10 REOZDC Model: Standard Features

10 REOZDC Model: Standard Features
Model:
10REOZDC
Compact Diesel
EPA-Certified for Stationary
Emergency Applications
Standard Features
D Kohler Co. provides one-source responsibility for the
generating system and accessories.
D The generator set and its components are
prototype-tested, factory-built, and production-tested.
D The generator set is CSA certified, file # LR 955.
D UL 2200 listing is available.
D The generator set engine is certified to meet the
Environmental Protection Agency (EPA) emergency
stationary emissions requirements.
D The generator set meets NFPA 110, Level 1, when
equipped with the necessary accessories and installed
per NFPA standards.
D A one-year limited warranty covers all generator set
systems and components. Two- and five-year
extended limited warranties are also available.
D Four-point mounting with vibration isolators.
D The brushless, rotating-field alternator has broadrange
reconnectability.
D Voltage regulation of ±0.25%.
D Sustained short-circuit capability.
D Customer connection box with field-connection terminal
blocks.
D Single-side access.
D Weather and sound enclosures are available.
d Enclosures reduce sound levels and protect the
generator set from the elements, animal intrusion,
and unwanted entry.
d Enclosures have a fade-, scratch-, and corrosionresistant Kohlerr Power Armortcream beige
automotive-grade textured finish and lockable, flushmounted door latches.
d See specification sheet G6-96 for enclosure features
and specifications.
Shown with available subbase fuel tank.
Generator Set Ratings
130 _C Rise
Standby Rating
Alternator
4H4
4J4
105 _C Rise
Prime Rating
Voltage
120/240
Hz
60
Ph
1
kW/kVA
Amps
kW/kVA
Amps
10.0/10.0
41.7
9.0/9.0
37.5
120/208
60
3
10.0/12.5
34.7
9.0/11.3
31.2
120/240
60
1
10.0/10.0
41.7
9.0/9.0
37.5
120/240
60
3
10.0/12.5
30.1
9.0/11.3
27.1
127/220
60
3
10.0/12.5
32.8
9.0/11.3
29.5
139/240
60
3
10.0/12.5
30.1
9.0/11.3
27.1
220/380
60
3
9.5/11.9
18.0
8.6/10.7
16.2
277/480
60
3
10.0/12.5
15.0
9.0/11.3
13.5
RATINGS: All three-phase units are rated at 0.8 power factor. Standby Ratings: Standby ratings apply to installations served by a reliable utility source. The standby rating is applicable to varying loads
for the duration of a power outage. There is no overload capability for this rating. Ratings are in accordance with ISO-3046/1, BS 5514, AS 2789, and DIN 6271. Prime Power Ratings: Prime power ratings
apply to installations where utility power is unavailable or unreliable. At varying load, the number of generator set operating hours is unlimited. A 10% overload capacity is available for one hour in twelve.
Ratings are in accordance with ISO-8528/1, overload power in accordance with ISO-3046/1, BS 5514, AS 2789, and DIN 6271. For limited running time and base load ratings, consult the factory. Obtain
the technical information bulletin (TIB-101) on ratings guidelines for the complete ratings definitions. The generator set manufacturer reserves the right to change the design or specifications without notice
and without any obligation or liability whatsoever. Contact your local Kohlerr generator set distributor for availability. GENERAL GUIDELINES FOR DERATING: ALTITUDE: Derate 1.0% per 100 m
(328 ft.) elevation above 200 m (656 ft.). TEMPERATURE: Derate 2.0% per 10_C (18_F) temperature above 25_C (77_F).
G5-374 (10REOZDC) 12/14c
Alternator Specifications
Specifications
Manufacturer
Type
Exciter type
Leads: quantity, type
4H4
4J4
Voltage regulator
Insulation:
Material
Temperature rise in 25_C ambient
Bearings, quantity
Coupling
Amortisseur windings
Voltage regulation, no-load to full-load
D NEMA MG1, IEEE, and ANSI standards compliance for
temperature rise and motor starting.
Alternator
Kohler
4-Pole, Rotating-Field
Brushless
D Sustained short-circuit current of up to 300% of the rated
current for up to 10 seconds.
D Sustained short-circuit current enabling downstream circuit
breakers to trip without collapsing the alternator field.
4
12, Reconnectable
Solid State
D Self-ventilated and dripproof construction.
D Windings are vacuum-impregnated with epoxy varnish for
dependability and long life.
Class H
130_C
1
Flexible Disc
Full
±0.25%
One-step load acceptance
100% of Rating
Peak motor starting kVA (35% dip for voltages below):
240 V
4H4 (4 lead)
28 (60 Hz)
240 V
4J4 (12 lead)
35 (60 Hz)
D Superior voltage waveform from a two-thirds pitch stator and
skewed rotor.
D Rotors dynamically balanced to minimize vibration.
D Copper windings to ensure minimal heat buildup. Insulation
meeting NEMA standards for class H insulation.
D Generator direct connected to the engine.
D Sealed precision ball bearings with a precision-machined
steel sleeve in the end bracket to prevent shaft misalignment
and extend bearing life.
Application Data
Engine
Engine Specifications
Manufacturer
Engine: model, type
Cylinder arrangement
Engine Electrical
60 Hz
Engine Electrical System
Yanmar
Battery-charging alternator:
3TNV82A, 4-Cycle
3 Inline
Volts (DC)
Displacement, L (cu. in.)
1.330 (81.14)
Bore and stroke, mm (in.)
82 x 84 (3.23 x 3.31)
Compression ratio
Combustion system
Main bearings: quantity, type
Rated rpm
Max. power at rated rpm, kWm (BHP)
Cylinder head material
Crankshaft material
Ground (negative/positive)
Ampere rating
19.2:1
Direct Injection
4, Replaceable Sleeve
1800
13.8 (18.5)
Starter motor rated voltage (DC)
60 Hz
Negative
12
70
12
Battery recommended cold cranking
amps (CCA):
Qty., CCA for 0_C (--18_F)
Battery voltage (DC)
One, 650
12
Fuel
Cast Iron
Fuel System
Forged Steel
60 Hz
Connecting rod material
Forged Carbon Steel
Fuel supply line
1/4 NPT
Governor: type, make
Mechanical, Yanmar
Fuel return line, mm (in.)
8 (0.31)
Maximum lift, m (ft.)
1 (3.3)
2.5%
Fuel pump
Electric
0.33%
Fuel filter
5 Micron
Frequency regulation:
No-load to full-load
Steady state
Frequency
Air cleaner type
Mechanically Adjustable
Fuel/water separator
Yes
Dry
Recommended fuel
Diesel Fuel
ASTM D975 No. 2-D
Exhaust
Exhaust System
Exhaust flow at rated kW, m3/min. (cfm)
Exhaust temperature at rated kW, _C (_F)
Maximum allowable back pressure,
kPa (in. Hg)
Exhaust outlet size at engine hookup
60 Hz
2.9 (104)
550 (1022)
12.8 (3.8)
1.5 NPT
Lubrication
Lubricating System
Type
Oil pan capacity with filter, L (qt.)
Oil filter
Oil cooler
G5-374 (10REOZDC) 12/14c
60 Hz
Pressure
3.6 (3.8)
Full flow, Cartridge
None
Application Data
Controller
Cooling
Radiator System
60 Hz
50 (122) *
Ambient temperature, _C (_F)
Type
Liquid
Capacity, engine only, L (qt.)
1.8 (1.9)
Engine jacket water flow, Lpm (gpm)
24.3 (6.4)
Capacity with unit-mounted radiator, L (qt.)
4.1 (4.3)
Heat rejected to cooling water at rated kW,
Btu/min.
574
Fan diameter, unit-mounted radiator,
mm (in.)
409 (16.1)
Fan, kW (HP)
0.6 (0.75)
Max. restriction of cooling air, intake and
discharge side of radiator, kPa (in. H2O)
0.125 (0.5)
Decision-Makerr 3000 Controller
Provides advanced control, system monitoring, and system diagnostics
for optimum performance and compatibility.
D Digital display and menu control provide easy local data access
D Measurements are selectable in metric or English units
D Remote communication thru a PC via network or
serial configuration
D Built-in alternator thermal overload protection
D NFPA 110 Level 1 capability
Refer to G6-100 for additional controller features and accessories.
* Enclosure with enclosed silencer reduces ambient
temperature capability by 5C (9F).
60 Hz
Remote Radiator System[
Exhaust manifold type
Dry
Connection sizes
Water inlet, mm (in.)
Water outlet, mm (in.)
Static head, maximum, m (ft.)
28 (1.1)
28 (1.1)
4 (13.1)
[ Contact your local distributor for cooling system options and
specifications based on your specific application.
Operation Requirements
Air Requirements
Radiator min. cooling air, m3/min. (cfm)
60 Hz
39 (1400)
Alternator min. cooling air, m3/min. (cfm)
4.8 (170)
Radiator min. cooling air, m3/min. (cfm)
39 (1400)
Combustion air, m3/min. (cfm)
1.1 (38)
Heat rejected to ambient air:
Engine, kW (Btu/min.)
10.6 (605)
Alternator, kW (Btu/min.)
1.8 (100)
60 Hz
Fuel Consumption
Diesel, Lph (gph), at % load
Standby Rating
100%
4.0
(1.1)
75%
2.7
(0.7)
50%
2.0
(0.5)
25%
1.3
(0.4)
Diesel, Lph (gph), at % load
Prime Rating
100%
3.5
(0.9)
75%
2.5
(0.7)
50%
1.9
(0.5)
25%
1.2
(0.3)
G5-374 (10REOZDC) 12/14c
Kohler Power Systems
Asia Pacific Headquarters
7 Jurong Pier Road
Singapore 619159
Phone (65) 6264-6422, Fax (65) 6264-6455
KOHLER CO., Kohler, Wisconsin 53044 USA
Phone 920-457-4441, Fax 920-459-1646
For the nearest sales and service outlet in the
US and Canada, phone 1-800-544-2444
KOHLERPower.com
Additional Standard Features
D
D
D
D
D
Maintenance and Literature
Battery Rack and Cables
Decision-Makerr 3000 Controller
Fuel/Water Separator
Oil Drain Extension
Oil Pressure Sender
- General Maintenance Literature Kit
- NFPA 110 Literature Kit
- Overhaul Literature Kit
- Production Literature Kit
Warranty
Available Accessories
- Five-Year Comprehensive Limited Warranty
- Two-Year Extended Limited Warranty
Cooling Systems
- Five-Year Extended Limited Warranty
- Remote Radiator Setup (radiator sold separately)
- Unit-Mounted Radiator w/Pusher Fan (included with enclosures)
Miscellaneous Accessories
- _______________________________________________
Cooling System Accessories
- _______________________________________________
- Block Heater
(recommended for ambient temperatures below 0_C [32_F])
- _______________________________________________
- _______________________________________________
- Coolant Added (N/A with remote radiator)
- Radiator Duct Flange (open units only)
- Remote Radiator, 12V
Enclosures (with enclosed silencer)
- Sound Enclosure (rated for 150 mph wind load)
- Weather Enclosure (rated for 150 mph wind load)
Open Units
- Exhaust Silencer (kit GM41678-KP2) (engine-mounted)
Dimensions and Weights
Electrical System
- Battery
- Battery Charger, 6 Amp
- Battery Charger, 10 Amp
- Battery Charger, 10 Amp with alarms (required for NFPA 110)
Open Units wIth Radiator:
Dimensions, L x W x H, mm (in.):
with skid only:
1730 x 860 x 899 (68.1 x 33.9 x 35.4)
with 40 gal. tank:
1730 x 860 x 949 (68.1 x 33.9 x 37.4)
with 80 gal. tank:
1730 x 860 x 1127 (68.1 x 33.9 x 44.4)
NOTE: Height does not include engine-mounted silencer.
- Battery Heater
(recommended for ambient temperatures below 0_C [32_F])
- Emergency Stop Switch, Remote
Weight, wet, max., kg (lb.):
with skid only:
with 40 gal. tank:
with 80 gal. tank:
- Line Circuit Breaker
For tanks and enclosures, see specification sheet G6-96.
- Electronic Governor
(isochronous, with 0.25% steady-state frequency regulation)
660 (1455)
586 (1290)
753 (1660)
- Preheat Kit
(recommended for ambient temperatures below 5_C [41_F])
Engine
- Auxiliary Fuel Pump
H
- Flexible Fuel Lines
Fuel Tank and Mounting (must select one)
- Skid only
- 40 Gallon Subbase Tank and Mounting
W
L
- 80 Gallon Subbase Tank and Mounting
Fuel Tank Accessories
- Inner Tank Leak Alarm
Controller Accessories
NOTE: This drawing is provided for reference only and should not be used for planning
installation. Contact your local distributor for more detailed information.
DISTRIBUTED BY:
- Communication Products and PC Software
- Input/Output Module
- Remote Serial Annunciator
- Run Relay
E 2011, 2012, 2013, 2014 by Kohler Co. All rights reserved.
G5-374 (10REOZDC) 12/14c