X26
CONTROLS
DATA MANAGEMENT
PROCESS AUTOMATION
MODEL
Designed for:
•
•
•
•
Climate simulation
Component testing
Ceramic drying rooms
Plant growth chambers
Features:
•
•
•
•
•
50 stored programs
500 program steps
0.1% accuracy
Real time clock
iTool program editor
software
• OPC link to Labview
• Modbus digital
communications
Temperature & Humidity
Environmental Chamber Controller
Accurate programming of temperature and humidity is provided by
the advanced X26 controller. 50 customer named programs can be
stored with up to 100 steps per program and 500 steps in total.
Boost heat, boost cool and compressor On/Off outputs are included
as standard.
Two user programmable event outputs are available to activate
external devices - such as vibration test equipment.
A real time clock can be set to start a program at defined times of
the day and week.
Program profiles can be set up either through the controller front
panel from iTools or via a Windows setpoint program editor. This
allows the storage of an unlimited number of programs and easy
editing and transfer of programs between controllers. iTools
software will save and reproduce, the complete configuration of the
controller. iTools also provides trend plotting facilities for
monitoring the process.
The advance features include program holdback, to guarantee soak
time at temperature and humidity and six sets of PID parameters to
give accurate control under varying combinations of temperature
and humidity.
The humidity can be derived from wet and dry bulb inputs or taken
directly from a humidity probe.
Modbus digital communications is available for connection to
supervisory computers or Programmable Logic Controllers.
Humidify
Temperature probe
Humidity probe
Spray
Cooling/dehumidify
By-pass
Heaters
Compressor
on/off
Heating
abc
Rear Terminal Connections
Common DC
Program Run Input D1
Program Hold Input D2
4A
Dual triac/relay
outputs for
compressor &
by-pass control
OR 2nd retrans
Output
Boost Heat Output D3
4C
4D
Boost Cool Output D4
Heating
Output
Water Drain Valve D5
Program Event Output 1 D6
Cooling
Output
Program Event Output 2 D7
VH
Temperature Input
(Dry bulb)
4B
5A
5C
5D
5
6A
M
O
D
U
L
E
5B
V+
V-
6D
Temp or - 1A
Humidity
Retrans + 1B
1C
C
HA
O
M
HB
M
S
HC
M
O
D
U
L
E
1D
4
M
O
D
U
L
E
Wet bulb
Input
OR 6B
Humidity
Probe 6C
Supply
VI
M
O
D
U
L
E
L
N
Earth
M
O HD
D
U HE
L
E HF
1
Line
100 to 240Vac -15%, +10%
Neutral
Program Reset
D8
E1
E2
AA
AB
3A
Humidfy
Output
3B
Dehumidfy 3C
Output
6
M
O
D
U
L
E
AC
3
BC
3D
High
Temperature
Alarm
BA
BB
Humidity
Probe
Input
Control Block Diagram
Real
Time
Clock
D1
OR
run
D1
D2
hold
D1
D8
reset
D1
V+
Setpoint Temp. setpoint
Program Humidity
SP
Temp PV (Dry bulb)
D1
6D
Hi Event
Boost
Cool SP
Lo Event
Boost cool OP
10S delay
Hum OP
PID
Wet
bulb
input
Boost heat OP
10S delay
Humidity
probe input
D1
BB
D1
6C
Boost
Heat SP
Temp OP
PID
D1
VD1
BA
Event 1
Event 2
Event outputs
Wait
Alarms
Humidity
Function
Block %RH
0
a
a>b
b
0
a
a>b
b
a
AND
b
Humidity/Temp retrans
Humidity/Temp retrans
1°C/33°F
D1
D6
D1
D7
D1
D3
D1
D4
Heating OP
D1
5A
Cooling OP
D1
5C
Humidify OP 3A
D1
Dehum OP
D1
3C
Min-On Compressor
D1
4A
Timer On/Off
D1
4B
Cooling by-pass
D1
1A
a
A>b
b
Drain valve
D1
D5
D1
4A
iTools Software
iTools is an advanced sofware tool for configuring the X26 and setting up the setpoint programs. The iTools configurator will edit,
store and ‘clone’ complete controller configurations. iTools employs an OPC to Modbus server to communicate with the X26. The
OPC server can be used as a link to other client software packages such as Labview and Wonderware.
Setpoint Program Editor
The setpoint program editor is a simple
way of setting up the humidity and
temperature profiles and the
programmable event outputs. The
editor will store, retrieve and download
program profiles. It will work ‘on-line’,
when program values are edited ‘live’ in
a connected controller, or ‘off-line,
when programs are edited before being
downloaded to a selected controller.
The number of stored programs is
limited only by the capacity of the PC
hard disk.
OPC scope is an iTools utility providing
trend plots of the process variables.
The time axis can be adjusted between
1 minute and 1 month. Data can also
be logged to hard disk in CSV format.
This can then be recalled and analysed
in an Excel spreadsheet.
Technical Specification
Temperature inputs
Input types
Accuracy
Sample rate
Cold Junction
Compensation
3-wire Pt100 input
(Wet and Dry bulbs)
J, K, T, L, N thermocouples. 3-wire Pt100
±0.1%
9Hz
>30 to 1 rejection of ambient temp. change
Bulb current: 0.3mA. Up to 22ohm in each
lead without error
Humidity probe input
Probe trans supply
24Vdc, 20mA max
Input signal range
0-1Vdc or 0-10Vdc (equivalent to 0-100%Rh)
Accuracy
±0.1%
Run, hold and reset digital inputs
Open circuit voltage
4Vdc nominal
Closed circuit current 0.8mA nominal
Heating, cooling, humidifying and dehumidifying outputs
Relay rating
2A, 264Vac resistive
Logic output
8Vdc, 12mA
Triac outputs
1A, 264Vac max
DC outputs
0-20mA or 0-10Vdc
Temperature and humidity retransmission outputs
Range
0-20mA or 0-10VDC (isolated)
Resolution
12 bits
Control Functions
Control mode
Tuning
Auto manual control
Alarms
Number of alarms
PID
Automatic one-shot tuning
Bumpless transfer between auto and
manual
One high temperature alarm
Setpoint programming
Number of programs 50
Number of setpoints
500
Event outputs
2
Program holdbacks
High and low holdback settable per
segment
Communications
Modbus
General
Display range
Supply
Operating ambient
Storage temperature
Panel sealing
Dimensions (mm)
EMC standards
Safety standards
RS232, RS422 or RS485 (2 or 4-wire)
Five digits with one decimal place
100 to 240Vac -15%. +10%
0 to 55°C and 5 to 95% RH noncondensing
-10 to +70°C
IP65
96W x 96H x 150D
Meets generic emissions standard
EN50081-1 and immunity standard
EN50082-2 for Heavy Industrial,
Light Industrial, Residential and
Commercial Environments
Meets EN61010, installation category II,
pollution degree 2
Ordering codes
Hardware coding
Controller
Type
Supply
Voltage
X26
VH
Configuration coding
Module 1
Retrans
85 to 264Vac
Module 1
Retransmission output
XX Not fitted
First character
TTemp. retrans.
H- Humidity retrans.
Second character
-Y
0-20mA
-A 4-20mA
-W 0-5Vdc
-G 1-5Vdc
-V
0-10Vdc
Module 4
Module 5
Heat + cool
Module 6
Module 3
Module 5
Humidity + dehumidify
outputs
XX Not fitted
TP Dual logic outputs
RR Dual relay outputs
TT Dual triac outputs
DO Dual 4-20mA OP’s
Heating + cooling
outputs
XX Not fitted
TP Dual logic outputs
RR Dual relay outputs
TT Dual triac outputs
DO Dual 4-20mA OP’s
Module 4
Module 6
XX Not fitted
Compressor on/off &
by-pass outputs
TT Dual triac
RR Dual relay output
2nd retransmission OP
First character
TTemp. retrans.
H- Humidity retrans.
Second character
-Y
0-20mA
-A 4-20mA
-W 0-5Vdc
-G 1-5Vdc
-V
0-10Vdc
Wet bulb or Trans
supply
XX Not fitted
PV Wet bulb input
MS 24Vdc Humidity
transmitter supply
Supply Voltage
VH
Module 3
Hum + Dehum
Comms
Manual
Temp (dry
bulb) Input
Comms
XX Not fitted
Modbus
A2 RS232
F2 4-wire,
RS485/RS422
Y2 2-wire RS485
Manual
XXX
ENG
FRA
GER
SPA
Not fitted
English
French
German
Spanish
Wet bulb
Input
Humidity
Input
Units
Dry and Wet Bulb Inputs
XX
Not used
°C
Range
°F
Resistance thermometer
Z
Pt100(RTD)
-200 to 850
-325 to 1562
Thermocouples
J
Type J
-210 to 1200
-340 to 2192
K
Type K
-200 to 1372
-325 to 2500
T
Type T
-200 to 400
-325 to 750
L
Type L
-200 to 900
-325 to 1650
N
Type N
-200 to 1300
-325 to 2370
Process inputs (linear)
M
-100 to +100mV Scaleable -1999 to 9999
Y
0 to 20mA
Scaleable -1999 to 9999
A
4 to 20mA
Scaleable -1999 to 9999
W
0 to 5Vdc
Scaleable -1999 to 9999
G
1 to 5Vdc
Scaleable -1999 to 9999
V
0 to 10Vdc
Scaleable -1999 to 9999
Units
C
F
°C
°F
Humidity Input
X
N
V
Y
A
W
Not used
0-1Vdc
0-10Vdc
0-20mA
4-20mA
0-5Vdc
Dimensional details
All dimensions in mm
150
96
Panel cut-out
-0.0
92 x 92
+0.8
96
EUROTHERM LIMITED
http://www.eurotherm.co.uk
UK SALES OFFICE
Eurotherm Ltd
Faraday Close Durrington Worthing BN13 3PL United Kingdom
Sales and support: Tel. +44 (0)1903 695888 Fax +44 (0)1903 695666
Sales and support in over 30 countries worldwide
Enquiries/orders to:
Tel. +44 (0)1903 268500 Fax +44 (0)1903 265982
email: [email protected]
U.S. OFFICE
Eurotherm Inc.
741 Miller Drive SE,
Suite F, Leesburg.
VA 20175-8993
Telephone Leesburg (+1 703) 443 0000
Fax (+1 703) 669 1300
http://www.eurotherm.com
© Copyright Eurotherm Limited 2001
All rights strictly reserved. No part of this document may be stored in a retrieval system, or any form or by any means without prior written permission from Eurotherm
Limited. Every effort has been taken to ensure the accuracy of this specification. However in order to maintain our technological lead we are continuously improving our
products which could, without notice, result in amendments or omissions to this specification. We cannot accept responsibility for damage, injury loss or expenses resulting
therefrom.
Part No. HA027707 Issue 2
Printed in England 04.02
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertisement