M-System ASW DC Alarm Instruction manual

Below you will find brief information for DC Alarm ASW ASW. This is a DC alarm module that includes a signal conditioner, input resistor (for current input types only), and a base socket. The module is designed for DIN rail mounting and can be used for various applications where it is crucial to monitor and trigger an alarm if the input signal exceeds or falls below the pre-set thresholds.

PDF Download
Document
DC Alarm ASW ASW  Instruction Manual | Manualzz

Advertisement

Advertisement

Advertisement

Key features

  • DIN rail mounting
  • Adjustable alarm setpoints
  • Hi and Lo output relays
  • 0-10V DC output for monitoring
  • Input resistor for current input
  • Wall mounting option
  • Input signal monitoring
  • Alarm relay operations
  • Power failure trip operation

Frequently asked questions

You can adjust the Hi and Lo setpoint by turning the corresponding adjustment knobs. The setpoints are proportional to voltage output 0-10VDC. You can measure the voltage at the Hi and Lo setpoint monitor jacks to verify the desired voltage is set.

The recommended operating temperature is between -5 to +60°C (23 to 140°F) with a relative humidity of 30 to 90% RH.

The maximum output load is 380V AC/100VA or 125V DC/30W for the relays.

The Hi and Lo output relays will turn on when the input signal exceeds the Hi setpoint or falls below the Lo setpoint, respectively. If a power failure occurs, the terminals 1-3 and 9-11 turn ON.

A 10-minute warm-up time is required for the ASW ASW to achieve complete performance.