SE1VA
SE Series
SPEC SHEET
1ch Alarm Detector (DC Voltage)
Features
(with two large displays)
Model:
SE1VA
• High limit alarm with standby • Low limit alarm with standby
Alarm Energized/
De-energized
Alarm HOLD function
Alarm delay function
Set value lock
Alarm hysteresis
Alarm hysteresis
ON
ON
OFF
OFF
Alarm value
Alarm value
Standby functions.
Model
SE1VA -
-
Alarm action: ON/OFF action
Alarm hysteresis: 0.1 to 100.0%FS
Alarm delay time: 0 to 9999 sec
Alarm Energized/De-energized, Selectable
Alarm HOLD function Enabled/Disabled, Selectable
Alarm 1, 2 outputs: Relay contact 1a
Control capacity: 3A 250V AC (resistive load)
1A 250V AC (inductive load cos =0.4)
Electric life: 100,000 cycles
Alarm 3 to 6 outputs: Open collector
Control capacity: 0.1A 24V DC
-
Socket
1: Screw fall prevention
Finger-safe (for Y terminal)
2: For Ring terminal
Power supply
0: 100 to 240V AC
1: 24V AC/DC
Output points
0: 2-points (Alarm 1, 2 outputs)
1: 6-points (Alarm 1 to 6 outputs)
Performance
Reference accuracy (Ambient temperature: 23 )
• DC voltage input: Within 0.1%
Indication accuracy: Within Reference input accuracy
digit
Input sampling period: 25msec, 125msec, 250msec
(Selectable by keypad)
Temperature coefficient: 0.015%/ or less
Insulation resistance: 10M or more, at 500V DC
(Input - Output - Power)
Dielectric strength: 1.5kV AC for 1 minute
(Input - Output - Power)
How to Order
Specify a model. (E.g.) SE1VA-1-0-0
Factory adjusted value:
Input
1 to 5V DC
Input Specifications
DC voltage
Input range
0 to 1V DC
0 to 5V DC
1 to 5V DC
0 to 10V DC
Input resistance
1M
Allowable signal
source resistance
2k or less
1k or less
Output Specifications
A maximum of 6 points of alarm output available.
For each alarm output, one of the following types can be
selected in [Alarm type]: High limit alarm, Low limit alarm,
High limit alarm with standby and Low limit alarm with
standby.
• High limit alarm
• Low limit alarm
Alarm hystereiss
Alarm hysteresis
ON
ON
OFF
OFF
Alarm value
Alarm value
General Structure
1
Case: Flame-resistant resin Color: Light gray
Front panel: Membrane sheet
Setting: Using the front keypad
Display: Input display: 7-segment Red LED display
4-digit, Character size, 10x4.6mm (HxW)
Set value display: 7-segment Red LED display
4-digit, Character size, 10x4.6mm (HxW)
Power indicator: Green LED
Power indicator
Input display
Set value display
UP Key
DOWN Key
MODE Key
SUB-MODE Key
Light sensor
SE1VA
Installation Specifications
Circuit Configuration & Terminal Arrangement
V(> 1V) DC
A3
output
A4
output
A5
output
+1
-
-
2
3
+
Insulation
circuit
Display/Setting
key circuit
Input
circuit
Insulation
circuit
4
CPU
5
6
Attached Functions
Auto-light function: Automatically measures and controls
brightness of the displays to conserve power.
Power failure countermeasure:
The data is backed up in non-volatile IC memory.
Self diagnosis: The CPU is monitored by a watchdog timer,
and when an abnormal status is found on the CPU, the
unit is switched to warm-up status turning all outputs OFF.
Environmental Specification
RoHS directive compliance
A6
output
V DC
Power supply: 100 to 240V AC 50/60Hz
24V AC/DC 50/60Hz
Allowable voltage range: 85 to 264V AC, 20 to 28V AC/DC
Power consumption: Approx. 9VA
Ambient temperature: -5 to 55
Ambient humidity: 35 to 85%RH (non-condensing)
Mounting: DIN rail
External dimensions: W30xH88xD108mm (socket
included)
Weight: Approx. 200g (socket included)
Insulation
circuit
7
Power
circuit
Output
circuit
Output
circuit
8
13
14
9
10
11
12
+
Power supply
+
A1 output
+
A2 output
-
Alarm 1, 2 outputs: Take the following measures for
relay contact protection and noise reduction.
• AC power
AC
9
Inductive load (coil)
Settings
10
Function keys
(1) UP Key: Increases a numerical value.
(2) DOWN Key: Decreases a numerical value.
(3) MODE Key: Selects a setting mode.
(4) SUB-MODE Key: Re-lights displays. (UP Key,
DOWN Key or MODE Key also re-lights displays.)
Displays and Indicator
Load
Varistor, CR circuit, etc.
• DC power
DC
9
Inductive load (coil)
10
Input display: Indicates the input value.
Indication of -2000 or less: The minus (-) sign and
input value light alternately.
Indication of 10000 or more: The lower 4 digits flash.
Under range: -10% of input span or less:
“
” flashes on the Input display.
Over range: 110% of input span or more:
“
” flashes on the Input display.
Warm-up indication: The input type is indicated on the
Input display for 3 seconds after power
is turned ON.
Set value display: Alarm 1 (A1) to Alarm 6 (A6) values are
indicated (follows the selection in “Display selection”.).
If the UP Key is pressed for 1 second during alarm value
indication, alarm values will be switched thus.
(A1
A2 • • • • A6
A1).
When power is turned ON, A1 value is indicated.
When alarm output is ON, “
” and the value selected
in [Display selection] are alternately indicated on the Set
value display. If the UP Key is pressed together with the
DOWN Key in the above status, the alarm output
currently being turned ON will be displayed.
(E.g.) If Alarm 1 and Alarm 3 outputs are ON, “
”
and “
” are displayed in order.
Power indicator: The green LED is lit when power is
turned ON.
Load
Diode, varistor,
CR circuit, etc.
Alarm 3 to 6 outputs: Connection example of Open
collector output
+
DC
-
External Dimensions (Scale: mm)
Ferrules
Y terminal
Ring terminal
SHINKO TECHNOS CO., LTD.
Tel: 81-72-727-6100
URL: http://www.shinko-technos.co.jp/e/
E-mail: [email protected]
201204016