Venstar T2700 Installation Instructions Manual

Add to my manuals
23 Pages

advertisement

Venstar T2700 Installation Instructions Manual | Manualzz

Digital

Thermostat

commercial

THERMOSTAT

T2700

HEAT

COOL

HEAT

PUMP

Control up to 3 Heat &

2 Cool Stages

3 Configurable Outputs

Backlit Display & Button

Legends

Aux Heat Indicator

Dry Contact Equipped

Soft Start

Set Point Limiting

Remote Sensor Ready

Outdoor Sensor Ready

Accepts EZ Programmer

Accepts Optional Humidity

Module: Controls Humidification and Dehumidification

Accepts Optional IR

Remote Control

Accepts Comfort Call

Phone Control Acessory

Use with most Air Conditioning & Heating Systems including: 1 or 2 Stage

Electric Cooling & 3 Stage Gas Heating, Heat Pump, Electric or Hydronic Heat.

INSTALLATION

INSTRUCTIONS

Venstar Inc. 08/07

CAUTION

Follow the Installation Instructions before proceeding.

Set the thermostat mode to “OFF” prior to changing settings in setup or restoring Factory Defaults.

CAUTION

NEVER PUT MORE THAN ONE

JUMPER ON THE SAME MISC

JUMPER BLOCK!

THIS MAY DAMAGE YOUR

THERMOSTAT AND VOID

YOUR WARRANTY.

MISC1

OK

MISC1

NOTE: Due to variations in environmental conditions, it is not always possible to achieve the desired humidification or dehumidification setpoint.

This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) this device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.

4Z95

Thermostat T2700

F C

Tested to Comply with FCC Standards

FOR HOME OR OFFICE USE

Page i

Table of Contents

Preparation

Remove & Replace the

Old Thermostat

Configuring the MISC

Outputs

Wire Connections

Sample Wiring

Diagrams

Test Operation

Calibrating the

Thermostat Sensors

TroubleShooting

5

6

7

8

1

2

3

4

Page iii

SECTION 1

Preparation

1

I2:00

Pm

AUTO

74

COOL

Proper installation of the thermostat will be accomplished by following these step by step instructions. If you are unsure about any of these steps, call a qualified technician for assistance.

Assemble tools

I2:00

Pm

AUTO

74

COOL

I2:00

Pm

AUTO

74

COOL

Flat Blade

Screwdriver

Wire cutter

& Stripper

Make sure your Heater/Air Conditioner is working properly before beginning installation of the thermostat.

I2:00

Pm

AUTO

74

COOL

Carefully unpack the thermostat. Save the screws, bracket, and instructions.

I2:00

Pm

AUTO

74

COOL

Turn off the power to the Heating/Air Conditioning system at the main fuse panel. Most residential systems have a separate breaker for disconnecting power to the furnace.

Page 1.1

SECTION 2

Remove & Replace the Old Thermostat

I2:00

Pm

AUTO

74

COOL

Remove the cover of the old thermostat.

If it does not come off easily check for screws.

2

I2:00

Pm

AUTO

74

COOL

I2:00

Pm

AUTO

74

COOL

I2:00

Pm

AUTO

74

COOL

Loosen the screws holding the thermostat base or subbase to the wall, and lift away.

Disconnect the wires from the old thermostat.

Tape the ends of the wires as you disconnect them, and mark them with the letter of the terminal for easy reconnection to the new thermostat.

Keep the old thermostat for reference purposes until your new thermostat is functioning properly.

Page 2.1

SECTION 3

Configuring the MISC Outputs

3

Section 3 Contents:

Configuring the Jumpers........3.2

Explanation of Jumper

Settings..................................3.3

Page 3.1

Configuring the Jumpers

For additional flexibility, your thermostat has three configurable outputs. These outputs are designed to have different functions

3 depending on how the jumpers are set (below).

Each output, labeled MISC1, MISC2, and MISC3 may be set for one of the four choices available.

In the diagram below, the MISC3 jumper has been set for HUM

(humidification) operation, the MISC2 jumper has been set for DEHUM

(dehumidification) operation, and the MISC1 jumper has been set for

Y2 (second stage cooling) operation.

HUM

DEHUM

MISC3 MISC2 MISC1

Y2

(MISC1

ONLY)

W1

Y1

G

MISC2

CK1

CKGND

R

C

INSTALL HUMIDITY

MODULE WITH SENSING

ELEMENT OUTWARD

ELEC

GAS

HP

GAS

B

O

W2

MISC1

RS2

MISC3

RS+5

RS1

RSGND

HUM

DEHUM

MISC3 MISC2 MISC1

Y2

(MISC1

ONLY)

CAUTION

NEVER PUT MORE THAN

ONE JUMPER ON THE SAME

MISC JUMPER BLOCK!

DOING SO MAY DAMAGE

YOUR THERMOSTAT AND

VOID THE WARRANTY.

MISC1

Page 3.2

MISC1

Explanation of Jumper Settings

3

HUM JUMPER SETTING

If the jumper for MISC1, MISC2, or MISC3 is set to HUM, the corresponding MISC screw terminal on the backplate will control a humidification system.

HUMIDIFICATION OPERATION - SECTION 8 of the Owner’s Manual

If your HVAC unit is equipped with a humidification system and the Humidity

Module (sold separately) has been installed, the thermostat will provide power to the MISC1, MISC2, or MISC3 terminal of the thermostat when the humidity in the home falls below the humidity setpoint you have chosen. The value for this setpoint ranges from 0% to 60%. If no humidity is desired or if a humidification system has not been installed, set the value to OFF.

DEHUM JUMPER SETTING

If the jumper for MISC1, MISC2, or MISC3 is set to DEHUM, terminal on the backplate will be connected to the dehumidification terminal of a furnace board.

NOTE: Not all furnaces have a dehumidification terminal.

the corresponding MISC screw

DEHUMIDIFICATION OPERATION - SECTION 9 of the Owner’s Manual

If your HVAC unit is equipped with a dehumidification system the thermostat will operate in one of two ways.

1) Normally Closed (NC): The thermostat will de-energize the MISC1, MISC2,

or MISC3 terminal of the thermostat (this MISC terminal is connected to the

DEHUM terminal on your furnace) to allow the fan to run in low speed when

the humidity in the home is above the dehumidify setpoint you have chosen

and there is a call for 1st stage cooling.

2) Normally Open (NO): The thermostat will energize the MISC1, MISC2, or

MISC3 terminal of the thermostat (this MISC terminal is connected to the

DEHUM terminal on your furnace) to allow the fan to run in low speed when

the humidity in the home is above the dehumidify setpoint you have chosen

and there is a call for 1st stage cooling.

Page 3.3

Explanation of Jumper Settings

(continued)

Y2 JUMPER SETTING

If the jumper for MISC1 is set to Y2 the second stage of cooling.

MISC1 screw terminal on the backplate will control a

3

Y2 OPERATION - SECTION 12 of the Owner’s Manual

The 2nd Stage of heat or cool is turned on when:

(A) The 1st Stage has been on for the two minutes.

And

(B) The temperature spread from the setpoint is equal to or greater

than: the setpoint plus the 1st stage deadband (step #19, page

12.5 of the Owner’s Manual), plus two degrees.

Cooling

Deadband Deadband db 1

(adj. 1-6 ) db 2

(adj. 0-10 )

Cool

Setpoint

1st Stage turn on

TEMPERATURE INCREASE

2nd Stage turn on

Page 3.4

SECTION 4

Wire Connections

4

I2:00

Pm

AUTO

74

COOL

If the terminal designations on your old thermostat do not match those on the new thermostat, refer to the chart below, or the wiring diagrams that follow.

Wire from the old thermostat terminal marked

G or F

Y1, Y or C

W1, W or H

Rh, R, M, Vr, A

C

O/B

W2

MISC1

MISC2

MISC3

RS+5

RS1

RSGND

RS2

CK1

CKGND

Function

Fan

Cooling

Heating

Power

Common

Rev. Valve

2nd Stage Heat

Configurable Output #1

Configurable Output #2

Configurable Output #3

Remote Sensor +5vdc

Remote Sensor Signal

Remote Sensor Ground

Remote Sensor Signal #2

Dry Contact Switch 1

Dry Contact Switch 2

Install on the new thermostat connector marked

G

Y1

W1/O/B

R

C

W1/O/B*

W2

MISC1

MISC2

MISC3

RS+5**

RS1**

RSGND**

RS2**

CK1

CKGND

* O/B is used if your system is a Heat Pump.

** For instructions on connecting these terminals see page 13.2

of the Owner’s Manual. Page 4.1

SECTION 5

Sample Wiring Diagrams

Section 5 Contents:

5

HVAC Equipment Wiring............5.2

MISC1, MISC2, and MISC3

Wiring........................................5.6

Remote Sensor, Outdoor Sensor

and CK1-CK2 wiring for the

Time Clock................................5.8

Page 5.1

5

6 Wire, 1 Stage Cooling, 1 Stage Heat

Residential & Commercial 1 Stage Cooling, with 1st Stage Gas Heat

OR Commercial Heat Pump 1 Stage Cooling with 2 Stage Heat

W2

MISC1

RS2

MISC3

RS+5

RS1

RSGND

W1/O/B

Y1

G

MISC2

CK1

CKGND

R

C

ELEC

GAS

HP

GAS

B

O

HUM

DEHUM

MISC3 MISC2 MISC1

Y2

(MISC1

ONLY)

W1

Y1

G

MISC2

CK1

CKGND

R

C

INSTALL HUMIDITY

MODULE WITH SENSING

ELEMENT OUTWARD

ELEC

GAS

HP

GAS

B

O

W2

MISC1

RS2

MISC3

RS+5

RS1

RSGND

6 Conductor 18 gauge unshielded cable from the thermostat to the equipment.

24 vac common

24 vac return

Fan relay

Compressor relay

1st stage heat circuit

2nd stage heat circuit

Page 5.2

6 Wire, 1 Stage Cooling, 1 Stage Heat

Residential & Commercial 1 Stage Cooling, with 1st Stage Electric Heat

W2

MISC1

RS2

MISC3

RS+5

RS1

RSGND

W1/O/B

Y1

G

MISC2

CK1

CKGND

R

C

ELEC

GAS

HP

GAS

B

O

24 vac common

24 vac return

Fan relay

Compressor relay

1st stage heat circuit

2nd stage heat circuit

HUM

DEHUM

MISC3 MISC2 MISC1

Y2

(MISC1

ONLY)

W1

Y1

G

MISC2

CK1

CKGND

R

C

INSTALL HUMIDITY

MODULE WITH SENSING

ELEMENT OUTWARD

ELEC

GAS

HP

GAS

B

O

W2

MISC1

RS2

MISC3

RS+5

RS1

RSGND

6 Conductor 18 gauge unshielded cable from the thermostat to the equipment.

Page 5.3

5

6 Wire, 1 Stage Cooling, 2 Stage Heat

Residential Heat Pump with O Reversing

Valve 1 Stage Cooling, with 2 Stage Heat

5

W2

MISC1

RS2

MISC3

RS+5

RS1

RSGND

W1/O/B

Y1

G

MISC2

CK1

CKGND

R

C

ELEC

GAS

HP

GAS

B

O

HUM

DEHUM

MISC3 MISC2 MISC1

Y2

(MISC1

ONLY)

W1

Y1

G

MISC2

CK1

CKGND

R

C

INSTALL HUMIDITY

MODULE WITH SENSING

ELEMENT OUTWARD

ELEC

GAS

HP

GAS

B

O

W2

MISC1

RS2

MISC3

RS+5

RS1

RSGND

6 Conductor 18 gauge unshielded cable from the thermostat to the equipment.

24 vac common

24 vac return

Fan Relay

Compressor Relay

Reversing Valve

2nd stage heat circuit

Page 5.4

6 Wire, 1 Stage Cooling, 2 Stage Heat

Residential Heat Pump with b Reversing

Valve 1 Stage Cooling, with 2 Stage Heat

W2

MISC1

RS2

MISC3

RS+5

RS1

RSGND

W1/O/B

Y1

G

MISC2

CK1

CKGND

R

C

ELEC

GAS

HP

GAS

B

O

24 vac common

24 vac return

Fan Relay

Compressor Relay

Reversing Valve

2nd stage heat circuit

HUM

DEHUM

MISC3 MISC2 MISC1

Y2

(MISC1

ONLY)

W1

Y1

G

MISC2

CK1

CKGND

R

C

INSTALL HUMIDITY

MODULE WITH SENSING

ELEMENT OUTWARD

ELEC

GAS

HP

GAS

B

O

W2

MISC1

RS2

MISC3

RS+5

RS1

RSGND

6 Conductor 18 gauge unshielded cable from the thermostat to the equipment.

Page 5.5

5

Adding a 2nd Stage of Cooling (MISC1).

5

W2

MISC1

RS2

MISC3

RS+5

RS1

RSGND

W1/O/B

Y1

G

MISC2

CK1

CKGND

R

C

HUM

DEHUM

MISC3 MISC2 MISC1

Y2

(MISC1

ONLY)

HUM

DEHUM

MISC3 MISC2 MISC1

Y2

(MISC1

ONLY)

W1

Y1

G

MISC2

CK1

CKGND

R

C

INSTALL HUMIDITY

MODULE WITH SENSING

ELEMENT OUTWARD

ELEC

GAS

HP

GAS

B

O

W2

MISC1

RS2

MISC3

RS+5

RS1

RSGND

2nd Stage Cooling

Page 5.6

Adding a Humidification System (MISC1) and Dehumidification System (MISC2)

*

.

W2

MISC1

RS2

MISC3

RS+5

RS1

RSGND

W1/O/B

Y1

G

MISC2

CK1

CKGND

R

C

HUM

DEHUM

MISC3 MISC2 MISC1

Y2

(MISC1

ONLY)

PROG

HUM

DEHUM

MISC3 MISC2 MISC1

Y2

(MISC1

ONLY)

W1

Y1

G

MISC2

CK1

CKGND

R

C

INSTALL HUMIDITY

MODULE WITH SENSING

ELEMENT OUTWARD

ELEC

GAS

HP

GAS

B

O

W2

MISC1

RS2

MISC3

RS+5

RS1

RSGND

HUM

NO HUM

Humidity Module

(Sold Separately)

Dehumidification

System

Humidification

System

*

Requires Humidity Module.

Page 5.7

5

5

CK1 and CK2 terminals wired to a Time Clock

For instructions on wiring the optional Remote and Outdoor

Sensors, please see page 13.2 of the Owner’s Manual

W2

MISC1

RS2

MISC3

RS+5

RS1

RSGND

W1/O/B

Y1

G

MISC2

CK1

CKGND

R

C

10

9

11

12

8

7

6

1

2

3

5

4

DRY CONTACT SWITCH - The terminals are ‘normally open’ (may be programmed for

normally closed operation, see page 14.2 of the Owner’s Manual). Closing or

completing the circuit will cause the thermostat to do one of the following:

1) If Occupied 1 is selected in step #24 of the Advanced Setup (see page 14.3 of Owner’s

Manual), when the dry contact is energized the thermostat will be forced into Occupied 1

setpoints (see Section 6 of Owner’s Manual).

2) If Service Pan is selected, when the dry contact is energized the thermostat will lockout

Y1 (compressor) and write Service Pan on the display.

Page 5.8

SECTION 6

Test Operation

AUTO

74

COOL

Turn the power on to the Heating/Air Conditioning system.

I2:00

Pm

AUTO

74

COOL

Press the MODE button repeatedly until the

HEAT icon appears on the display. Press the

UP or DOWN buttons until the set temperature is

6

10 degrees above room temperature; the furnace should turn on.

AUTO

74

COOL

AUTO

74

COOL

Press the MODE button repeatedly until the

COOL icon appears on the display. Press the UP or DOWN buttons until the set temperature is 10 degrees below room temperature; the air conditioner should turn on. NOTE: Most equipment has a time delay of 5 minutes between cool cycles. This feature is defeatable on the thermostat. Consult the Owner's Manual under

Setup, cycles per hour.

Press the UP button until the setpoint is equal to the room temperature. Press the FAN button to Fan On. The fan should turn on and run continuously.

NOTE: Due to the Random Start feature, outputs may not energize for up to 30

seconds when the thermostat is first powered (see page 14.5 of the

Owner’s Manual)

Page 6.1

Calibrating the Temperature and Humidity Sensors

Under normal circumstances it will not be necessary to adjust the calibration of the temperature and humidity sensors. If calibration is required, please contact a trained HVAC technician to correctly perform the following procedure.

7

MODE

Place the thermostat in the

OFF mode.

OFF

I2:00

Pm

Su

72

MODE

FAN

Press and hold the MODE button. While holding the

MODE button, press and hold the FAN button for 5 seconds.

All icons will appear on the display.

Service Filter

Pan UV Light

AUTO

OFFON

Override

FanOn

DeHumidify

I88 Setup

H

I

88

C OOL

Outside

Remote

A UX H EAT

L

O

88

PRESS

THERMOSTAT SENSOR

Press the UP and DOWN buttons at the same time twice. The thermostat temperature will be displayed and may be calibrated using the UP or DOWN buttons.

CALIBRATE

TWICE

MODE

REMOTE SENSOR

MODE

Press the MODE button once. The remote sensor temperature will be displayed and may be calibrated using the

UP or DOWN buttons. If a remote sensor is not installed, only dashes will appear.

HUMIDITY SENSOR

Press the MODE button once. The relative humidity at the thermostat will be displayed and may be calibrated using the

UP or DOWN buttons.

Remote

CALIBRATE

CALIBRATE

After calibration is complete, press the MODE button once to return to normal operation.

Page 7.1

SECTION 8

TroubleShooting

I2:00

Pm

AUTO

74

COOL

I2:00

Pm

AUTO

74

COOL

I2:00

Pm

AUTO

74

COOL

I2:00

Pm

AUTO

74

COOL

SYMPTOM: The air conditioning does not attempt to

turn on.

CAUSE: The compressor timer lockout may prevent the

air conditioner from turning on, for a period of time.

REMEDY: Consult the Owner's Manual in the Setup

section to defeat the cycles per hour and

compressor timeguard.

8

SYMPTOM: The display is blank.

CAUSE: Lack of proper power.

REMEDY: Make sure power is turned on to the furnace

and that you have 24vac between R & W. If C is

used, 24vac between R & C.

SYMPTOM: The air conditioning does not attempt to

turn on.

CAUSE: The cooling setpoint is set too high.

REMEDY: Consult the Owner's Manual in the Setup

section to lower the cooling setpoint limit.

SYMPTOM: The heating does not attempt to turn on.

CAUSE: The heating setpoint is set too low.

REMEDY: Consult the Owner's Manual in the Setup

section to raise the heating setpoint limit.

NOTE: Due to the Random Start feature, outputs may not energize for up to 30

seconds when the thermostat is first powered (see page 14.5 of the

Owner’s Manual)

Page 8.1

TroubleShooting

I2:00

Pm

AUTO

74

COOL

SYMPTOM: When controlling a residential heat pump,

and asking for cooling, the heat comes on.

CAUSE: The thermostat reversing valve jumper is set

for “b”.

REMEDY: Set the reversing valve jumper for “O”. See

pages 5.4 and 5.5.

8

I2:00

Pm

AUTO

74

COOL

SYMPTOM: When calling for cooling, both the heat

and cool come on.

CAUSE: The thermostat equipment jumper is configured

for “HP” and the HVAC unit is a Gas/Electric.

REMEDY: Set the equipment jumper for “Gas”. See

pages 5.2 and 5.3.

NOTE: Due to the Random Start feature, outputs may not energize for up to 30

seconds when the thermostat is first powered (see page 14.5 of the

Owner’s Manual)

P/N 88-602

Page 8.2

Rev. 1