Carrier | HRVCCLHA | Product Data - HVACpartners

HRVCCLHA
Heat Recovery Ventilator
ERVCCLHA
Energy Recovery Ventilator
Product Data
The Heat Recovery Ventilation (HRV) and Energy Recovery
Ventilator (ERV) systems offered by Carrier are the finest on the
market today. These units provide efficient and cost effective heat
recovery during the heating season when needed most.
As temperatures drop below 23_F (--5_C), indoor air is recirculated
periodically through the heat exchanger core to prevent frost from
forming. Competitors’ methods of supplementary electric defrost
waste energy. Unlike rotary wheel heat exchangers which mix air
streams, these cross--flow or counterflow heat exchangers ensure
that there is no mixing of the stale air stream with the fresh outdoor
air stream.
A filter installed on the incoming outdoor air stream removes large
airborne particles from the intake air stream before they enter the
heat exchanger and reduces the maintenance required. The units’
acoustically engineered design make Carrier ventilators the quietest
on the market and ensures that comfort is felt, not heard.
Unlatching two (2) suitcase style latches allows easy removal of the
filters and core for cleaning.
NOTE: The HRV should not be installed in an attic or
unconditioned space unless provisions are made for drain line
freezing and condensation.
STANDARD FEATURES
HRV
S Energy saving defrost cycle
S Cross--flow, counterflow heat exchangers
S One filter on incoming air; one filter on outgoing air to
protect core
S Acoustical design
S No--tools maintenance
S Polypropylene heat exchanger core
A10299
ERV
Drainless design
Integrated airflow balancing points
Integrated furnace interlock
High pressure blowers
Onboard control for continuous high/low ventilator operation
Energy saving defrost cycle
Cross--flow, counterflow heat exchangers
One filter on incoming air; one filter on outgoing air to
protect core
S No--tools maintenance
S Enthalpic heat exchanger core
S
S
S
S
S
S
S
S
MODEL NUMBER NOMENCLATURE
1
E
2
R
3
V
4
C
5
C
6
L
7
H
8
A
9
1
10
1
11
5
Product Type
ERV -- Energy Recovery Ventilator
HRV -- Heat Recovery Ventilator
12
0
Maximum Capacity
150 -- 150 CFM
200 -- 200 CFM
250 -- 250 CFM
Brand
CC -- Carrier
Electrical Supply
1 -- 115 Volts
Style
LHA -- Large Horizontal
ERV / HRV
Energy Star (Canada)
S
S
S
These products earned the
ENERGY STAR® by meeting strict
energy efficiency guidelines set by
Natural Resources Canada and
the US EPA. They meet ENERGY
STAR requirements only when
used in Canada.
HRVCCLHA1150
ERVCCLHA1150
ERVCCLHA1250
Climate Map for Energy and Heat Recovery Ventilators
Edmonton
Vancouver
Calgary
Regina
Helena
Salem
Winnipeg
Timmins
Bismark
Montreal
Green Bay
Boise
Minneapolis
Salt Lake
City
Denver
Springfield
Topeka
Oklahoma City
Boston
Hartford
Madison
Des Moines
Sacramento
Syracuse
Ottawa
Milwaukee
Chicago
Detroit
Indianapolis
Harrisburg
Washington D.C.
Raleigh
Nashville
Atlanta
Columbia
Honolulu
Austin
Baton Rouge
Orlando
HRV Recommended
ERV Recommended w/HRV or ERV Wall Control
ERV Recommended
A00099
2
DIMENSIONS
A10318
ERV / HRV
Fig. 1 -- ERVCCLHA1150 / ERVCCLHA1200 Dimensions
A10319
Fig. 2 -- HRVCCLHA1150 / HRVCCLHA1250 Dimensions
PHYSICAL DATA
MODEL
Port Locations
Core Type
Weight — lb (kg)
Shipping Weight — lb (kg)
Shipping Dimensions in. (mm)
Height
Width
Length
ERVCCLHA1150
Sides
Enthalpic transfer
media, Cross Flow
74 (33.6)
78 (35.4)
ERVCCLHA1200
Sides
Enthalpic transfer
media, Cross Flow
76 (34.5)
80 (36.3)
HRVCCLHA1150
Side
Polypropylene
Cross Flow
65 (29.5)
75 (34)
HRVCCLHA1250
Side
Polypropylene
Cross Flow
73 (33.2)
83 (37.6)
19.75 (502)
20.5 (521)
40.5 (1029)
19.75 (502)
20.5 (521)
40.5 (1029)
23-1/16
36-1/16
17-13/16
22-15/16
35-1/16
22-15/16
HRVCCLHA1150
120
150
1.4
HRVCCLHA1250
120
218
1.9
ELECTRICAL DATA
MODEL
Voltage
Max Power — watts
Max Amps
ERVCCLHA1150
120
150
1.3
ERVCCLHA1200
120
240
2.1
3
PERFORMANCE DATA
HVI Rated Energy Performance
MODEL
ERVCCLHA1150
Heat
Cool
ERVCCLHA1200
Heat
ERV / HRV
Cool
HRVCCLHA1150
Heat
Cool
HRVCCLHA1250
_C
_F
L/S
CFM
0
0
0
--- 25
35
0
0
0
--- 25
35
0
0
0
--- 25
35
0
0
0
--- 25
35
32
32
32
--- 13
95
32
32
32
--- 13
95
32
32
32
--- 13
95
32
32
32
--- 13
95
30
46
66
22
31
39
54
79
31
39
31
56
64
97
141
47
65
80
114
167
65
82
66
119
66
77
137
92
63
84
113
169
116
81
85
124
61
60
57
49
APPARENT
SENSIBLE
EFFECTIVENESS
75
71
69
80
60
58
56
41
72
69
66
86
0.60
0.53
0.45
0.47
69
60
81
70
0
0
34
72
114
62
80
0.08
31
56
86
34
66
119
182
72
85
124
197
114
69
60
53
62
81
70
62
80
0
0
0
0.08
SUPPLY
TEMP
MODE
Heat
Cool
NET
AIR FLOW
POWER
SENSIBLE
CONSUMED RECOVERY
(WATTS)
EFFICIENCY
LATENT
RECOVERY
MOISTURE
TRANSFER
0.62
0.58
0.52
0.56
TOTAL
RECOVERY
EFFICIENCY
56
52
Ventilation Performance
MODEL
ERVCCLHA1150
ERVCCLHA1200
HRVCCLHA1150
HRVCCLHA1250
EXT. STATIC
PRESSURE
PA
25
75
100
150
200
25
75
100
150
200
25
75
100
150
200
25
75
100
150
175
IN W.G.
0.1
0.3
0.4
0.6
0.8
0.1
0.3
0.4
0.6
0.8
0.1
0.3
0.4
0.6
0.8
0.1
0.3
0.4
0.6
0.7
GROSS AIR FLOW
NET SUPPLY
AIR FLOW
L/S
84
74
70
58
41
105
93
86
70
50
83
75
71
59
43
110
98
89
71
64
SUPPLY
CFM
179
156
148
124
87
222
198
183
148
107
175
159
150
126
91
234
208
189
151
136
NOTE: For additional data points, refer to HVI Directory at www.hvi.org
4
L/S
85
75
71
59
42
106
94
88
71
51
83
75
71
60
43
112
100
91
72
65
CFM
181
158
151
125
88
225
200
186
150
108
176
159
151
127
91
237
211
192
153
138
L/S
92
85
77
54
20
106
100
93
75
29
83
75
69
49
21
112
99
91
70
44
EXHAUST
CFM
196
181
163
114
43
225
212
198
158
61
175
158
146
103
45
237
210
193
149
94
CONTROL FEATURES
CONTROL
DESCRIPTION
OneTouch
Basic
Standard
FAN SPEED
CONTROL
Yes
Yes
Yes
DEHUMIDISTAT
CONTROL
No
No
Yes
CONTINUOUS
MODE
Yes
Yes
Yes
INTERMITTENT
MODE
Yes
No
Yes
Basic Control:
Allows the user to manually set fan speed to low or high as required to maximize comfort.
Standard Control:
Offers automatic dehumidistat control and the option to select continuous or intermittent fan operation. Setting the wall control to low will
activate the continuous mode.
Allows control of ventilator with the touch of a button. This control will operate as a main wall control. The OneTouch will operate the unit
in Intermittent Mode (20 minutes per hour), continuous low speed, continuous high speed, and off.
AUTOMATIC DEFROST CYCLE FEATURES
All models offer a non--electric defrost cycle feature which prevents frost and ice buildup within the heat recovery core. When the outside air
temperature falls below 23_F (--5_C) it is electronically sensed and the dampers close the outside air ports. This allows warm indoor air to
recirculate within the heat recovery core. The frequency of this cycle increases as the outside air temperature decreases.
MODEL
*
{
25_F TO 55_F
(---5_C TO ---15_C)
4_F TO ---17_F
(---15.6_C TO ---27.3_C)
BELOW ---18_F
(---27.8_C)
DEFROST*
EXCHANGE{
DEFROST*
EXCHANGE{
DEFROST*
EXCHANGE{
ERVCCLHA
6 Minutes
60 Minutes
6 Minutes
32 Minutes
6 Minutes
20 Minutes
HRVCCLHA
6 Minutes
60 Minutes
6 Minutes
32 Minutes
6 Minutes
20 Minutes
All defrost times are in the standard mode (as shipped)
Time between defrost when within specified temperature range
5
ERV / HRV
OneTouch Control:
METHOD TO SIZE ERVs and HRVs
Ventilator Sizing
Tables 1 and 2 should be used to determine the required airflow for a home. These guidelines are taken from ASHRAE 62.2--2007.
Table 2 – Ventilation Air Requirements, L/s
Table 1 – Ventilation Air Requirements, cfm
FLOOR
AREA (ft2)
ERV / HRV
<1500
1501--- 3000
3001--- 4500
4501--- 6000
6001--- 7500
>7500
0---1
30
45
60
75
90
105
2---3
45
60
75
90
105
120
BEDROOMS
4---5
6---7
60
75
75
90
90
105
105
120
120
135
135
150
FLOOR
AREA (m2)
>7
90
105
120
135
150
165
<139
139.1--- 279
279.1--- 418
418.1--- 557
557.1--- 697
>697
0---1
14
21
28
35
42
50
2---3
21
28
35
42
50
57
BEDROOMS
4---5
28
35
42
50
57
64
6---7
35
42
50
57
64
71
>7
42
50
57
64
71
78
HEATING AND COOLING LOAD CHARTS
Although the ventilators process the outside air before it enters the home, additional heating and cooling loads need to be considered.
HEATING LOAD BTUH
Outside
Temp °F
–25
–20
–15
–10
–5
0
5
10
15
20
25
30
35
40
ERV1150
5186
4919
5075
4783
4491
4200
4234
3918
3958
3611
3264
2916
2569
2222
Heating Load (Btuh) @
Inside Design Temp 72°F
ERV1200
HRV1150
HRV1250
8143
6636
10603
7723
6294
10057
7967
5952
9510
7509
5610
8964
7051
5268
8417
6594
4925
7871
6647
4583
7324
6151
4241
6777
6214
3899
6231
5669
3557
5684
5124
3215
5138
4579
2873
4591
4034
2531
4045
3489
2189
3498
The heating load chart shows the heating loads in Btuh for a range
of winter design temperatures for each model of ventilator.
EXAMPLE: The heating design temperature for Little Rock, AR is
20_F. The additional heating load of the ERVCCLHA1200 at
20_F is 559 Btuh. This additional load should be taken into
consideration when sizing the heating equipment.
COOLING LOAD BTUH
Cooling Load (Btuh) @ Inside Design Temp
72°F and 50% Relative Humidity
Outside
Enthalpy
Btu/lb
ERV1150
ERV1200
HRV1150
HRV1250
30
31
32
33
34
35
36
37
38
39
40
41
42
380
618
855
1093
1331
1568
1806
2043
2281
2519
2756
2994
3231
640
1040
1441
1841
2241
2641
3041
3441
3842
4242
4642
5042
5442
670
1090
1509
1928
2347
2766
3185
3604
4023
4442
4861
5280
5699
1071
1741
2411
3080
3750
4419
5089
5759
6428
7098
7767
8437
9107
The cooling load chart shows loads in Btuh as well. To use the
cooling load chart, first find the design enthalpy from a
psychrometric chart using the design dry bulb and wet bulb
temperatures. The cooling load can then be found for a range of
enthalpies for each ventilator.
EXAMPLE: The design dry bulb temperature for Miami is 90_F
and the average wet bulb at that temperature is 77_F. Using the
psychrometric chart, the enthalpy is about 40.5 Btu per pound
(Btu/lb) of dry air, which would round up to 41 Btu/lb dry air. In
the left column, at 41 Btu/lb dry air, the ERVCCLHA1200 has an
additional cooling load of 5042 Btuh, while the HRV1150CFM
unit has an additional cooling load of 8437 Btuh.
6
Dry Bulb
Temperature F
Wet Bulb,
Dewpoint or
Saturation
Temperature F
8
7
9
12
30
20%
40%
60%
1
35
+0.
Btu
40
Btu
40
+0.2
Below 32˚F, properties and enthalpy deviation lines are for ice.
25
30
80%
18
17
16
15
14
13
12
11
10
20
25
35
cu ft
12.5
+
+0
.4
tu
B
0.3
20
19
45
45
Btu
23
22
21
50
50
u
t
5B
.
+0
26
25
24
55
55
60
60
38
65
70
46
75
%
80
40
80
%
50
%
60
%
30
10%
85
20%
85
95
95
ERV / HRV
90
90
Enthalpy at saturation, Btu per pound of dry air
U
49
PSYCHOMETRIC CHART
28
27
cu ft
13.0
32
31
30
29
34
35
65
2
-.0
33
36
37
4
-.0
Bt
u
39
Bt
u
42
u
40
41
70
Bt
6
-.0
44
45
9
-.0
43
47
75
8B
tu
BT
-.01
48
cu ft
0%
Re
70
ity
m
Hu
ive
lat
%
80
%
id
13.5
100
100
105
105
0
10
20
30
40
50
60
70
80
90
100
110
120
130
140
150
160
170
180
Grains of moisture
per pound of dry air
air -0.3
Btu
of dry
r pound
iation Btu pe
Enthalpy dev
BTU
-.02
cu ft
14.0
110
0
.001
.002
.003
.004
.005
.006
.007
.008
.009
.010
.011
.012
.013
.014
.015
.016
.017
.018
.019
.020
.021
.022
.023
.024
.025
Sensible
heat
factor
.95
.85
.90
.80
.75
.70
.65
.60
.55
.50
.45
.40
.35
Pounds of moisture
per pound of dry air
f dry
air
nd o
pou
per
cu ft
A989394
14.5
7
ERV / HRV
Ventilator installed with forced air system
A99297
Ventilator installed with independent air distribution
A99298
8
ACCESSORIES
VENTILATOR ACCESSORY NUMBER NOMENCLATURE
2
V
3
B
4
C
5
N
6
0
7
1
8
0
Product
9
1
10
C
11
B
12
S
Control Description
CAU -- Carrier Automatic Control
CBS -- Carrier Basic Control
CLC -- Carrier Latent Control
CLT -- Carrier OneTouch Control
CST -- Carrier Standard Control
KV -- Ventilator Accessory Kit
Series
A -- Original Series
B -- Second Series
Accessory Description
HOD -- Intake Hood
KIT -- Airflow Measuring Kit
6FM -- Flow Collar 6--in.
7FM -- Flow Collar 7--in.
8FM -- Flow Collar 8--in.
Type
AC01 -- Accessory
CN01 -- Control
TM01 -- Timer
AC01 -- Accessory
Timer Description
120C -- 20 Minute Timer Kit
160M -- 60 Minute Timer Kit
Package Quantity
01 -- Single Pack
KIT NUMBER
DESCRIPTION
WHERE USED
KVBCN0101CAU
Automatic Wall Control
Used with HRVs
KVBCN0101CBS
Basic Wall Control
Used with HRVs
KVBCN0101CLC
Latent Wall Control
Used with ERVs
KVBCN0101CLT
Carrier OneTouch Control
Used with ERVs and HRVs as a main wall control
KVBCN0101CST
Standard HRV Control
Used with HRVs
KVAAC0101HOD
Exterior Intake and Exhaust Hood
Used with ERVs and HRVs, 2 Required
KVBAC0101KIT
Airflow Measuring Kit
Start up Balancing Kit, includes (2) 6 in. Flow Meter Collars & Magnehelic Gauge
KVATM010120C
20 Minute Push Button Timer
Used with ERVs and HRVs when 20 minute manual operation is required
KVATM010160M
60 Minute Timer
Used with ERVs and HRVs, time is adjustable between 10 and 60 minutes
KVAAC01016FM
6 in. Flow Meter Collar
Used with ERVs and HRVs, at start up, when 6 in. duct work is connected to HRV
KVAAC01017FM
7 in. Flow Meter Collar
Used with ERVs and HRVs, at start up, when 7 in. duct work is connected to HRV
KVAAC01018FM
8 in. Flow Meter Collar
Used with ERVs and HRVs, at start up, when 8 in. duct work is connected to HRV
KVAFK0201150
Internal Filter
Used with HRVCCLHA1150, HRVCCLHA1250 Unit 15 1/2 in. x 7 in. x 5/8 in.
9
ERV / HRV
1
K
ERV / HRV
Copyright 2011 Carrier Corp. S 7310 W. Morris St. S Indianapolis, IN 46231
Printed in U.S.A.
Edition Date: 07/11
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
10
Catalog No: ERVHRVLHA ---02PD
Replaces: ERVHRVLHA--- 01PD