Delta | PD-01 | Specifications | Delta PD-01 Specifications

PROFIBUS DP
RTU-PD01 Slave Communication Module
Operation Manual
DVP-0215820-01
PROFIBUS DP Slave Communicaion Module RTU-PD01
Table of Content
1
Introduction to RTU-PD01....................................................................................................................2
1.1 Product Introduction .......................................................................................................................2
1.2 Features ...........................................................................................................................................2
2
Product Profile and Outline ...............................................................................................................3
3
Installation .............................................................................................................................................4
3.1 Definition of PROFIBUS DP Port ....................................................................................................4
3.2 Connecting to PROFIBUS DP Port by 35mm DIN Rail .....................................................................4
3.3 Installing RTU-PD01 and I/O Module on DIN Rail.............................................................................5
4
Components ..........................................................................................................................................6
5
Establishing PROFIBUS DP Network by RTU-PD01 ............................................................................7
6
Transmission Distance and Baud Rate.................................................................................................7
7
GSD File ...................................................................................................................................................8
8
RTU-PD01 Settings and Configurations ...............................................................................................8
8.1 RTU-PD01 Settings...........................................................................................................................8
8.2 Configuration Items ...........................................................................................................................9
8.3 Settings of Configuration Items ....................................................................................................... 11
9
LED Indicator and Trouble-shooting ...................................................................................................23
10 Application Example 1..........................................................................................................................25
DVP-PLC Operation Manual
1
PROFIBUS DP Slave Communicaion Module RTU-PD01
1
Introduction to RTU-PD01
1.1
Product Introduction
1. Thank you for choosing Delta RTU-PD01 PROFIBUS DP Slave Communication Module. To ensure
correct installation and operation of the product, please read this operation manual carefully before
using it.
2. This operation manual only provides introductory information on RTU-PD01. Detailed information
about PROFIBUS DP protocol is not included in this manual. Please refer to relevant literatures for
more information on PROFIBUS DP protocol.
3. RTU-PD01 is a PROFIBUS DP slave communication module for connecting Delta’s Slim series
special I/O modules, digital I/O modules and standard Modbus devices to PROFIBUS DP network.
1.2
Features
1. Supports PROFIBUS DP cyclic data transmission.
2. Auto-detects baud rates; supports max. 12Mbps.
3. Self-diagnosis
4. Able to connect to max. 8 DVP-Slim type special I/O modules (i.e. analog I/O, temperature
measurement, counter and positioning modules) and 16 digital I/O modules (max. 256 digital I/O
points).
5. The RS-485 COM port is able to connect to max. 16 standard Modbus slave stations.
6. Supports max. 100 bytes of data input and 100 bytes of data output.
2
DVP-PLC Operation Manual
PROFIBUS DP Slave Communicaion Module RTU-PD01
2
Profuct Profile and Outline
2.1 Parts and Dimensions
1
2
3
5
6
4
7
9
10
15
11
16
12
17
8
13
14
Unit: mm
1. POWER indicator
2. NET indicator
3. RS-485 indicator
4. RUN/STOP switch
5. RUN indicator
6. ALARM indicator
7. Address setup switch
8. PROFIBUS DP COM port
9. I/O module positioning hole
10. Nameplate
11. I/O module connection port
12. DIN rail (35mm)
13. I/O module fixing clip
14. DIN rail fixing clip
15. RS-485 COM port
16. I/O module fixing notch
17. DC24V power supply interface
2.2 Specifications
PROFIBUS DP Port!
Interface
DB9 connector
Transmission method
High-speed RS-485
Transmission cable
Shielded twisted pair cable
Electrical isolation
500VDC
Communication
Message type
Cyclic data exchange
Module name
RTU-PD01
GSD file
DELA09B9.GSD
Product ID
09B9 (HEX)
DVP-PLC Operation Manual
3
PROFIBUS DP Slave Communicaion Module RTU-PD01
Serial transmission
speed supported
(auto-detection)
9.6kbps; 19.2kbps; 93.75kbps; 187.5kbps; 500kbps; 1.5Mbps; 3Mbps; 6Mbps;
12Mbps (bits per second)
Electrical Specification
Power supply voltage
24VDC
Insulation voltage
500VDC
Power consumption
2.5W
Weight
90g
Environment
3
Noise immunity
ESD (IEC 61131-2,IEC 61000-4-2): 8kV Air Discharge
EFT (IEC 61131-2,IEC 61000-4-4): Power Line:±2kV,Digital Input:±2kV
Comunication I/O: ±2kV
Conducted Susceptibility Test (EN61000-4-6, IEC 61131-2 9.10): 150kHz ~
80MHz,10V/m
RS (IEC 61131-2, IEC 61000-4-3): 26MHz ~ 1GHz, 10V/m
Storage/operation
Operation: 0°C ~ 50°C (temperature), 50 ~ 90% (humidity), pollution degree 2
Storage: -25°C ~ 70°C (temperature), 5 ~ 95% (humidity)
Shock/vibration
immunity
International standards: IEC 61131-2,IEC 68-2-6 (TEST Fc)/IEC 61131-2& IEC
68-2-27 (TEST Ea)
Installation
3.1 Definition of PROFIBUS DP Port
PIN
PIN name
Definition
1
--
N/C
2
--
N/C
3
RxD/TxD-P
Sending/receiving data P(B)
4
--
N/C
5
DGND
Data reference potential (C)
6
VP
Power voltage – positive
7
--
N/C
8
RxD/TxD-N
Sending/receiving data N(A)
9
--
N/C
9
5
6
1
3.2 Connecting to PROFIBUS DP Port
Insert PROFIBUS DP bus connector into PROFIBUS DP port on RTU-PD01 (see the figure below)
Screw it tight to ensure RTU-PD01 and PROFIBUS DP bus are properly connected.
4
DVP-PLC Operation Manual
PROFIBUS DP Slave Communicaion Module RTU-PD01
3.3 Installing RTU-PD01 and I/O Module on DIN Rail
z Use 35mm DIN rail.
z Open the DIN rail clips on RTU-PD01 and I/O module. Insert RTU-PD01 and I/O module on the
DIN rail.
z Clip up the DIN rail clips on RTU-PD01 and I/O module to fix them on the DIN rail (see the figure
below).
DVP-PLC Operation Manual
5
PROFIBUS DP Slave Communicaion Module RTU-PD01
4
Components
4.1 RUN/STOP Switch
Status
Description
1. Special I/O module switches from RUN to STOP.
RUN => STOP
RUN
2. All Y points on digital output module turn OFF.
3. Modbus function switch
4. RUN LED turns off.
1. RTU-PD01 re-detects the number of digital I/O points and
specialI/O modules.
STOP
2. Special I/O module switches from STOP to RUN.
STOP => RUN
3. Enable digital I/O modules.
4. Enable Modbus function.
5. RUN LED turns on.
4.2 Address Setup Switch
The two rotary address setup switches, x160 and x161, set up the node address of RTU-PD01 on
PROFIBUS DP network in hex form. The range for rotation is 0 ~ F.
Address
Definition
1
H’1~ H’7D
H’0 or H’7E ~ H’FF
x16
Valid PROFIBUS address
0
x16
Invalid PROFIBUS address. NET LED will flash in red
color if the node address falls within this range.
Example: If you need to set the node address of RTU-PD01 to 26 (decimal), simply switch x161 switch
to “1” and x160 to “A”. 26 (decimal) = 1A (hex) = 1x161 + Ax160.
Note:
z
Switch off the power supply before setting up the node address of RTU-PD01. Re-power the
module after the setup is completed.
6
z
Changing the value on the switch during the operation of RTU-PD01 is invalid.
z
Use slot type screwdriver to set up the switch. Be careful not to scratch the module.
DVP-PLC Operation Manual
PROFIBUS DP Slave Communicaion Module RTU-PD01
5
Establishing PROFIBUS DP Network by RTU-PD01
The right-side interface on RTU-PD01 is connectable to DVP-Slim series special I/O modules and
digital I/O modules. The RS-485 port is connectable to standard Modbus devices. See the figure below
for the connection of Slim series I/O modules and Modbus devices and into the PROFIBUS DP
network.
6
Transmission Distance and Baud Rate
The baud rate range for PROFIBUS DP is 9.6kbps ~ 12Mbps, and the length of transmission cable
varies upon the transmission speed. The transmission distance ranges from 100m to 1,200m. See the
table below for the baud rates RTU-PD01 supports and their corresponding communication distance.
Baud rate (bps)
9.6k
19.2k
93.75k
187.5k
500k
1.5M
3M
6M
12M
Distance (m)
1,200
1,200
1,200
1,000
400
200
100
100
100
DVP-PLC Operation Manual
7
PROFIBUS DP Slave Communicaion Module RTU-PD01
7
GSD File
The GSD file is a text file and can be used to identify PROFIBUS DP device (master or slave).A GSD
file usually contains the supplier’s information, baud rates supported and applicable I/O messages.
When using RTU-PD01, you have to first import the GSD file to the configuration software for
PROFIBUS DP master. After the import of the file, the configuration software for master will display
RTU-PD01 and its configuration settings. You can download the GSD file for RTU-PD01 at Delta’s
website: http://www.delta.com.tw/
8
RTU-PD01 Settings and Configurations
8.1 RTU-PD01 Settings
When you set up RTU-PD01 in the configuration software for PROFIBUS DP master, there will be
plenty of setup items for you to choose from, which adds flexibility to the manipulation of RTU-PD01.
See the figure below for RTU-PD01 settings.
Definitions of settings:
Setup item
Setting
Enable
When the Modbus device is configured with
many addresses and the addresses are
consecutive, all contents in the consecutive
addresses can be read or written at a time.
Disable
When the Modbus device is configured with
many addresses, only contents in a single
address can be read or written.
Acceleration mode
8
Definition
DVP-PLC Operation Manual
PROFIBUS DP Slave Communicaion Module RTU-PD01
Setup item
Setting
7, O, 2
8, E, 1
8, O, 1
Definition
Modbus protocol
7, E, 1
7, O, 1
7, E, 2
Modbus baudrate
1,200bps
2,400bps
4,800bps
9,600bps
Modbus mode
RTU/ASCII
Modbus communication mode
Hold I/O data
RTU-PD01 retains the I/O data before getting
offline after getting offline from the master.
Clear I/O data
RTU-PD01 reset all the I/O data to 0 after
getting offline from the master.
Ignore & continue I/O exchange
RTU-PD01 continues exchanging data with
the master even when Modbus read/write
error occurs.
Stop I/O exchange &report fault
RTU-PD01 stops exchanging data with the
master when Modbus read/write error occurs.
Ignore & continue I/O exchange
RTU-PD01 continues exchanging data with
the master even when the Modbus slave is
disconnected.
Continue & report alarm
RTU-PD01 continues exchanging data with
the master and alarms it when there is
Modbus slave getting disconnected.
Stop I/O exchange & report fault
RTU-PD01 stops exchanging data with the
master and reports error to it when there is
Modbus slave getting disconnected.
Ignore & continue I/O exchange
RTU-PD01 continues exchanging data with
the master even when error occurs in the
right-side special I/O module.
Continue & report alarm
RTU-PD01 continues exchanging data with
the master and alarms it when error occurs in
the right-side special I/O module.
Stop I/O exchange & report fault
RTU-PD01 stops exchanging data with the
master and reports error to it when error
occurs in the right-side special I/O module.
Modbus timeout setting
(ms)
0 ~ 65535
Modbus communication timeout. Unit: ms
Diagnose cycle (s)
1 ~ 20
Cycle for RTU-PD01 to diagnose the
right-side special I/O module. Unit: s
Loss communication
with master
8, N, 1
8, N, 2
19,200bps
38,400bps
57,600bps
115,200bps
Modbus slave error
Loss modbus slave
IO module error
Modbus communication format (including
data bit, stop bit and parity bit)
Modbus serial transmission speed
8.2 Configuration Items
RTU-PD01 offers every flexible configuration method when being configured in PROFIBUS DP master
configuration tool, for example, you can configure digital I/O modules or special I/O modules by the
actual name of the module, or self-define the cofiguration.
DVP-PLC Operation Manual
9
PROFIBUS DP Slave Communicaion Module RTU-PD01
Configuration item
Configurable device
Configuration method
Modbus 1 read address
Modbus 2 read address
Modbus 4 read address
Modbus 8 read address
Modbus 1 write address
Modbus 2 write address
Modbus 4 write address
Modbus devices connected to RTU-PD01
Modbus
Modbus 8 write address
Modbus 1 read & write address
Modbus 2 read & write address
Modbus 4 read & write address
Modbus 8 read & write address
DVP08SM11N
DVP08SM11N connected to RTU-PD01
DVP08SN11R/T
DVP08SN11R or DVP08SN11T connected to
RTU-PD01
DVP08SP11R/T
DVP08SP11R or DVP08SP11T connected to
RTU-PD01
DVP16SP11R/T
DVP16SP11R or DVP16SP11T connected to
RTU-PD01
DVP08ST
DVP08ST module connected to RTU-PD01
Standard configuration
method for digital I/O
module
8 DI
8 DO
8 DIDO
16 DI
16 DO
16 DIDO
32 DI
Digital I/O modules connected to RTU-PD01
Self-defined
configuration method
for digital I/O module
32 DO
32 DIDO
64 DI
64 DO
64 DIDO
10
DVP04AD
DVP04AD-S connected to RTU-PD01
DVP06AD
DVP06AD-S connected to RTU-PD01
DVP02DA
DVP02DA-S connected to RTU-PD01
DVP04DA
DVP04DA-S connected to RTU-PD01
DVP06XA
DVP06XA-S connected to RTU-PD01
DVP04PT
DVP04PT-S connected to RTU-PD01
DVP04TC
DVP04TC-S connected to RTU-PD01
Standard configuration
method for special I/O
module
DVP-PLC Operation Manual
PROFIBUS DP Slave Communicaion Module RTU-PD01
Configuration item
Configurable device
Configuration method
1 AI
2 AI
4 AI
8 AI
1 AO
2 AO
4 AO
Special I/O modules connected to RTU-PD01
Self-defined
configuration method
for special I/O module
8 AO
1 AIAO
2 AIAO
4 AIAO
8 AIAO
8.3 Settings of Configuration Items
8.3.1 Settings of Configuration Items for Digital I/O Modules
There are 2 types of configuration items for digital I/O modules, standard configuration and
self-defined configuration. By standard configuration, the digital I/O module is named after its
actual name, whereas it is named after the number of points by self-defined configuration. You do
not have to set up parameters in the configuration. The digital I/O can correspond to the master
directly after the configuration
8.3.2 Settings of Configuration Items for Special I/O Modules
The special I/O module is named after its actual name in the configuration. You can configure
special I/O module by standard configuration items. Detailed configuration methods will be
explained in the following paragraphs.
z Configuration method for DVP06AD-S and DVP04AD-S
Refer to the figure below for the relevant parameters to configure DVP06AD-S. DVP04AD-S and
DVP06AD-S have the same parameters to set, except that DVP06AD-S has two more parameters for
input channels to set than does DVP04AD-S (Therefore, only the parameter settings for DVP06AD-S
are introduced in this section).
DVP-PLC Operation Manual
11
PROFIBUS DP Slave Communicaion Module RTU-PD01
Definitions of configuration items:
Parameter
Location
CH1 input mode
CH2 input mode
CH3 input mode
CH4 input mode
CH5 input mode
CH6 input mode
Value
Definition
0~7
The location of DVP06AD-S at the right side of RTU-PD01. The
location of the first special I/O module at the right side of
RTU-PD01 is 0, the second is 1 and so forth. This rule is only
applicable on special I/O modules.
-10V ~ +10V
The input channel on DVP06AD-S is set to mode 0: Voltage input
mode. Input range: -10V ~ +10V
-6V ~ +10V
The input channel on DVP06AD-S is set to mode 1: Voltage input
mode. Input range: -6V ~ +10V.
-12mA ~ +20mA
The input channel on DVP06AD-S is set to mode 2: Current input
mode. Input range: -12mA ~ +20mA
-20mA ~ +20mA
The input channel on DVP06AD-S is set to mode 3: Current input
mode. Input range: -20mA ~ +20mA
Current value
Current value of the input signal in all channels on DVP06AD-S
Average value
Average value of the input signals in all channels on DVP06AD-S
1 ~ 4096
The average times
Input value mode
Average times
z Configuration method for DVP04DA-S and DVP02DA-S
Refer to the figure below for the relevant parameters to configure DVP04DA-S. DVP04DA-S and
DVP02DA-S have the same parameters to set, except that DVP04DA-S has two more parameters for
input channels to set than does DVP02DA-S (Therefore, only the parameter settings for DVP04DA-S
are introduced in this section).
12
DVP-PLC Operation Manual
PROFIBUS DP Slave Communicaion Module RTU-PD01
Definitions of configuration items:
Parameter
Location
CH1 output mode
CH2 output mode
CH3 output mode
CH4 output mode
Value
Definition
0~7
The location of DVP04DA-S at the right side of RTU-PD01. The
location of the first special I/O module at the right side of RTU-PD01 is
0, the second is 1 and so forth. This rule is only applicable on special
I/O modules.
0V ~ 10V
The output channel on DVP04DA-S is set to mode 0: Voltage output
mode. Output range: 0V ~ +10V
2V ~ 10V
The output channel on DVP04DA-S is set to mode 1: Voltage output
mode. Output range: 2V ~ 10V
4mA ~ 20mA
The output channel on DVP04DA-S is set to mode 2: Current output
mode. Output range: 4mA ~ 20mA
0mA ~ 20mA
The output channel on DVP04DA-S is set to mode 3: Current output
mode. Output range: 0mA ~ 20mA
z Configuration method for DVP06XA-S
Refer to the figure below for the relevant parameters to configure DVP06XA-S.
DVP-PLC Operation Manual
13
PROFIBUS DP Slave Communicaion Module RTU-PD01
Definitions of configuration items:
Parameter
Location
CH1 input mode
CH2 input mode
CH3 input mode
CH4 input mode
CH5 output mode
CH6 output mode
Input value mode
Set average times
14
Value
Definition
0~7
The location of DVP06XA-S at the right side of RTU-PD01. The
location of the first special I/O module at the right side of
RTU-PD01 is 0, the second is 1 and so forth. This rule is only
applicable on special I/O modules.
-10V ~ +10V
The input channel on DVP06XA-S is set to mode 0: Voltage input
mode. Input range: -10V ~ +10V
-6V ~ +10V
The input channel on DVP06XA-S is set to mode 1: Voltage input
mode. Input range: -6V ~ +10V
-12mA ~ +20mA
The input channel on DVP06XA-S is set to mode 2: Current input
mode. Input range: -12mA ~ +20mA
-20mA ~ +20mA
The input channel on DVP06XA-S is set to mode 3: Current input
mode. Input range: -20mA ~ +20mA
0V ~ 10V
The output channel on DVP06XA-S is set to mode 0: Voltage
output mode. Output range: 0V ~ +10V
2V ~ 10V
The output channel on DVP06XA-S is set to mode 1: Voltage
output mode. Output range: 2V ~ 10V
4mA ~ 20mA
The output channel on DVP06XA-S is set to mode 2: Current
output mode. Output range: 4mA ~ 20mA
0mA ~ 20mA
The output channel on DVP06XA-S is set to mode 3: Current
output mode. Output range: 0mA ~ 20mA
Current value
Current value of the input signal in CH1 ~ CH4 on DVP06XA-S
Average value
Average value of the input signals in CH1 ~ CH4 on DVP06XA-S
1 ~ 4096
The average times
DVP-PLC Operation Manual
PROFIBUS DP Slave Communicaion Module RTU-PD01
z Configuration method for DVP04PT-S
Refer to the figure below for the relevant parameters to configure DVP04PT-S.
Definitions of configuration items:
Parameter
Location
Value
0~7
The location of DVP04PT-S at the right side of RTU-PD01. The
location of the first special I/O module at the right side of
RTU-PD01 is 0, the second is 1 and so forth. This rule is only
applicable on special I/O modules.
Centigrade (°C)
Collecting temperature in Centigrade by CH1 ~ CH4 on
DVP04PT-S
Fahrenheit (°F)
Collecting temperature in Fahrenheit by CH1 ~ CH4 on
DVP04PT-S
Current value
Current value of the collected temperature at CH1 ~ CH4 on
DVP04PT-S
Average value
Average value of the collected temperatures at CH1 ~ CH4 on
DVP04PT-S
1 ~ 4096
The average times.
Temperature mode
Input value mode
Average times
Definition
z Configuration method for DVP04TC-S
Refer to the figure below for the relevant parameters to configure DVP04TC-S.
DVP-PLC Operation Manual
15
PROFIBUS DP Slave Communicaion Module RTU-PD01
Definitions of configuration items:
Parameter
Value
Definition
Location
0~7
The location of DVP04TC-S at the right side of RTU-PD01. The
location of the first special I/O module at the right side of
RTU-PD01 is 0, the second is 1 and so forth. This rule is only
applicable on special I/O modules.
CH1 input mode
J, K, R, S, T
Thermocouple type for CH1 on DVP04TC-S
CH2 input mode
J, K, R, S, T
Thermocouple type for CH2 on DVP04TC-S
CH3 input mode
J, K, R, S, T
Thermocouple type for CH3 on DVP04TC-S
CH4 input mode
J, K, R, S, T
Thermocouple type for CH4 on DVP04TC-S
Current value
Current value of the collected temperature at CH1 ~ CH4 on
DVP04TC-S
Average value
Average value of the collected temperatures at CH1 ~ CH4 on
DVP04TC-S
1 ~ 4096
The average times
Centigrade (°C)
Collecting temperature in Centigrade by CH1 ~ CH4 on
DVP04TC-S
Fahrenheit (°F)
Collecting temperature in Fahrenheit by CH1 ~ CH4 on
DVP04TC-S
Input value mode
average times
Temperature mode
8.3.3 Self-Defined Configuration Settings for Special I/O Modules
In self-defined configuration, special I/O modules are named after their configurable number of
control registers (CR). You can choose the CR in the special I/O module to be read or written
when configuring. See the following paragraphs for the meanings of each configuration item.
16
DVP-PLC Operation Manual
PROFIBUS DP Slave Communicaion Module RTU-PD01
z Configuration method for 8AI, 4AI, 2AI and 1AI modules
Refer to the figure below for the relevant parameters to configure an 8AI module. 8AI, 4AI, 2AI and
1AI modules have the same parameters to set, except that the number of configurable CRs in 1AI, 2AI
and 4AI modules is different from that of 8AI module (Therefore, only the parameter settings for 8AI
are introduced in this section).
Definitions of configuration items:
Parameter
Value
Location
0~7
Module
DVP04AD
DVP06AD
DVP02DA
DVP04DA
Input CR number 1:
Slave → Master
0 ~ 48
Input CR number 2
0 ~ 48
Input CR number 3
0 ~ 48
Input CR number 4
0 ~ 48
Input CR number 5
0 ~ 48
Input CR number 6
0 ~ 48
Input CR number 7
0 ~ 48
Input CR number 8
0 ~ 48
DVP-PLC Operation Manual
Definition
The location of the special I/O module at the right
side of RTU-PD01. The location of the first special
I/O module at the right side of RTU-PD01 is 0, the
second is 1 and so forth. This rule is only applicable
on special I/O modules.
DVP06XA
DVP04PT
DVP04TC
DVP01PU
Special I/O module in use
No. of the CR in special I/O module to be read by
PROFIBUS DP master
17
PROFIBUS DP Slave Communicaion Module RTU-PD01
z Configuration method for 8AO, 4 AO, 2AO and 1AO modules
Refer to the figure below for the relevant parameters to configure an 8AI module. 8AO, 4AO, 2AO and
1AO modules have the same parameters to set, except that the number of configurable CRs in 1AO,
2AO and 4AO modules is different from that of 8AO module (Therefore, only the parameter settings
for 8AO are introduced in this section).
Definitions of configuration items:
Parameter
18
Value
Location
0~7
Module
DVP04AD
DVP06AD
DVP02DA
DVP04DA
Output CR number 1:
Master → Slave
0 ~ 48
Output CR number 2
0 ~ 48
Output CR number 3
0 ~ 48
Output CR number 4
0 ~ 48
Output CR number 5
0 ~ 48
Output CR number 6
0 ~ 48
Output CR number 7
0 ~ 48
Output CR number 8
0 ~ 48
Definition
The location of the special I/O module at the right
side of RTU-PD01. The location of the first
special I/O module at the right side of RTU-PD01
is 0, the second is 1 and so forth. This rule is only
applicable on special I/O modules.
DVP06XA
DVP04PT
DVP04TC
DVP01PU
Special I/O module in use
No. of the CR in special I/O module to be written
by PROFIBUS DP master
DVP-PLC Operation Manual
PROFIBUS DP Slave Communicaion Module RTU-PD01
z Configuration method for 8AIAO, 4AIAO, 2AIAO and 1AIAO modules
Refer to the figure below for the relevant parameters to configure an 8AIAO module. 8AIAO, 4AIAO,
2AIAO and 1AIAO modules have the same parameters to set, except that the number of configurable
CRs in 1AIAO, 2AIAO and 4AIAO modules is different from that of 8AIAO module (Therefore, only the
parameter settings for 8AIAO are introduced in this section).
Definitions of configuration items:
Parameter
Value
Location
0~7
Module
DVP04AD
DVP06AD
DVP02DA
DVP04DA
Input CR number 1:
Slave → Master
0 ~ 48
Input CR number 2
0 ~ 48
Input CR number 3
0 ~ 48
Input CR number 4
0 ~ 48
Input CR number 5
0 ~ 48
Input CR number 6
0 ~ 48
Input CR number 7
0 ~ 48
Input CR number 8
0 ~ 48
DVP-PLC Operation Manual
Definition
The location of the special I/O module at the
right side of RTU-PD01. The location of the first
special I/O module at the right side of
RTU-PD01 is 0, the second is 1 and so forth.
This rule is only applicable on special I/O
modules.
DVP06XA
DVP04PT
DVP04TC
DVP01PU
Special I/O module in use
No. of the CR in special I/O module to be read
by PROFIBUS DP master
19
PROFIBUS DP Slave Communicaion Module RTU-PD01
Parameter
Value
Output CR number 1:
Master → Slave
0 ~ 48
Output CR number 2
0 ~ 48
Output CR number 3
0 ~ 48
Output CR number 4
0 ~ 48
Output CR number 5
0 ~ 48
Output CR number 6
0 ~ 48
Output CR number 7
0 ~ 48
Output CR number 8
0 ~ 48
Definition
No. of the CR in special I/O module to be written
by PROFIBUS DP master
8.3.4 Modbus Configuration Settings
In Modbus configuration, parameters are named after the address of configurable Modbus
device. See the following paragraphs for the meanings of each configuration item.
z Configuration method for Modbus 8 read address, Modbus 4 read address, Modbus 2 read address
and Modbus 1 read address
Refer to the figure below for the relevant parameters to configure Modbus 8 read address. Modbus 8
read address, Modbus 4 read address, Modbus 2 read address and Modbus 1 read address have the
same parameters to set, except that the addresses of configurable Modbus device for Modbus 4 read
address, Modbus 2 read address and Modbus 1 read address are different from that of Modbus 8
read address (Therefore, only the parameter settings for Modbus 8 read address are introduced in
this section).
20
DVP-PLC Operation Manual
PROFIBUS DP Slave Communicaion Module RTU-PD01
Definitions of configuration items:
Parameter
Value
Node ID
1 ~ 254
Read address 1: Slave →
Master
0 ~ 65535
Read address 2
0 ~ 65535
Read address 3
0 ~ 65535
Read address 4
0 ~ 65535
Read address 5
0 ~ 65535
Read address 6
0 ~ 65535
Read address 7
0 ~ 65535
Read address 8
0 ~ 65535
Definition
Address of Modbus device connected to RTU-PD01
Parameter address of Modbus device to be read by
PROFIBUS DP master
z Configuration method for Modbus8 write address, Modbus 4 write address, Modbus 2 write address,
and Modbus 1 write address
Refer to the figure below for the relevant parameters to configure Modbus 8 write address. Modbus 8
write address, Modbus 4 write address, Modbus 2 write address and Modbus 1 write address have
the same parameters to set, except that the addresses of configurable Modbus device for Modbus 4
write address, Modbus 2 write address and Modbus 1 write address are different from that of Modbus
8 write address (Therefore, only the parameter settings for Modbus 8 write address are introduced in
this section).
DVP-PLC Operation Manual
21
PROFIBUS DP Slave Communicaion Module RTU-PD01
Definitions of configuration items:
Parameter
Value
Node ID
Write address 1
Master → Slave
1 ~ 254
:
Definition
Address of Modbus device connected to RTU-PD01
0 ~ 65535
Write address 2
0 ~ 65535
Write address 3
0 ~ 65535
Write address 4
0 ~ 65535
Write address 5
0 ~ 65535
Write address 6
0 ~ 65535
Write address 7
0 ~ 65535
Write address 8
0 ~ 65535
Parameter address of Modbus device to be written by
PROFIBUS DP master
z Configuration method for Modbus 8 read & write address, Modbus 4 read & write address, Modbus 2
read & write address and Modbus 1 read & write address
Refer to the figure below for the relevant parameters to configure Modbus 8 read & write address.
Modbus 8 read & write address, Modbus 4 read & write address, Modbus 2 read & write address and
Modbus 1 read & write address have the same parameters to set, except that the addresses of
configurable Modbus device for Modbus 4 read & write address, Modbus 2 read & write address and
Modbus 1 read & write address are different from that of Modbus 8 read & write address (Therefore,
only the parameter settings for Modbus 8 read & write address are introduced in this section).
22
DVP-PLC Operation Manual
PROFIBUS DP Slave Communicaion Module RTU-PD01
Definitions of configuration items:
Parameter
9
Value
Node ID
1 ~ 254
Read address 1:
Slave → Master
0 ~ 65535
Read address 2
0 ~ 65535
Read address 3
0 ~ 65535
Read address 4
0 ~ 65535
Read address 5
0 ~ 65535
Read address 6
0 ~ 65535
Read address 7
0 ~ 65535
Read address 8
0 ~ 65535
Write address 1:
Master → Slave
0 ~ 65535
Write address 2
0 ~ 65535
Write address 3
0 ~ 65535
Write address 4
0 ~ 65535
Write address 5
0 ~ 65535
Write address 6
0 ~ 65535
Write address 7
0 ~ 65535
Write address 8
0 ~ 65535
Definition
Address of Modbus device connected to RTU-PD01
Parameter address of Modbus device to be read by
PROFIBUS DP master
Parameter address of Modbus device to be written by
PROFIBUS DP master
LED Indicator and Trouble-shooting
There are 5 LED indicators on RTU-PD01: POWER, NET, RS-485, RUN and ALARM.
z POWER LED
POWER LED displays whether the power supply on RTU-PD01 is working normally.
LED status
Indication
How to correct
Green light on
Normal
---
Off
No power supply
Check if the power supply is normal.
z NET LED
NET LED displays whether the communication between RTU-PD01 and PROFIBU DP master is
working normally.
LED status
Green light on
Red light on
Indication
How to correct
Normal
---
RTU-PD01 is not connected to
the master.
1. Check if RTU-PD01 is connected to PROFIBUS
DP bus.
2. Check if the communication cable between
RTU-PD01 and PROFIBUS DP master is in
normal status.
DVP-PLC Operation Manual
23
PROFIBUS DP Slave Communicaion Module RTU-PD01
LED status
Red light on
Red light flashes
Indication
How to correct
RTU-PD01 is not connected to
the master.
3. Check if the actual address of RTU-PD01 is
consistent with the one set in the master
configuration software.
RTU-PD01 setting or
configuration error
1. Check if the PROFIBUS address of RTU-PD01
is between 1 and 125 (decimal).
2. Check if the I/O modules actually connected to
RTU-PD01 and their order are consistent with
the software configuration.
z RS-485 LED
RS-485 LED displays whether the RS-485 communication between RTU-PD01 and the Modbus
device connected is working normally.
LED status
Indication
How to correct
Green light on
Normal
---
Green light
flashes
The Modbus function has not
been enabled, or no Modbus
slave is configured.
---
Red light on
All Modbus slaves are off-line
Check if the RS-485 cable is working normally, or
the communication format is correct.
Red light flahses
The RS-485 communication
with part of the Modbus devices
connected is abnormal.
Check if part of the RS-485 devices connected
have not responded or responded incorrectly.
z RUN LED
RUN LED displays whether RTU-PD01 is operating or in stop status.
RUN status
Indication
Green light on
RTU-PD01 is operating.
Off
RTU-PD01 is in stop status.
z ALARM LED
ALARM LED displays whether the right-side special I/O module is working normally and the power
supply is sufficient.
LED status
How to correct
Off
Normal
---
Red light on
DV24V power supply is
insufficient.
Check if the power supply is overloaded.
Red light slowly
flashes (on 0.5s
and off 0.5s)
Error in special I/O module
Please refer to the explanations on error
registersfor special I/O module in “DVP-PLC
Application Manual – Special Modules”.
Special I/O module is off-line.
1. Check if the power supply on special I/O module
is normal.
2. Check if the connection between RTU-PD01 and
special module is working normally.
Red light fast
flashes (on 0.3s
and off 0.3s)
24
Indication
DVP-PLC Operation Manual
PROFIBUS DP Slave Communicaion Module RTU-PD01
10 Application Example 1
Mission:
Exchanging data between S7-300 (Siemens PLC) and RTU-PD01 through PROFIBUS DP network
Connecting RTU-PD01 to PROFIBUS DP network:
1. S7-300 as the PROFIBUS DP master; RTU-PD01 as the slave. See the PROFIBUS DP network in
the figure below.
2. Set the PROFIBUS address of RTU-PD01 to “1”.
3. Connect RTU-PD01 to DVP16SP, DVP08SP, DVP04AD-S and DVP02DA-S in order at its right hand
side. Make sure the connection and wiring between RTU-PD01 and the special I/O modules and to
the entire network is correct.
Configuring RTU-PD01 in PROFIBUS DP network (the software configuration):
z Create a new project by software wizard
1. Open SIMATIC Manager.
DVP-PLC Operation Manual
25
PROFIBUS DP Slave Communicaion Module RTU-PD01
2. Select “File” => “New Project Wizard”.
3. Click “Next” in the wizard.
26
DVP-PLC Operation Manual
PROFIBUS DP Slave Communicaion Module RTU-PD01
4. Select “CPU315-2 DP” for CPU as we are using the S7-300 model. Click “Next”.
5. Select the block we need and click “Next”.
DVP-PLC Operation Manual
27
PROFIBUS DP Slave Communicaion Module RTU-PD01
6. Enter the project name and click “Finish”.
7. A new window will appear after the project is created.
z Add PROFIBUS DP bus
1. Select “SIMATIC 300 Station” in the project created. Double click “Hardware”, and a new window
(HW-Config) will appear.
28
DVP-PLC Operation Manual
PROFIBUS DP Slave Communicaion Module RTU-PD01
2. In the “HW Config” window, double click “DP” in the left-hand side column and a dialog box will
appear.
DVP-PLC Operation Manual
29
PROFIBUS DP Slave Communicaion Module RTU-PD01
3. Click “Properties” in the dialog box, leading to another dialog box.
4. Select “Address” in the dialog box to be the address of the master. Then Click “New” to go to the
next dialog box.
30
DVP-PLC Operation Manual
PROFIBUS DP Slave Communicaion Module RTU-PD01
5. Select communication speed and bus type, then click “OK”.
6. Confirm the communication speed and master address for PROFIBUS DP bus, then click “OK”.
DVP-PLC Operation Manual
31
PROFIBUS DP Slave Communicaion Module RTU-PD01
7. Confirm the information on the PROFIBUS DP bus in the dialog box and click “OK”.
8. Once all the parameters are set, a PROFIBUS DP bus will appear after the UR window.
32
DVP-PLC Operation Manual
PROFIBUS DP Slave Communicaion Module RTU-PD01
z Add GSD file
1. Select “Options” => “Install New GSD” in the HW Config window.
2. Find the path of the GSD file, select it and click “Install” to add the GSD file needed.
DVP-PLC Operation Manual
33
PROFIBUS DP Slave Communicaion Module RTU-PD01
3. We can then see RTU-PD01 in the right-hand side column. RTU-PD01 is the module added.
z Add RTU-PD01 slave and set up parameters
1. Select PROFIBUS DP on the right-hand side column and double click “RTU-PD01” to open a dialog
box.
34
DVP-PLC Operation Manual
PROFIBUS DP Slave Communicaion Module RTU-PD01
2. In the dialog box, select the address of RTU-PD01 slave. The address has to be the same as the
setting of address setup switch on RTU-PD01. Click “OK”.
3. Add PROFIBUS DP bus to RTU-PD01.
DVP-PLC Operation Manual
35
PROFIBUS DP Slave Communicaion Module RTU-PD01
4. Select Slot 0 and double click “DVP16SP11R/T” in the right-hand side column.
5. Configure DVP16SP11R/T to Slot 0.
6. Configure other slots as configuring Slot 0. To configure, select one of the slots and double click on
the items to be configured in the right-hand side column. Apply it to configure Slot 0 ~ Slot 4.
36
DVP-PLC Operation Manual
PROFIBUS DP Slave Communicaion Module RTU-PD01
7. Slot 0 and Slot 1 are for the configuration of digital I/O modules. The configuration of digital I/O
modules does not require other parameter settings. When you configure digital I/O modules by
self-defined method, and if the number of I/O points is less than 8, the calculation will be based on
the number 8. For example, Slot 1 is configured 8DIDO, and its corresponding digital I/O module is
DVP08SP (4 input points and 4 output points). See the following paragraph for detailed
corresponding relations between slots and I/O modules.
8. Double click the configured Slot 2 in “HW Config” window to open the dialog box in the figure below.
Refer to 8.3.2 for the definition of every parameter in this dialog box.
DVP-PLC Operation Manual
37
PROFIBUS DP Slave Communicaion Module RTU-PD01
9. Double click the configured Slot 3 in “HW Config” window to open the dialog box in the figure below.
Refer to 8.3.3 for the definition of every parameter in this dialog box.
10. Double click the configured Slot 4 in “HW Config” window to open the dialog box in the figure below.
Refer to 8.3.4 for the definition of every parameter in this dialog box.
38
DVP-PLC Operation Manual
PROFIBUS DP Slave Communicaion Module RTU-PD01
11. After all the configuration items for RTU-PD01 are set, double click the RTU-PD01 slave on the
PROFIBUS DP bus in “HW Config” window to open the dialog box in the figure below. Refer to 8.1
for the definition of every parameter in this dialog box.
12. After all the parameters are set, download the parameters, and once the master is connected to
RTU-PD01, the NET indicator on RTU-PD01 will constantly be On in green color.
DVP-PLC Operation Manual
39
PROFIBUS DP Slave Communicaion Module RTU-PD01
Data Mapping
See the table below for the data mapping relations under the parameter settings.
Register in S7-300
master
40
Data transmission direction
in PROFIBUS DP network
Slave devices and addresses connected to
RTU-PD01
QB0 bit 0 ~ bit 7
Y0 ~ Y7 on DVP16SP
QB1 bit 0 ~ bit 3
Y0 ~ Y3 on DVP08SP
PQW256
Output value in CH1 on DVP02DA-S
PQW258
Output value in CH2 on DVP02DA-S
PQW260
Modbus address 8192
PQW262
Modbus address 8193
IB0 bit 0 ~ bit 7
X0 ~ X7 on DVP16SP
IB1 bit 0 ~ bit 3
X0 ~ X3 on DVP08SP
PIW256
Input value in CH1 on DVP04AD-S
PIW258
Input value in CH2 on DVP04AD-S
PIW260
Input value in CH3 on DVP04AD-S
PIW262
Input value in CH4 on DVP04AD-S
PIW264
Modbus address 8449
PIW266
Modbus address 8450
DVP-PLC Operation Manual
PROFIBUS DP Slave Communicaion Module RTU-PD01
Program Example
z
When M0.0 = ON, write 1 to Y0 ~ Y7 on DVP16SP and Y0 ~ Y3 on DVP08SP connected to RTU-PD01.
z
When M0.1 = ON, read the status on X0 ~ X7 on DVP16SP connected to RTU-PD01 to MB0, and the
status on X0 ~ X3 on DVP08SP to MB1.
z
You can also read or write other devices connected to RTU-PD01 by using MOVE instruction.
DVP-PLC Operation Manual
41
PROFIBUS DP Slave Communicaion Module RTU-PD01
MEMO
42
DVP-PLC Operation Manual