352 3 fr~v~Fiche technique

352 3 fr~v~Fiche technique
HEAT RECOVERY VENTILATOR
Venmar HRV Solo 2.4
Part no. 45928
114 to 250 CFM (0.3 in. w.g.)
108 to 235 CFM (0.4 in. w.g.)
Controls
• Choose between these two following main controls:
- Altitude programmable digital control
with SMART mode
no. 40445
- Deco-Touch digital control
no. 40400
• Also, the following auxiliary wall controls can be added:
- 20/40/ 60-min. push button
no. 03364
- 60-min. Mechanical timer
no. 00910
- Dehumidistat
no. 11297
For more details about controls, refer to their specification sheet and
to the Main and auxiliary wall control user guide at www.venmar.ca.
Options
VB0230
FOR RENOVATION AND CUSTOM BUILT HOUSES
Designed for homeowners seeking the best performance, added
value and quality.
Recognized for its unsurpassed quality and superior craftsmanship,
this new member of Solo Series features a new level of exceptional
performance. It is guaranteed to satisfy the homeowner looking for
durability, reliability and performance.
• Complete line of registers and diffusers
• Electric duct heater
No Negative Pressure Defrost
Defrost system ensures that no negative pressure is created by air
exhausted to the outdoors, as the air is recirculated into the house,
helping to prevent any backdraft.
Solid Performances
• Best heat recovery in its category
• Best airflow range in its category
• Exclusive convertible HRV to an ERV (Latent Recovery Core)
• Blower design makes the unit quieter than ever
Superior Craftsmanship
• External electrical access side panel
• Integrated balancing dampers
• All serviceable parts removable in 5 minutes
• Aluminum framed foam filter
• Improved sliding system for core insertion
• Exclusive, deeper one piece condensation tray
to prevent water leakage
• No sharp angles on metal parts
• Exclusive, reinforced housing
• Improved defrost damper and damper mechanism,
designed to operate during the toughest weather conditions
Tradition of Quality
• Proven technology and mechanical simplicity for heat recovery
• Low motor temperature operation for longer life expectancy
WARRANTY
The HRV Solo 2.4 unit is protected by a complete 5-year warranty
on all parts. The heat recovery core is covered by a limited lifetime
warranty, with the original proof of purchase.
Available at:
FILTERED AIR
STALE AIR
TO BUILDING
FROM BUILDING
VF0020
OUTSIDE TEMPERATURE DEFROST CYCLE MIN./
°C
°F
OPERATING MIN.
WARMER
WARMER
NO DEFROST
THAN -5
THAN 23
-5 TO -27 23 TO -17
6/32
- 27
-17
6/20
AND LESS
AND LESS
Heat Recovery Core
Dimensions: 12” x 12” x 16.75”
Exchange surface: 166 ft.2
Weight: 9.5 lb.
Material: Polypropylene
Type: Cross Flow
Warranty: Limited lifetime
Requirements and standards
• Complies with the CSA C22.2 no. 113 Standard applicable to ventilators
• Complies with CSA C444 requirements regulating the installation of
Heat Recovery Ventilators
• Technical data was obtained from published results of tests relating
to CSA C439 Standards
• HVI certified
DIMENSIONS: HRV SOLO 2.4
34.625” (879 mm)
30.25” (768 mm)
6.00” (152 mm)
36.00” (914 mm)
Power Cord
Hanging Strap
Mounting Location
Wing Nut
for Blower
Assembly
Service
21.125” (537 mm)
Damper
Actuator
Blower
Assembly
Access
Door
2.19” (55 mm)
VK0044A
NOTE: ALL
20.00” (508 mm)
Drain Fitting
1.50” (38 mm)
UNITS PORTS WERE CREATED TO BE CONNECTED TO DUCTS HAVING A MINIMUM OF
USING AN APPROPRIATE TRANSITION (E.G.:
6” DIAMETER TO 7” DIAMETER TRANSITION).
VENTILATION PERFORMANCE
6” DIAMETER,
Remote / Main
Control Wires
BUT IF NEED BE, THEY CAN BE CONNECTED TO BIGGER SIZED DUCTS BY
ENERGY PERFORMANCE
GROSS AIR FLOW
SUPPLY
EXHAUST
L/S
CFM
L/S
CFM
125
264
126
268
124
262
118
251
116
245
114
241
106
224
107
226
91
193
96
204
79
167
81
172
59
124
57
121
NET SUPPLY
AIR FLOW
L/S
CFM
119
253
118
250
111
235
102
216
87
185
76
160
57
120
2.50” (63 mm)
Electrical Compartment
SUPPLY
NET AIR
TEMPERATURE
FLOW
°C
°F
L/S
CFM
HEATING
0
32 51 109
0
32 73 155
0
32 102 215
-25 -13 52 110
COOLING
-25 -13
225
POWER
SENSIBLE
APPARENT
LATENT RECOVERY/
CONSUMED
RECOVERY
SENSIBLE
MOISTURE
WATTS
EFFICIENCY
EFFECTIVENESS
TRANSFER
92
128
191
104
%
70
65
62
60
%
77
72
70
94
-0.01
-0.02
-0.01
0.05
TOTAL RECOVERY EFFICIENCY
NOT TESTED
100
200
150
125
100
SUPPLY (L/S)
EXHAUST
(L/S)
75
80
70
60
50
50
40
VG0053
25
0
25
50
75
100
AIRFLOW (L/S)
0
VG0040
APPARENT
(%)
NET (%)
90
175
EFFICIENCY
EXTERNAL STATIC PRESSURE – PASCALS
(250 PASCALS = 1” OF WATER)
EXTERNAL
STATIC PRESSURE
PA
IN. W.G.
50
0.2
75
0.3
100
0.4
125
0.5
150
0.6
175
0.7
200
0.8
19.00” (483 mm)
0
25
50
75
100
125
150
GROSS AIR FLOW – L/S (0.47 L/S = 1 CFM)
NOTE: All specifications are subject to change without notice.
SPECIFICATIONS
• Model: HRV Solo 2.4
• Part Number: 45928
• Total Assembled Weight (including
polypropylene core): 73 lb.
• Round shaped ports; fit 6” round ducts
• Drains: 1/2” fittings with 10 ft PVC drain
• Filters: 2 washable 30 ppi reticulated foam
11.75” x 16.75” x 0.75”
Project:
Location:
Part no.: 45928
Qty.:
Submitted by:
• Housing: Pre-painted steel
• Fan Speed Control:
• Insulation: 1” aluminum foil faced fiberglass
- Low, increased low and high speed
• Mounting: Suspension by chains and springs - Two speeds available to user
- Low or increased low speed is selected
• Supply and Exhaust Blower Motor:
at the time of installation
- Bearings: Sleeve bearings
- Type: PSC
• Unit Electrical Characteristics:
Volts Frequency Amps Watts
120
60 Hz
1.9
202
REMARKS
Date:
Residential Products Group, 550 Lemire Blvd., Drummondville, Qc, Canada J2C 7W9 - Tel.: 1-800-567-3855 Fax: 1-800-567-1715
www.venmar-usa.com
HRVSOLO2.4d150202