thru 1”) applications.
Option for actuator with built-in auxiliary switch.
6. [Coil optimization 2-1/2” through 6” shall be accomplished by
utilizing a pressure independent control valve assembly; two
temperature sensors providing feedback of coil inlet water
temperature and coil outlet water temperature; and a flow
meter to provide analog flow feedback. Software shall control
the valve to avoid the coil differential temperature from falling
below a programmed setpoint. Independent trend logs data
shall be available by means of BACnet MS/TP trending data to
include, but not be limited, to inlet and outlet coil water
temperatures, valve position, absolute flow, absolute valve
position, absolute power and heating/cooling energy in BTU/
hr.]
7. The manufacturer shall provide a published commissioning
procedure following the guidelines of the National Environmental
Balancing Bureau (NEBB) and the Testing Adjusting Balancing
Bureau (TABB).
8. The control valve shall require no maintenance and shall not
include replaceable cartridges.
9. NPS 2” and smaller pressure independent control valves for
individual coil control shall be provided as part of a pipe package
supplied by the valve manufacturer. The supply side of the coil
shall contain an integrated isolation ball valve/manual air vent
[strainer/shut-off valve/drain] with a P/T port. The return side shall
contain a union fitting with a P/T port, pressure independent control
valve, an integrated isolation ball valve/manual air vent with a P/T
port. Shut-off valves as an integrated part of the pressure
independent control valve are prohibited. [A [12”] [24”] flexible
hose set shall be provided for each coil supply and return
connection for all pipe packages.]
Actuator/Valve Specification
g. Flow Characteristics: Linear or equal percentage
characteristics.]
Choose option when specifying globe valves in a steam system
application.
1. NPS 2 to 12: Valve body shall be full lugged cast iron 200 psig
body with a 304 stainless steel disc, EPDM seat, extended neck
and shall meet ANSI Class 125/150 flange standards. Disc-tostem connection shall utilize an internal spline. The shaft shall be
supported at four locations by RPTFE bushings.
2. NPS 14 and Larger: Valve body shall be full lugged cast iron 150
psig body with a 304 stainless steel disc, EPDM seat, extended
neck and shall meet ANSI Class 125/150 flange standards. Discto-stem connection shall utilize a dual-pin method to prevent the
disc from settling onto the liner. The shaft shall be supported at four
locations by RPTFE bushings.
3. Sizing:
a. Two-Position: Line size or size using a pressure differential of
1 psi.
b. Modulating: [3 psig] 5 psig or twice the load pressure drop,
whichever is more. Size for the design flow with the disc in a
60-degree-open-position and a design velocity not to exceed 12
feet per second.
4. Close-Off Pressure Rating: NPS 2-12” 200 psi bubble tight shut-off.
NPS 14 and larger, 150 psi bubble tight shut-off.
01/12 - Subject to change. © Belimo Aircontrols (USA), Inc.
H. Butterfly Valves – High Performance:
1. Valve body shall be full lugged carbon steel ANSI Class 150 [300]
body with a 316 stainless steel disc without a nylon coating, RTFE
seat, and be ANSI Class 150300 flange standards. Blowout-proof
shaft shall be 17-4ph stainless steel and shall be supported at four
locations by glass-backed TFE bushings. Valve packing shall be
Chevron TFE and shall include fully adjustable packing flange and
separable packing gland. Valve body shall have long stem design
to allow for 2” insulation (minimum). Valve face-to-face dimensions
shall comply with API 609 and MSS-SP-68. Valve assembly shall
be completely assembled and tested, ready for installation.
2. Sizing:
a. Two-Position: Line size or size using a pressure differential of
1 psi.
b. Modulating: [3 psig] 5 psig or twice the load pressure drop,
whichever is more. Size for the design flow with the disc in a
60-degree-open-position with the design velocity less than 32
feet per second.
3. Flow Characteristics: Modified equal percentage, unidirectional.
4. Close-Off Pressure Rating: 150 [285] psi bubble tight shut-off.
5. Media Temperature Range: ANSI Class 150 [300] limitations.
6. Max Differential Pressure: 285 psi @ 100 deg F for ANSI 150 (725
psi @ 100 deg F for ANSI 300).
Select 2.16.B. Industrial Actuators when specifying 2.16.G Butterfly
Valves – Resilient Seat and 2.16.H Butterfly Valves – High
Performance.)
Zone Valves (On/Off Two-Position Applications):
1. NPS 1 and Smaller: Forged brass body rated at no less than 300
psi, stainless steel stems, female, NPT union or sweat with a
stainless steel stem and EPDM seals.
2. The manufacturer shall warrant all components for a period of 2
years from the date of production.
3. All zone valves for individual coil control shall be provided as part of
a pipe package supplied by the valve manufacturer. The supply
side of the coil shall contain a strainer/shut-off ball valve/drain [an
integrated 100% port isolation valve/manual air vent] with a P/T
port. The return side of the coil shall contain a union fitting with a
P/T port, zone valve, an integrated manual balancing valve/union/
isolation ball valve/manual air vent with P/T port. Shut-off valves as
an integrated part of the zone valve are prohibited. [A [12”] [24”]
flexible hose set shall be provided for each coil supply and
return connection for all pipe packages.]
800-543-9038 USA
2.8 SMOKE DAMPERS
I. Damper Motors:
G. Butterfly Valves – Resilient Seat:
I.
To be inserted into Section 233300 – AIR DUCT ACCESSORIES
1. Manufactured, brand labeled or distributed by BELIMO.
2. Size for torque required for damper seal at load conditions with one
actuator per damper section. .Mechanically paralleled or
‘piggybacked’ actuators are not permitted.
3. Coupling: V-bolt dual nut clamp with a V-shaped toothed cradle.
Aluminum clamps or set screws are not acceptable.
4. Overload Protection: Microprocessor or an electronic based motor
controller providing burnout protection if stalled before full rotation is
reached. The actuator shall be electronically cut off at full open to
eliminate noise generation with the holding noise level to be
inaudible.
5. Power Requirements: 0.23A (running) and 0.09A (holding) at 24Vac or 27 VA (running) and 10 VA (holding) at 120V-ac.
6. Actuator timing shall be 15 sec [75 sec] [local codes].
7. Temperature Rating: Actuator shall have a UL555S listing by the
damper manufacturer for 350ºF [250ºF].
8. [Proportional Smoke Damper Actuators shall meet all
requirements specified above and shall modulate 0-100% open
in response to a 2-10vdc or 4-20mA control signal. A 2-10vdc
feedback output shall provide a 2-10vdc signal for position
indication.
a. Power Requirements (Proportional): Maximum (running) 12
VA at 24-V ac or 8 W at 24-V dc. Maximum (holding) 5VA at
24-V ac or 3 W at 24-V dc.
b. A manual override winder and locking mechanism shall be
provided for override operation of the actuator on a loss of
power.]
9. [Balancing Smoke Damper Actuators shall meet all
requirements specified above and shall include an integral
adjustable maximum opening potentiometer for airflow
adjustment.
a. Power Requirements (Balancing): Maximum (running) 9.5
VA at 24-V ac or 6 W at 24-V dc. Maximum (holding) 5VA at
24-V ac or 3 W at 24-V dc.
b. A manual override winder and locking mechanism shall be
provided for override operation of the actuator on a loss of
power to the actuator.]
The following replaces item 2.8.K.1
1. Auxiliary switches for [signaling] [fan control] [or] [position
indication].
2.9 COMBINATION FIRE AND SMOKE DAMPERS
O. Damper Motors:
1. Manufactured, brand labeled or distributed by BELIMO.
2. Size for torque required for damper seal at load conditions.
3. Coupling: V-bolt dual nut clamp with a V-shaped toothed cradle.
Aluminum clamps or set screws are not acceptable.
4. Overload Protection: Microprocessor or an electronic based motor
controller providing burnout protection if stalled before full rotation is
reached. The actuator shall be electronically cut off at full open to
eliminate noise generation with the holding noise level to be
inaudible.
5. Power Requirements: 0.23A (running) and 0.09A (holding) at 24Vac or 27 VA (running) and 10 VA (holding) at 120V-ac.
6. Actuator timing shall be 15 sec [75 sec] [local codes].
7. Temperature Rating: Actuator shall have UL555 and UL555S
listings by the damper manufacturer for 350ºF [250ºF].
8. [Proportional Combination Fire and Smoke Damper Actuators
shall meet all requirements specified above and shall
modulate 0-100% open in response to a 2-10vdc or 4-20mA
control signal. A 2-10vdc feedback output shall provide a
2-10vdc signal for position indication.
866-805-7089 CANADA
203-791-8396 LATIN AMERICA/CARIBBEAN
3
Actuator/Valve Specification
a. Power Requirements (Proportional): Maximum (running) 12
VA at 24-V ac or 8 W at 24-V dc. Maximum (holding) 5VA at
24-V ac or 3 W at 24-V dc.
b. A manual override winder and locking mechanism shall be
provided for override operation of the actuator on a loss of
power.]
9. [Balancing Combination Fire and Smoke Damper Actuators
shall meet all requirements specified above and shall include
an integral adjustable maximum opening potentiometer for
airflow adjustment.
a. Power Requirements (Balancing): Maximum (running) 9.5
VA at 24-V ac or 6 W at 24-V dc. Maximum (holding) 5VA at
24-V ac or 3 W at 24-V dc.
b. A manual override winder and locking mechanism shall be
provided for override operation of the actuator on a loss of
power to the actuator.]
The following replaces item 2.9.Q.1
1. Auxiliary switches for [signaling] [fan control] [or] [position
indication].
2. Housing: Steel housing, aluminum is unacceptable.
3. Agency Listing: ISO 9001, UL873, or UL60730.
4. The manufacturer shall warrant all components for a period of 5
years from the date of production, with the first two years
unconditional.
NOTE TO SPECIFIER
01/12 - Subject to change. © Belimo Aircontrols (USA), Inc.
Any (or all) of the following manufacturers are listed per UL555S with Belimo
actuators: Air Balance, Arlan, E.H. Price, Greenheck, Leader, Lloyd Industries,
Nailor, Pottorff, Prefco, Ruskin and Safe-Air.
800-543-9038 USA
4
866-805-7089 CANADA
203-791-8396 LATIN AMERICA/CARIBBEAN
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertisement