SIM900 Safety Test Report

SIM900 Safety Test Report
Test Report issued under the responsibility of:
Page 1 of 37
TEST REPORT
IEC 60950-1:2005 (2nd Edition) and/or EN 60950-1:2006
Information technology equipment – Safety –
Part 1: General requirements
Report Reference No. ....................:
GLESO09120440901
Date of issue ....................................:
January 21, 2010
Total number of pages .....................:
37 pages
CB Testing Laboratory...................:
SGS-CSTC Standards Technical Services Co., Ltd. - E&E Lab
Guangzhou
Address ............................................:
198 Kezhu Road, Scientech Park, Guangzhou Economic &
Technology Development District, Guangzhou, Guangdong, China
510663
Applicant’s name............................:
Shanghai Simcom Ltd.
Address ............................................:
SIM Technology Building, No.633, Jinzhong Road, Changning
District, Shanghai P.R. China (Postalcode 200335)
Test specification:
Standard...........................................:
IEC 60950-1:2005 (2nd Edition) and/or
EN 60950-1:2006 + A11:2009
Test procedure .................................:
SGS-CSTC
Non-standard test method…………..:
N/A
Test Report Form No. ....................:
IECEN60950_1C (Modified by SGS-CSTC, dated 2009-04, added
content of A11:2009 for EN 60950-1:2006)
Test Report Form(s) Originator ........:
SGS Fimko Ltd.
Master TRF ......................................:
Dated 2007-06
Copyright © 2007 IEC System for Conformity Testing and Certification of Electrical Equipment
(IECEE), Geneva, Switzerland. All rights reserved.
This publication may be reproduced in whole or in part for non-commercial purposes as long as the IECEE is acknowledged as
copyright owner and source of the material. IECEE takes no responsibility for and will not assume liability for damages resulting from
the reader's interpretation of the reproduced material due to its placement and context.
This report is not valid as a CB Test Report unless signed by an approved CB Testing Laboratory and appended
to a CB Test Certificate issued by an NCB in accordance with IECEE 02.
Test item description .....................:
GSM/GPRS Module
Trade Mark ....................................... :
Manufacturer .................................... :
Same as applicant
Model/Type reference ...................... :
SIM900
Ratings ............................................. :
3,4-4,5 VDC
Page 3 of 37
Report No.: GLESO09120440901
Summary of testing:
Tests performed (name of test and test clause):
Testing location:
These tests fulfil the requirements of standard
ISO/IEC 17025.
SGS-CSTC Standards Technical Services Co., Ltd.
- E&E Lab Guangzhou
When determining the test conclusion, the
Measurement Uncertainty of test has been
considered.
198 Kezhu Road, Scientech Park, Guangzhou
Economic & Technology Development District,
Guangzhou, Guangdong, China 510663
This test report includes:
Annex 1: 2 pages of Photos.
Summary of compliance with National Differences:
-Copy of marking plate
TRF No. IECEN60950_1C
Page 4 of 37
Report No.: GLESO09120440901
Test item particulars .................................................. :
Equipment mobility .................................................... : [ ] movable [ ] hand-held
[ ] transportable
[ ] stationary [ x ] for building-in [ ] direct plug-in
Connection to the mains ........................................... : [ ] pluggable equipment [ ] type A [ ] type B
[ ] permanent connection
[ ] detachable power supply cord
[ ] non-detachable power supply cord
[ x ] not directly connected to the mains
Operating condition ................................................... : [ x ] continuous
[ ] rated operating / resting time:
Access location ........................................................ : [ ] operator accessible
[ ] restricted access location
Over voltage category (OVC) ................................... : [ ] OVC I
[ x ] other:
[ ] OVC II
[ ] OVC III
[ ] OVC IV
Mains supply tolerance (%) or absolute mains supply -values ....................................................................... :
Tested for IT power systems .................................... : [ ] Yes
[ x ] No
IT testing, phase-phase voltage (V) ......................... : -Class of equipment ................................................... : [ ] Class I [ ] Class II
[ ] Not classified
[ x ] Class III
Considered current rating (A) ................................... : -Pollution degree (PD) ............................................... : [ ] PD 1
[ x ] PD 2
[ ] PD 3
IP protection class .................................................... : IPX0
Altitude during operation (m) .................................... : < 2000 m
Altitude of test laboratory (m) ................................... : < 2000 m
Mass of equipment (kg) ............................................ : 0,011 Kg
Possible test case verdicts:
- test case does not apply to the test object .................: N (N/A)
- test object does meet the requirement.......................: P (Pass)
- test object does not meet the requirement.................: F (Fail)
Testing ..........................................................................:
Date of receipt of test item ............................................: December 29, 2009
Date(s) of performance of tests ....................................: December 29, 2009 – January 07, 2010
TRF No. IECEN60950_1C
Page 5 of 37
Report No.: GLESO09120440901
General remarks:
The test results presented in this report relate only to the object tested.
This report shall not be reproduced, except in full, without the written approval of the Issuing testing laboratory.
"(See Enclosure #)" refers to additional information appended to the report.
"(See appended table)" refers to a table appended to the report.
Note: This TRF includes EN Group Differences together with National Differences and Special National
Conditions, if any. All Differences are located in the Appendix to the main body of this TRF.
Throughout this report a comma is used as the decimal separator.
This document is issued by the Company subject to its General Conditions of Service, available on request
or accessible at www.sgs.com/terms_and_conditions.htm and, for electronic format documents, subject to
Terms and Conditions for Electronic Documents at www.sgs.com/terms_e-document.htm.
Attention is drawn to the limitation of liability, indemnification and jurisdiction issues defined therein. Any
holder of this document is advised that information contained hereon reflects the Company’s findings at the
time of its intervention only and within the limits of Client’s instructions, if any. The Company’s sole
responsibility is to its Client and this document does not exonerate parties to a transaction from exercising
all their rights and obligations under the transaction documents. This document cannot be produced except
in full, without prior written approval of the Company. Any unauthorized alteration, forgery or falsification of
the content or appearance of this document is unlawful and offenders may be prosecuted to the fullest
extent of the law.
General product information:
The SIM900 was GSM/GPRS Module for M2M applications.
This equipment is a built-in Module, When installing it into the end system, the requirement in EN 60950-1:
2006 + A11 should be complied.
TRF No. IECEN60950_1C
Page 6 of 37
Report No.: GLESO09120440901
IEC/EN 60950-1
Clause
Requirement + Test
1
GENERAL
P
1.5
Components
P
1.5.1
General
P
Comply with IEC 60950-1 or relevant component
standard
Result – Remark
(see appended table 1.5.1)
Verdict
P
1.5.2
Evaluation and testing of components
P
1.5.3
Thermal controls
N
1.5.4
Transformers
N
1.5.5
Interconnecting cables
N
1.5.6
Capacitors bridging insulation
N
1.5.7
Resistors bridging insulation
N
1.5.7.1
Resistors bridging functional, basic or
supplementary insulation
N
1.5.7.2
Resistors bridging double or reinforced insulation
between a.c. mains and other circuits
N
1.5.7.3
Resistors bridging double or reinforced insulation
between a.c. mains and antenna or coaxial cable
N
1.5.8
Components in equipment for IT power systems
N
1.5.9
Surge suppressors
N
1.5.9.1
General
N
1.5.9.2
Protection of VDRs
N
1.5.9.3
Bridging of functional insulation by a VDR
N
1.5.9.4
Bridging of basic insulation by a VDR
N
1.5.9.5
Bridging of supplementary, double or reinforced
insulation by a VDR
N
1.6
Power interface
P
1.6.1
AC power distribution systems
N
1.6.2
Input current
1.6.3
Voltage limit of hand-held equipment
N
1.6.4
Neutral conductor
N
1.7
Marking and instructions
P
1.7.1
Power rating
see appended table 1.6.2
Built-in equipment which shall
P
N
be evaluated in end system.
Rated voltage(s) or voltage range(s) (V) .............. :
N
Symbol for nature of supply, for d.c. only .............. :
N
Rated frequency or rated frequency range (Hz) ... :
N
Rated current (mA or A) ........................................ :
N
TRF No. IECEN60950_1C
Page 7 of 37
Report No.: GLESO09120440901
IEC/EN 60950-1
Clause
1.7.2
Requirement + Test
Result – Remark
Verdict
Manufacturer’s name or trade-mark or identification See marking plate
mark ...................................................................... :
P
Model identification or type reference ................... : See marking plate
P
Symbol for Class II equipment only ...................... :
N
Other markings and symbols ................................ : See marking plate
P
Safety instructions and marking
P
Built-in equipment which shall
be evaluated in end system.
1.7.2.1
General
1.7.2.2
Disconnect devices
1.7.2.3
Overcurrent protective device
N
1.7.2.4
IT power distribution systems
N
1.7.2.5
Operator access with a tool
N
1.7.2.6
Ozone
N
1.7.3
Short duty cycles
N
1.7.4
Supply voltage adjustment ................................... :
N
Methods and means of adjustment; reference to
installation instructions ......................................... :
N
1.7.5
Power outlets on the equipment .......................... :
N
1.7.6
Fuse identification (marking, special fusing
characteristics, cross-reference) ......................... :
N
1.7.7
Wiring terminals
N
1.7.7.1
Protective earthing and bonding terminals .......... :
N
1.7.7.2
Terminals for a.c. mains supply conductors
N
1.7.7.3
Terminals for d.c. mains supply conductors
N
1.7.8
Controls and indicators
N
1.7.8.1
Identification, location and marking ..................... :
N
1.7.8.2
Colours ................................................................ :
N
1.7.8.3
Symbols according to IEC 60417 ........................ :
N
1.7.8.4
Markings using figures ....................................... :
N
1.7.9
Isolation of multiple power sources .................... :
N
1.7.10
Thermostats and other regulating devices ......... :
N
1.7.11
Durability
N
1.7.12
Removable parts
N
1.7.13
Replaceable batteries ......................................... :
N
Language(s) ........................................................ :
⎯
1.7.14
Equipment for restricted access locations ........... :
N
2
PROTECTION FROM HAZARDS
P
2.1
Protection from electric shock and energy hazards
N
TRF No. IECEN60950_1C
P
.
N
Page 8 of 37
Report No.: GLESO09120440901
IEC/EN 60950-1
Clause
Requirement + Test
Result – Remark
2.1.1
Protection in operator access areas
Built-in equipment which shall
Verdict
N
be evaluated in end system.
2.1.1.1
Access to energized parts
N
Test by inspection ................................................. :
N
Test with test finger (Figure 2A) ............................ :
N
Test with test pin (Figure 2B) ................................ :
N
Test with test probe (Figure 2C) ........................... :
N
2.1.1.2
Battery compartments
N
2.1.1.3
Access to ELV wiring
N
Working voltage (Vpeak or Vrms); minimum
distance through insulation (mm)
⎯
2.1.1.4
Access to hazardous voltage circuit wiring
N
2.1.1.5
Energy hazards ..................................................... :
N
2.1.1.6
Manual controls
N
2.1.1.7
Discharge of capacitors in equipment
N
Measured voltage (V); time-constant (s) ............... :
⎯
Energy hazards – d.c. mains supply
N
a) Capacitor connected to the d.c. mains supply . :
N
b) Internal battery connected to the d.c. mains
supply .................................................................... :
N
2.1.1.9
Audio amplifiers .................................................... :
N
2.1.2
Protection in service access areas
N
2.1.3
Protection in restricted access locations
N
2.2
SELV circuits
P
2.2.1
General requirements
P
2.2.2
Voltages under normal conditions (V) .................. :
P
2.2.3
Voltages under fault conditions (V) ....................... :
P
2.2.4
Connection of SELV circuits to other circuits ..... :
2.3
TNV circuits
2.3.1
Limits
2.1.1.8
SELV
P
P
Built-in equipment which shall
N
be evaluated in end system.
Type of TNV circuits .............................................. :
⎯
2.3.2
Separation from other circuits and from accessible
parts
N
2.3.2.1
General requirements
N
2.3.2.2
Protection by basic insulation
N
2.3.2.3
Protection by earthing
N
TRF No. IECEN60950_1C
Page 9 of 37
Report No.: GLESO09120440901
IEC/EN 60950-1
Clause
Requirement + Test
2.3.2.4
Protection by other constructions ......................... :
N
2.3.3
Separation from hazardous voltages
N
Insulation employed............................................... :
⎯
Connection of TNV circuits to other circuits
N
Insulation employed............................................... :
⎯
2.3.5
Test for operating voltages generated externally
N
2.4
Limited current circuits
N
2.4.1
General requirements
N
2.4.2
Limit values
N
Frequency (Hz) ...................................................... :
⎯
Measured current (mA).......................................... :
⎯
Measured voltage (V)............................................. :
⎯
Measured circuit capacitance (nF or µF) ............... :
⎯
2.4.3
Connection of limited current circuits to other
circuits
N
2.5
Limited power sources
N
a) Inherently limited output
N
b) Impedance limited output
N
c) Regulating network limited output under normal
operating and single fault condition
N
d) Overcurrent protective device limited output
N
Max. output voltage (V), max. output current (A),
max. apparent power (VA)..................................... :
⎯
Current rating of overcurrent protective device (A) .:
⎯
2.6
Provisions for earthing and bonding
N
2.6.1
Protective earthing
2.3.4
Result – Remark
Built-in equipment which shall
Verdict
N
be evaluated in end system.
2.6.2
Functional earthing
N
2.6.3
Protective earthing and protective bonding
conductors
N
2.6.3.1
General
N
2.6.3.2
Size of protective earthing conductors
N
2
2.6.3.3
Rated current (A), cross-sectional area (mm ),
AWG ...................................................................... :
⎯
Size of protective bonding conductors
N
2
Rated current (A), cross-sectional area (mm ),
AWG ...................................................................... :
TRF No. IECEN60950_1C
⎯
Page 10 of 37
Report No.: GLESO09120440901
IEC/EN 60950-1
Clause
Requirement + Test
Result – Remark
Verdict
Protective current rating (A), cross-sectional area
(mm2), AWG........................................................... :
⎯
2.6.3.4
Resistance of earthing conductors and their
terminations; resistance (Ω), voltage drop (V), test
current (A), duration (min) ..................................... :
N
2.6.3.5
Colour of insulation ................................................ :
N
2.6.4
Terminals
N
2.6.4.1
General
N
2.6.4.2
Protective earthing and bonding terminals
N
Rated current (A), type, nominal thread diameter
(mm)....................................................................... :
⎯
2.6.4.3
Separation of the protective earthing conductor
from protective bonding conductors
N
2.6.5
Integrity of protective earthing
N
2.6.5.1
Interconnection of equipment
N
2.6.5.2
Components in protective earthing conductors and
protective bonding conductors
N
2.6.5.3
Disconnection of protective earth
N
2.6.5.4
Parts that can be removed by an operator
N
2.6.5.5
Parts removed during servicing
N
2.6.5.6
Corrosion resistance
N
2.6.5.7
Screws for protective bonding
N
2.6.5.8
Reliance on telecommunication network or cable
distribution system
N
2.7
Overcurrent and earth fault protection in primary circuits
N
2.7.1
Basic requirements
N
Instructions when protection relies on building
installation
N
2.7.2
Faults not simulated in 5.3.7
N
2.7.3
Short-circuit backup protection
N
2.7.4
Number and location of protective devices .......... :
N
2.7.5
Protection by several devices
N
2.7.6
Warning to service personnel ................................ :
N
2.8
Safety interlocks
N
2.8.1
General principles
N
2.8.2
Protection requirements
N
2.8.3
Inadvertent reactivation
N
2.8.4
Fail-safe operation
N
2.8.5
Moving parts
N
TRF No. IECEN60950_1C
Page 11 of 37
Report No.: GLESO09120440901
IEC/EN 60950-1
Clause
Requirement + Test
Result – Remark
2.8.6
Overriding
N
2.8.7
Switches and relays
N
2.8.7.1
Contact gaps (mm) ............................................... :
N
2.8.7.2
Overload test
N
2.8.7.3
Endurance test
N
2.8.7.4
Electric strength test
N
2.8.8
Mechanical actuators
N
2.9
Electrical insulation
N
2.9.1
Properties of insulating materials
Built-in equipment which shall
Verdict
N
be evaluated in end system.
2.9.2
Humidity conditioning
N
Relative humidity (%), temperature (°C) ............... :
⎯
2.9.3
Grade of insulation
N
2.9.4
Separation from hazardous voltages
N
Method(s) used ..................................................... :
⎯
2.10
Clearances, creepage distances and distances through insulation
N
2.10.1
General
N
Built-in equipment which shall
be evaluated in end system.
2.10.1.1
Frequency .............................................................:
N
2.10.1.2
Pollution degrees .................................................. :
N
2.10.1.3
Reduced values for functional insualtion
N
2.10.1.4
Intervening unconnected conductive parts
N
2.10.1.5
Insulation with varying dimensions
N
2.10.1.6
Special separation requirements
N
2.10.1.7
Insulation in circuits generating starting pulses
N
2.10.2
Determination of working voltage
N
2.10.2.1
General
Built-in equipment which shall
N
be evaluated in end system.
2.10.2.2
RMS working voltage
N
2.10.2.3
Peak working voltage
N
2.10.3
Clearances
N
2.10.3.1
General
Built-in equipment which shall
N
be evaluated in end system.
2.10.3.2
Mains transient voltages
N
a) AC mains supply ............................................... :
N
b) Earthed d.c. mains supplies .............................. :
N
TRF No. IECEN60950_1C
Page 12 of 37
Report No.: GLESO09120440901
IEC/EN 60950-1
Clause
Requirement + Test
Result – Remark
Verdict
c) Unearthed d.c. mains supplies ..........................:
N
d) Battery operation ............................................... :
N
2.10.3.3
Clearances in primary circuits
N
2.10.3.4
Clearances in secondary circuits
N
2.10.3.5
Clearances in circuits having starting pulses
N
2.10.3.6
Transients from a.c. mains supply ........................ :
N
2.10.3.7
Transients from d.c. mains supply ........................ :
N
2.10.3.8
Transients from telecommunication networks and
cable distribution systems ..................................... :
N
2.10.3.9
Measurement of transient voltage levels
N
a) Transients from a mains suplply
N
For an a.c. mains supply ....................................... :
N
For a d.c. mains supply ......................................... :
N
b) Transients from a telecommunication network :
N
2.10.4
Creepage distances
N
2.10.4.1
General
Built-in equipment which shall
N
be evaluated in end system.
2.10.4.2
Material group and caomparative tracking index
N
CTI tests ................................................................. :
⎯
2.10.4.3
Minimum creepage distances
N
2.10.5
Solid insulation
N
2.10.5.1
General
N
2.10.5.2
Distances through insulation
N
2.10.5.3
Insulating compound as solid insulation
N
2.10.5.4
Semiconductor devices
N
2.10.5.5.
Cemented joints
N
2.10.5.6
Thin sheet material – General
N
2.10.5.7
Separable thin sheet material
N
Number of layers (pcs)........................................... :
⎯
2.10.5.8
Non-separable thin sheet material
N
2.10.5.9
Thin sheet material – standard test procedure
N
Electric strength test
⎯
Thin sheet material – alternative test procedure
N
Electric strength test
⎯
2.10.5.11
Insulation in wound components
N
2.10.5.12
Wire in wound components
N
Working voltage ..................................................... :
N
a) Basic insulation not under stress ...................... :
N
2.10.5.10
TRF No. IECEN60950_1C
Page 13 of 37
Report No.: GLESO09120440901
IEC/EN 60950-1
Clause
Requirement + Test
Result – Remark
Verdict
b) Basic, supplemetary, reinforced insulation ....... :
N
c) Compliance with Annex U ................................. :
N
Two wires in contact inside wound component;
angle between 45° and 90° ................................... :
N
Wire with solvent-based enamel in wound
components
N
Electric strength test
⎯
Routine test
N
Additional insulation in wound components
N
Working voltage .....................................................:
N
- Basic insulation not under stress ........................:
N
- Supplemetary, reinforced insulation ................... :
N
2.10.6
Construction of printed boards
N
2.10.6.1
Uncoated printed boards
N
2.10.6.2
Coated printed boards
N
2.10.6.3
Insulation between conductors on the same inner
surface of a printed board
N
2.10.6.4
Insulation between conductors on different layers of
a printed board
N
Distance through insulation
N
Number of insulation layers (pcs) .......................... :
N
2.10.7
Component external terminations
N
2.10.8
Tests on coated printed boards and coated
components
N
2.10.8.1
Sample preparation and preliminary inspection
N
2.10.8.2
Thermal conditioning
N
2.10.8.3
Electric strength test
N
2.10.8.4
Abrasion resistance test
N
2.10.9
Thermal cycling
N
2.10.10
Test for Pollution Degree 1 environment and
insulating compound
N
2.10.11
Tests for semiconductor devices and cemented
joints
N
2.10.12
Enclosed and sealed parts
N
3
WIRING, CONNECTIONS AND SUPPLY
N
3.1
General
N
3.1.1
Current rating and overcurrent protection
N
3.1.2
Protection against mechanical damage
N
3.1.3
Securing of internal wiring
N
2.10.5.13
2.10.5.14
TRF No. IECEN60950_1C
Page 14 of 37
Report No.: GLESO09120440901
IEC/EN 60950-1
Clause
Requirement + Test
Result – Remark
3.1.4
Insulation of conductors
N
3.1.5
Beads and ceramic insulators
N
3.1.6
Screws for electrical contact pressure
N
3.1.7
Insulating materials in electrical connections
N
3.1.8
Self-tapping and spaced thread screws
N
3.1.9
Termination of conductors
N
10 N pull test
N
3.1.10
Sleeving on wiring
N
3.2
Connection to a mains supply
N
3.2.1
Means of connection
N
3.2.1.1
Connection to an a.c. mains supply
N
3.2.1.2
Connection to a d.c. mains supply
N
3.2.2
Multiple supply connections
N
3.2.3
Permanently connected equipment
N
Number of conductors, diameter of cable and
conduits (mm) ....................................................... :
⎯
3.2.4
Appliance inlets
N
3.2.5
Power supply cords
N
3.2.5.1
AC power supply cords
N
Type ...................................................................... :
2
Verdict
⎯
Rated current (A), cross-sectional area (mm ),
AWG ..................................................................... :
⎯
3.2.5.2
DC power supply cords
N
3.2.6
Cord anchorages and strain relief
N
Mass of equipment (kg), pull (N) ......................... :
⎯
Longitudinal displacement (mm) ........................... :
⎯
3.2.7
Protection against mechanical damage
N
3.2.8
Cord guards
N
Diameter or minor dimension D (mm); test mass (g)
............................................................................... :
⎯
Radius of curvature of cord (mm) .......................... :
⎯
3.2.9
Supply wiring space
N
3.3
Wiring terminals for connection of external conductors
N
3.3.1
Wiring terminals
N
3.3.2
Connection of non-detachable power supply cords
N
3.3.3
Screw terminals
N
3.3.4
Conductor sizes to be connected
N
TRF No. IECEN60950_1C
Page 15 of 37
Report No.: GLESO09120440901
IEC/EN 60950-1
Clause
Requirement + Test
Result – Remark
Verdict
Rated current (A), cord/cable type, cross-sectional
area (mm2)............................................................. :
⎯
Wiring terminal sizes
N
Rated current (A), type, nominal thread diameter
(mm) ..................................................................... :
⎯
3.3.6
Wiring terminal design
N
3.3.7
Grouping of wiring terminals
N
3.3.8
Stranded wire
N
3.4
Disconnection from the mains supply
N
3.4.1
General requirement
3.3.5
Built-in equipment which shall
N
be evaluated in end system.
3.4.2
Disconnect devices
N
3.4.3
Permanently connected equipment
N
3.4.4
Parts which remain energized
N
3.4.5
Switches in flexible cords
N
3.4.6
Number of poles - single-phase and d.c. equipment
N
3.4.7
Number of poles - three-phase equipment
N
3.4.8
Switches as disconnect devices
N
3.4.9
Plugs as disconnect devices
N
3.4.10
Interconnected equipment
N
3.4.11
Multiple power sources
N
3.5
Interconnection of equipment
N
3.5.1
General requirements
Built-in equipment which shall
N
be evaluated in end system.
3.5.2
Types of interconnection circuits .......................... :
N
3.5.3
ELV circuits as interconnection circuits
N
3.5.4
Data ports for additional equipment
N
4
PHYSICAL REQUIREMENTS
N
4.1
Stability
N
Angle of 10°
N
Test force (N) ........................................................ :
N
4.2
Mechanical strength
N
4.2.1
General
N
4.2.2
Steady force test, 10 N
N
4.2.3
Steady force test, 30 N
N
TRF No. IECEN60950_1C
Page 16 of 37
Report No.: GLESO09120440901
IEC/EN 60950-1
Clause
Requirement + Test
Result – Remark
4.2.4
Steady force test, 250 N
N
4.2.5
Impact test
N
Fall test
N
Swing test
N
4.2.6
Drop test; height (mm) .......................................... :
N
4.2.7
Stress relief test
N
4.2.8
Cathode ray tubes
N
Picture tube separately certified ........................... : (
N
4.2.9
High pressure lamps
N
4.2.10
Wall or ceiling mounted equipment; force (N) ...... :
N
4.3
Design and construction
N
4.3.1
Edges and corners
Built-in equipment which shall
Verdict
N
be evaluated in end system.
4.3.2
Handles and manual controls; force (N) .............:
N
4.3.3
Adjustable controls
N
4.3.4
Securing of parts
N
4.3.5
Connection by plugs and sockets
N
4.3.6
Direct plug-in equipment
N
Torque .................................................................. :
⎯
Compliance with the relevant mains plug standard
.............................................................................. :
N
4.3.7
Heating elements in earthed equipment
N
4.3.8
Batteries
N
- Overcharging of a rechargeable battery
N
- Unintentional charging of a non-rechargeable
battery
N
- Reverse charging of a rechargeable battery
N
- Excessive discharging rate for any battery
N
4.3.9
Oil and grease
N
4.3.10
Dust, powders, liquids and gases
N
4.3.11
Containers for liquids or gases
N
4.3.12
Flammable liquids ................................................ :
N
Quantity of liquid (l) .............................................. :
N
Flash point (°C) .................................................... :
N
4.3.13
Radiation
N
4.3.13.1
General
N
4.3.13.2
Ionizing radiation
N
TRF No. IECEN60950_1C
Page 17 of 37
Report No.: GLESO09120440901
IEC/EN 60950-1
Clause
Requirement + Test
Result – Remark
Verdict
Measured radiation (pA/kg) .................................. :
⎯
Measured high-voltage (kV) ................................. :
⎯
Measured focus voltage (kV) ............................... :
⎯
CRT markings ...................................................... :
⎯
Effect of ultraviolet (UV) radiation on materials
N
Part, property, retention after test, flammability
classification ......................................................... :
N
4.3.13.4
Human exposure to ultraviolet (UV) radiation ...... :
N
4.3.13.5
Laser (including LEDs)
N
Laser class ........................................................... :
⎯
4.3.13.6
Other types .......................................................... :
N
4.4
Protection against hazardous moving parts
N
4.4.1
General
N
4.4.2
Protection in operator access areas .................... :
N
4.4.3
Protection in restricted access locations ............. :
N
4.4.4
Protection in service access areas
N
4.5
Thermal requirements
P
4.5.1
General
P
4.5.2
Temperature tests
P
Normal load condition per Annex L ..................... :
⎯
4.3.13.3
4.5.3
Temperature limits for materials
4.5.4
Touch temperature limits
N
4.5.5
Resistance to abnormal heat ............................... :
N
4.6
Openings in enclosures
N
4.6.1
Top and side openings
N
Dimensions (mm) ................................................. :
⎯
Bottoms of fire enclosures
N
Construction of the bottomm, dimensions (mm) .. :
⎯
4.6.3
Doors or covers in fire enclosures
N
4.6.4
Openings in transportable equipment
N
4.6.4.1
Constructional design measures
N
Dimensions (mm) ................................................. :
⎯
4.6.4.2
Evaluation measures for larger openings
N
4.6.4.3
Use of metallized parts
N
4.6.5
Adhesives for constructional purposes
N
4.6.2
TRF No. IECEN60950_1C
see appended table 4.5
P
Page 18 of 37
Report No.: GLESO09120440901
IEC/EN 60950-1
Clause
Requirement + Test
Result – Remark
Verdict
Conditioning temperature (°C), time (weeks) ....... :
⎯
4.7
Resistance to fire
P
4.7.1
Reducing the risk of ignition and spread of flame
N
Method 1, selection and application of components
wiring and materials
N
Method 2, application of all of simulated fault
condition tests
P
4.7.2
Conditions for a fire enclosure
N
4.7.2.1
Parts requiring a fire enclosure
N
4.7.2.2
Parts not requiring a fire enclosure
N
4.7.3
Materials
N
4.7.3.1
General
N
4.7.3.2
Materials for fire enclosures
N
4.7.3.3
Materials for components and other parts outside
fire enclosures
N
4.7.3.4
Materials for components and other parts inside
fire enclosures
P
4.7.3.5
Materials for air filter assemblies
N
4.7.3.6
Materials used in high-voltage components
N
5
ELECTRICAL REQUIREMENTS AND SIMULATED ABNORMAL CONDITIONS
P
5.1
Touch current and protective conductor current
N
5.1.1
General
N
5.1.2
Configuration of equipment under test (EUT)
N
5.1.2.1
Single connection to an a.c. mains supply
N
5.1.2.2
Redundant multiple connections to an a.c. mains
supply
N
5.1.2.3
Simultaneous multiple connections to an a.c. mains
supply
N
5.1.3
Test circuit
N
5.1.4
Application of measuring instrument
N
5.1.5
Test procedure
N
5.1.6
Test measurements
N
Supply voltage (V) ................................................ :
⎯
Measured touch current (mA) .............................. :
⎯
Max. allowed touch current (mA) ......................... :
⎯
Measured protective conductor current (mA) ...... :
⎯
Max. allowed protective conductor current (mA) .. :
⎯
Equipment with touch current exceeding 3,5 mA
N
5.1.7
TRF No. IECEN60950_1C
Page 19 of 37
Report No.: GLESO09120440901
IEC/EN 60950-1
Clause
Requirement + Test
5.1.7.1
General ................................................................ :
N
5.1.7.2
Simultaneous multiple connections to the supply
N
5.1.8
Touch currents to telecommunication networks and
cable distribution systems and from
telecommunication networks
N
5.1.8.1
Limitation of the touch current to a
telecommunication network or to a cable
distribution system
N
Supply voltage (V) ................................................ :
⎯
Measured touch current (mA) .............................. :
⎯
Max. allowed touch current (mA) ......................... :
⎯
Summation of touch currents from
telecommunication networks
N
a) EUT with earthed telecommunication ports ..... :
N
b) EUT whose telecommunication ports have no
reference to protective earth
N
5.2
Electric strength
N
5.2.1
General
N
5.2.2
Test procedure
N
5.3
Abnormal operating and fault conditions
P
5.3.1
Protection against overload and abnormal
operation
P
5.3.2
Motors
N
5.3.3
Transformers
N
5.3.4
Functional insulation ............................................. :
N
5.3.5
Electromechanical components
P
5.3.6
Audio amplifiers in ITE ......................................... :
N
5.3.7
Simulation of faults
P
5.3.8
Unattended equipment
N
5.3.9
Compliance criteria for abnormal operating and
fault conditions
P
5.3.9.1
During the tests
P
5.3.9.2
After the tests
P
6
CONNECTION TO TELECOMMUNICATION NETWORKS
N
6.1
Protection of telecommunication network service persons, and users of other
equipment connected to the network, from hazards in the equipment
N
6.1.1
Protection from hazardous voltages
N
6.1.2
Separation of the telecommunication network from earth
N
5.1.8.2
TRF No. IECEN60950_1C
Result – Remark
Verdict
Page 20 of 37
Report No.: GLESO09120440901
IEC/EN 60950-1
Clause
Requirement + Test
Result – Remark
6.1.2.1
Requirements
Built-in equipment which shall
Verdict
N
be evaluated in end system.
Supply voltage (V) ................................................ :
⎯
Current in the test circuit (mA) ........................... :
⎯
6.1.2.2
Exclusions ............................................................ :
N
6.2
Protection of equipment users from overvoltages on telecommunication networks
N
6.2.1
Separation requirements
N
6.2.2
Electric strength test procedure
N
6.2.2.1
Impulse test
N
6.2.2.2
Steady-state test
N
6.2.2.3
Compliance criteria
N
6.3
Protection of the telecommunication wiring system from overheating
N
Max. output current (A) ........................................ :
⎯
Current limiting method ........................................ :
⎯
7
CONNECTION TO CABLE DISTRIBUTION SYSTEMS
N
7.1
General
N
Built-in equipment which shall
be evaluated in end system.
7.2
Protection of cable distribution system service
persons, and users of other equipment connected
to the system, from hazardous voltages in the
equipment
N
7.3
Protection of equipment users from overvoltages
on the cable distribution system
N
7.4
Insulation between primary circuits and cable
distribution systems
N
7.4.1
General
N
7.4.2
Voltage surge test
N
7.4.3
Impulse test
N
A
ANNEX A, TESTS FOR RESISTANCE TO HEAT AND FIRE
N
A.1
Flammability test for fire enclosures of movable
equipment having a total mass exceeding 18 kg,
and of stationary equipment (see 4.7.3.2)
N
A.1.1
Samples ................................................................ :
⎯
Wall thickness (mm).............................................. :
⎯
A.1.2
Conditioning of samples; temperature (°C) ......... :
N
A.1.3
Mounting of samples ............................................ :
N
TRF No. IECEN60950_1C
Page 21 of 37
Report No.: GLESO09120440901
IEC/EN 60950-1
Clause
Requirement + Test
A.1.4
Test flame (see IEC 60695-11-3)
N
Flame A, B, C or D ............................................... :
⎯
A.1.5
Test procedure
N
A.1.6
Compliance criteria
N
Sample 1 burning time (s)..................................... :
⎯
Sample 2 burning time (s)..................................... :
⎯
Sample 3 burning time (s)..................................... :
⎯
A.2
Flammability test for fire enclosures of movable equipment having a total mass not
exceeding 18 kg, and for material and components located inside fire enclosures
(see 4.7.3.2 and 4.7.3.4)
N
A.2.1
Samples, material ................................................. :
⎯
Wall thickness (mm).............................................. :
⎯
A.2.2
Conditioning of samples; temperature (°C) ......... :
N
A.2.3
Mounting of samples ............................................ :
N
A.2.4
Test flame (see IEC 60695-11-4)
N
Flame A, B or C ................................................... :
⎯
A.2.5
Test procedure
N
A.2.6
Compliance criteria
N
Sample 1 burning time (s)..................................... :
⎯
Sample 2 burning time (s)..................................... :
⎯
Sample 3 burning time (s)..................................... :
⎯
Alternative test acc. to IEC 60695-11-5, cl. 5 and 9
N
Sample 1 burning time (s)..................................... :
⎯
Sample 2 burning time (s)..................................... :
⎯
Sample 3 burning time (s)..................................... :
⎯
A.3
Hot flaming oil test (see 4.6.2)
N
A.3.1
Mounting of samples
N
A.3.2
Test procedure
N
A.3.3
Compliance criterion
N
B
ANNEX B, MOTOR TESTS UNDER ABNORMAL CONDITIONS (see 4.7.2.2 and
5.3.2)
N
B.1
General requirements
N
Position ................................................................ :
⎯
Manufacturer ........................................................ :
⎯
Type ..................................................................... :
⎯
Rated values ....................................................... :
⎯
Test conditions
N
A.2.7
B.2
TRF No. IECEN60950_1C
Result – Remark
Verdict
Page 22 of 37
Report No.: GLESO09120440901
IEC/EN 60950-1
Clause
Requirement + Test
B.3
Maximum temperatures
N
B.4
Running overload test
N
B.5
Locked-rotor overload test
N
Test duration (days) ............................................. :
⎯
Electric strength test: test voltage (V) .................. :
⎯
B.6
Running overload test for d.c. motors in secondary
circuits
N
B.6.1
General
N
B.6.2
Test procedure
N
B.6.3
Alternative test procedure
N
B.6.4
Electric strength test; test voltage (V) .................. :
N
B.7
Locked-rotor overload test for d.c. motors in
secondary circuits
N
B.7.1
General
N
B.7.2
Test procedure
N
B.7.3
Alternative test procedure
N
B.7.4
Electric strength test; test voltage (V) ................. :
N
B.8
Test for motors with capacitors
N
B.9
Test for three-phase motors
N
B.10
Test for series motors
N
Operating voltage (V) ........................................... :
⎯
ANNEX C, TRANSFORMERS (see 1.5.4 and 5.3.3)
N
Position ................................................................ :
⎯
Manufacturer ........................................................ :
⎯
Type ..................................................................... :
⎯
Rated values ....................................................... :
⎯
Method of protection ............................................. :
⎯
C.1
Overload test
N
C.2
Insulation
N
Protection from displacement of windings ............:
N
D
ANNEX D, MEASURING INSTRUMENTS FOR TOUCH-CURRENT TESTS
(see 5.1.4)
N
D.1
Measuring instrument
N
D.2
Alternative measuring instrument
N
E
ANNEX E, TEMPERATURE RISE OF A WINDING (see 1.4.13)
N
C
TRF No. IECEN60950_1C
Result – Remark
Verdict
Page 23 of 37
Report No.: GLESO09120440901
IEC/EN 60950-1
Clause
Requirement + Test
F
ANNEX F, MEASUREMENT OF CLEARANCES AND CREEPAGE DISTANCES
(see 2.10 and Annex G)
N
G
ANNEX G, ALTERNATIVE METHOD FOR DETERMINING MINIMUM
CLEARANCES
N
G.1
Clearances
N
G.1.1
General
N
G.1.2
Summary of the procedure for determining
minimum clearances
N
G.2
Determination of mains transient voltage (V)
N
G.2.1
AC mains supply .................................................. :
N
G.2.2
Earthed d.c. mains supplies ................................. :
N
G.2.3
Unearthed d.c. mains supplies ............................ :
N
G.2.4
Battery operation .................................................. :
N
G.3
Determination of telecommunication network
transient voltage (V) ............................................. :
N
G.4
Determination of required withstand voltage (V)
N
G.4.1
Mains transients and internal repetitive peaks .... :
N
G.4.2
Transients from telecommunication networks ..... :
N
G.4.3
Combination of transients
N
G.4.4
Transients from cable distribution systems
N
G.5
Measurement of transient voltages (V)
N
a) Transients from a mains supply
N
For an a.c. mains supply
N
For a d.c. mains supply
N
b) Transients from a telecommunication network
N
G.6
Determination of minimum clearances ................ :
N
H
ANNEX H, IONIZING RADIATION (see 4.3.13)
N
J
ANNEX J, TABLE OF ELECTROCHEMICAL POTENTIALS (see 2.6.5.6)
N
Metal(s) used ....................................................... :
⎯
K
ANNEX K, THERMAL CONTROLS (see 1.5.3 and 5.3.8)
N
K.1
Making and breaking capacity
N
K.2
Thermostat reliability; operating voltage (V) ........ :
N
K.3
Thermostat endurance test; operating voltage (V)
.............................................................................. :
N
K.4
Temperature limiter endurance; operating voltage
(V) ........................................................................ :
N
TRF No. IECEN60950_1C
Result – Remark
Verdict
Page 24 of 37
Report No.: GLESO09120440901
IEC/EN 60950-1
Clause
Requirement + Test
K.5
Thermal cut-out reliability
N
K.6
Stability of operation
N
L
ANNEX L, NORMAL LOAD CONDITIONS FOR SOME TYPES OF ELECTRICAL
BUSINESS EQUIPMENT (see 1.2.2.1 and 4.5.2)
P
L.1
Typewriters
N
L.2
Adding machines and cash registers
N
L.3
Erasers
N
L.4
Pencil sharpeners
N
L.5
Duplicators and copy machines
N
L.6
Motor-operated files
N
L.7
Other business equipment
P
M
ANNEX M, CRITERIA FOR TELEPHONE RINGING SIGNALS (see 2.3.1)
N
M.1
Introduction
N
M.2
Method A
N
M.3
Method B
N
M.3.1
Ringing signal
N
M.3.1.1
Frequency (Hz) .................................................... :
⎯
M.3.1.2
Voltage (V) ........................................................... :
⎯
M.3.1.3
Cadence; time (s), voltage (V) ............................. :
⎯
M.3.1.4
Single fault current (mA) ...................................... :
⎯
M.3.2
Tripping device and monitoring voltage ............... :
N
M.3.2.1
Conditions for use of a tripping device or a
monitoring voltage
N
M.3.2.2
Tripping device
N
M.3.2.3
Monitoring voltage (V) .......................................... :
N
N
ANNEX N, IMPULSE TEST GENERATORS (see 1.5.7.2, 1.5.7.3, 2.10.3.9, 6.2.2.1,
7.3.2, 7.4.3 and Clause G.5)
N
N.1
ITU-T impulse test generators
N
N.2
IEC 60065 impulse test generator
N
P
ANNEX P, NORMATIVE REFERENCES
⎯
Q
ANNEX Q, Voltage dependent resistors (VDRs) (see 1.5.9.1)
N
a) Preferred climatic categories ........................... :
N
b) Maximum continuous voltage .......................... :
N
c) Pulse current .................................................... :
N
TRF No. IECEN60950_1C
Result – Remark
Verdict
Page 25 of 37
Report No.: GLESO09120440901
IEC/EN 60950-1
Clause
Requirement + Test
Result – Remark
Verdict
R
ANNEX R, EXAMPLES OF REQUIREMENTS FOR QUALITY CONTROL
PROGRAMMES
N
R.1
Minimum separation distances for unpopulated
coated printed boards (see 2.10.6.2)
N
R.2
Reduced clearances (see 2.10.3)
N
S
ANNEX S, PROCEDURE FOR IMPULSE TESTING (see 6.2.2.3)
N
S.1
Test equipment
N
S.2
Test procedure
N
S.3
Examples of waveforms during impulse testing
N
T
ANNEX T, GUIDANCE ON PROTECTION AGAINST INGRESS OF WATER
(see 1.1.2)
N
⎯
U
ANNEX U, INSULATED WINDING WIRES FOR USE WITHOUT INTERLEAVED
INSULATION (see 2.10.5.4)
N
⎯
V
ANNEX V, AC POWER DISTRIBUTION SYSTEMS (see 1.6.1)
N
V.1
Introduction
N
V.2
TN power distribution systems
N
W
ANNEX W, SUMMATION OF TOUCH CURRENTS
N
W.1
Touch current from electronic circuits
N
W.1.1
Floating circuits
N
W.1.2
Earthed circuits
N
W.2
Interconnection of several equipments
N
W.2.1
Isolation
N
W.2.2
Common return, isolated from earth
N
W.2.3
Common return, connected to protective earth
N
X
ANNEX X, MAXIMUM HEATING EFFECT IN TRANSFORMER TESTS (see clause
C.1)
N
X.1
Determination of maximum input current
N
X.2
Overload test procedure
N
Y
ANNEX Y, ULTRAVIOLET LIGHT CONDITIONING TEST (see 4.3.13.3)
N
TRF No. IECEN60950_1C
Page 26 of 37
Report No.: GLESO09120440901
IEC/EN 60950-1
Clause
Requirement + Test
Y.1
Test apparatus ..................................................... :
N
Y.2
Mounting of test samples ..................................... :
N
Y.3
Carbon-arc light-exposure apparatus .................. :
N
Y.4
Xenon-arc light exposure apparatus .................... :
N
Z
ANNEX Z, OVERVOLTAGE CATEGORIES (see 2.10.3.2 and Clause G.2)
N
AA
ANNEX AA, MANDREL TEST (see 2.10.5.8)
N
BB
ANNEX BB, CHANGES IN THE SECOND EDITION
⎯
TRF No. IECEN60950_1C
Result – Remark
Verdict
Page 27 of 37
Report No.: GLESO09120440901
IEC/EN 60950-1
Clause
Requirement + Test
Result – Remark
Verdict
EN 60950-1:2006 + A11:2009 – CENELEC COMMON MODIFICATIONS
Contents
Add the following annexes:
P
Annex ZA (normative)
Normative references to international publications
with their corresponding European publications
Annex ZB (normative)
Annex ZC (informative)
General
A-deviations
Delete all the “country” notes in the reference document according to the following
list:
1.4.8
1.5.8
2.2.3
2.3.2.1
2.7.1
3.2.1.1
4.3.6
4.7.3.1
6
6.2.2
7.1
G.2.1
1.3.Z1
Special national conditions
Note 2
Note 2
Note
Note 2
Note
Note
Note 1 & 2
Note 2
Note 2 & 5
Note 6.
Note 3
Note 2
1.5.1
1.5.9.4
2.2.4
2.3.4
2.10.3.2
3.2.4
4.7
5.1.7.1
6.1.2.1
2.2.1
7.2
Annex H
Note 2 & 3
Note
Note
Note 2
Note 2
Note 3.
Note 4
Note 3 & 4
Note 2
Note 2
Note
Note 2
1.5.7.1
1.7.2.1
2.3.2
2.6.3.3
2.10.5.13
2.5.1
4.7.2.2
5.3.7
6.1.2.2
6.2.2.2
7.3
P
Note
Note 4, 5 & 6
Note
Note 2 & 3
Note 3
Note 2
Note
Note 1
Note
Note
Note 1 & 2
Add the following subclause:
N
1.3.Z1 Exposure to excessive sound pressure
The apparatus shall be so designed and constructed as to present no danger when
used for its intended purpose, either in normal operating conditions or under fault
conditions, particularly providing protection against exposure to excessive sound
pressures from headphones or earphones.
NOTE Z1 A new method of measurement is described in EN 50332-1, Sound system
equipment:
Headphones and earphones associated with portable audio equipment - Maximum sound
pressure level measurement methodology and limit considerations - Part 1: General method
for “one package equipment”, and in EN 50332-2, Sound system equipment: Headphones
and earphones associated with portable audio equipment - Maximum sound pressure level
measurement methodology and limit considerations - Part 2: Guidelines to associate sets
with headphones coming from different manufacturers.
1.5.1
Add the following NOTE:
N
NOTE Z1 The use of certain substances in electrical and electronic equipment is restricted
within the EU: see Directive 2002/95/EC
1.7.2.1
Add the following NOTE:
NOTE Z1 In addition, the instructions shall include, as far as applicable, a warning that
excessive sound pressure from earphones and headphones can cause hearing loss
TRF No. IECEN60950_1C
N
Page 28 of 37
Report No.: GLESO09120440901
IEC/EN 60950-1
Clause
Requirement + Test
2.7.1
Replace the subclause as follows:
Result – Remark
Verdict
N
Basic requirements
To protect against excessive current, short-circuits and earth faults in PRIMARY
CIRCUITS, protective devices shall be included either as integral parts of the
equipment or as parts of the building installation, subject to the following, a), b) and
c):
a) except as detailed in b) and c), protective devices necessary to comply with the
requirements of 5.3 shall be included as parts of the equipment;
b) for components in series with the mains input to the equipment such as the
supply cord, appliance coupler, r.f.i. filter and switch, short-circuit and earth fault
protection may be provided by protective devices in the building installation;
c) it is permitted for PLUGGABLE EQUIPMENT TYPE B or PERMANENTLY
CONNECTED EQUIPMENT, to rely on dedicated overcurrent and short-circuit
protection in the building installation, provided that the means of protection, e.g.
fuses or circuit breakers, is fully specified in the installation instructions.
If reliance is placed on protection in the building installation, the installation
instructions shall so state, except that for PLUGGABLE EQUIPMENT TYPE A the
building installation shall be regarded as providing protection in accordance with
the rating of the wall socket outlet.
2.7.2
This subclause has been declared ‘void’.
P
3.2.3
Delete the NOTE in Table 3A, and delete also in this table the conduit sizes in
parentheses.
N
3.2.5.1
Replace
N
“60245 IEC 53” by “H05 RR-F”;
“60227 IEC 52” by “H03 VV-F or H03 VVH2-F”;
“60227 IEC 53” by “H05 VV-F or H05 VVH2-F2”.
In Table 3B, replace the first four lines by the following:
| Up to and including 6
|
| Over 6 up to and including 10 |
| Over 10 up to and including 16 |
(0,75)
(1,0) c)
0,75 a)
1,0
1,5
b)
|
|
|
In the conditions applicable to Table 3B delete the words “in some countries” in
condition a).
In NOTE 1, applicable to Table 3B, delete the second sentence.
3.3.4
In Table 3D, delete the fourth line: conductor sizes for 10 to 13 A, and replace with
the following:
| Over 10 up to and including 16 |
1,5 to 2,5
|
1,5 to 4
N
|
Delete the fifth line: conductor sizes for 13 to 16 A.
4.3.13.6
Add the following NOTE:
NOTE Z1 Attention is drawn to 1999/519/EC: Council Recommendation on the limitation of
exposure of the general public to electromagnetic fields 0 Hz to 300 GHz. Standards taking
into account this Recommendation which demonstrate compliance with the applicable EU
Directive are indicated in the OJEC.
TRF No. IECEN60950_1C
N
Page 29 of 37
Report No.: GLESO09120440901
IEC/EN 60950-1
Clause
Requirement + Test
Annex H
Replace the last paragraph of this annex by:
Result – Remark
Verdict
N
At any point 10 cm from the surface of the OPERATOR ACCESS AREA, the dose
rate shall not exceed 1 μSv/h (0,1 mR/h) (see NOTE). Account is taken of the
background level.
Replace the notes as follows:
NOTE These values appear in Directive 96/29/Euratom.
Delete NOTE 2.
Bibliography
Additional EN standards.
⎯
ZA
NORMATIVE REFERENCES TO INTERNATIONAL PUBLICATIONS WITH THEIR
CORRESPONDING EUROPEAN PUBLICATIONS
⎯
ZB
SPECIAL NATIONAL CONDITIONS
P
1.2.4.1
In Denmark, certain types of Class I appliances (see 3.2.1.1) may be provided with
a plug not establishing earthing conditions when inserted into Danish socketoutlets.
N
1.2.13.14
In Norway and Sweden, for requirements see 1.7.2.1 and 7.3 of this annex.
N
1.5.7.1
In Finland, Norway and Sweden, resistors bridging BASIC INSULATION in
CLASS I PLUGGABLE EQUIPMENT TYPE A must comply with the requirements
in 1.5.7.1. In addition when a single resistor is used, the resistor must withstand the
resistor test in 1.5.7.2.
N
1.5.8
In Norway, due to the IT power system used (see annex V, Figure V.7), capacitors
are required to be rated for the applicable line-to-line voltage (230 V).
N
1.5.9.4
In Finland, Norway and Sweden, the third dashed sentence is applicable only to
equipment as defined in 6.1.2.2 of this annex.
N
1.7.2.1
In Finland, Norway and Sweden, CLASS I PLUGGABLE EQUIPMENT TYPE A
intended for connection to other equipment or a network shall, if safety relies on
connection to protective earth or if surge suppressors are connected between the
network terminals and accessible parts, have a marking stating that the equipment
must be connected to an earthed mains socket-outlet.
N
The marking text in the applicable countries shall be as follows:
In Finland: "Laite on liitettävä suojamaadoituskoskettimilla varustettuun
pistorasiaan"
In Norway: “Apparatet må tilkoples jordet stikkontakt”
In Sweden: “Apparaten skall anslutas till jordat uttag”
TRF No. IECEN60950_1C
Page 30 of 37
Report No.: GLESO09120440901
IEC/EN 60950-1
Clause
Requirement + Test
Result – Remark
Verdict
In Norway and Sweden, the screen of the cable distribution system is normally not
earthed at the entrance of the building and there is normally no equipotential
bonding system within the building. Therefore the protective earthing of the building
installation need to be isolated from the screen of a cable distribution system.
It is however accepted to provide the insulation external to the equipment by an
adapter or an interconnection cable with galvanic isolator, which may be provided
by e.g. a retailer.
The user manual shall then have the following or similar information in Norwegian
and Swedish language respectively, depending on in what country the equipment
is intended to be used in:
“Equipment connected to the protective earthing of the building installation through
the mains connection or through other equipment with a connection to protective
earthing – and to a cable distribution system using coaxial cable, may in some
circumstances create a fire hazard. Connection to a cable distribution system has
therefore to be provided through a device providing electrical isolation below a
certain frequency range (galvanic isolator, see EN 60728-11).”
NOTE In Norway, due to regulation for installations of cable distribution systems, and in Sweden, a
galvanic isolator shall provide electrical insulation below 5 MHz. The insulation shall withstand a
dielectric strength of 1,5 kV r.m.s., 50 Hz or 60 Hz, for 1 min.
Translation to Norwegian (the Swedish text will also be accepted in Norway):
“Utstyr som er koplet til beskyttelsesjord via nettplugg og/eller via annet jordtilkoplet
utstyr – og er tilkoplet et kabel-TV nett, kan forårsake brannfare. For å unngå dette
skal det ved tilkopling av utstyret til kabel-TV nettet installeres en galvanisk isolator
mellom utstyret og kabel- TV nettet.”
Translation to Swedish:
”Utrustning som är kopplad till skyddsjord via jordat vägguttag och/eller via annan
utrustning och samtidigt är kopplad till kabel-TV nät kan i vissa fall medfőra risk főr
brand. Főr att undvika detta skall vid anslutning av utrustningen till kabel-TV nät
galvanisk isolator finnas mellan utrustningen och kabel-TV nätet.”
1.7.5
In Denmark, socket-outlets for providing power to other equipment shall be in
accordance with the Heavy Current Regulations, Section 107-2-D1, Standard
Sheet DK 1-3a, DK 1-5a or DK 1-7a, when used on Class I equipment. For
STATIONARY EQUIPMENT the socket-outlet shall be in accordance with Standard
Sheet DK 1-1b or DK 1-5a.
N
For CLASS II EQUIPMENT the socket outlet shall be in accordance with Standard
Sheet DKA 1-4a.
2.2.4
In Norway, for requirements see 1.7.2.1, 6.1.2.1 and 6.1.2.2 of this annex.
N
2.3.2
In Finland, Norway and Sweden there are additional requirements for the
insulation. See 6.1.2.1 and 6.1.2.2 of this annex.
N
2.3.4
In Norway, for requirements see 1.7.2.1, 6.1.2.1 and 6.1.2.2 of this annex.
N
2.6.3.3
In the United Kingdom, the current rating of the circuit shall be taken as 13 A, not
16 A.
N
2.7.1
In the United Kingdom, to protect against excessive currents and short-circuits in
the PRIMARY CIRCUIT of DIRECT PLUG-IN EQUIPMENT, tests according to 5.3
shall be conducted, using an external protective device rated 30 A or 32 A. If these
tests fail, suitable protective devices shall be included as integral parts of the
DIRECT PLUG-IN EQUIPMENT, so that the requirements of 5.3 are met.
N
2.10.5.13
In Finland, Norway and Sweden, there are additional requirements for the
insulation, see 6.1.2.1 and 6.1.2.2 of this annex.
N
TRF No. IECEN60950_1C
Page 31 of 37
Report No.: GLESO09120440901
IEC/EN 60950-1
Clause
Requirement + Test
3.2.1.1
In Switzerland, supply cords of equipment having a RATED CURRENT not
exceeding 10 A shall be provided with a plug complying with SEV 1011 or IEC
60884-1 and one of the following dimension sheets:
SEV 6532-2.1991
SEV 6533-2.1991
SEV 6534-2.1991
Result – Remark
Plug Type 15
Plug Type 11
Plug Type 12
3P+N+PE
L+N
L+N+PE
Verdict
N
250/400 V, 10 A
250 V, 10 A
250 V, 10 A
In general, EN 60309 applies for plugs for currents exceeding 10 A. However, a 16
A plug and socket-outlet system is being introduced in Switzerland, the plugs of
which are according to the following dimension sheets, published in February 1998:
SEV 5932-2.1998
SEV 5933-2.1998
SEV 5934-2.1998
3.2.1.1
Plug Type 25
Plug Type 21
Plug Type 23
3L+N+PE
L+N
L+N+PE
230/400 V, 16 A
250 V, 16 A
250 V, 16 A
In Denmark, supply cords of single-phase equipment having a rated current not
exceeding13 A shall be provided with a plug according to the Heavy Current
Regulations, Section 107-2-D1.
N
CLASS I EQUIPMENT provided with socket-outlets with earth contacts or which
are intended to be used in locations where protection against indirect contact is
required according to the wiring rules shall be provided with a plug in accordance
with standard sheet DK 2-1a or DK 2-5a.
If poly-phase equipment and single-phase equipment having a RATED CURRENT
exceeding 13 A is provided with a supply cord with a plug, this plug shall be in
accordance with the Heavy Current Regulations, Section 107-2-D1 or EN 60309-2.
3.2.1.1
In Spain, supply cords of single-phase equipment having a rated current not
exceeding 10 A shall be provided with a plug according to UNE 20315:1994.
N
Supply cords of single-phase equipment having a rated current not exceeding 2,5
A shall be provided with a plug according to UNE-EN 50075:1993.
CLASS I EQUIPMENT provided with socket-outlets with earth contacts or which
are intended to be used in locations where protection against indirect contact is
required according to the wiring rules, shall be provided with a plug in accordance
with standard UNE 20315:1994.
If poly-phase equipment is provided with a supply cord with a plug, this plug shall
be in accordance with UNE-EN 60309-2.
3.2.1.1
In the United Kingdom, apparatus which is fitted with a flexible cable or cord and
is designed to be connected to a mains socket conforming to BS 1363 by means of
that flexible cable or cord and plug, shall be fitted with a ‘standard plug’ in
accordance with Statutory Instrument 1768:1994 - The Plugs and Sockets etc.
(Safety) Regulations 1994, unless exempted by those regulations.
N
NOTE ‘Standard plug’ is defined in SI 1768:1994 and essentially means an approved plug
conforming to BS 1363 or an approved conversion plug.
3.2.1.1
In Ireland, apparatus which is fitted with a flexible cable or cord and is designed to
be connected to a mains socket conforming to I.S. 411 by means of that flexible
cable or cord and plug, shall be fitted with a 13 A plug in accordance with Statutory
Instrument 525:1997 - National Standards Authority of Ireland (section 28) (13 A
Plugs and Conversion Adaptors for Domestic Use) Regulations 1997.
N
3.2.4
In Switzerland, for requirements see 3.2.1.1 of this annex.
N
3.2.5.1
In the United Kingdom, a power supply cord with conductor of 1,25 mm2 is
allowed for equipment with a rated current over 10 A and up to and including 13 A.
N
TRF No. IECEN60950_1C
Page 32 of 37
Report No.: GLESO09120440901
IEC/EN 60950-1
Clause
Requirement + Test
Result – Remark
3.3.4
In the United Kingdom, the range of conductor sizes of flexible cords to be
accepted by terminals for equipment with a RATED CURRENT of over 10 A up to
and including 13 A is:
Verdict
N
• 1,25 mm2 to 1,5 mm2 nominal cross-sectional area.
4.3.6
In the United Kingdom, the torque test is performed using a socket outlet
complying with BS 1363 part 1:1995, including Amendment 1:1997 and
Amendment 2:2003 and the plug part of DIRECT PLUG-IN EQUIPMENT shall be
assessed to BS 1363: Part 1, 12.1, 12.2, 12.3, 12.9, 12.11, 12.12, 12.13, 12.16 and
12.17, except that the test of 12.17 is performed at not less than 125 °C. Where the
metal earth pin is replaced by an Insulated Shutter Opening Device (ISOD), the
requirements of clauses 22.2 and 23 also apply.
N
4.3.6
In Ireland, DIRECT PLUG-IN EQUIPMENT is known as plug similar devices. Such
devices shall comply with Statutory Instrument 526:1997 - National Standards
Authority of Ireland (Section 28) (Electrical plugs, plug similar devices and sockets
for domestic use) Regulations, 1997.
N
5.1.7.1
In Finland, Norway and Sweden TOUCH CURRENT measurement results
exceeding 3,5 mA r.m.s. are permitted only for the following equipment:
N
• STATIONARY PLUGGABLE EQUIPMENT TYPE A that
○
is intended to be used in a RESTRICTED ACCESS LOCATION
where
equipotential bonding has been applied, for example, in a
telecommunication centre; and
○
has provision for a permanently connected PROTECTIVE EARTHING
CONDUCTOR; and
○
is provided with instructions for the installation of that conductor by a
SERVICE PERSON;
• STATIONARY PLUGGABLE EQUIPMENT TYPE B;
• STATIONARY PERMANENTLY CONNECTED EQUIPMENT.
TRF No. IECEN60950_1C
Page 33 of 37
Report No.: GLESO09120440901
IEC/EN 60950-1
Clause
Requirement + Test
Result – Remark
6.1.2.1
In Finland, Norway and Sweden, add the following text between the first and
second paragraph of the compliance clause:
Verdict
N
If this insulation is solid, including insulation forming part of a component, it shall at
least consist of either
-
two layers of thin sheet material, each of which shall pass the electric
strength test below, or
one layer having a distance through insulation of at least 0,4 mm, which
shall
pass the electric strength test below.
If this insulation forms part of a semiconductor component (e.g. an optocoupler),
there is no distance through insulation requirement for the insulation consisting of
an insulating compound completely filling the casing, so that CLEARANCES and
CREEPAGE DISTANCES do not exist, if the component passes the electric
strength test in accordance with the compliance clause below and in addition
-
passes the tests and inspection criteria of 2.10.11 with an electric strength
test of 1,5 kV multiplied by 1,6 (the electric strength test of 2.10.10 shall be
performed using 1,5 kV), and
-
is subject to ROUTINE TESTING for electric strength during manufacturing,
using a test voltage of 1,5 kV.
It is permitted to bridge this insulation with a capacitor complying with
EN 132400:1994, subclass Y2.
A capacitor classified Y3 according to EN 132400:1994, may bridge this insulation
under the following conditions:
-
the insulation requirements are satisfied by having a capacitor classified Y3
as defined by EN 132400, which in addition to the Y3 testing, is tested with
an impulse test of 2,5 kV defined in EN 60950-1:2006, 6.2.2.1;
-
the additional testing shall be performed on all the test specimens as
described in EN 132400;
-
the impulse test of 2,5 kV is to be performed before the endurance test in
EN 132400, in the sequence of tests as described in EN 132400.
6.1.2.2
In Finland, Norway and Sweden, the exclusions are applicable for
PERMANENTLY CONNECTED EQUIPMENT, PLUGGABLE EQUIPMENT TYPE
B and equipment intended to be used in a RESTRICTED ACCESS LOCATION
where equipotential bonding has been applied, e.g. in a telecommunication centre,
and which has provision for a permanently connected PROTECTIVE EARTHING
CONDUCTOR and is provided with instructions for the installation of that conductor
by a SERVICE PERSON.
N
7.2
In Finland, Norway and Sweden, for requirements see 6.1.2.1 and 6.1.2.2 of this
annex.
N
The term TELECOMMUNICATION NETWORK in 6.1.2 being replaced by the term
CABLE DISTRIBUTION SYSTEM.
7.3
In Norway and Sweden, for requirements see 1.2.13.14 and 1.7.2.1 of this annex.
N
ZC
A-DEVIATIONS (informative)
N
TRF No. IECEN60950_1C
Page 34 of 37
Report No.: GLESO09120440901
IEC/EN 60950-1
Clause
Requirement + Test
Result – Remark
1.5.1
Switzerland (Ordinance on environmentally hazardous substances SR 814.081,
Annex 1.7, Mercury - Annex 1.7 of SR 814.81 applies for mercury.)
Verdict
N
Add the following:
NOTE In Switzerland, switches containing mercury such as thermostats, relays and level
controllers are not allowed.
1.7.2.1
Germany (Gesetz über technische Arbeitsmittel und Verbraucherprodukte (Geräteund Produktsicherheitsgesetz – GPSG) [Law on technical labour equipment and
consumer products], of 6th January 2004, Section 2, Article 4, Clause (4), Item 2).
N
If for the assurance of safety and health certain rules during use, amending or
maintenance of a technical labour equipment or readymade consumer product are
to be followed, a manual in German language has to be delivered when placing the
product on the market.
Of this requirement, rules for use even only by SERVICE PERSONS are not
exempted.
1.7.13
Switzerland (Ordinance on chemical hazardous risk reduction SR 814.81, Annex
2.15 Batteries)
Annex 2.15 of SR 814.81 applies for batteries.
TRF No. IECEN60950_1C
N
Page 35 of 37
Report No.: GLESO09120440901
IEC/EN 60950-1
Clause
Requirement + Test
1.5.1
TABLE: List of critical components
Object/part No.
PWB
Result – Remark
Manufacturer/
trademark
P
Type/model
Various
Verdict
Technical data
Standard
(Edition / year)
V-1, 120 °C
Various
Mark(s) of
conformity1)
--
UL
1
) An asterisk indicates a mark which assures the agreed level of surveillance
Supplementary information:--
1.6.2
TABLE: Electrical data (in normal conditions)
P
U (V)
I (A)
Irated (A)
P (W)
Fuse #
Ifuse (A)
4,5
0,032
--
0,141
--
--
Condition/status
Normal condition
Supplementary information:--
2.10.3 and
2.10.4
TABLE: Clearance and creepage distance measurements
Clearance (cl) and creepage
distance (cr) at/of/between:
N
U peak
(V)
U r.m.s.
(V)
Required cl
(mm)
cl
(mm)
Required cr
(mm)
cr
(mm)
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
Functional:
-Basic/supplementary:
Reinforced:
Supplementary information:--
2.10.5
TABLE: Distance through insulation measurements
Distance through insulation (DTI) at/of:
-Supplementary information:--
TRF No. IECEN60950_1C
N
U peak
(V)
U rms
(V)
Test
voltage
(V)
Required DTI
(mm)
DTI
(mm)
--
--
--
--
--
Page 36 of 37
Report No.: GLESO09120440901
IEC/EN 60950-1
Clause
Requirement + Test
4.3.8
TABLE: Batteries
Result – Remark
Verdict
N
The tests of 4.3.8 are applicable only when appropriate battery
data is not available
--
--
Is it possible to install the battery in a reverse polarity position?
--
--
Non-rechargeable batteries
Discharging
Meas.
current
Manuf.
Specs.
Max.
current
during
normal
condition
--
--
Max.
current
during
fault
condition
--
--
Unintentional
charging
Rechargeable batteries
Charging
Discharging
Reversed
charging
Meas.
current
Manuf.
Specs.
Meas.
current
Manuf.
Specs.
Meas.
current
Manuf.
Specs.
--
--
--
--
--
--
--
--
--
--
--
--
--
--
Test results:
--
Verdict
- Chemical leaks
--
--
- Explosion of the battery
--
--
- Emission of flame or expulsion of molten metal
--
--
- Electric strength tests of equipment after completion of tests
--
--
Supplementary information:--
4.5
TABLE: Thermal requirements
P
Supply voltage (V) .......................... :
4,5
⎯
Ambient Tmin (°C) ............................. :
23,6
⎯
Ambient Tmax (°C) ............................ :
24,0
⎯
Maximum measured temperature T of part/at::
Allowed
Tmax
(°C)
T (°C)
PWB surface (near U102)
32,4
63
PWB surface (near U105)
32,5
63
Supplementary information:-Temperature T of winding:
--
t1 (°C)
R1 (Ω)
t2 (°C)
R2 (Ω)
T (°C)
--
--
--
--
--
Supplementary information: the Tam is 80°C considered
TRF No. IECEN60950_1C
Allowed Insulation
class
Tmax (°C)
--
--
Page 37 of 37
Report No.: GLESO09120440901
IEC/EN 60950-1
Clause
Requirement + Test
Result – Remark
4.5.5
TABLE: Ball pressure test of thermoplastic parts
N
Allowed impression diameter (mm) .....................: ≤ 2 mm
⎯
Part
Verdict
Test temperature Impression diameter
(mm)
(°C)
--
--
--
Supplementary information:--
4.7
TABLE: Resistance to fire
Part
Manufacturer of
material
PWB
Various
P
Type of material
Thickness Flammability
(mm)
class
Various
1,2
V-1
Evidence
UL
Supplementary information:--
5.2
TABLE: Electric strength tests, impulse tests and voltage surge tests
Test voltage applied between:
N
Voltage shape Test voltage Breakdown
(AC, DC,
(V)
Yes / No
impulse, surge)
Functional:
--
--
--
--
--
--
--
--
--
--
Basic/supplementary:
-Reinforced:
-Supplementary information:--
- - - End of Report - - -
TRF No. IECEN60950_1C
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertisement