Bard H 12AA-A, H 24AA-A, H 36AA-A, H 42AA-A, H 48AA-A, H 60AA-A, H 72AA-A, H 24LA-A, H 36LA-A, H 42LA-A, H 48LA-A, H 60LA-A, H 72LA-A wall-mounted packaged air conditioner Installation instructions
Below you will find brief information for wall-mounted packaged air conditioner H 12AA-A, H 24AA-A, H 36AA-A, H 42AA-A, H 48AA-A. These units are designed for use with or without duct work. Flanges are provided for attaching the supply and return ducts. The unit is secured by wall mounting brackets. A bottom mounting bracket, attached to skid for shipping, is provided for ease of installation, but is not required. The unit itself is suitable for 0 clearance, but the supply air duct flange and the first 3' of supply air duct require a minimum of 1/4" clearance to combustible material.
Advertisement
Advertisement
INSTALLATION INSTRUCTIONS
WALL-MOUNTED PACKAGED
AIR CONDITIONER
Models:
H12AA-A
H24AA-A
H36AA-A
H42AA-A
H48AA-A
H60AA-A
H72AA-A
H24LA-A
H36LA-A
H42LA-A
H48LA-A
H60LA-A
H72LA-A
Bard Manufacturing Company, Inc.
Bryan, Ohio 43506 www.bardhvac.com
Manual: 2100-647A
Supersedes: 2100-647
Date: 10-12-15
Page 1 of 30
CONTENTS
Getting Other Information and Publications .... 3
Wall Mount General Information ......................... 4
Air Conditioner Wall Mount Model Nomenclature ....... 4
Shipping Damage ................................................... 4
General .................................................................. 4
Duct Work .............................................................. 5
Filters .................................................................... 5
Condensate Drain .................................................. 5
Installation ............................................................... 6
Wall Mounting Information ...................................... 6
Mounting the Unit .................................................. 6
Wiring – Main Power ............................................. 15
Wiring – Low Voltage Wiring ................................... 16
Dirty Filter Switch and Relay .................................. 16
Economizer Fail Time Delay Relay .......................... 16
Start Up ................................................................... 17
General ................................................................ 17
Topping Off System Charge .................................... 17
Safety Practices.................................................... 17
Important Installer Note ........................................ 17
High Pressure and Low Pressure Switches ............... 18
Condenser Fan Operation ...................................... 18
Service Hints........................................................ 18
Sequence of Operation .......................................... 18
Compressor Control Module ................................... 18
Pressure Service Ports ........................................... 19
Service ..................................................................... 20
Fan Blade Setting Dimensions ............................... 20
Removal of Fan Shroud ......................................... 20
R410A Refrigerant Charge ..................................... 20
Figures
Figure 1 H12 Unit Dimensions ........................... 7
Figure 2 H24-72 Unit Dimensions ...................... 8
Figure 3A H12 Mounting Instructions ................... 9
Figure 3B H24 Mounting Instructions ................. 10
Figure 3C H36 Mounting Instructions ................. 11
Figure 3D H42-72 Mounting Instructions ............ 12
Figure 4 Electric Heat Clearance ...................... 13
Figure 5 Wall Mounting Instructions ................. 14
Figure 6 Wall Mounting Instructions ................. 14
Figure 7 Common Wall Mounting Installations ... 15
Figure 8 Fan Blade Setting .............................. 20
Figure 9A H***A Wiring Diagram – Top ............... 28
Figure 9B H***A Wiring Diagram – Bottom .......... 29
Figure 10 H***A Low Voltage Diagram for Unit and MV Connections ........................... 30
Tables
Table 1
Table 2
Table 3
Sequence of Operation ....................... 19
Fan Blade Dimension ......................... 20
Cooling Pressure ................................ 21
Table 4A Electrical Specifications H**A Series ... 22
Table 4B Electrical Specifications H**L Series ... 23
Table 5
Table 6
Table 7
Recommended Airflow ........................ 24
Indoor Blower Performance ................. 24
Max ESP of Operation Elec Heat Only .. 24
Table 8A H12 Electric Heat .............................. 24
Table 8B H24-72 Electric Heat ......................... 24
Table 9 Optional Accessories .......................... 25
Table 10 Vent and Control Options .................... 25
Table 11 Unit Low Voltage Terminal Connection
Chart – MV Series Controller ............... 26
Table 12 Unit Low Voltage Terminal Connection
Chart – Cooling/Heating Thermostat ..... 27
Manual 2100-647A
Page 2 of 30
GETTING OTHER INFORMATION AND PUBLICATIONS
These publications can help when installing the furnace. They can usually be found at the local library or purchased directly from the publisher. Be sure to consult the current edition of each standard.
National Electrical Code ......................ANSI/NFPA 70
For more information, contact these publishers:
ACCA Air Conditioning Contractors of America
1712 New Hampshire Ave. N.W.
Washington, DC 20009
Telephone: (202) 483-9370
Fax: (202) 234-4721
Standard for the Installation ..............ANSI/NFPA 90A of Air Conditioning and Ventilating Systems
Standard for Warm Air .......................ANSI/NFPA 90B
Heating and Air Conditioning Systems
ANSI American National Standards Institute
11 West Street, 13th Floor
New York, NY 10036
Telephone: (212) 642-4900
Fax: (212) 302-1286
Load Calculation for ......................... ACCA Manual J
Residential Winter and Summer Air Conditioning
Duct Design for Residential ............... ACCA Manual D
Winter and Summer Air Conditioning and Equipment
Selection
ASHRAE American Society of Heating, Refrigeration and Air Conditioning Engineers, Inc.
1791 Tullie Circle, N.E.
Atlanta, GA 30329-2305
Telephone: (404) 636-8400
Fax: (404) 321-5478
NFPA National Fire Protection Association
Batterymarch Park
P.O. Box 9101
Quincy, MA 02269-9901
Telephone: (800) 344-3555
Fax: (617) 984-7057
Manual 2100-647A
Page 3 of 30
WALL MOUNT GENERAL INFORMATION
AIR CONDITIONER WALL MOUNT MODEL NOMENCLATURE
H 42 A 4 – A 05
MODEL SERIES
REVISIONS
CAPACITY
12 – 1 Ton
24 – 2 Ton
36 – 3 Ton
42 – 3½ Ton
48 – 4 Ton
60 – 5 Ton
72 – 6 Ton
A – Right Hand Air Conditioner
L – Left Hand Air Conditioner
VOLTS & PHASE
A – 230/208/60/1
KW
Y P X X X J
CONTROL MODULES
(See Spec. Sheet)
COLOR OPTIONS
X – Beige (Standard)
1 – White
4 – Buckeye Gray
5 – Desert Brown
6 – Dark Bronze
A – Aluminum
S – Stainless Steel
COIL OPTIONS
X – Standard
1 – Phenolic Coated Evaporator
2 – Phenolic Coated Condenser
3 – Phenolic Coated Evaporator
and Condenser
OUTLET OPTIONS
X – Front (Standard)
VENTILATION OPTIONS
B – Blank-Off Plate (No Ventilation)
Y – 100% Economizer Temperature
Z – 100% Economizer Enthalpy
FILTER OPTIONS
P – 2 inch Pleated MERV 8
!
WARNING
Electrical shock hazard.
Have a properly trained individual perform these tasks.
Failure to do so could result in electric shock or death.
!
CAUTION
Cut hazard.
Wear gloves to avoid contact with sharp edges.
Failure to do so could result in personal injury.
SHIPPING DAMAGE
Upon receipt of equipment, the carton should be checked for external signs of shipping damage. If damage is found, the receiving party must contact the last carrier immediately, preferably in writing, requesting inspection by the carrier’s agent.
GENERAL
The equipment covered in this manual is to be installed by trained, experienced service and installation technicians.
The refrigerant system is completely assembled and charged. All internal wiring is complete.
The unit is designed for use with or without duct work.
Flanges are provided for attaching the supply and return ducts.
These instructions explain the recommended method to install the air cooled self-contained unit and the electrical wiring connections to the unit.
These instructions and any instructions packaged with any separate equipment required to make up the entire air conditioning system should be carefully read before beginning the installation. Note particularly “Starting
Procedure” and any tags and/or labels attached to the equipment.
While these instructions are intended as a general recommended guide, they do not supersede any national and/or local codes in any way. Authorities having jurisdiction should be consulted before the installation is made. See Page 3 for information on codes and standards.
Size of unit for a proposed installation should be based on heat loss calculation made according to methods of
Air Conditioning Contractors of America (ACCA). The air duct should be installed in accordance with the
Standards of the National Fire Protection Association for the Installation of Air Conditioning and Ventilating
Systems of Other Than Residence Type, NFPA No.
90A, and Residence Type Warm Air Heating and Air
Conditioning Systems, NFPA No. 90B. Where local regulations are at a variance with instructions, installer should adhere to local codes.
Manual 2100-647A
Page 4 of 30
DUCT WORK
All duct work, supply and return, must be properly sized for the design airflow requirement of the equipment. Air Conditioning Contractors of America
(ACCA) is an excellent guide to proper sizing. All duct work or portions thereof not in the conditioned space should be properly insulated in order to both conserve energy and prevent condensation or moisture damage.
Refer to Table 5 for maximum static pressure available for duct design.
Design the duct work according to methods given by the Air Conditioning Contractors of America (ACCA).
When duct runs through unheated spaces, it should be insulated with a minimum of one inch of insulation.
Use insulation with a vapor barrier on the outside of the insulation. Flexible joints should be used to connect the duct work to the equipment in order to keep the noise transmission to a minimum.
For the H Model Series 36-72, a 1/4" clearance to combustible material for the first 3' of duct attached to the outlet air frame is required. See Wall Mounting
Instructions and Figures 3A-D and Figure 4 for further details.
Ducts through the walls must be insulated and all joints taped or sealed to prevent air or moisture entering the wall cavity.
Some installations may not require any return air duct.
A metallic return air grille is required with installations not requiring a return air duct. The spacing between louvers on the grille shall not be larger than 5/8".
Any grille that meets with 5/8" louver criteria may be used. It is recommended that Bard Return Air
Grille Kit RG2W thru RG5W or RFG2W thru RFG5W be installed when no return duct is used. Contact distributor or factory for ordering information. If using a return air filter grille, filters must be of sufficient size to allow a maximum velocity of 400 fpm.
NOTE:
If no return air duct is used, applicable installation codes may limit this cabinet to installation only in a single story structure.
FILTERS
A 2" pleated MERV 8 is standard with each unit. The filter slides into position making it easy to service. This filter can be serviced from the outside by removing the filter access panel.
CONDENSATE DRAIN
A plastic drain hose extends from the drain pan at the top of the unit down to the unit base. There are openings in the unit base for the drain hose to pass through. In the event the drain hose is connected to a drain system of some type, it must be an open or vented type system to assure proper drainage.
Manual 2100-647A
Page 5 of 30
INSTALLATION
WALL MOUNTING INFORMATION
1. Two holes for the supply and return air openings must be cut through the wall as shown in Figures
3A-D on pages 9-12.
2. On wood frame walls, the wall construction must be strong and rigid enough to carry the weight of the unit without transmitting any unit vibration.
3. Concrete block walls must be thoroughly inspected to insure that they are capable of carrying the weight of the installed unit.
MOUNTING THE UNIT
1. These units are secured by wall mounting brackets which secure the unit to the outside wall surface at both sides. A bottom mounting bracket, attached to skid for shipping, is provided for ease of installation, but is not required.
2. The unit itself is suitable for 0 clearance, but the supply air duct flange and the first 3' of supply air duct require a minimum of 1/4" clearance to combustible material for Model Series H36, H42,
H48, H60 and H72. However, it is generally recommended that a 1" clearance is used for ease of installation and maintaining the required clearance to combustible material. See Figures
3A-D for details on opening sizes.
Minimum Clearances Required to
Combustible Materials
MODELS
SUPPLY AIR DUCT
FIRST 3'
H12A
H24A, H24L
0"
H36A, H36L
H42A, H42L
H48A, H48L
H60A, H60L
H72A, H72L
1/4"
CABINET
0"
0"
!
WARNING
Failure to provide the 1/4" clearance between the supply duct and a combustible surface for the first 3' of duct can result in fire causing damage, injury or death.
Clearances Required for Service Access and
Adequate Condenser Airflow
MODELS
LEFT
SIDE
RIGHT
SIDE
DISCHARGE
SIDE
H12A, H24A, H36A
H24L, H36L
15"
20"
20"
15"
10'
10'
H42A, H48A, H60A, H72A
H42L, H48L, H60L, H72L
20"
20"
20"
20"
10'
10'
NOTE:
For side-by-side installation of two H**A models there must be 20" between units. This can be reduced to 15" by using a H**L model (left side compressor and controls) for the left unit and H**A (right side compressor and controls) for right unit.
3. Locate and mark lag bolt locations and bottom mounting bracket location (see Figures 3A-D).
4. Mount bottom mounting bracket.
5. Hook top rain flashing, attached to front-right corner of supply flange for shipping, under back bend of top.
6. Position unit in opening and secure with fasteners sufficient for the application such as 5/16 lag bolts; use 7/8" diameter flat washers on the lag bolts.
7. Secure rain flashing to wall and caulk across entire length of top (see Figures 3A-D).
8. For additional mounting rigidity, the return air and supply air frames or collars can be drilled and screwed or welded to the structural wall itself
(depending upon wall construction). Be sure to observe required clearance if combustible wall.
9. On side-by-side installations, maintain a minimum of 20" clearance on right side to allow access to control panel and heat strips, and to allow proper airflow to the outdoor coil. Additional clearance may be required to meet local or national codes.
10. Care should be taken to ensure that the recirculation and obstruction of condenser discharge air does not occur. Recirculation of condenser discharge air can be from either a single unit or multiple units. Any object such as shrubbery, a building or other large object can cause obstructions to the condenser discharge air. Recirculation or reduced airflow caused by obstructions will result in reduced capacity, possible unit pressure safety lockouts and reduced unit service life.
For units with blow through condensers, it is recommended there be a minimum distance of 10' between the front of the unit and any barrier or 20' between the fronts of two opposing (facing) units.
Manual 2100-647A
Page 6 of 30
FIGURE 1
H12AA Unit Dimensions
32.00
30.13
17.00
5.00
5.00
10.00
22.25
TOP RAIN FLASHING
SHIPPING LOCATION
OPTIONAL
ELECTRICAL
ENTRANCE
25.750
2.50
BACK VIEW
DRAIN HOSE
31.06
19.72
BUILT-IN RAIN
HOOD 2° PITCH
HEATER & FILTER
ACCESS
VENTILATION
AIR
LOW VOLTAGE
ENTRANCE
14.63
1.50
48.00
ELECTRICAL
ENTRANCE
21.88
19.72
CONDENSER
AIR OUTLET
20.43
COND.
AIR
INLET
3.88
FRONT VIEW
CONDENSER AIRFLOW
IS BLOW THRU
RIGHT SIDE VIEW
MIS-3599
NOTE: Maintain a minimum of 20" clearance on right side to allow access to control panel and allow proper airflow to outdoor
condenser coil. Allow 15" on left side.
Manual 2100-647A
Page 7 of 30
FIGURE 2
Dimensions of Basic Unit for Architectural and Installation Requirements (Nominal)
MODEL
WIDTH
(W)
DEPTH
(D)
HEIGHT
(H)
SUPPLY RETURN
A B C B E F G I J K L M N O P Q R S T
H24A, L
33.300 17.125
74.563
7.88 19.88 11.88 19.88 35.00 10.88 29.75 20.56 30.75 32.06 33.25 31.00 2.63 34.13 26.06 10.55 4.19 12.00
9.00
H36A, L
38.200 17.125
74.563
7.88 27.88 13.88 27.88 40.00 10.88 29.75 17.93 30.75 32.75 33.25 31.00 2.75 39.13 26.75 9.14
4.19 12.00
9.00
H42A, L
H48A, L
H60A, L
H72A, L
42.075 22.432
42.075 22.432
84.875
93.000
9.88 29.88 15.88 29.88 43.88 13.56 31.66 30.00 32.68 26.94 34.69 32.43 3.37 43.00 23.88 10.00 1.44 16.00
1.88
9.88 29.88 15.88 29.88 43.88 13.56 37.00 30.00 40.81 35.06 42.81 40.56 3.37 43.00 31.00 10.00 1.44 16.00 10.00
All dimensions are in inches. Dimensional drawings are not to scale.
Built In
4° Pitch
D
E
O
H**A
RIGHT
UNIT
W
2.13
A
Supply Air Opening
.44
R
C. Breaker/
(Lockable)
I
Mounting
(Built In)
Top Rain
Flashing
B
S
S
5.88
F
Filter Access Panel 1
Ventilation Air
Economizer
Controls
Standard flush vent
C H
Return Air Opening
S
S
G
Condenser
Air Outlet
7"
Low Voltage
Cond.
Air
Inlet
J
K
L
M
P
S
T
Drain
N
Front View Side View
Q
Not used when EWM economizer is installed. Filter access is through the EWM hood.
Back View
MIS-3624
H**L
LEFT
UNIT
.44
E
O
Supply Air Opening
B
Built In
4° Pitch
D
Panel
C. Breaker/
Disconnect
Access Panel
W
R
S
S
Brackets
(Built In)
2.13
A
I
Shipping
Location non-Econ.
models
Economizer
(opposite side)
S
Return Air Opening
Optional
Electrical
C
Filter Access Panel
1
Ventilation Air
S
H
S
P
M
L K
J
Cond.
Air
Inlet
7"
T
High Voltage
Electrical
Drain
Back View N Side View
Q
Not used when EWM economizer is installed. Filter access is through the EWM hood.
Manual 2100-647A
Page 8 of 30
Front View
MIS-3625
5.88
F
G
FIGURE 3A
H12AA Mounting Instructions
SEAL WITH BEAD OF CAULKING
ALONG ENTIRE LENGTH OF TOP.
TOP
WALL
RAIN FLASHING
SUPPLIED
FOAM AIR SEAL
WALL STRUCTURE
SUPPLY AIR DUCT
RETURN AIR
OPENING
2.500
7.031
17.000
7.031
5.000
10.000
5.000
19.719
19.719
6.969
17.000
WALL OPENING AND HOLE
LOCATION VIEW
NOTE:
IT IS RECOMMENDED THAT A BEAD OF SILICONE
CAULKING BE PLACED BEHIND THE SIDE MOUNTING
FLANGES AND UNDER TOP FLASHING AT TIME OF
INSTALLATION.
MIS-3600
Manual 2100-647A
Page 9 of 30
Manual 2100-647A
Page 10 of 30
1 16
1 16
13 16
1 2
1 8
4" Ty
7 8
4" Ty
7 8
11 16
1 8
4" Ty
7 8
7 8
4" Ty
7 8
1 16
11 16
Manual 2100-647A
Page 11 of 30
Manual 2100-647A
Page 12 of 30
1 2
7 8
1 8
4" Ty
1 8
1 2
4" Ty
1 2
7 8
FIGURE 4
Electric Heat Clearance
NOTE:
SIDE SECTION VIEW OF SUPPLY AIR
DUCT FOR WALL MOUNTED UNIT SHOWING 1/4"
CLEARANCE TO COMBUSTIBLE SURFACES.
!
WARNING
A
minimum
of 1/4" clearance must be maintained between the supply air duct and combustible materials. This is required for the first 3' of ducting.
It is important to insure that the 1/4" minimum spacing is maintained at all points.
Failure to do this could result in overheating the combustible material and may result in a fire causing damage, injury or death.
Manual 2100-647A
Page 13 of 30
SUPPLY AIR
OPENING
RETURN AIR
OPENING
FIGURE 5
Wall Mounting Instructions
RETURN AIR
OPENING
FACTORY SUPPLIED
RAIN FLASHING.
MOUNT ON UNIT
BEFORE INSTALLATION
WALL STRUCTURE
SUPPLY AIR
DUCT
RETURN AIR
OPENING
CONCRETE BLOCK WALL INSTALLATION
MIS-549 B
Manual 2100-647A
Page 14 of 30
WOOD OR STEEL SIDING
WOOD FRAME WALL INSTALLATION
BOTTOM MOUNTING
INSTALLING UNIT.
SIDE VIEW
MIS-548 A
FRAMING MATERIAL
2 x 4'S, 2 x 6'S &/OR
STRUCTURAL STEEL
FIGURE 6
Wall Mounting Instructions
ATTACH TO TOP
PLATE OF WALL
1.000" CLEARANCE
ALL AROUND DUCT
INTERIOR FINISHED WALL
OVER FRAME
1.000" CLEARANCE
ALL AROUND DUCT
EXTERIOR FINISH WALL
OVER FRAME
ATTACH TO BOTTOM
PLATE OF WALL
SEE UNIT DIMENSIONS, FIGURE 2,
FOR ACTUAL DIMENSIONS.
E + 1.000
B
1.000
SUPPLY DUCT
OPENING
A
I
RETURN DUCT
OPENING
C
K
2 x 6
C
L
THIS STRUCTURAL MEMBER
LOCATED TO MATCH STUD
SPACING FOR REST OF WALL.
A SECOND MEMBER MAY BE
REQUIRED FOR SOME WALLS.
RAIN
FLASHING
OUTSIDE
WALL
FIGURE 7
Common Wall Mounting Installations
RAFTERS
FINISHED CEILING SURFACE
SUPPLY AIR DUCT
W/ GRILLE
RETURN AIR
OPENING W/ GRILLE
SUPPLY DUCT MAY BE LOCATED IN AN ATTIC
OR BELOW CEILING RAFTERS AS SHOWN
RAFTERS
SUPPLY AIR DUCT
FINISHED CEILING SURFACE
RETURN AIR
OPENING W/ GRILLE
OUTSIDE
WALL
FREE AIR FLOW
NO DUCT
DUCTED SUPPLY
RETURN AT UNIT
SUPPLY DUCT MAYBE LOCATED IN AN ATTIC
WIRING – MAIN POWER
Refer to the unit rating plate for wire sizing information and maximum fuse or circuit breaker size. Each outdoor unit is marked with a “Minimum Circuit Ampacity”. This means that the field wiring used must be sized to carry that amount of current. Depending on the installed KW of electric heat, there may be two field power circuits
CEILING SURFACE required. If this is the case, the unit serial plate will so indicate. All models are suitable only for connection with copper wire. Each unit and/or wiring diagram will be marked “Use Copper Conductors Only”. These
SPACE
instructions
must be
adhered to. Refer to the National
Electrical Code (NEC) for complete current carrying capacity data on the various insulation grades of wiring material. All wiring must conform to NEC and all local codes.
WALL
FALSE WALL INSTALLATION
used heater sizes. Also shown are the number of field power circuits required for the various models with heaters.
The unit rating plate lists a “Maximum Time Delay
Relay Fuse” or circuit breaker that is to be used with
FLASHING
SUPPLY DUCT MAYBE LOCATED IN AN ATTIC
OR BELOW CEILING RAFTERS AS SHOWN the equipment. The correct size must be used for proper circuit protection and also to assure that there will be no nuisance tripping due to the momentary high starting current of the compressor motor.
LOWERED
CEILING
The disconnect access door on this unit may be locked to prevent unauthorized access to the disconnect. To convert for the locking capability, bend the tab located in the bottom left-hand corner of the disconnect
WALL
SLEEVE
See “Start Up” section beginning on page 17 for important information on three phase scroll compressor start ups.
RETURN AIR
FINISHED CEILING
SURFACE opening under the disconnect access panel straight out. This tab will now line up with the slot in the door.
When shut, a padlock may be placed through the hole in the tab preventing entry.
RAISED FLOOR
RETURN AIR
GRILLE
CLOSET INSTALLATION
See Tables 4A and 4B (pages 22 and 23) for electrical specifications.
MIS-550 C
Manual 2100-647A
Page 15 of 30
WIRING – LOW VOLTAGE WIRING
Low Voltage Connection
These units use a 24-volt AC low voltage circuit. Tables
11 and 12 on pages 26 and 27 show the low voltage connections for units operated with the MV Series controller or connected directly to a cooling/heating thermostat.
All models are equipped with dual primary voltage transformers. All equipment leaves the factory wired on 240V tap. For 208V operation, reconnect from
240V to 208V tap. The acceptable operating voltage range for the 240 and 208V taps are:
TAP RANGE
240
208
253 – 216
220 – 187
NOTE:
The voltage should be measured at the field power connection point in the unit and while the unit is operating at full load (maximum amperage operating condition).
DIRTY FILTER SWITCH AND RELAY
These units include an adjustable dirty filter indicator switch. This switch if connected to normally closed contacts on the filter relay wired to terminals 10 and
11 on the low voltage terminal block.
Filter Replacement Procedure
For units
not equipped
with economizer:
1. Turn off unit power.
2. Remove filter door.
3. Replace filter.
4. Press Reset button.
5. Verify filter light is off.
6. Replace filter door.
7. Turn on unit power.
For units
equipped
with economizer:
1. Turn off unit power.
2. Remove hood cover.
3. Remove mist eliminator. Inspect and clean if necessary.
4. Remove filter door.
5. Remove and replace filter.
6. Replace filter door.
7. Replace mist eliminator.
8. Replace hood cover.
9. Turn on unit power.
Manual 2100-647A
Page 16 of 30
Filter Switch Adjustment
1. Turn off unit power.
2. Remove upper front door. Front screws on unit top can be removed for ease of removing upper front door.
3. Locate filter switch on control panel side next to blower assembly.
4. Remove single phillips head screw on front of cover. Remove cover.
5. Set pressure by adjusting knob. Do not adjust knob drastically to avoid nuisance alarm signalw or non-functionality.
6. Replace cover.
7. Replace upper front door.
8. Turn on unit power.
ECONOMIZER FAIL TIME DELAY RELAY
NOTE:
Applies only to units with economizers.
These units employ a time delay relay to open the nomally closed contacts at terminals 12 and 13 on the low voltage terminal block. This will activate an alarm signal on the MV Series controller. The time delay is set to 500 seconds as a factory default. Avoid adjustment to settings lower than 180 seconds.
Timer to be set here
(500 seconds)
MIS-3054
MIS-3054
START UP
THESE UNITS REQUIRE R-410A
REFRIGERANT AND POLYOL ESTER OIL.
GENERAL
1. Use separate service equipment to avoid cross contamination of oil and refrigerants.
2. Use recovery equipment rated for R-410A refrigerant.
3. Use manifold gauges rated for R-410A (800 psi/250 psi low).
4. R-410A is a binary blend of HFC-32 and HFC-125.
5. R-410A is nearly azeotropic—similar to R-22 and
R-12. Although nearly azeotropic, charge with liquid refrigerant.
6. R-410A operates at 40-70% higher pressure than
R-22, and systems designed for R-22 cannot withstand this higher pressure.
7. R-410A has an ozone depletion potential of zero, but must be reclaimed due to its global warming potential.
8. R-410A compressors use Polyol Ester oil.
9. Polyol Ester oil is hygroscopic; it will rapidly absorb moisture and strongly hold this moisture in the oil.
10. A liquid line dryer must be used; even a deep vacuum will not separate moisture from the oil.
11. Limit atmospheric exposure to 15 minutes.
12. If compressor removal is necessary, always plug compressor immediately after removal. Purge with small amount of nitrogen when inserting plugs.
TOPPING OFF SYSTEM CHARGE
If a leak has occurred in the system, Bard
Manufacturing
recommends
reclaiming, evacuating
(see criteria above) and charging to the nameplate charge. If done correctly, topping off the system charge can be done without problems.
With R-410A, there are no significant changes in the refrigerant composition during multiple leaks and recharges. R-410A refrigerant is close to being an azeotropic blend (it behaves like a pure compound or single component refrigerant). The remaining refrigerant charge in the system may be used after leaks have occurred and then “top-off” the charge by utilizing the pressure charts on the inner control panel cover as a guideline.
REMEMBER:
When adding R-410A refrigerant, it must come out of the charging cylinder/tank as a liquid to avoid any fractionation, and to insure optimal system performance. Refer to instructions for the cylinder that is being utilized for proper method of liquid extraction.
!
WARNING
Failure to conform to these practices could lead to damage, injury or death.
SAFETY PRACTICES
1. Never mix R-410A with other refrigerants.
2. Alwasys use gloves and safety glasses. Polyol
Ester oils can be irritating to the skin, and liquid refrigerant will freeze the skin.
3. Never use air and R-410A to leak check; the mixture may become flammable.
4. Do not inhale R-410A; the vapor attacks the nervous system, creating dizziness, loss of coordination and slurred speech. Cardiac irregularities, unconsciousness and ultimate death can result from breathing this concentration.
5. Do not burn R-410A. This decomposition produces hazardous vapors. Evacuate the area if exposed.
6. Use only cylinders rated DOT4BA/4BW 400.
7. Never fill cylinders over 80% of total capacity.
8. Store cylinders in a cool area, out of direct sunlight.
9. Never heat cylinders above 125°F.
10. Never trap liquid R-410A in manifold sets, gauge lines or cylinders. R-410A expands significantly at warmer temperatures. Once a cylinder or line is full of liquid, any further rise in temperature will cause it to burst.
IMPORTANT INSTALLER NOTE
For improved start up performance wash the indoor coil with dishwashing detergent.
Manual 2100-647A
Page 17 of 30
HIGH PRESSURE AND LOW PRESSURE
SWITCHES
All H**A/H**L wall mounted air conditioner series models are supplied with a remote reset for the high and low pressure switches. The first time the high or low pressure switches are tripped, they will reset automatically. If tripped a second time, reset the switches by turning the thermostat off, then back on again, resetting the compressor control module.
CONDENSER FAN OPERATION
NOTE: Certain models may be equipped with a low ambient control (LAC), and if so equipped the condenser fan motor may have a delayed start until system refrigerant operating pressure builds up.
After starting, the fan motor may or may not cycle depending upon ambient conditions. This is normal operation.
The condenser fan motor on 230/208 volt, one and three phase, 60 HZ units is a two-speed motor that comes factory wired on high speed for peak performance. If ambient conditions permit, it can be reconnected to low speed (red wire) for lower sound level. See unit wiring diagram.
SERVICE HINTS
1. Caution owner/operator to maintain clean air filters at all times and to not needlessly close off supply and return air registers. This reduces airflow through the system, which shortens equipment service life as well as increasing operating costs.
2. Check all power fuses or circuit breakers to be sure they are the correct rating.
3. Periodic cleaning of the outdoor coil to permit full and unrestricted airflow circulation is essential.
SEQUENCE OF OPERATION
COOLING – 24VAC from MV controller at terminal 4 (Y) pulls in compressor contactor, starting the compressor and outdoor motor. (See Note under Condenser Fan
Operation if equipped with low ambient control.)
Terminal 9 (G) indoor motor circuit is energized by the MV controller on any call for cooling operation or can be energized by manual fan switch on subbase for constant air circulation. On a call for heating from the
MV controller makes at the relay board pulling in heat contact for the strip heat and blower operation. On a call for second stage heat, R-W2 makes bringing on second heat contactor, if so equipped. See Table 1 on following page.
COMPRESSOR CONTROL MODULE
The compressor control module (CCM) is standard on all models covered by this manual. The compressor control module is an anti-short cycle/lockout timer with high and low pressure switch monitoring and alarm relay output.
Adjustable Delay-on-Make and Delay-on-Break Timer
On initial power up and any time power is interrupted to the unit, the delay-on-make period begins, which is the time set on the potentiometer (delay-on-break time) plus 10% of the delay-on-break setting. When the delay-on-make period is complete and the high pressure switch and low pressure switch are closed, the compressor contactor is energized. Upon shutdown
(end of the call for cooling), the delay-on-break timer starts and prevents restart (next call for cooling) until the delay-on-break period has expired.
During routine operation of the unit with no power interruptions, the compressor will operate on demand with no delay.
High Pressure Switch and Lockout Sequence
If the high pressure switch opens, the compressor contactor will de-energize immediately. The lockout timer will go into a
soft lockout
and stay in soft lockout until the high pressure switch closes and the delay-onbreak time has expired. If the high pressure switch opens again in this same operating cycle, the unit will go into
manual lockout
condition and the alarm relay circuit will energize. Recycling the wall thermostat or main power resets the manual lockout.
Low Pressure Switch, Bypass and Lockout Sequence
If the low pressure switch opens for more than 120 seconds, the compressor contactor will de-energize and go into a soft lockout. Regardless the state of the low pressure switch, the contactor will re-energize after the delay-on-make time delay has expired. If the low pressure switch remains open, or opens again for longer than 120 seconds, the unit will go into manual lockout condition and the alarm relay circuit will energize.
Recycling the wall thermostat or main power resets the manual lockout.
Alarm Relay Output
Alarm terminal is output connection for applications where alarm relay is employed. This terminal is powered whenever the compressor is locked out due to
HPC or LPC sequences as described.
NOTE:
Both high and low pressure switch controls are inherently automatic reset devices. The high pressure switch and low pressure switch cut out and cut in settings are fixed by specific air conditioner unit model. The lockout features, both soft and manual, are a function of the compressor control module.
Manual 2100-647A
Page 18 of 30
Adjustments
Adjustable Delay-on-Make and Delay-on-Break Timer
The potentiometer is used to select delay-on-break time from 30 seconds to 5 minutes. Delay-on-make (DOM) timing on power up and after power interruptions is equal to 2 minutes plus 10% of delay-on-break (DOB) setting:
0.5 minute (30 seconds) DOB = 123 second DOM
1.0 minute (60 seconds) DOB = 126 second DOM
2.0 minute (120 seconds) DOB = 132 second DOM
3.0 minute (180 seconds) DOB = 138 second DOM
4.0 minute (240 seconds) DOB = 144 second DOM
5.0 minute (300 seconds) DOB = 150 second DOM
During routine operation of the unit with no power interruptions, the compressor will operate on demand with no delay.
Typical Settings for Dual Unit Installation:
Unit 1: DOB set at 2 minutes and DOM is 132 seconds
Unit 2: DOB set at 4 minutes and DOM is 144 seconds
PRESSURE SERVICE PORTS
High and low pressure service ports are installed on all units so that the system operating pressures can be observed. A pressure table can be found on page
21 covering all models. It is imperative to match the correct pressure table to the unit by model number.
TABLE 1
Sequence of Operation
9
10
11
12
13
14
15
16
17
18
7
8
5
6
3
4
1
2
Terminal
19
Description
Compressor on Output Signal from Jade to MV
24VAC HOT
from Terminal 2 Connected to Unit Transformer
24VAC COMMON
from Unit Transformer to MV
Unit Compressor Operation
Close Damper Input (Close Blade 100%)
Electric Heat On Operation, Stage 1 and 2
1st Stage Cooling Input, 1st Stage Cooling Signal to Jade
2nd Stage Cooling Input, 2nd Stage Cooling Signal to Jade
Blower Operation (Indoor Blower On)
Filter Switch Normally Closed Dry Contacts
Filter Switch Normally Closed Dry Contacts
Blade Switch Delay Relay Normally Closed Dry Contacts
Blade Switch Delay Relay Normally Closed Dry Contacts
Occupied Signal Input, Econ Emergency Open (Open Blade 100%)
Econ Open Output (
6V HOT, 24V HOT
after Blade Open 100% and delay)
Alarm Relay Common Dry Contact
Alarm Relay Normally Open Dry Contact
Alarm Relay Normally Closed Dry Contact
24VAC HOT
to Terminal 2 from Unit Transformer Through Smoke Alarm Jumper
Wire*
Use
Economizer Only
24V HOT
24V COMMON
Cooling Operation
Economizer Only
Heating Operation
Economizer Only
Economizer Only
Blower Operation
Alarm Signal
Alarm Signal
Economizer Only
Economizer Only
Economizer Only
Economizer Only
Comp Alarm Signal
Comp Alarm Signal
Comp Alarm Signal
24V HOT
"Y1"
"Y2"
"G"
"4"
"5"
"8"
"9"
Series "2"
Reference
"A"
"R"
"C"
"Y"
"F"
"W1"
"E"
"10"
"3"
"2"
"1"
"RT"
20 2nd Stage Heating On Operated Through Jumper to Terminal 6
Heating Operation,
2nd Stage
"W2'
21
Blade Switch Terminal
24V HOT
When Blade is Open, Sends Signal from Switch to Delay Relay
Economizer Only "7"
* Replace jumper wire with smoke alarm connections to interrupt 24VAC unit power if smoke alarm is used in shelter. Jumper can also be removed to break 24VAC power to unit.
Manual 2100-647A
Page 19 of 30
SERVICE
FAN BLADE SETTING DIMENSIONS
The correct fan blade setting for proper air delivery across the outdoor coil is shown in Figure 8. Refer to
Table 2 for unit specific dimension.
Any service work requiring removal or adjustment in the fan and/or motor area will require that the dimensions below be checked and blade adjusted in or out on the motor shaft accordingly.
FIGURE 8
Fan Blade Setting
AIRFLOW
MIS-1724
"A"
REMOVAL OF FAN SHROUD
1. Disconnect all power to the unit.
2. Remove the screws holding both grilles, one on each side of unit, and remove grilles.
3. Remove nine (9) screws holding fan shroud to condenser and bottom.
4. Unwire condenser fan motor.
5. Slide complete motor, fan blade and shroud assembly out the left side of the unit.
6. Service motor/fan as needed.
7. Reverse steps to reinstall
.
R-410A REFRIGERANT CHARGE
This unit was charged at the factory with the quantity of refrigerant listed on the serial plate. AHRI capacity and efficiency ratings were determined by testing with this refrigerant charge quantity.
The pressure table on the following page shows nominal pressures for the units. Since many installation specific situations can affect the pressure readings, this information should only be used by certified technicians as a guide for evaluating proper system performance. They shall not be used to adjust charge. If charge is in doubt, reclaim, evacuate and recharge the unit to the serial plate charge.
H12
H24
H36
H42
H48
H60
H72
TABLE 2
Fan Blade Dimension
Model
Dimension
A
2.25"
1.00"
1.25"
1.75"
Manual 2100-647A
Page 20 of 30
TABLE 3
Cooling Pressure
Air Temperature Entering Outdoor Coil °F
Model
Return Air Temp
(DB/WB)
Pressure 75 80 85 90 95 100 105 110 115 120 125
H12A
H24A/L
H36A/L
H42A/L
H48A/L
H60A/L
H72A/L
75/62
80/67
85/72
75/62
80/67
85/72
75/62
80/67
85/72
75/62
80/67
85/72
75/62
80/67
85/72
75/62
80/67
85/72
75/62
80/67
85/72
Low Side
High Side
Low Side
High Side
Low Side
High Side
Low Side
High Side
Low Side
High Side
Low Side
High Side
Low Side
High Side
Low Side
High Side
Low Side
High Side
Low Side
High Side
Low Side
High Side
Low Side
High Side
Low Side
High Side
Low Side
High Side
Low Side
High Side
Low Side
High Side
Low Side
High Side
Low Side
High Side
Low Side
High Side
Low Side
High Side
Low Side
High Side
125
296
134
304
137
333
117
323
137
343
120
330
128
338
132
350
125
331
129
343
123
323
132
331
139
315
123
314
132
322
127
344
136
353
141
365
117
332
125
340
129
352
129
316
138
324
138
355
120
346
139
367
122
353
131
362
136
375
128
355
132
367
125
346
134
355
143
335
124
334
133
343
129
362
138
371
143
384
119
353
127
362
131
375
132
336
141
345
140
377
122
370
142
393
125
377
134
387
139
401
130
379
135
392
128
371
137
380
146
357
126
355
135
364
131
380
140
390
145
404
121
376
129
386
134
400
134
359
143
368
142
401
124
394
144
419
127
402
136
412
141
426
133
404
138
418
130
395
139
405
148
381
128
377
137
387
134
401
143
411
148
425
122
402
131
412
136
426
137
381
146
391
143
425
127
419
146
447
130
428
139
439
144
454
136
430
141
445
132
421
141
432
151
405
129
401
138
411
136
421
145
432
150
447
124
427
133
438
138
453
139
405
149
415
145
451
129
446
149
474
132
454
141
466
146
482
138
457
143
473
135
447
144
458
154
430
131
425
140
436
137
444
147
455
152
471
126
454
135
466
140
482
141
429
151
440
147
479
131
473
151
503
134
482
143
494
148
511
140
485
145
502
137
474
146
486
156
455
133
451
142
463
140
467
150
479
155
496
128
483
137
495
142
512
144
454
154
466
149
508
134
500
153
532
136
510
145
523
150
541
143
513
148
531
138
501
148
514
159
482
135
479
144
491
142
492
152
505
157
523
130
512
139
525
144
543
146
481
156
493
151
538
136
528
155
561
137
540
147
554
152
573
145
542
150
561
140
528
150
542
161
510
137
507
146
520
145
518
155
531
160
550
132
542
141
556
146
575
148
508
158
521
154
569
137
558
157
592
139
570
149
585
154
605
147
572
152
592
142
558
152
572
164
539
139
536
149
550
148
545
158
559
164
579
134
574
143
589
148
610
Low side pressure ± 4 PSIG
High side pressure ± 10 PSIG
Tables are based upon rated CFM (airflow) across the evaporator coil. If there is any doubt as to correct operating charge being in the system, the charge should be removed, system evacuated and recharged to serial plate charge weight.
NOTE:
Pressure table based on high speed condenser fan operation. If condensing pressures appear elevated, check condenser fan wiring. See “Condenser Fan Operation”.
150
537
160
551
156
602
138
587
159
623
141
601
151
616
156
638
148
602
153
623
144
587
154
602
167
570
141
567
151
582
151
573
161
588
167
609
136
607
145
623
150
645
Manual 2100-647A
Page 21 of 30
TABLE 4A
Electrical Specifications H***A Series
MODEL
Rated Volts
& Phase
No. Field
Power
Circuits
Minimum
Circuit
Ampacity
Single Circuit
Maximum
External
Fuse or
Circuit
Breaker
Field
Power
Wire
Size
Ground
Wire
Minimum
Circuit
Ampacity
Ckt.
A
Ckt.
B
Ckt.
C
H12AA-A0Z
A03
A05
230/208-1
H24AA-A00,
A0Z
A04
A05
A08
A10
230/208-1
H36AA-A00*,
A0Z*
A05*
A08
A10*
A15
230/208-1
H42AA-A00,
A0Z
A05
A10
A15
A20
230/208-1
H48AA-A00,
A0Z
A05
A10
A15
A20
230/208-1
H60AA-A00,
A0Z
A05
A10
A15
A20
230/208-1
H72AA-A00,
A0Z
A05
A10
A15
A20
230/208-1
1
1
1
1
1
1
1
1
1
1
1
1
1 or 2
1
1
1
1 or 2
1 or 2
1
1
1
1 or 2
1 or 2
1
1
1
1 or 2
1 or 2
1
1
1
1 or 2
1 or 3
9
20
27
21
25
30
46
56
29
32
47
58
84
32
32
58
84
110
34
34
58
84
110
38
38
60
86
112
58
58
62
88
114
15
20
30
30
30
30
50
60
35
35
50
60
90
50
50
60
90
125
50
50
60
90
125
60
60
60
90
125
60
60
70
90
125
14
12
10
10
10
10
8
6
8
8
8
6
4
8
8
6
4
2
8
8
6
4
2
8
8
6
3
2
6
6
6
3
2
14
12
10
10
10
10
10
10
10
10
10
10
8
10
10
10
8
6
10
10
10
8
6
10
10
10
8
6
10
10
8
8
6
58
58
58
58
58
60
60
58
58
58
26
26
52
26
52
26
52
26
52
52 52
60
60
60
60
60
60
60
60
60
60
30
30
60
30
60
30
60
30
60
Multiple Circuit
Maximum
External Fuse or
Circuit Breaker
Ckt.
A
Ckt.
B
Ckt.
C
60 60
Field Power
Wire Size
Ckt.
A
6
6
6
6
6
6
6
6
6
6
Wire Size
Ckt.
B
Ckt.
C
Ckt.
A
10
10
6
10
6
10
6
10
6
6 6
10
10
10
10
10
10
10
10
10
10
Ground
Ckt.
B
10
10
10
10
10
10
10
10
10
Ckt.
C
10 10
These “Minimum Circuit Ampacity” values are to be used for sizing the field power conductors. Refer to the National Electrical code (latest version), Article 310 for power conductor sizing.
Maximum size of the time delay fuse or circuit breaker for protection of field wiring conductors.
Based on 75°C copper wire. All wiring must conform to the National Electrical Code and all local codes.
* Top outlet supply option is available only factory installed and only on the selected models.
CAUTION:
When more than one field power circuit is run through one conduit, the conductors must be derated. Pay special attention to Note 8 of Table 310 regarding Ampacity Adjustment Factors when more than three (3) current carrying conductors are in a raceway.
IMPORTANT:
While this electrical data is presented as a guide, it is important to electrically connect properly sized fuses and conductor wires in accordance with the National Electrical Code and all local codes.
Manual 2100-647A
Page 22 of 30
MODEL
TABLE 4B
Electrical Specifications H***L Series
Single Circuit
Rated Volts
& Phase
No. Field
Power
Circuits
Minimum
Circuit
Ampacity
Maximum
External
Fuse or
Circuit
Breaker
Field
Power
Wire
Size
Ground
Wire
Minimum
Circuit
Ampacity
Ckt.
A
Ckt.
B
Dual Circuit
Maximum
External Fuse or
Circuit Breaker
Field Power
Wire Size
Ckt.
A
Ckt.
B
Ckt.
A
Ckt.
B
H24LA-A00,
A0Z
A05
A08
A10
H36LA-A00,
A0Z
A05
A10
A15
H42LA-A00,
A0Z
A05
A10
A15
H48LA-A00,
A0Z
A05
A10
A15
230/208-1
230/208-1
230/208-1
230/208-1
H60LA-A00,
A0Z
A05
A10
A15
230/208-1
H72LA-A00,
A0Z
A05
A10
A15
230/208-1
1
1
1
1
1
1
1
1 or 2
1
1
1
1 or 2
1
1
1
1 or 2
1
1
1
1 or 2
1
1
1
1 or 2
34
34
58
84
29
32
58
84
58
58
62
88
38
38
60
86
32
32
58
84
21
30
46
56
50
50
60
90
35
35
60
90
60
60
70
90
60
60
60
90
50
50
60
90
30
30
50
60
8
8
6
4
6
4
8
8
6
6
6
3
8
8
6
3
6
4
8
8
10
10
8
6
10
10
10
8
10
10
10
8
10
10
8
8
10
10
10
8
10
10
10
8
10
10
10
10
58
58
58
60
58
58
26
26
26
26
26
52
60
60
60
60
60
60
30
30
30
30
30
60
6
6
6
6
6
6
10
10
10
10
10
6
Ground
Wire Size
Ckt.
A
Ckt.
B
10
10
10
10
10
10
10
10
10
10
10
10
These “Minimum Circuit Ampacity” values are to be used for sizing the field power conductors. Refer to the National Electrical code (latest version), Article 310 for power conductor sizing.
Maximum size of the time delay fuse or circuit breaker for protection of field wiring conductors.
Based on 75°C copper wire. All wiring must conform to the National Electrical Code and all local codes.
* Top outlet supply option is available only factory installed and only on the selected models.
CAUTION:
When more than one field power circuit is run through one conduit, the conductors must be derated. Pay special attention to Note 8 of Table 310 regarding Ampacity Adjustment Factors when more than three (3) current carrying conductors are in a raceway.
IMPORTANT:
While this electrical data is presented as a guide, it is important to electrically connect properly sized fuses and conductor wires in accordance with the National Electrical Code and all local codes.
Manual 2100-647A
Page 23 of 30
Model
Outlet
Speed
-A0Z
-A03
-A04
-A05
-A08
-A10
-A15
-A20
TABLE 5
Recommended Airflow
Model
H12A
H24A, H24L
H36A, H36L
H42A, H42L
H48A, H48L
H60A, H60L
H72A, H72L
Nominal
Rated
CFM *
400
800
1100
1350
1550
1800
1900
Nominal
Rated
ESP *
.20
.30
.30
.40
.35
.30
.25
* Rated CFM and ESP on factory speed connection.
Recommended
Airflow Range
360 - 530
700 - 950
1000 - 1300
1250 - 1600
1450 - 1750
1700 - 2000
1800 - 2100
Factory Speed
Connection
Single
Single
High
Low
High
High
Medium
Speed
ESP
(In. H
2
0)
0.0
0.1
0.2
0.3
0.4
0.5
TABLE 6
Indoor Blower Performance
H12
Single
Dry
Coil
Wet
Coil
H24
Single
Dry
Coil
High
Wet
Coil
Dry
Coil
H36
Low High
H42
Low High
H48
Low
Wet
Coil
Dry
Coil
Wet
Coil
Dry
Coil
Wet
Coil
Dry
Coil
Wet
Coil
Dry
Coil
Wet
Coil
Dry
Coil
High
Wet
Coil
Dry
Coil
H60
Low
Wet
Coil
Dry
Coil
High
H72
Medium Low
Wet
Coil
Dry
Coil
Wet
Coil
Dry
Coil
Wet
Coil
Dry
Coil
Wet
Coil
530 500 1010 975 1400 1310 965 955 1980 1940 1800 1705 2000 1940 1750 1700 2105 2010 1540 1460 2255 2155 2075 2015 1995 1930
475 450 960 925 1340 1260 940 930 1905 1880 1700 1640 1910 1865 1675 1615 2045 1960 1480 1395 2185 2095 2010 1965 1950 1870
425 400 905 870 1265 1185 905 890 1820 1760 1615 1565 1820 1770 1600 1540 1970 1885 1400 1315 2115 2035 1960 1915 1885 1825
375 360 835 800 1180 1100 860 850 1735 1665 1530 1450 1720 1605 1500 1425 1895 1800 1300 1220 2050 1970 1915 1865 1835 1785
315 300 750 720 1080 1010 800 785 1615 1565 1425 1350 1575 1500 1375 1320 1800 1700 1220 1150 1985 1920 1860 1815 1780 1720
N/A N/A 640 610 970 895 705 680 1510 1380 1100 1000 1420 1190 1075 1030 1705 1605 1110 1070 1925 1855 1810 1765 1725 1615
H12A
FRONT
Single
.35
.35
.35
H24A/L
FRONT
Single
.50
.50
.50
TABLE 7
Maximum ESP of Operation
Electric Heat Only
High
.50
FRONT
Low
.50
H36A/L
High
.50
.50
.50
.50
.50
.40
.50
.50
.45
.35
.50
TOP
Low
.50
.45
.35
.50
.50
.50
.50
H42A/L, H48A/L
FRONT
High
.50
Low
.50
.50
.50
.50
.45
H60A/L, H72A/L
FRONT
High
.50
Low
.50
.50
.50
.50
.50
.50
.50
.50
.40
Models
(KW)
3
5
TABLE 8A
H12A Electric Heat
Amps
240V-1
BTUH
15.0
20.8
12760
17540
Amps
208V-1
BTUH
13.0
18.1
9705
13275
Models
(KW)
10
15
20
3
4
5
8
TABLE 8B
H24-72A/L Electric Heat
Amps
240V-1
BTUH
15.0
16.7
20.8
33.3
12760
13650
17540
27300
41.6
62.5
83.2
34130
51250
68260
Amps
208V-1
BTUH
13.0
14.4
18.1
28.8
9705
10240
13275
20475
36.2
54.0
72.1
25600
38400
51200
Manual 2100-647A
Page 24 of 30
TABLE 9
Optional Accessories
Right Hand Units Left Hand Units
Heater Kits
Circuit Breakers
(WMCB)
&
Pull Disconnects
(WMPD)
901147-A03
901147-A05
EHWA02-A05B
EHW02A-A08B
EHWA02A-A10B
EHWA24-A04B
EHWA03-A05B
EHWA03-A08B
EHWA03-A10B
EHWA03-A15B
EHW4TA-A05
EHWA05-A10B
EHWA05-A15B
EHWA05-A20B
EHW5TA-A05
EHW72A-A10B
EHW72A-A15B
EHW72A-A20B
WMCB-03A
WMCB-05A
WMCB-08A
WMCB-09A
X
X
X
X
X
X
X
X
X
X
X
X
X X
X X X
X X X
X X X
X X
X
X
X
X X
X
X
TABLE 10
Vent and Control Options
Heater Kits
Circuit Breakers
(WMCB)
&
Pull Disconnects
(WMPD)
EHWA02A-A05LB X
EHW02A-A08LB X
EHWA02-A10LB X
EHWA03-A05LB
EHWA03-A10LB
EHWA03-A15LB
EHW4TA-A05L
EHWA05-A10LB
EHWA05-A15LB
EHW6TA-A05L
EHW72A-A10LB
EHW72A-A15LB
WMCB-03A
WMCB-05A
WMCB-08A
WMCB-09A
X
X
X
X
X
X X X
X X X
X X X
X X
X X
X
X
X
Part Number
CMC-14
CMC-15
CMC-23
CMC-24
CMC-28
BOP-1A
BOP-2
EWM1-E
EWM1-T
EWM2-E
EWM2-T
BOP-3
EWM3-E
EWM3-T
BOP-5
EWM5-E
EWM5-T
Description
ODT
Start Kit (230V 1-Phase)
DDC
DDC
LAC
Blank Off Plate
Economizer - Bldg. Equipment, Enthalpy
Economizer - Bldg. Equipment, DB Temp.
Economizer - Bldg. Equipment, Enthalpy
Economizer - Bldg. Equipment, DB Temp.
Blank Off Plate
Economizer - Bldg. Equipment, Enthalpy
Economizer - Bldg. Equipment, DB Temp.
Blank Off Plate
Economizer - Bldg. Equipment, Enthalpy
Economizer - Bldg. Equipment, DB Temp.
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
H42 H48 H60 H72
X
X
X
X
X
X
X
X
X
X
Manual 2100-647A
Page 25 of 30
TABLE 11
Unit Low Voltage Terminal Connection Chart – MV Series Controller
4
8
9
10
11
5
6
7
Terminal
1
2
3
12
13
14
15
16
17
18
19
20
21
Description MV Terminal Connection
Compressor on Output Signal from Jade to MV
24VAC HOT
from Terminal 2 Connected to Unit Transformer to MV
24VAC COMMON
from Unit Transformer to MV
Unit Compressor Operation, Unit Receives Signal from MV for Compressor/
Condenser Fan On
Close Damper Input (Close Blade 100%), Unit Receives Signal from MV
Electric Heat On Operation, Stage 1 and 2, Unit Receives Signal from MV
1st Stage Cooling Input, 1st Stage Cooling Signal to Jade from MV
2nd Stage Cooling Input, 2nd Stage Cooling Signal to Jade from MV
Blower Operation (Indoor Blower On), Unit Receives Signal from MV
Filter Switch Normally Closed Dry Contacts, MV Signals Dirty Filter Alarm
Filter Switch Normally Closed Dry Contacts, MV Signals Dirty Filter Alarm
Blade Switch Delay Relay Normally Closed Dry Contacts, MV Signals Blade
Switch Fail Alarm*
Blade Switch Delay Relay Normally Closed Dry Contacts, MV Signals Blade
Switch Fail Alarm*
Occupied Signal Input, Econ Emergency Open (Open Blade 100%), Unit
Receives Signal from MV
Econ Open Output (
6V HOT, 24V HOT
after Blade Open 100% and Delay), Sends
Signal to MV
Alarm Relay Common Dry Contact, MV Signals Compressor Fail Alarm
Alarm Relay Normally Open Dry Contact, MV Signals Compressor Fail Alarm
Alarm Relay Normally Closed Dry Contact
24VAC HOT
to Terminal 2 from Unit Transformer Through Smoke Alarm Jumper
Wire**
2nd Stage Heating On Operated Through Jumper to Terminal 6
Blade Switch Terminal
24V HOT
When Blade is Open, Sends Signal from Switch to Delay Relay
"A" on Relay Board
"R" on Relay Board
"C" on Relay Board
"Y" on Relay Board
"F" on Relay Board
"W" on Relay Board
"Y1" on Relay Board
"Y2" on Relay Board
"G" on Relay Board
"4" on Relay Board
"5" on Relay Board
"8" on Relay Board
"9" on Relay Board
"ECONE" on Alarm Board
"DAMPER" on Comm Board
"LOCKOUT 3" on Alarm
Board
"LOCKOUT 2" on Alarm
Board
Not Used on MV
Building Smoke Alarm
(optional)
Not Used on MV
Not Used on MV
Revision
"2"
Reference
"A"
"R"
"C"
"Y"
"F"
"W1"
"Y1"
"Y2"
"G"
"4"
"5"
"8"
"9"
"E"
"10"
"3"
"2"
"1"
"RT"
"W2'
"7"
* Blade switch delay relay fail alarm set to 500 second delay from factory.
** Replace jumper wire with smoke alarm connections to interrupt 24VAC unit power if smoke alarm is used in shelter. Jumper can also be removed to break 24VAC power to unit.
Manual 2100-647A
Page 26 of 30
TABLE 12
Unit Low Voltage Terminal Connection Chart – Cooling/Heating Thermostat
Terminal
4
8
9
10
11
12
5
6
7
13
14
15
16
17
18
1
2
3
19
20
21
Description Thermostat Connection
Compressor on Output Signal from Jade
24VAC HOT
from Terminal 2 Connected to Unit Transformer to Thermostat
24VAC COMMON
from Unit Transformer to Thermostat
Unit Compressor Operation, Unit Receives Signal from MV for Compressor/
Condenser Fan On
Close Damper Input (Close Blade 100%)
Electric Heat On Operation, Stage 1 and 2, Unit Receives Signal from Thermostat
1st Stage Cooling Input, 1st Stage Cooling Signal – Economizer Use Only
2nd Stage Cooling Input, 2nd Stage Cooling Signal – Economizer Use Only
Blower Operation (Indoor Blower On), Unit Receives Signal from Thermostat
Filter Switch Normally Closed Dry Contacts
Filter Switch Normally Closed Dry Contacts
Blade Switch Delay Relay Normally Closed Dry Contacts
Blade Switch Delay Relay Normally Closed Dry Contacts
Occupied Signal Input, Econ Emergency Open (Open Blade 100%)
Econ Open Output (
6V HOT, 24V HOT
after Blade Open 100% and Delay)
Alarm Relay Common Dry Contact
Alarm Relay Normally Open Dry Contact
Alarm Relay Normally Closed Dry Contact
24VAC HOT
to Terminal 2 from Unit Transformer Through Smoke Alarm Jumper
Wire*
2nd Stage Heating On Operated Through Jumper to Terminal 6
Blade Switch Terminal
24V HOT
When Blade is Open, Sends Signal from Switch to Delay Relay
Not Used
"R" on Tstat
"C" on Tstat
"Y" on Tstat
Not Used
"W" on Tstat
Economizer 24V Signal
Economizer 24V Signal
"G" on Tstat
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Building Smoke Alarm
(optional)
Not Used
Not Used
* Replace jumper wire with smoke alarm connections to interrupt 24VAC unit power if smoke alarm is used in shelter. Jumper can also be removed to break 24VAC power to unit.
Revision
"2"
Reference
"A"
"R"
"C"
"Y"
"F"
"W1"
"Y1"
"Y2"
"G"
"4"
"5"
"8"
"9"
"E"
"10"
"3"
"2"
"1"
"RT"
"W2'
"7"
Manual 2100-647A
Page 27 of 30
FIGURE 9A
H***A Wiring Diagram
–
Top
/Black Red
Red
Red
Black hite /W Black
Wht Blk/
Pink
Black
Black
Red ow/ Yell hite /W Black ow Yell ow Yell ow ow
Yell
Yell
M
HER
FAN hite hite
/W
/W ow
Black
Yell
Red
/Black
/Black
/Black
/Black
Orange
Blue
Red
Blue
Red
Blue lack
/Blue ow/B
Red
Blue
Red
Black
Brown
Yell hite /W
/Black Orange
Red hite /W Red hite /W Black hite /W Black
Red
Red
Blue
Blue
Manual 2100-647A
Page 28 of 30
Red hite n/W ow/ Yell
Brow
Green
White ow/ Yell ow hite hite
/W
/W
Yell
Black
Red hite /W Blue ple Pur
Pink
FIGURE 9B
H***A Wiring Diagram
–
Bottom
ow Yell ed
White ite /Wh ow/ ow/R Yell
Yell
Blue ite
White ple
/Wh Red
Pur wn/ Bro ite
Pink
/Wh Black
Green
Red
Red
Red
Black
Yellow
Yellow
Yellow
M
HER
FAN
Blk/Wht
Pink ed ow/R Yell ite /Wh Black ite ite /Wh
/Wh ow
Black
Yell
Red
Blue
/Black
/Black
/Black
/Black
Orange
Blue
Blue
Red
Red lack wn ow/B
/Blue
Bro
Yell
Red
Blue
Red
Black ite /Wh
/Black Orange
Red ite /Wh Black
Red
Red
Blue
Blue ed
White wn/ ow/R Yell
Bro
Green
White ow/ Yell ite ite ow
/Wh
/Wh
Yell
Black
Red ite /Wh Blue ple Pur
Pink
RED BL
7 4
Manual 2100-647A
Page 29 of 30
Y1
Y2
A
F
EE
DR
G
L3
L2
4
5
W
MV
Controller
C
R
8
9
Y
FIGURE 10
H***A Low Voltage Ladder Diagram for Unit and MV Connections
Low Voltage
Terminal Strip
3
2
10
11
1
5
7
8
14
15
13
21
19
16
17
18
12
6
20
9
4
Blk/Wht
Pin 6 on Vent Plug
Filter Light
Pin 9 on Vent Plug
R on
Compressor
Control Module
Filter
Switch
Red/Wht
Red/Wht
Rd/W
Org/Blk
Filter Reset Button
Org/Blk
1
5
Blue/Blk
Filter
Relay
Blue/Blk
Bk/W
3
4
Pin 6 on Heater Plug
Orange
Blue
Brown
Blower Relay
Pin 3 on Heater Plug
Pin 1 on Heater Plug
Blk/Wht
Black
2 4
Blue
5
Red
Alarm Relay
Red/Blk
Red/Blk
NC COM
Pin 12 on V. Plug
Yel/Blk
Red/Blue
Yellow
Yellow
T2 T1
Blk/Wht
Hot
Time Delay Relay
Y
Comp. Control Module
Hi Press. Sw.
HPC
Transformer 24VAC
Common
CC
Compressor
Contactor
LPC
Red Red
LPC ALR
Bk/Wh
Alarm Relay
Blue
Lo Press. Sw.
Blue
Pin 8 on Vent Plug
Pink
1 3
Blue/Wht
Purple
Pink
Pin 1 on Vent Plug
Pin 2 on Vent Plug
Pin 5 on Vent Plug
Low Voltage
Ladder Diagram for Unit and MV
Connections
Yel/Red
Pin 7 on Vent Plug
Pin 10 on Vent Plug
Brown/Wht
MIS-3712
Manual 2100-647A
Page 30 of 30
Advertisement
Key features
- Wall-mounted installation
- Ductless or ducted operation
- Adjustable filter switch
- R-410A refrigerant
- High and low pressure switches
- Two-speed condenser fan motor
- Optional electric heat
- Compressor control module
- Low ambient control
- Clean air filters