Installation, Operation and Maintenance Manual

AIR DEHUMIDIFIER DESICCANT ROTOR TYPE

MODEL DFRB-060-E

SERIAL N

º: 1113348

According to the current European Union Rules on Machinery Safety, the reading of these instructions is Imperative before installing the unit.

FISAIR, S.L.

Uranio,20 - P.I. AIMAYR

28330 San Martin de la Vega

MADRID (SPAIN)

+34-91 692 15 14 - +34-91 691 64 56 e-mail : [email protected]

www.fisair.com

Ciudad de Frías, 33, P. I. Camino de Getafe

28021 Madrid

Tel: 91 723 38 40 - Fax: 91 505 30 86 e-mail: [email protected]

DISTRIBUTOR :

L’Energía, 20 P. I. Famades

08940 Cornellá de Llobregat (Barcelona)

Tel: 93 377 69 09 - Fax: 93 377 46 73 e-mail: [email protected]

www.tecniseco.es

Installation, Operation and Maintenance Manual

Desiccant Rotor Type Air Dehumidifiers DFRB series

INDEX

1. Introduction ....................................................................................................................2

1.1 Operating instructions....................................................................................................... 2

1.2 Typographic distinctions .................................................................................................... 2

2. Safety notes ....................................................................................................................2

2.1 General............................................................................................................................ 2

2.2 Operational safety notes.................................................................................................... 2

3. Transport ........................................................................................................................3

3.1 General............................................................................................................................ 3

3.2 Packing............................................................................................................................ 3

3.3 Interim storage................................................................................................................. 3

3.4 Check for complete and correct delivery of goods................................................................ 3

4. General description ........................................................................................................4

4.1 Background ...................................................................................................................... 4

4.2 The desiccant wheel. Operating principle whit integral heat recovery .................................... 4

4.3 Dehumidifier main components identification...................................................................... 5

4.4 The PTC heater ................................................................................................................ 6

4.5 Regulation and control ...................................................................................................... 6

4.6 Options and ancillary components...................................................................................... 7

5. Installation .....................................................................................................................7

5.1 Location of the unit........................................................................................................... 7

5.2 Service Areas ................................................................................................................... 7

5.3 Air duct connections.......................................................................................................... 8

5.4 Electric mains connections................................................................................................. 9

5.5 Control equipment locations and connections...................................................................... 9

6. Start up ...........................................................................................................................9

6.1 Unit start up..................................................................................................................... 9

6.2 Stopping the unit.............................................................................................................. 9

7. Maintenance .................................................................................................................10

7.1 Preventative maintenance ............................................................................................... 10

7.2 Corrective maintenance................................................................................................... 10

7.3 Desiccant wheel service................................................................................................... 10

8. Fault finding..................................................................................................................11

9. Overall dimensions.......................................................................................................12

10. General technical data sheet......................................................................................13

Addenda

A Delivered unit technical data sheet

B Wiring Diagram

C Spare Parts List

F-2833 - 1 - Technical Data Subject to alterations

Installation, Operation and Maintenance Manual

Desiccant Rotor Type Air Dehumidifiers DFRB series

1. Introduction.

2. Safety notes.

Dear customer,

2.1 General.

The FISAIR dehumidifier is our answer to today's technical requirements. It satisfies them by means of its operational safety, its operational comfort and its economic efficiency.

To be sure of operating your FISAIR dehumidifier efficiently please read these

Operation and Maintenance Instructions.

Sequential step to be checked.

These safety notes are required by law. They are for your protection and to prevent accidents.

Warning notes and safety symbols:

The following safety symbols shown in the text will warn about dangers and danger sources. Get familiar with these symbols.

Use the steam humidifier only in proper and safe conditions, paying attention to all notes in these instructions.

If you have any questions...please contact us:

Fisair S.L.

Phone (34) 91 692 15 14

Fax (34) 91 691 64 56 or your local dealer

1.1 Operating instructions.

Attention: Not observing this warning can lead to injury or danger to your life and/or damage to the unit.

Attention, Voltage: Dangerous electrical current. Not observing this warning can lead to injury or danger to your life.

F

Note: Materials/operational equipment; must be handled and/or disposed of according to the law.

Note: Further explanation or cross-references to other sections of the text in the Operation and

Maintenance Instructions.

The correct use of the air dehumidifier also includes adherence to our installation, dismantling, refitting, commissioning, operation and maintenance instructions as well as taking correct disposal steps.

2.2 Operational safety notes.

!

In General:

Only qualified and authorised personnel may operate the unit. Persons transporting or working on the unit, must have read and understood the corresponding parts of the Operation and Maintenance Instructions and specially the chapter “Safety notes“. Additionally, operating personnel must be informed of any possible dangers. You should place a copy of the Operation and

Maintenance Instruction at the unit's operational location (or near the unit).

Observe all safety and warning notices.

If there should be malfunctions, shut down the unit immediately and secure against being restarted. Faults should be rectified immediately.

During repair work, guarantee operational safety of the unit by using qualified personnel.

1.2 Typographic distinctions.

Only use original FISAIR spare-parts.

Enumeration with preceding heading: General enumeration.

For the effective operation of this unit refer to any national regulations restricting or governing its use.

» Enumeration with preceding double chevron: Work or maintenance steps that must be followed sequentially.

!

Accident prevention regulations:

Observe the accident prevention regulations:

F-2833 - 2 - Technical Data Subject to alterations

Installation, Operation and Maintenance Manual

Desiccant Rotor Type Air Dehumidifiers DFRB series

"Electrical Installation and Electrical Equipment" or equivalent national codes. In this way you can prevent injury to yourself or others.

!

Operation of the unit.

Do not impair the safety of the unit.

Periodically check all protection and warning devices for proper functioning.

Safety equipment is not to be removed or put out of operation.

!

Installation, dismantling, maintenance and repair of the Unit.

Turn off power, when doing maintenance work or repairs to the unit.

Extensions to the unit or installation of additional equipment is only allowed after obtaining written approval from the manufacturer.

!

Electrical parts.

Work on electrical parts must be carried out by qualified electricians.

Turn off the power and secure against restart when working on electrical parts.

Immediately turn the unit off when faults occur in the electrical energy supply.

Only use original type fuses of correct rating.

Make periodical checks of the electrical equipment.

Defects, like loose connections or burned cables must be repaired immediately.

Test all installed protective devices after installation or repairs (e.g. grounding).

3. Transport.

3.1 General.

F

Note: Transport the air dehumidifier carefully. Prevent damage from careless loading and unloading and avoid the use of unnecessary force.

3.2 Packing.

F

Note: Observe the pictograms displayed on the package.

3.3 Interim storage.

During storage, keep the unit dry and protected from frost.

3.4 Check for complete and correct delivery of goods.

Upon receipt of the unit, make sure that:

!

Type and serial number on the name plate correspond to the order and supply information,

!

Equipment is complete and in perfect condition.

F

Note: Immediately file a written claim with your shipping agent in case of transport damage or missing parts.

F-2833 - 3 - Technical Data Subject to alterations

Installation, Operation and Maintenance Manual

Desiccant Rotor Type Air Dehumidifiers DFRB series

4. General description.

4.1 Background.

Modern standards concerning human comfort and the environmental requirements for manufacturing, storage & preservation of products and materials, make increasing demands on the control of moisture content in the working environment.

Where the natural or treated environment have an ambient condition holding more water vapour than the specified or desirable conditions, it is necessary to integrate equipment which can reduce humidity to the desired level.

FISAIR ROTARY DESICCANT DEHUMIDIFIER provides the solution

The FISAIR dehumidifier is simple to install, reliable in operation and will provide long lasting humidity control at a reasonable running cost.

4.2 The desiccant wheel. Operating principle with integral heat recovery

In DFRB series the face of the cylinder is divided in three zones:

!

The Process Air Zone occupies 210 degrees approximately of the circle's face. In this section the desiccant removes moisture from the process air passing through the rotating desiccant cylinder.

!

The Reactivation Air Zone occupies 90 degrees approximately of the circle's face. In this section the reactivation air passes counterflow, previously heated to a temperature enough to open the desiccant pores, removing moisture from the desiccant.

!

The Heat Recovery Zone occupies resting 60 degrees of the circle's face. In this section the reactivation air, before reaching the air heater, passes through the desiccant wheel in the

Process Air direction, cooling down the desiccant material while reactivation air is pre-heated causing the heater consumption to decrease.

WET AIR HEATER

Drying

(210 º)

REACTIVATION

AIR

PROCESS

AIR INLET

DRY AIR

DRIVING MOTOR

FISAIR dehumidifiers operate on the adsorption property of a desiccant synthesised activated silica gel manufactured into a cylindrical wheel shape with multiple axial channels.

60 º

(*)

Reactivation

(90 º)

Heat

Recovery

(*) For DFRB-015-E model the face of the cylinder have other divisions:

!

!

!

Process air zone: 180

º.

Reactivation air zone: 90º.

Heat recovery zone: 90º.

A gear motor via a pulley and driving belt rotates the cylinder at a low speed to provide a continuous and uniform operation, with a low energy consumption.

Perimetric and radial air seals separate air circuits and prevent air loss to ensure maximum performance.

F-2833 - 4 - Technical Data Subject to alterations

Installation, Operation and Maintenance Manual

Desiccant Rotor Type Air Dehumidifiers DFRB series

4.3 Dehumidifier main components identification.

1 2 3 7 4 6 3

PROCESS

AND REACTIVATION

AIR

WET

AIR

DRY

AIR

PROCESS AND

REACTIVATION AIR

WET

AIR

1 5

7

4

1

6

5

1

DESICCANT ROTOR

2

OUTER FRAME

3

ELECTRIC CABINET

4

FAN

5

6

ROTOR DRIVING MOTOR

7

AIR FILTER

DRY

AIR

The above schematic drawing shows the FISAIR series

DFRB dehumidifiers main components disposition as well as the air flow diagrams.

These models have relative low air flow and they incorporate a direct driven single ear centrifugal fan that moves the process/dry air as well as the reactivation/wet air. The air is aspired by the fan through circular connections, filtered and impelled against one face of the desiccant rotor. By means of the opportune partitions of the frontal area of the desiccant rotor, part of the impelled air suffers a direction change of 180 degrees, passes through the reactivation air heater, and then crosses counterflow the desiccant rotor which is this way reactivated for a new cycle. Dry air and wet air outlets are made also with circular standard connections.

F-2833 - 5 - Technical Data Subject to alterations

Installation, Operation and Maintenance Manual

Desiccant Rotor Type Air Dehumidifiers DFRB series

The unit electrical components are disposed into an enclosure with a folding cover located at the upper right front of the unit that can be accessed loosening the screws. The following items can be found in the front:

!

One ammeter to show the reactivation heater current.

!

One on/off switch with lighting indicator.

!

Two cable conduits for the electric mains and the hygrostat connection cables and/or remote on/off.

!

In 3-phase models, an isolating switch.

The driving motor, fan and filter are easily accessible by dismounting the upper cover of the unit, fixed by Tknob screws, that can be tighten or loosen by hand.

The air heater is located at the bottom central part of the unit. This can be accessed dismounting the front protection cover which acts also as reactivation air deflector.

4.4 The PTC heater.

FISAIR DFRB series dehumidifiers use a PTC (Positive

Temperature Coefficient) heater to heat the reactivation air with aluminium fins instead of a conventional electric resistance heater.

PTC heater is a semiconductor with variable electric resistance depending on its surface temperature. It is a ceramic polycrystalline compound, basically Barium

Titannate with self temperature limitation. When connected to mains the semiconductor surface reaches a maximum temperature of 230º C (aprox.), absorbing a variable electric power depending on the air flow that crosses through it. Typical operating diagrams of these heaters are:

Resistance

Temperature

Resistance-Temperature Diagram

Power

Air Flow

Power - Air Flow Diagram

PTC heater surface temperature self limitation effect provides the following advantages:

» Since the manufacture materials are designed to support the highest surface temperature, fire risk is limited even without air flow.

» The harmful atmospheric dust combustion doesn't happen.

» A limiting thermostat to protect heater is not necessary.

» Since dehumidification capacity is proportional to reactivation power and through the PTC heater this is proportional to the heated air flow, its reduction will proportionally decrease the unit capacity. This effect is inmediately and easily noticed at the integral ammeter of the unit when the wet air discharge duct is strangled or obstructed.

4.5 Regulation and control.

As a consequence of the PTC heater operation explained above, dehumidifier DFRB drying capacity can be regulated in two different ways:

!

On-Off Control: When you use the hygrostat terminals marked as H1 on wiring diagram, if the circuit is opened the PTC heater is switched off. The air on the unit keeps on blowing but it is not dehumidified.

When using connection marked as H2 on wiring diagram, if the circuit is opened the unit is completely switched off.

F

Note: The hygrostat must have a 10 A electric cut-off resistive capacity. Otherwise an auxiliary relay must be installed.

F-2833 - 6 - Technical Data Subject to alterations

Installation, Operation and Maintenance Manual

Desiccant Rotor Type Air Dehumidifiers DFRB series

!

!

!

!

Proportional Control.- Other way to reduce the air heater power consumption and consequently the drying capacity of the unit, is to install a regulation damper in the wet air discharge duct. If the damper is driven by a proportional humidity controller, the dehumidifier capacity will be proportionally controlled in a modular way.

4.6 Options and ancillary components.

On demand, DFRB series of FISAIR dehumidifiers can be provided with:

Control Hygrostat On-Off.

Runtime Counter.

!

Manually or motor driven air flow regulation dampers.

Wall mounting or self carrier base.

5. Installation.

5.1 Location of the unit.

Before installing FISAIR dehumidifiers the following points should be considered

» If the dehumidifier has to be stored for a significant period prior to installation it should be protected from external damage and dust and construction material.

F

Note: In the case of outdoor storage, weatherproof covers should be employed.

» The FISAIR DFRB dehumidifier is designed for internal installation, for outdoor use please apply to your local representative for special construction details.

» Once final location is defined ensure that there is enough space for servicing to be carried out. Take care to ensure that ducting connections are made without stressing the unit.

5.2 Service Areas.

Using the attached dimensioned drawings of the relevant model, consider periodically:

» Air filters must be cleaned or changed.

» The desiccant wheel faces should be inspected and cleaned and the air seals adjusted as necessary.

» Driving belt should be checked for fatigue and its tightness checked.

» Check the operation of fans and motors and the reactivation heater. In case of failure, repair or replace.

» Check the components in the control box, service or change as necessary.

F

Note: To service/replace the main inside components, dismount the top cover and sided plates. This will provide enough space to service everything.

Pay attention to avoid that ducting connections and unit location do not prevent servicing.

F-2833 - 7 - Technical Data Subject to alterations

Installation, Operation and Maintenance Manual

Desiccant Rotor Type Air Dehumidifiers DFRB series

5.3 Air duct connections.

ALL FRESH AIR

INNER MOUNTING OUTER MOUNTING

1a

3

DFRB

CONTROLLED

SITE

2

1a

3

1b

DFRB

2

CONTROLLED

SITE

1b

INNER MOUNTING

PARTIAL/TOTAL RECIRCULATION

OUTER MOUNTING

3

1b

1a

DFRB

CONTROLLED

SITE

2

1a

3

1b

DFRB

2

CONTROLLED

SITE

1a 1b

2

3

PROCESS/REACTIVATION AIR

DRY AIR

WET AIR (ALWAYS SLOPED DESCENDING)

Different operation options of the unit as 'All Fresh Air' or 'Partial/Total Recirculation' systems and the possibility of mounting the unit inside or outside of the site which humidity is being controlled, determine the use of one of the above duct mounting diagrams:

!

In the diagrams are indicated two regulation dampers located at wet and dry air ducts used to adjust each circuit air flow and consequently the dehumidifier capacity.

Additionally, in the Partial/Total Recirculation diagrams you can see a third damper located in one of the process air inlets that can be used to over pressure the controlled site, minimising air infiltration from adjacent rooms.

The static pressure available for ducts can be found in the unit data-sheet.

Also, the wet air duct must facilitate the draining of the condensing water produced when this air becomes cooler

F-2833 - 8 - Technical Data Subject to alterations

Installation, Operation and Maintenance Manual

Desiccant Rotor Type Air Dehumidifiers DFRB series

due to heat transmission. To achieve this the duct must slope downstream and the wet air outlet must be placed as far as possible from the process air intakes, to avoid losses of performance.

5.4 Electric mains connections.

Attention: The dehumidifier works with medium electrical power and voltage and its connection to the mains must be done by qualified personnel and according to the applicable local electrical regulations.

The unit must be connected to the electrical network of the installation through a short circuiting and ground leakage protection line, with wires section/sensitivity as corresponds to the dehumidifier power.

5.5 Control equipment locations and connections.

The location and mounting instruction for the control equipment are normally specified by the corresponding supplier.

In case of On-Off Control using a Hygrostat you can choose between the complete unit switch off or the reactivation air heater switch off, as described before.

6. Start up.

6.1 Unit start up.

Once the ductwork has been completed and the equipment is connected to the electrical mains, as well as to the control equipment, proceed in this way:

Attention: Before using the control panel, verify that all mechanical elements can work freely and the unit has no installation d e b r i s inside.

» Check that the air flow regulation dampers, if exist, are opened.

» Check that hygrostat set point - if exists - is at least 10-

15% lower than environmental humidity.

» Check that electric mains is protected with a fuse adequate to the unit power.

» Switch on the unit. Integral pilot must light. Fan starts operation and the ammeter reading reaches the upper limit due to the PTC heater consumption. PTC heater, like motors, have a consumption peak on starting 2 or

3 times the normal consumption.

» Wait a few minutes allowing the desiccant wheel to rotate several times until drying and regeneration processes are stabilized. Check that dry air temperature is lightly higher than the process air temperature, and the wet air temperature is higher than the dry air temperature. Adjust air flows to specific requirements of each application.

» Measure foreseen thermohygrometric parameters.

To reduce the unit capacity you have to strangle the wet air stream, this automatically reduces consumption indicated by the ammeter.

6.2 Stopping the unit.

The equipment can be stopped manually or automatically.

Manual mode:

» Just operate the control switch to its "OFF" position.

Automatic mode:

» The unit will be shut-off when jumper H2, shown in the wiring diagram, is open (this stops the unit totally). In case of opening jumper H1, the reactivation air heater is shut-off while the two motors keep on running.

F-2833 - 9 - Technical Data Subject to alterations

Installation, Operation and Maintenance Manual

Desiccant Rotor Type Air Dehumidifiers DFRB series

7. Maintenance.

7.1 Preventative maintenance.

The Following service schedule can be used.

OPERATION

Filters cleaning

Rotor driving check

Fan impellers inspection

Inner inspection (desiccant rotor surfaces) driving belt tension and absence of unexpected materials.

Electrical consumption and terminals tightening

General cleaning

FREQUENCY

Weekly

Weekly

Monthly

Every second month

Every second month

Yearly

7.2 Corrective maintenance.

The (desiccant rotor type) FISAIR dehumidifiers series

DFRB have a very simple design and their components should have very few problems.

The fans/motors are of standard manufacture and in case of electrical or mechanical damages any skilled serviceman may do the repairing. The PTC heaters can be easily changed or serviced when necessary

(normally after a very long working period) like any other conventional air heater element (resistor).

Also, minor components like filters, dampers, driving belt and electric box components could be replaced after their useful life and the user will have to define the necessity of storing these parts, depending on their availability through local dealers.

7.3 Desiccant wheel service.

This is the only dehumidifier component that needs any special attention.

Concerning the mechanical operation, the rotor should not require attention for a very long time. Its rotation speed is so low (20-24 r.p.h.) that the bearings and desiccant material housing cannot suffer any mechanical damage normally. However, it is very important to verify periodically the correct operation of the driving device because it directly affects the drying process.

Regarding the water vapour adsorption process, the main rotor component, activated silicagel, works by fixing the water vapour molecules in its micropores in the process air stream, leaving them when the heated reactivation air stream passes through the rotor channels.

This process is not affected by the normal environmental air conditions, nor by accidents of the installation that can be expected (for example, water direct action on the rotor does not affect the material, which is also fireproof).

Usual dust deposits on rotor surfaces can be removed by vacuum or blowing as well as by washing (please contact your dealer for written method when needed).

F-2833 - 10 - Technical Data Subject to alterations

Installation, Operation and Maintenance Manual

Desiccant Rotor Type Air Dehumidifiers DFRB series

8. Fault finding

Immediately switch off the dehumidifier if a fault occurs. Faults are only to be remedied by qualified personnel following the proper safety instructions.

Fault

The unit has stopped

The unit works, but it does not perform as expected.

Check the following points:

Measures

∑ Electric mains are powered and the pilot lights on. If not, reset the mains protections.

∑ If pilot lights on, check if the air has reached the hygrostat set point.

∑ If electric mains are powered, the hygrostat demands operation and the unit is not operating, please ask the dehumidifier supplier for technical assistance, since electrical components checking is to be to performed.

Check the following points:

∑ Wet air duct is not obstructed.

∑ Air filter is not too dirty

∑ Desiccant wheel rotates softly and continuously, and the rotor surfaces are not obstructed.

∑ The dry air outlet duct temperature is slightly higher than the process air duct, and the wet air duct temperature is higher than the dry air duct.

∑ Dry air and Wet air flow.

∑ If all this checking is successful, a measurement of the unit capacity must be performed as well as to review the single facility design parameters.

F-2833 - 11 - Technical Data Subject to alterations

Installation, Operation and Maintenance Manual

Desiccant Rotor Type Air Dehumidifiers DFRB series

9. Overall dimensions.

F-2833 - 12 - Technical Data Subject to alterations

Installation, Operation and Maintenance Manual

Desiccant Rotor Type Air Dehumidifiers DFRB series

10. General technical data sheet.

Model

FISAIR Dehumidifier Technical Data

Dry Air Flow m3/h

Nominal Capacity

Kg/h(*)

Electrical

Mains

DFRB-015-E

DFRB-020-E

DFRB-026-E

DFRB-036-E

125

150

200

300

0.6

0.8

1.2

1.6

230V/1N/50Hz

230V/1N/50Hz

230V/1N/50Hz

230V/1N/50Hz

DFRB-045-E

DFRB-060-E

DFRA-090-E

700 4.2 400V/3N/50Hz

* Nominal capacities corresponding to 20 ºC and 60 % RH processed air conditions.

350

500

1.9

2.7

230V/1N/50Hz

400V/3N/50Hz

F

Note: Technical data are subjected to change without prior notice.

Electrical Power kW

Reactivation

0.9

1.2

Total

1.3

1.8

2.1

3.4

4.5

1

1.4

1.6

2.2

2.5

3.6

4.8

F-2833 - 13 - Technical Data Subject to alterations

DFRB-060-E

TECHNICAL DATA - SHEET

TECHNICAL DATA

PROCESS/DRY

AIR FLOW

AVAILABLE PRESSURE

FOR DUCTING

WET AIR FLOW

AVAILABLE PRESSURE

FOR DUCTING

NOMINAL DRYING

CAPACITY(*)

TOTAL

POWER SUPPLY

MOTORS POWER

NOMINAL

POWER

REACTIVATION

MAX. BUILT-IN

POWER

ELECTRICAL SUPPLY

680/500

150

180

Pa

100 Pa

2.7

kg/h

3.6

0.19

3.41

6 kW kW kW kW

400V/III+N/50Hz

(g/kg).

CAPACITY DIAGRAM.(*)

SPECIFIC CAPACITY DIAGRAM.

FISAIR DEHUMIDIFIERS.

(ºC)

(g/kg).

PROCESS AIR MOISTURE CONTENT (Xe)

SETTLED PARAMETERS :

PROCESS/REACTIVATION AIR TEMPERATURE : 20 ºC

ΔT

REACTIVATION HEATER ACCORDING TO NOMINAL POWER

EQUAL PROCESS/REACTIVATION AIR MOISTURE CONTENT

(*) Nominal capacity: 20ºC and 60% R.H.

(*) At other operating conditions.pls.ask for the corresponding performances.

DFRB-060-E

SPECIFICATION :

Air dehumidifier by high performance desiccant silicagel rotary element, brand

FISAIR, model DFRB-060-E:

Self-supporting stainless steel sheet housing, easily serviceable.

Air intake with G4 filter mat, centrifugal simple ear air fan with direct motor drive.

Rotary desiccant element driven by gear motor, teeth pulley and transmission belt, with three front sections; for dry, heat recovery and wet air streams.

Partition and peripheral contact-type air seals.

Desiccant reactivation air heater PTC-type, with self limited operation temperature.

Process inlet, dry and wet outlets; with round connectors with rubber seals.

On-off switch with on-light.

Operation Ampere gage.

Performance, airflows and other data as per front page.

Hygrostat connections H1(PTC on/off) and H2 (Unit on/off).

OVERALL DIMENSIONS:

REMARK: - Approx. Weight: 66 kg.

- All dimensions in mm.

FISAIR S.L

Uranio 20, PI Aimayr

28330 San Martín de la Vega

Madrid - SPAIN

Ph.: +34 916921514 Fax: +34 916916456

Email: [email protected]

www.fisair.com

Distributor:

Installation, Operation and Maintenance Manual

Desiccant Rotor Type Air Dehumidifiers DFRB series

C.- Spare part list dehumidifier DFRB-060-E.

ITEM

DESCRIPTION PART #

1 Dessicant rotor

2 Silicone seal

3 Felt seal

4 Drive motor

5 Driving belt

6 Pulley

7 Process air fan

8 Air filter 287x592x50 mm

9 PTC Heater element

10 A-meter

200105

303020

303030

205214

211630

213312

201101

231100

207065

251005

QUANTITY

1

1

1

1

1,5 m

1,8 m

1

1

3

1

F-2833 Technical Data Subject to alterations

POLITEX A40

Code

Name

Description

SF350AR4

A40

SYNTHETIC FILTER MEDIA

Ventilation and industrial or civil conditioning plants. Pre-filtration and separation of particulates with medium low granulometry. dimensions composition regeneration thickness max. working temperature max. working R.H.

product density advisable cross speed initial pressure drop final pressure drop avarage gravimetric efficiency dust holding capacity classification ( EN 779:2002) flame resistance roll 2x20 m polyester fiber yes

14-16 mm

100 °C

100 %

350 g/m²

1,5 m/s

34 Pa

250 Pa

90,8 %

575 g/m²

G4

F1 - DIN.53438

rev. 00_05

Sede - Headquarter

Via S.Luca, 51

31038 Paese (TV) Italy

Tel +39.0422.4594

Fax +39.0422.459590 [email protected] www.generalfilter.com

Div. Commerciale - Trade Office

Via Caracciolo, 13

20010 Barbaiana di Lainate (MI) Italy

Tel +39.02.93550640

Fax +39.02.93255670 [email protected] www.generalfilter.com

General Filter Italia spa si riserva il diritto di cambiare i dati della presente scheda senza alcun preavviso.

DECLARACIÓN CE DE CONFORMIDAD

EC CONFORMITY DECLARATION

EG KONFORMITATSERLARüNG

DECLARATION CE DE CONFORMITÉ

Departamento de Dirección Técnica

Technical Direction Department

Abteilung von der technischen Leitung

Département de Direction Technique

FISAIR S.L.

C/ Uranio, 20 (Pol. Ind. Aimayr)

28330 San Martín de la Vega (Madrid) ESPAÑA

Tfº (34) 916921514

Fax (34) 916916456

DECLARAMOS Bajo nuestra única responsabilidad que el deshumidificador de aire:

WE DECLARE, under our own responsability that the air dehumidifier:

Unter unserer ausschließlicher Verantwortung ERKLÄREN WIR, daß der Luftentfeuchter:

NOUS DECLARONS, sous notre unique responsabilité que le deshydrateur d'air:

MARCA

/BRAND/MARKE/MARQUE:

MODELO

/MODEL/MODELL/MODELE:

FISAIR DFR B-060-E

Nº SERIE

/SERIAL NUMBER/

SERIENNUMMER/Nº DE SÉRIE:

1 113348

AÑO DE FABRICACIÓN

/YEAR OF MANUFACTURE

/BAUJAHR/ANNÉE DE FABRICATION:

20 11

Se adapta a las normas:

Meets the regulations:

Den Normen entspricht:

S'adapte aux normes:

EN 12100-1

EN 12100-2

EN 60204-1

EN 61000-6-1

EN 61000-6-3

EN 13857

Es conforme a los requisitos esenciales de las Directivas

:

Conforms to the essential requirements of the Directives:

Und den von den Richtlinien aufgestellten Grundvoraussetzungen Rechnung trägt:

Et est conforme aux conditions essentielles des Directives:

98/37/CEE

89/336/CEE

93/68/CEE

2006/42/CEE

2004/108/CEE

2006/95/CEE

Con exclusión de responsabilidades sobre las partes o componentes adicionados o montados por el cliente.

With no liability for the parts or components added or assembled by the customer.

Unter Ausschluß der Verantwortung über die vom Kunden bereitgestellten und/oder angebauten Teile.

Avec exclusion des responsabilités concernant les parties ou les composants ajoutés ou assemblés par le client.

Departamento Dirección Técnica

/Technical Direction Department/Département de Direction

Technique/Abteilung von der technischen Leitung:

Hugo J. López Álvarez

San Martin de la Vega,

Noviembre 2011

advertisement

Related manuals

Frequently Answers and Questions

What safety precautions should be considered during installation and maintenance?
Turn off power before doing maintenance or repairs, observe accident prevention regulations, use qualified personnel, and obtain written approval for extensions or additional equipment.
What is the general principle behind the desiccant wheel's operation?
The desiccant wheel rotates through two airstreams, absorbing moisture from the process air and releasing it into the regeneration air during heating.
What type of electrical connections are required for the fisair DFRB-060-E?
The unit requires electrical mains connections, including a power supply, neutral, and grounding.
What is the recommended location for installing the fisair DFRB-060-E?
The installation location should allow for sufficient service space around the unit and consider factors like ambient temperature, humidity, and air quality.
What is the purpose of the PTC heater in the fisair DFRB-060-E?
The PTC heater helps maintain the required regeneration temperature by generating heat, which aids in the moisture removal process.