PROFIBUS ®-DP System Description
PROFIBUS-DP is an industrial network protocol that connects field I/O devices in order to eliminate hard wiring. The
network connection increases device-level diagnostic capabilities, while also providing high-speed communication between
devices.
PROFIBUS-DP is based on the RS-485 serial data transfer standard. In most cases, the termination and physical media rules
for PROFIBUS-DP are the same as those required for RS-485 communication. A PROFIBUS-DP network supports up to
126 nodes and virtually an unlimited amount of I/O. The bus uses a trunkline/dropline topology. Power and
communication are provided via separate cables, allowing easy segmentation of the power structure to avoid overloading.
PROFIBUS-DP is capable of running at data rates as high as 12 Mbaud. When used at high data rates, the cable drop length
from the trunk to a node is severely limited. For example, when used at 12 Mbaud, nodes must be directly connected to
the trunk, with no drop length allowed.
BL20 I/O System
Typical System Configuration
PROFIBUS Cable
FLDP-IOM-88-0002-ST
Power Supply
E
D
RSSW RKSW 455-1M
RSM RKM 50-1M
RSM 2RKM 50
E
Valve
PLC & PB Master Controller
E
A
E
E
E
Sensor
RSM RKM 50-1M
C
VB2
C
C
C
RSSW RKSW 455-1M
RKSW D9T 455-1M
FLDP IOM-32-0001
FLDP IOM-88-0001
RKSW 45-TR
BL67 I/O System
Basic Parts List
A typical PROFIBUS-DP system consists of the following parts:
• A - Master
• B - Slaves
• C - Communication cable
• D - Power supply
• E - Power cable
PROFIBUS-DP stations require a network master (also called a scanner) to interface the stations to the host controller.
TURCK PROFIBUS-DP stations are designed to be fully compatible with PROFIBUS-DP equipment from other
manufacturers.
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
K2
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
TURCK
Industrial Connectivity Products
Cordsets
TURCK offers a complete line of molded PROFIBUS-DP cordsets to facilitate network installation, resulting in a faster
start-up and fewer wiring errors. The bus and drop cables are specially designed foil-shielded, high-flex cables with very low
inductance and capacitance to minimize propagation delay time. PROFIBUS-DP cables consist of a shielded and twisted
data pair with a bare drain wire.
In most cases, connections of the bus cable to the stations are made using 5-pin reverse-key eurofast ® (M12) connectors. A
variety of stations are also available that support D9 type connections. Power for most stations is provided through one or
two 5-pin minifast ® (7/8-16UN) connectors.
TURCK cordsets for the PROFIBUS-DP system are available in standard lengths. Please contact your local sales
representative to order custom lengths.
Diagnostics
TURCK network stations provide increased diagnostics over using traditional hard-wired I/O systems. TURCK stations also
serve as a buffer between I/O devices and the PROFIBUS-DP network by detecting short circuits without disrupting
communication.
The PROFIBUS-DP system includes a provision for special diagnostic data messages. These messages are triggered when a
fault occurs at the station (for example a short circuit on a sensor). When the master asks the station for data, the station
responds and includes a flag to indicate that diagnostic data is present. The master then asks for the diagnostic data, which
is mapped to a special location in the controller's memory.
Addressing
The valid range of PROFIBUS-DP node addresses is 0 to 125. TURCK station's addresses are usually set via rotary dials or
switches on the node. Changes to the address settings take effect when the station power is cycled or when the station
receives a software reset. Care must be taken to prevent the same address from being assigned to more than one node in a
system. Bihl+Wiedemann PROFIBUS-DP to AS-I gateways addresses are set in software using the on-unit display.
Communication Rate/Cycle Time
PROFIBUS-DP specifications define multiple transmission speeds ranging from 9.6 kbaud to 12 Mbaud. All nodes on a
network must communicate at the same rate.
The complete cycle time of a PROFIBUS-DP system is affected by several factors:
• Number of nodes being scanned
• Amount of data produced and consumed by the nodes
• Network communication rate
• Cycle time of the control program
All of these factors must be considered when calculating the cycle time of a particular network.
K3
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Industrial
Automation
GSD Files
GSD files contain detailed information about a PROFIBUS-DP device, including I/O data size and the devices configurable
parameters. The information in an GSD file, when used with a PROFIBUS-DP configuration tool, guides a user through the
steps necessary to configure a device. GSD files are available on the TURCK website (www.turck.com).
Maximum Ratings
The PROFIBUS-DP bus uses a trunkline/dropline topology. The trunk is the main communication cable and requires the
appropriate RS-485 termination at both ends of the trunk. Terminating resistors are available as plug-in eurofast ® modules
or can be built into the D9 connectors. The length of the trunk depends on the communication rate. Drops or branches off
the trunk are allowed, but are greatly limited as the communication rate increases. The table shows the maximum ratings
for a trunk at different communication rates.
Communication Rate
Max. Segment Length
9.6 kbps
1200 m
19.2 kbps
1200 m
93.75 kbps
1200 m
187.5 kbps
1000 m
500 kbps
400 m
1.5 Mbps
200 m
12 Mbps
100 m
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
K4
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
TURCK
Modular Industrial I/O PROFIBUS ®-DP Products
PROFIBUS-DP AIM™ Stations
TURCK’s Advanced I/O Module (AIM) PROFIBUS stations are extremely rugged stations designed for machine mounting.
These stations allow easy connection of standard I/O devices such as sensors, limit switches, valves and pilot lights to a
PROFIBUS network, typically without a protective enclosure. This is made possible by epoxy-filled station housings,
all-metal connectors and visible rotary address switches, among other things.
Mechanical Specifications
TURCK PROFIBUS AIM stations are designed for machine mounting with no separate enclosure or housing necessary.
Quick-disconnect capability, combined with an epoxy-filled housing, creates an extremely durable station that can be
mounted in most industrial environments. Detailed environmental specifications are as follows:
•
•
•
•
•
•
Housing material: Nylon 6
Connector material: Nickel-plated brass
Protection level: NEMA 1,3,4,12,13; IEC IP 67
Operating temperature: FLDP style 0° to +55°C (-40° to +158°F)
FXDP style -25° to +55°C (-40° to +158°F)
Vibration: 50 g @ 10 to 500 Hz
Other housing and connector materials available upon request.
The station’s components are identified in the following figure.
Power Connectors
I/O Connectors
Address switches
Network Connectors
K5
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Industrial
Automation
Connectors
PROFIBUS ® AIM™ stations provide connections for the bus, I/O and auxiliary power.
Bus Connectors
eurofast ® (M12) (reverse keyed) is the standard bus connector for PROFIBUS AIM stations.
PROFIBUS eurofast Pinouts
1 = 5 VDC*
2 = BUS _A
3 = Gnd
4 = BUS_B
5 = Shield
* Female connector only
Male
Female
5-Pin
5-Pin
PROFIBUS-DP
Different I/O connector pinouts are used for different station types. Stations are available with one or two inputs per
connector, one or two outputs per connector, or one input and one output per connector. The pin assignments for these
styles are:
eurofast Pinouts
Female
1 - V+ (24 VDC)
2 - Signal B (Odd numbered input)
3 - V- (0 VDC)
4 - Signal A (Even numbered input)
5 - N/C
5-Pin
Screw Terminal I/O Connection
AIM stations with part numbers ending in “ST” support screw terminal I/O and bus connections. The screw terminals for
these stations are located on the back of the station. The back of the station is also fitted with a foam gasket to allow the
station to be mounted to the outside of a cabinet or field I/O box (i.e. motor control center).
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
K6
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
TURCK
Modular Industrial I/O PROFIBUS ®-DP Products
Auxiliary Power Connectors
PROFIBUS ® AIM™ stations accept one or two 24 VDC power supplies via the minifast ® (7/8-16UN) connectors located at
the top of the station. Stations with only inputs require the UB supply to power station electronics and I/O. Stations with
both inputs and outputs need both supplies (UB and UL) to be connected. In this case, UB powers the station electronics
and the inputs, while UL powers the outputs. For further details, see the individual station entries in this catalog.
minifast Power Pinouts
Male
Female
5-Pin
5-Pin
1 = Gnd
2 = Gnd
3 = PE
4 = UB
5 = UL
Power
Common power ratings for AIM stations include:
•
•
•
•
Voltage: 18-30 VDC (both UB and UL)
Input Voltage: 18-30 VDC (From UB)
Input Signal Current (each input): OFF < 2 mA; ON 4 mA (@ nominal 24 VDC)
Input Delay: 2.5 ms
Addressing
PROFIBUS AIM stations must have a network address for communication. The address for AIM stations may be set via the
visible rotary switches under the clear plastic cover on the front of the station.
The pair of switches represents the address as a decimal number; the left switch being the 10’s multiplier and the right
switch the 1’s multiplier. To program the station, rotate the switches with a small slotted screwdriver until the arrows on the
switch point to the appropriate numbers for the chosen address. Some stations (with outputs) have a third switch. This
switch is used to enable auxiliary power diagnostics. If the switch is on, the loss of output power (UL) will trigger a
PROFIBUS diagnostic message.
K7
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Industrial
Automation
Diagnostics
AIM™ stations provide two LEDs for diagnosing communication and power problems.
Bus
• Green: Working properly
• Red: No communication
Power
• Off: No power
• Green: Power present
• Red: UB present, but UL missing (stations with outputs only)
There is an additional LED for each I/O point on the station. This LED indicates:
• Off: Point is off
• Green: Point is on
• Red: Point is in short-circuit state (advanced diagnostic stations only)
Missing input supply voltage
VO
Missing output supply voltage
SC
Short circuit at the station (or at the particular I/O point if specified)
PROFIBUS-DP
Abbreviations Used in Diagnostic Data Maps
VI
Connecting Devices to an AIM Station
AIM stations typically provide a eurofast ® (M12) connection for each I/O point. Standard TURCK I/O cordsets can be used
to connect physical devices in the field to the AIM station. Some AIM stations, specifically those with I/O counts greater
than eight total points, connect two signals to each connector. If the signals being connected are on the same physical
device (for example a sensor with two outputs), a simple four or five-wire cordset can be used for connection.
If the signals are on two separate devices, a splitter can be used to separate the AIM I/O connector into two individual
eurofast connectors. The recommended splitter is wired such that the second signal pin on the AIM station (pin 2) is wired
to the default signal pin (pin 4) on the second splitter arm - requiring no special wiring by the user. The splitter is simply
plugged into the AIM I/O connector and each arm is plugged into the appropriate I/O devices, as shown:
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
K8
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
TURCK
Modular Industrial I/O PROFIBUS ®-DP Products
TURCK’s USA website is your most complete and up-to-date source for product documentation,
CAD files and more. Search results produce downloadable documentation or request for quote
(RFQ). Additional product information or CAD files are easily requested and promptly filled.
Visit our site for new product releases, approvals, white papers, application support and more.
Access to all TURCK catalogs, press
releases, white papers and tutorials
Complete category listing
of TURCK products
Search for products
by part number, ID
number or key word
Access to CAD, wiring
and pinout diagrams
Download or e-mail
files, request for quote
Option to
e-mail pages
Contact a
TURCK representative
www.turck.com
K9
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Industrial
Automation
Ethernet™ Selection Guide
Housing
I/O Type
I/O Direction
Pages
Input
K11
Output
K17
Input & Output
K21
Discrete
Input & Output
K35
Repeater
N/A
K37
Input
K43
Output
K47
Input & Output
K45, K49
Input
K51
Output
K55
Counter
K57
Encoder
K59
Serial
K61
AIM
Discrete
PROFIBUS-DP
FDP20
Piconet
Discrete
Analog
Special Function
Gateways
BL67
K75
BL20
K77
N/A
AS-I
K67
Piconet
K65
PROFIBUS ®-DP & ®-PA Media
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
L1
www.turck.com
K10
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
TURCK
Modular Industrial I/O PROFIBUS ®-DP Products
Standard Input Stations
• Rugged, Fully Potted Stations
• Rotary Address Switches
• IP 67 Protection
• Automatic Baud Rate Sensing
Electrical
• Operating Current: <110 mA plus sum of input currents (from UB)
• Sensor Current: <500 mA per four inputs (from UB)
Power Distribution
• Inputs: UB power supply
Mechanical
• Operating Temperature: 0 to +55°C (+32 to +131°F)
• Protection: NEMA 1,3,4,12,13 / IEC IP 67
• Vibration: 50 g @ 10-500 Hz
Material
• Connectors: Nickel-plated brass
• Housing: Nylon 6
FLDP-IM 8-0001
FLDP-IM 16-0001
Diagnostics (Logical)
• Input short-circuit and power supply status mapped to PROFIBUS diagnostic
table, one bit indicating each fault for the entire station
Diagnostics (Physical)
• One (...IM 8-0001) or two (...IM 16-0001) LEDs indicates short-circuit for I/O
groups
• LEDs to indicate status of PROFIBUS communication and power supply
minifast ® Power Pinouts
Male
Female
5-Pin
5-Pin
1 = Gnd
2 = Gnd
3 = PE
4 = UB
5 = NC
PROFIBUS eurofast ® Pinouts
1 = 5 VDC*
2 = BUS _A
3 = Gnd
4 = BUS_B
5 = Shield
* Female connector only
K11
Male
Female
5-Pin
5-Pin
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Industrial
Automation
Data
Sensor Style
Gro
up
Dia
gno
stic
s
Ind
ivi
Dia dual
gno
stic
s
Wi
reDe Break
tec
tion
Pinout
Inp
ut
C o s per
nne
cto
r
Input Count
Co
Part Number
nne
cto
rs
Inputs
I/O Map
FLDP-IM 8-0001
8
0-7
S
1
PNP
X
1
FLDP-IM 16-0001
16
0-7
2S
2
PNP
X
2
Input Connectors
2S
PROFIBUS-DP
S
Mating cordset:
RK 4.4T-*-RS 4.4T
Mating cordset:
RK 4.4T-*-RS 4.4T
Splitter:
VBRS 4.4-2RK 4T-*/*
I/O Data Map 2
I/O Data Map 1
In
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0
I-7
I-6
I-5
I-4
I-3
I-2
I-1
In
I-0
Diagnosis
Status
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0
-
-
-
-
-
VI
-
SC
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0
I-7
I-6
I-5
I-4
I-3
I-2
I-1
I-0
1
I-15
I-14
I-13
I-12
I-11
I-10
I-9
I-8
Diagnosis
Status
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0
-
-
-
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
-
-
VI
www.turck.com
-
SC
K12
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
TURCK
Modular Industrial I/O PROFIBUS ®-DP Products
Standard Input Station
• Rugged, Fully Potted Stations
• Rotary Address Switches
• IP 67 Protection
• Automatic Baud Rate Sensing
Electrical
• Operating Current: <110 mA plus sum of input currents (from UB)
• Sensor Current: <500 mA per eight inputs (from UB)
Power Distribution
• Inputs: UB power supply
Mechanical
• Operating Temperature: 0 to +55°C (+32 to +131°F)
• Protection: NEMA 1,3,4,12,13 / IEC IP 67
• Vibration: 50 g @ 10-500 Hz
Material
• Connectors: Nickel-plated brass
• Housing: Nylon 6
FLDP-IM 32-0001
Diagnostics (Logical)
• Input short-circuit and power supply status mapped to PROFIBUS diagnostic
table, one bit indicating each fault for the entire station
Diagnostics (Physical)
• Four LED short-circuits for I/O (groups of eight inputs)
• LEDs to indicate status of PROFIBUS communication and power supply
minifast ® Power Pinouts
Male
Female
5-Pin
5-Pin
1 = Gnd
2 = Gnd
3 = PE
4 = UB
5 = NC
PROFIBUS eurofast ® Pinouts
1 = 5 VDC*
2 = BUS _A
3 = Gnd
4 = BUS_B
5 = Shield
* Female connector
only
K13
Male
Female
5-Pin
5-Pin
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Industrial
Automation
FLDP-IM 32-0001
32
Pinout
0-15
2S
Data
Gro
up
Dia
gno
stic
s
Ind
ivi
Dia dual
gno
stic
s
Wi
reDe Break
tec
tion
Input Count
Co
Part Number
nne
cto
Inp
ut
C o s per
nne
cto
r
rs
Inputs
Sensor Style
2
PNP
X
I/O Map
1
Input Connectors
PROFIBUS-DP
2S
Mating cordset:
RK 4.4T-*-RS 4.4T
Splitter:
VBRS 4.4-2RK 4T-*/*
I/O Data Map 1
Byte
In
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0
I-7
I-6
I-5
I-4
I-3
I-2
I-1
1
I-15
I-14
I-13
I-12
I-11
I-10
I-9
I-0
I-8
2
I-23
I-22
I-21
I-20
I-19
I-18
I-17
I-16
3
I-31
I-30
I-29
I-28
I-27
I-26
I-25
I-24
Diagnosis
Status
Byte
0
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
-
-
-
-
-
VI
-
SC
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
K14
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
TURCK
Modular Industrial I/O PROFIBUS ®-DP Products
Deluxe Input Stations
• Rugged, Fully Potted Stations
• Rotary Address Switches
• IP 67 Protection
• Automatic Baud Rate Sensing
Electrical
• Operating Current: <70 mA plus sum of input currents (from UB)
• Sensor Current: <120 mA per connector (input or pair of inputs) (from UB)
Power Distribution
• Inputs: UB power supply
Mechanical
• Operating Temperature: -25 to +55°C (-13 to +131°F)
• Protection: NEMA 1,3,4,12,13 / IEC IP 67
• Vibration: 50 g @ 10-500 Hz
Material
• Connectors: Nickel-plated brass
• Housing: Nylon 6
Diagnostics (Logical)
FXDP-IM 8-0001
FXDP-IM 16-0001
• Input short-circuit mapped to PROFIBUS diagnostic table, one bit indicating a fault
for each connector (input or pair of inputs)
• One bit is mapped to PROFIBUS diagnostic table indicating the status of the power
supply
Diagnostics (Physical)
• One LED indicates short-circuit for each I/O point
• LEDs to indicate status of PROFIBUS communication and power supply
minifast ® Power Pinouts
Male
Female
5-Pin
5-Pin
1 = Gnd
2 = Gnd
3 = PE
4 = UB
5 = NC
PROFIBUS eurofast ® Pinouts
1 = 5 VDC*
2 = BUS _A
3 = Gnd
4 = BUS_B
5 = Shield
* Female connector
only
K15
Male
Female
5-Pin
5-Pin
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Industrial
Automation
Pinout
Data
Sensor Style
Gro
up
Dia
gno
stic
s
Ind
ivi
Dia dual
gno
stic
s
Wi
reDe Break
tec
tion
Input Count
Co
Part Number
nne
cto
Inp
ut
C o s per
nne
cto
r
rs
Inputs
I/O Map
FXDP-IM 8-0001
8
0-7
S
1
PNP
X
X
1
FXDP-IM 16-0001
16
0-7
2S
2
PNP
X
X
2
Input Connectors
S
Mating cordset:
RK 4.4T-*-RS 4.4T
PROFIBUS-DP
2S
Mating cordset:
RK 4.4T-*-RS 4.4T
Splitter:
VBRS 4.4-2RK 4T-*/*
I/O Data Map 2
Byte
I/O Data Map 1
In
Byte
0
Byte
Diag
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
I-7
I-6
I-5
I-4
I-3
I-2
I-1
I-0
-
-
-
-
-
VI
-
SC
1
-
-
-
-
-
-
-
-
2
-
-
-
-
-
-
-
-
SC-7
SC-6
SC-5
SC-4
SC-3
SC-2
SC-1
SC-0
I-7
I-6
I-5
I-4
I-3
I-2
I-1
I-0
1
I-15
I-14
I-13
I-12
I-11
I-10
I-9
I-8
Byte
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0
3
In
Diag
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0
-
-
-
-
-
VI
-
SC
1
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
2
3
SC-15, SC-13, SC-11, SC-9, SC-7, SC-5, SC-3, SC-1,
14
12
10
8
6
4
2
0
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
K16
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
TURCK
Modular Industrial I/O PROFIBUS ®-DP Products
Standard Output Stations
• Rugged, Fully Potted Stations
• Rotary Address Switches
• IP 67 Protection
• Automatic Baud Rate Sensing
Electrical
• Operating Current: <150 mA (from UB)
• Output Current: <500 mA per output (...0001) or 2 A per output
(...0002) (from UL)
Power Distribution
• Outputs: UL power supply
Mechanical
• Operating Temperature: 0 to +55 °C (-13 to +131°F)
• Protection: NEMA 1,3,4,12,13 / IEC IP 67
• Vibration: 50 g @ 10-500 Hz
Material
• Connectors: Nickel-plated brass
• Housing: Nylon 6
Diagnostics (Logical)
• UB and UL power supply status mapped to PROFIBUS diagnostic table, one bit
indicating each fault for the entire station
FLDP-OM 8-0001
FLDP-OM 8-0002
FLDP-OM 16-0001
Diagnostics (Physical)
• LEDs to indicate status of PROFIBUS communication and power supplies
minifast ® Power Pinouts
Male
Female
5-Pin
5-Pin
1 = Gnd
2 = Gnd
3 = PE
4 = UB
5 = UL
PROFIBUS eurofast ® Pinouts
1 = 5 VDC*
2 = BUS _A
3 = Gnd
4 = BUS_B
5 = Shield
* Female connector
only
K17
Male
Female
5-Pin
5-Pin
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Industrial
Automation
I/O
Ma
p
Wi
re
De -Brea
tec
k
tion
rre
nt
Gro
u
Dia p
gno
stic
s
Ind
ivid
Dia ual
gno
stic
s
Data
Cu
Ou
tp
C o uts pe
nne
r
cto
r
Pin
out
Co
Part Number
nne
Ou
tp
Co ut
unt
cto
rs
Outputs
FLDP-OM 8-0001
8
0-7
G
1
0.5 A
1
FLDP-OM 8-0002
8
0-7
H
1
2A
1
FLDP-OM 16-0001
16
0-7
2G
2
0.5 A
2
Input/Output Connectors
2G
H
PROFIBUS-DP
G
Mating cordset:
RK 4.4T-*-RS 4.4T
Mating cordset:
RK 4.4T-*-RS 4.4T
Splitter:
VBRS 4.4-2RK 4T-*/*
I/O Data Map 2
I/O Data Map 1
Out
Byte
0
Mating cordset:
RK 4.5T-*-RS 4.5T
Byte
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
O-7
O-6
O-5
O-4
O-3
O-2
O-1
O-0
Out
Diagnosis
Diag
Byte
0
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
-
-
-
-
-
VI
VO
-
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0
O-7
O-6
O-5
O-4
O-3
O-2
O-1
O-0
1
O-15
O-14
O-13
O-12
O-11
O-10
O-9
O-8
Diagnosis
Diag
Byte
0
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
-
-
-
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
-
-
VI
www.turck.com
VO
-
K18
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
TURCK
Modular Industrial I/O PROFIBUS ®-DP Products
Deluxe Output Stations
• Rugged, Fully Potted Stations
• Rotary Address Switches
• IP 67 Protection
• Automatic Baud Rate Sensing
Electrical
• Operating Current: <70 mA (from UB)
• Output Current: <1.4 A per output (from UL)
Power Distribution
• Outputs: UL power supply
Mechanical
• Operating Temperature: -25 to +55°C (-13 to +131°F)
• Protection: NEMA 1,3,4,12,13 / IEC IP 67
• Vibration: 50 g @ 10-500 Hz
Material
• Connectors: Nickel-plated brass
• Housing: Nylon 6
Diagnostics (Logical)
• Output short-circuit and power supply status mapped to PROFIBUS diagnostic
table, one bit indicating a fault for each output point
FXDP-OM 8-0001
FXDP-OM 16-0001
Diagnostics (Physical)
• One LED indicates short-circuit for each output point
• LEDs to indicate status of PROFIBUS communication and power supply
minifast ® Power Pinouts
Male
Female
5-Pin
5-Pin
1 = Gnd
2 = Gnd
3 = PE
4 = UB
5 = UL
PROFIBUS eurofast ® Pinouts
1 = 5 VDC*
2 = BUS _A
3 = Gnd
4 = BUS_B
5 = Shield
* Female connector
only
K19
Male
Female
5-Pin
5-Pin
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Industrial
Automation
Data
Gro
up
Dia
gno
stic
s
Ind
ivi
Dia dual
gno
stic
s
Wi
reDe Break
tec
tion
Pinout
Ou
tp
C o uts pe
nne
r
cto
r
Output Count
Co
Part Number
nne
cto
rs
Outputs
Current
I/O Map
FXDP-OM 8-0001
8
0-7
H
1
1.4 A
X
X
1
FXDP-OM 16-0001
16
0-7
2H
2
1.4 A
X
X
2
Input/Output Connectors
2H
Mating cordset:
RK 4.4T-*-RS 4.4T
PROFIBUS-DP
H
Mating cordset:
RK 4.4T-*-RS 4.4T
Splitter:
VBRS 4.4-2RK 4T-*/*
I/O Data Map 2
I/O Data Map 1
Out
Byte
0
Byte
Diag
Byte
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
O-7
O-6
O-5
O-4
O-3
O-2
O-1
Out
O-0
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0
-
-
-
-
-
VI
VO
SC
1
SC-7
SC-6
SC-5
SC-4
SC-3
SC-2
SC-1
SC-0
2
-
-
-
-
-
-
-
3
-
-
-
-
-
-
-
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0
O-7
O-6
O-5
O-4
O-3
O-2
O-1
O-0
1
O-15
O-14
O-13
O-12
O-11
O-10
O-9
O-8
Byte
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0
-
-
-
-
-
VI
VO
SC
1
SC-7
SC-6
SC-5
SC-4
SC-3
SC-2
SC-1
SC-0
-
2
SC-15 SC-14 SC-13 SC-12 SC-11 SC-10 SC-9
SC-8
-
3
Diag
-
-
-
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
-
-
-
www.turck.com
-
-
K20
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
TURCK
Modular Industrial I/O PROFIBUS ®-DP Products
Standard Input/Output
Stations
• Rugged, Fully Potted Stations
• Rotary Address Switches
• IP 67 Protection
• Automatic Baud Rate Sensing
Electrical
• Operating Current: <150 mA plus sum of input currents (from UB)
• Sensor Current: <500 mA per group inputs (from UB group is all inputs
for IOM 84 and IOM 88-0002, two groups of four
inputs for IOM 88-0001))
• Output Current: See table on facing page (from UL)
Power Distribution
• Inputs: UB power supply
• Outputs: UL power supply
Mechanical
• Operating Temperature: 0 to +55°C (+32 to +131°F)
• Protection: NEMA 1,3,4,12,13 / IEC IP 67
• Vibration: 50 g @ 10-500 Hz
FLDP-IOM 84-0001
FLDP-IOM 88-0001
FLDP-IOM 88-0002
FLDP-IOM 88-0004
Material
• Connectors: Nickel-plated brass
• Housing: Nylon 6
Diagnostics (Logical)
• Input short-circuit and power supply status mapped to PROFIBUS diagnostic
table, one bit indicating each fault for the entire station
Diagnostics (Physical)
• One LED indicates short-circuit for all inputs
• LEDs to indicate status of PROFIBUS communication and power supply
minifast ® Power Pinouts
Male
Female
5-Pin
5-Pin
1 = Gnd
2 = Gnd
3 = PE
4 = UB
5 = UL
PROFIBUS eurofast ® Pinouts
1 = 5 VDC*
2 = BUS _A
3 = Gnd
4 = BUS_B
5 = Shield
* Female connector
only
K21
Male
Female
5-Pin
5-Pin
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Industrial
Automation
I/O
Ma
p
Data
Ind
iv
Dia idual
gno
stic
s
Wi
reDe Brea
tec
k
tion
sor
Sen
Ou
tp
C o uts p
n n e er
cto
r
Cu
rre
nt
le
Gro
up
Dia
gno
stic
s
Ind
ivid
Dia ual
gno
stic
s
Wi
reB
r
De
tec eak
tion
Ou
tp
Co ut
unt
Co
nne
cto
rs
Pin
out
Outputs
Sty
rs
Pin
out
Inp
u
C o ts per
nne
cto
r
cto
nne
Part Number
Co
Inp
ut C
oun
t
Inputs
FLDP-IOM 84-0001
8
0-3
2S
2
PNP
X
4
4-7
H
1
2A
1
FLDP-IOM 88-0001
8
0-7
C
1
PNP
X
8
0-7
C
1
0.5 A
2
FLDP-IOM 88-0002
8
0-3
2S
2
PNP
X
8
4-7
2G
2
0.5 A
2
FLDP-IOM 88-0004*
8
0-3
2S
2
PNP
X
8
4-7
2G
2
0.5 A
2
* High speed (0.2 ms) inputs
C
2S
Mating cordset:
RK 4.4T-*-RS 4.4T
Splitter:
VB2-RS 4.4T-1/2RK 4.4T-*/*/S651
Mating cordset:
RK 4.4T-*-RS 4.4T
Splitter:
VBRS 4.4-2RK 4T-*/*
H
2G
Mating cordset:
RK 4.4T-*-RS 4.4T
Mating cordset:
RK 4.4T-*-RS 4.4T
Splitter:
VBRS 4.4-2RK 4T-*/*
I/O Data Map 1
In
Byte
Out
I/O Data Map 2
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0
I-7
I-6
I-5
I-4
I-3
I-2
I-1
I-0
In
0
-
O-6
-
O-4
-
O-2
-
O-0
Out
Diagnosis
Diag
PROFIBUS-DP
Input/Output Connectors
Byte
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0
I-7
I-6
I-5
I-4
I-3
I-2
I-1
I-0
0
O-7
O-6
O-5
O-4
O-3
O-2
O-1
O-0
Diagnosis
Byte
0
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
-
-
-
-
-
VI
VO
SC
Diag
Byte
0
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
-
-
-
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
-
-
VI
www.turck.com
VO
SC
K22
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
TURCK
Modular Industrial I/O PROFIBUS ®-DP Products
Standard Input/Output
Station
• Rugged, Fully Potted Stations
• Screw Terminal Connections
• IP 67 Protection
• Automatic Baud Rate Sensing
Electrical
• Operating Current: <150 mA plus sum of input currents (from UB)
• Sensor Current: <500 mA sum of all inputs (from UB)
• Output Current: <500 mA per output (from UL)
Power Distribution
• Inputs: UB power supply
• Outputs: UL power supply
Mechanical
• Operating Temperature: 0 to +55 °C (+32 to +131 °F)
• Protection: NEMA 1,3,4,12,13 / IEC IP 67
• Vibration: 50 g @ 10-500 Hz
Material
• Connectors: Nickel-plated brass
• Housing: Nylon 6
Diagnostics (Logical)
FLDP-IOM 88-0002-ST
• Input short-circuit and power supply status mapped to PROFIBUS diagnostic
table, one bit indicating each fault for the entire station
Diagnostics (Physical)
• One LED indicates short-circuit for all inputs
• LEDs to indicate status of PROFIBUS communication and power supply
minifast ® Power Pinouts
Male
Female
5-Pin
5-Pin
1 = Gnd
2 = Gnd
3 = PE
4 = UB
5 = UL
PROFIBUS eurofast ® Pinouts
1 = 5 VDC*
2 = BUS _A
3 = Gnd
4 = BUS_B
5 = Shield
* Female
connector only
K23
Male
Female
5-Pin
5-Pin
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Industrial
Automation
FLDP-IOM 88-0002-ST
8
0-3
ST,
2S
2
PNP
X
8
4-7
ST,
2G
2
Data
Ind
iv
Dia idual
gno
stic
s
Wi
reDe Brea
tec
k
tion
I/O
Ma
p
Ou
tp
C o uts p
n n e er
cto
r
Cu
rre
nt
sor
Sty
le
Gro
u
Dia p
gno
stic
s
Ind
ivid
Dia ual
gno
stic
s
Wi
reDe Brea
tec
k
tion
Ou
tpu
Co t
unt
Co
nne
cto
rs
Pin
out
Outputs
Sen
cto
rs
Pin
out
Inp
u
C o ts per
nne
cto
r
nne
Co
Part Number
Inp
ut C
oun
t
Inputs
0.5 A
1
Input/Output Connectors
2S
2G
Mating cordset:
RK 4.4T-*-RS 4.4T
Splitter:
VBRS 4.4-2RK 4T-*/*
PROFIBUS-DP
ST
Mating cordset:
RK 4.4T-*-RS 4.4T
Splitter:
VBRS 4.4-2RK 4T-*/*
I/O Data Map 1
In
Byte
Out
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0
I-7
I-6
I-5
I-4
I-3
I-2
I-1
I-0
0
O-7
O-6
O-5
O-4
O-3
O-2
O-1
O-0
Diagnosis
Diag
Byte
0
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
-
-
-
-
-
VI
VO
SC
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
K24
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
TURCK
Modular Industrial I/O PROFIBUS ®-DP Products
Standard Input/Output
Stations
• Rugged, Fully Potted Stations
• Rotary Address Switches
• IP 67 Protection
• Automatic Baud Rate Sensing
Electrical
• Operating Current: <110 mA plus sum of input currents (from UB)
• Sensor Current: <500 mA per eight inputs (from UB)
• Output Current: <500 mA per output (from UL)
Power Distribution
• Inputs: UB power supply
• Outputs: UL power supply
Mechanical
• Operating Temperature: 0 to +55°C (+32 to +131°F)
• Protection: NEMA 1,3,4,12,13 / IEC IP 67
• Vibration: 50 g @ 10-500 Hz
Material
• Connectors: Nickel-plated brass
• Housing: Nylon 6
FLDP-IOM 1616-0001
FLDP-IOM 248-0001
Diagnostics (Logical)
• Input short-circuit and power supply status mapped to PROFIBUS diagnostic
table, one bit indicating each fault for the entire station
Diagnostics (Physical)
• One LED indicates short-circuit for each group of eight inputs
• LEDs to indicate status of PROFIBUS communication and power supply
minifast ® Power Pinouts
Male
Female
5-Pin
5-Pin
1 = Gnd
2 = Gnd
3 = PE
4 = UB
5 = UL
PROFIBUS eurofast ® Pinouts
1 = 5 VDC*
2 = BUS _A
3 = Gnd
4 = BUS_B
5 = Shield
* Female
connector only
K25
Male
Female
5-Pin
5-Pin
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Industrial
Automation
I/O
Ma
p
Data
Ind
iv
Dia idual
gno
stic
s
Wi
reB
r
De
tec eak
tion
Cu
rre
nt
Sty
le
Gro
up
Dia
gno
stic
s
Ind
ivid
Dia ual
gno
stic
s
Wi
reB
r
De
tec eak
tion
Ou
tp
Co ut
unt
Co
nne
cto
rs
Pin
out
Ou
tp
C o uts p
n n e er
cto
r
Outputs
sor
Sen
rs
Pin
out
Inp
u
C o ts per
nne
cto
r
cto
nne
Part Number
Co
Inp
ut C
oun
t
Inputs
FLDP-IOM 1616-0001
16
0-7
2S
2
PNP
X
16
8-15
2G
2
0.5 A
1
FLDP-IOM 248-0001
24
0-11
2S
2
PNP
X
8
12-15 2G
2
0.5 A
2
Input/Output Connectors
2G
Mating cordset:
RK 4.4T-*-RS 4.4T
Splitter:
VBRS 4.4-2RK 4T-*/*
Mating cordset:
RK 4.4T-*-RS 4.4T
Splitter:
VBRS 4.4-2RK 4T-*/*
I/O Data Map 2
I/O Data Map 1
Byte
In
Out
Byte
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0
I-7
I-6
I-5
I-4
I-3
I-2
I-1
I-0
1
I-15
I-14
I-13
I-12
I-11
I-10
I-9
I-8
0
O-7
O-6
O-5
O-4
O-3
O-2
O-1
O-0
2
O-15
O-14
O-13
O-12
O-11
O-10
O-9
O-8
Diagnosis
Diag
PROFIBUS-DP
2S
In
Out
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0
I-7
I-6
I-5
I-4
I-3
I-2
I-1
1
I-15
I-14
I-13
I-12
I-11
I-10
I-9
I-0
I-8
2
I-23
I-22
I-21
I-20
I-19
I-18
I-17
I-16
0
O-7
O-6
O-5
O-4
O-3
O-2
O-1
O-0
Diagnosis
Byte
0
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
-
-
-
-
-
VI
VO
SC
Diag
Byte
0
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
-
-
-
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
-
-
VI
www.turck.com
VO
SC
K26
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
TURCK
Modular Industrial I/O PROFIBUS ®-DP Products
Input/Output Station for
Robot Control
• Rugged, Fully Potted Stations
• Rotary Address Switches
• IP 67 Protection
• Automatic Baud Rate Sensing
Electrical
• Operating Current: <110 mA plus sum of input currents (from UB)
• Sensor Current: <500 mA per group of eight or twelve inputs (from UB)
• Output Current: <500 mA per output (from UL)
Power Distribution
• Inputs: UB power supply
• Outputs: UL power supply
Mechanical
• Operating Temperature: 0 to +55°C (+32 to +131°F)
• Protection: NEMA 1,3,4,12,13 / IEC IP 67
• Vibration: 50 g @ 10-500 Hz
Material
FLDP-IOM 2012-0001
• Connectors: Nickel-plated brass
• Housing: Nylon 6
Diagnostics (Logical)
• Input short-circuit and power supply status mapped to PROFIBUS diagnostic
table, one bit indicating each fault for the entire station
Diagnostics (Physical)
• One LED indicates short-circuit for each group of inputs
• LEDs to indicate status of PROFIBUS communication and power supply
PROFIBUS eurofast ® Pinouts
Male
Female
5-Pin
5-Pin
1 = 5 VDC*
2 = BUS _A
3 = Gnd
4 = BUS_B
5 = Shield
* Female connector only
minifast ® Power Pinouts
Male
Female
5-Pin
5-Pin
1 = Gnd2
2 = Gnd
3 = PE
4 = UB
5 = UL
K27
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Industrial
Automation
FLDP-IOM 2012-0001
20
X1,X2 B2
8, 12
PNP
X
12
X1,X2
B2
8,4
nt
Data
Ind
iv
Dia idual
gno
stic
s
Wi
reDe Brea
tec
k
tion
I/O
Ma
p
Cu
rre
sor
Sty
le
Gro
u
Dia p
gno
stic
s
Ind
ivid
Dia ual
gno
stic
s
Wi
reDe Brea
tec
k
tion
Ou
tp
Co ut
unt
Co
nne
cto
rs
Pin
out
Ou
tp
C o uts p
n n e er
cto
r
Outputs
Sen
cto
rs
Pin
out
Inp
u
C o ts per
nne
cto
r
nne
Co
Part Number
Inp
ut C
oun
t
Inputs
0.5 A
1
Input/Output Connectors
PROFIBUS-DP
B2
I/O Data Map 1
Byte
In
Out
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0
X1I7
X1I6
X1I5
X1I4
X1I3
X1I2
X1I1
1
X2I7
X2I6
X2I5
X2I4
X2I3
X2I2
X2I1
X1I0
X2I0
2
-
-
-
-
X2I11 X2I10 X2I9
X2I8
0
X1O7
X1O6
X1O5
X1O4
X1O3
X1O2
X1O1
X1O0
1
-
-
-
-
X2O3
X2O2
X2O1
X2O0
Diagnosis
Status
Byte
0
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
-
-
-
-
-
UI
UO
SC
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
K28
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
TURCK
Modular Industrial I/O PROFIBUS ®-DP Products
Standard Input/Output
Stations
• Rugged, Fully Potted Stations
• Rotary Address Switches
• IP 67 Protection
• Automatic Baud Rate Sensing
Electrical
• Operating Current: <150 mA plus sum of input currents (from UB)
• Sensor Current: <500 mA per group inputs (from UB group is all inputs
for IOM 84 and IOM 88-0002, two groups of four
inputs for IOM 88-0001))
• Output Current: See table on facing page (from UL)
Power Distribution
• Inputs: UB power supply
• Outputs: UL power supply
Mechanical
• Operating Temperature: 0 to +55°C (+32 to +131°F)
• Protection: NEMA 1,3,4,12,13 / IEC IP 67
• Vibration: 50 g @ 10-500 Hz
Material
FLDP-IOM124-0001
FLDP-IOM124-0002
• Connectors: Nickel-plated brass
• Housing: Nylon 6
Diagnostics (Logical)
• Input short-circuit and power supply status mapped to PROFIBUS diagnostic
table, one bit indicating each fault for the entire station
Diagnostics (Physical)
• One LED indicates short-circuit for all inputs
• LEDs to indicate status of PROFIBUS communication and power supply
C0
C4
DeviceNet multifast Pinout
C1
C5
C2
C6
C3
C7
Male
Female
17-Pin
17-Pin
1=
2=
3=
4=
5=
6=
7=
8=
9=
K29
0 V, us1
0 V, US2
+24, US2
+24, US1
PE
*
Us COM
*
KSR2
10 =KSR1
11 =*
12 =Us CAN high
13 =Devnet high
14 =Devnet low
15 =RBST
16 =UL
17 =Us CAN low
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Industrial
Automation
I/O
Ma
p
Ind
iv
Dia idual
gno
stic
s
Wi
reDe Brea
tec
k
tion
sor
Sen
Ou
tp
C o uts p
n n e er
cto
r
Cu
rre
nt
le
Gro
up
Dia
gno
stic
s
Ind
ivid
Dia ual
gno
stic
s
Wi
reB
r
De
tec eak
tion
Ou
tp
Co ut
unt
Co
nne
cto
rs
Pin
out
Sty
rs
Pin
out
Inp
u
C o ts per
nne
cto
r
cto
Data
Co
nne
Outputs
Inp
ut C
oun
t
Inputs
FLDP-IOM124-0001
12
6
2S
2
PNP
X
4
2
2G
2
2A
1
FLDP-IOM124-0002
12
6
2S
2
PNP
X
4
2
2G
2
2A
1
Part Number
Input/Output Connectors
PROFIBUS-DP
2G
2S
Mating cordset:
RK 4.4T-*-RS 4.4T
Splitter:
VBRS 4.4-2RK 4T-*/*
Mating cordset:
RK 4.4T-*-RS 4.4T
Splitter:
VBRS 4.4-2RK 4T-*/*
I/O Data Map 1
Byte
In
Out
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0
C4P2
C4P4
C2P2
C2P4
C1P2
C1P4
C0P2
C0P4
1
-
-
-
-
C6P2
C6P4
C5P2
C5P4
0
-
-
-
-
C7P2
C7P4
C3P2
C3P4
Diagnosis
Diag
Byte
0
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
-
-
-
-
-
UB
UL
SC
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
K30
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
TURCK
Modular Industrial I/O PROFIBUS ®-DP Products
Deluxe Input/Output
Stations
• Rugged, Fully Potted Stations
• Rotary Address Switches
• IP 67 Protection
• Automatic Baud Rate Sensing
Electrical
• Operating Current: <70 mA plus sum of input currents (from UB)
• Sensor Current: <120 mA per connector (input or pair of inputs) (from UB)
• Output Current: 1.4 A per output (from UL)
Power Distribution
• Inputs: UB power supply
• Outputs: UL power supply
Mechanical
• Operating Temperature: -25 to +55°C (-13 to +131°F)
• Protection: NEMA 1,3,4,12,13 / IEC IP 67
• Vibration: 50 g @ 10-500 Hz
Material
• Connectors: Nickel-plated brass
• Housing: Nylon 6
FXDP-IOM 88-0001
FXDP-CSG 88-0001
FXDP-XSG 16-0001
Diagnostics (Logical)
• I/O and power supply faults mapped to PROFIBUS diagnostic table, one bit
per output and one bit per input connector
Diagnostics (Physical)
• One LED indicates short-circuit for each I/O point
• LEDs to indicate status of PROFIBUS communication and power supply
minifast ® Power Pinouts
Male
Female
5-Pin
5-Pin
1 = Gnd
2 = Gnd
3 = PE
4 = UB
5 = UL
PROFIBUS eurofast ® Pinouts
1 = 5 VDC*
2 = BUS _A
3 = Gnd
4 = BUS_B
5 = Shield
* Female
connector only
K31
Male
Female
5-Pin
5-Pin
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Industrial
Automation
I/O
Ma
p
Data
Ind
iv
Dia idual
gno
stic
s
Wi
reDe Brea
tec
k
tion
Ou
tp
C o uts p
n n e er
cto
r
Cu
rre
nt
Sty
le
Gro
u
Dia p
gno
stic
s
Ind
ivid
Dia ual
gno
stic
s
Wi
reB
r
De
tec eak
tion
Ou
tpu
t
Co
nne
cto
rs
Pin
out
Outputs
sor
Sen
cto
rs
Pin
out
Inp
u
C o ts per
nne
cto
r
Part Number
Co
Inp
nne
ut C
oun
t
Inputs
FXDP-IOM 88-0001
8
0-3
2S
2
PNP
X
8
4-7
2G
2
1.4 A
X
1
FXDP-CSG 88-0001
8
0-7
C
1
PNP
X
8
0-7
C
1
1.4 A
X
2
FXDP-XSG 16-0001
16
0-7
2X
1
PNP
X
16
0-7
2X
1
1.4 A
X
3
Input/Output Connectors
C
Mating cordset:
RK 4.4T-*-RS 4.4T
Splitter:
VBRS 4.4-2RK 4T-*/*
2X
Mating cordset:
RK 4.4T-*-RS 4.4T
Splitter:
VB2-RS 4.4T-1/2RK 4.4T-*/*/S651
I/O Data Map 1
In
I-7
I-6
I-5
I-4
I-3
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3
Diag
Out
0
1
Mating cordset:
RK 4.4T-*-RS 4.4T
Splitter:
Mating cordset:
RK 4.4T-*-RS 4.4T
Splitter:
VBRS 4.4-2RK 4T-*/*
VBRS 4.4-2RK 4T-*/*
I/O Data Map 2
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3
0
2G
PROFIBUS-DP
2S
-
-
-
-
-
SC-15 SC-14 SC-13 SC-12 SC-11
2
-
-
-
-
0
O-7
O-6
O-5
O-4
Bit 2
Bit 1
Bit 0
I-2
I-1
I-0
Bit 2
Bit 1
Bit 0
Byte
0
-
-
-
-
-
UB
UL
SC
1
SC-7
-
SC-5
-
SC-3
-
SC-1
-
2
SC-15
-
SC-13
-
SC-11
-
SC-9
-
3
SC-I7 SC-I6 SC-I5 SC-I4 SC-I3 SC-I2 SC-I1 SC-I0
UB
UL
SC
SC-10
SC-9
SC-8
In
Diag
SC-7,6 SC-5,4 SC-3,2 SC-1,0
O-3
O-2
O-1
O-0
Out
Byte
0
0
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
I-7
I-6
I-5
I-4
I-3
I-2
I-1
I-0
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
O-7
O-6
O-5
O-4
O-3
O-2
O-1
O-0
I/O Data Map 3
Byte
In
I-7
I-6
I-5
I-4
I-3
I-2
I-1
I-0
1
I-15
I-14
I-13
I-12
I-11
I-10
I-9
I-8
Byte
Diag
Out
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0
-
-
-
-
-
UB
UL
SC
1
SC-7
SC-6
SC-5
SC-4
SC-3
SC-2
SC-1
SC-1
2
SC-15 SC-14 SC-13 SC-12 SC-11 SC-10 SC-9
SC-8
3
SC-I SC-I SC-I SC-I
15,14 13,12 11,10 9,8
SC-I
7,6
SC-I
5,4
SC-I
3,2
SC-I
1,0
0
O-7
O-6
O-5
O-4
O-3
O-2
O-1
O-0
1
O-15
O-14
O-13
O-12
O-11
O-10
O-9
O-8
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
K32
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
TURCK
Modular Industrial I/O PROFIBUS ®-DP Products
PROFIBUS-DP FDP20 Stations
TURCK’s FDP20 PROFIBUS stations are low-cost screw-terminal connection stations designed for mounting in an enclosure.
These stations provide easy connection of standard I/O devices such as push buttons, pilot lights, motor starters and drives to
a PROFIBUS network. FDP20 stations are designed to easily upgrade existing equipment to a PROFIBUS network.
Mechanical Specifications
TURCK FDP20 stations are designed to be mounted in standard equipment enclosures (operator stations, motor control
centers, etc.). These stations use screw terminal connections for all I/O and network wiring. Detailed environmental
specifications include:
• Housing material: Nylon 6
• Protection level: IP 20
• Operating temperature: 0 to +55°C (32 to +131°F)
The station’s components are identified in the figure below.
Address Switches
PROFIBUS-DP Connector
Connectors
I/O and Power Connectors
Bus connectors
PROFIBUS-DP D9 Connector
Label
I/O
connectors
Each FDP20 version uses a different screw terminal connector. Detailed pinout information is given in the product
information on the following pages.
K33
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Industrial
Automation
Power
FDP20 stations provide an auxiliary power connection for I/O devices and station electronics. Power can be applied
separately to different I/O groups as shown in the following diagram.
Power ratings for FDP20 stations:
Operating Voltage: 18-30 VDC (24 VDC nominal)
Internal Current Consumption: <75 mA (@ nominal 24 VDC) plus sum of I/O currents
Input Signal Current (each input): OFF < 0.5 mA; ON 1-3.4 mA
Input Delay: 2.5 ms
Output Current: 1.8 A max per output (XSG version only)
PROFIBUS-DP
•
•
•
•
•
Addressing
PROFIBUS ® stations must have a network address for communication. The address for FDP20 stations may be set via the
visible rotary switches on the front of the station.
The pair of switches represents the address as a decimal number; the left switch being the 10’s multiplier and the right
switch the 1’s multiplier. To program the stations, rotate the switches with a small slotted screwdriver until the arrows are
pointing at the appropriate numbers for the chosen address.
Diagnostics
FDP20 stations provide LEDs for diagnosing communication problems.
Bus
• Green: Normal operation
• Red: No communication
Voltage Supply
• Green: Power present
• Red: No power
Input/Output Status
• Off: Point is off
• Green: Point is on
Common short-circuit Indication (Two LEDs for entire station)
• Red: short-circuit within group of inputs
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
K34
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
TURCK
Modular Industrial I/O PROFIBUS ®-DP Products
Enclosure Mounted
Input/Output Station
• In-Cabinet I/O
• Ideal for Retrofits
• IP 20 Protection
• Automatic Baud Rate Detection
Electrical
• Operating Current: <75 mA plus sensor currents (from Auxiliary power)
• Input Current: <700 mA sum of all inputs (from Auxiliary power)
• Output Current: <1.8 A per output (from Auxiliary power)
Power Distribution
• Inputs: Auxiliary power
• Outputs: Auxiliary power supply
Mechanical
• Operating Temperature: 0 to +55°C (+32 to +131°F)
• Protection: IEC IP 20
Material
• Housing: Nylon
Diagnostics (Physical)
FDP20-16XSG
FDP20-16S
• LEDs to indicate status of PROFIBUS-DP communication
PROFIBUS-DP D9 Connector
3 = BUS_B
5 = DGnd
6 = +5VDC
8 = BUS_A
K35
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Industrial
Automation
FDP20-16XSG
16
FLX-DP
PNP
16
FDP20-16S
16
FL-DP
PNP
0
0.5 A
Da
ta M
ap
nt
rre
Cu
Pin
out
FLX-DP
Data
Ind
iv
Dia idual
gno
stic
s
Wi
reB
re
De
tec ak
tion
Outputs
Gro
up
Dia
gno
stic
s
Ind
ivid
Dia ual
gno
stic
s
Wi
reB
re
De
tec ak
tion
Ou
tp
Co ut
unt
Sty
sor
Sen
Part Number
Pin
out
Inp
ut C
oun
t
le
Inputs
1
2
Input/Output Connectors
FL-DP
FLX-DP
User supplied
device power
PROFIBUS-DP
User supplied
device power
Indicates I/O groups which can be powered from separate Aux. power supplies if desired
I/O Data Map 2
I/O Data Map 1
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
In
Out
0
I-7
I-6
I-5
I-4
I-3
I-2
I-1
I-0
1
I-15
I-14
I-13
I-12
I-11
I-10
I-9
I-8
0
O-7
O-6
O-5
O-4
O-3
O-2
O-1
O-0
1
O-15
O-14
O-13
O-12
O-11
O-10
O-9
O-8
In
0
I-7
I-6
I-5
I-4
I-3
I-2
I-1
I-0
1
I-15
I-14
I-13
I-12
I-11
I-10
I-9
I-8
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
K36
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
TURCK
Modular Industrial I/O PROFIBUS ®-DP Products
Profibus-DP Repeater
• Extend Network Length
• Allows More Than 32 Stations on Network
• Extend Drop Lengths
• Isolate Communication Segments
Electrical
• Operating Current: <60 mA
Power Distribution
• Station: Auxiliary power supply (UB)
Mechanical
• Operating Temperature: 0 to +55°C (+32 to +131°F)
• Protection: NEMA 1,3,4,12,13 and IEC IP 67
• Vibration: 50 g @ 10-500 Hz
Material
• Connectors: Nickel-plated brass
• Housing: Nylon 6
Diagnostics (Physical)
REP-DP-0002
• LEDs indicate communication status for each segment and power supply
PROFIBUS eurofast ® Pinouts
1 = 5 VDC*
2 = BUS _A
3 = Gnd
4 = BUS_B
5 = Shield
* Female
connector only
Male
Female
5-Pin
5-Pin
minifast ® Power
Pinouts
Not used
Male
1 = Gnd
2 = Gnd
3 = PE
4 = UB
5 = NC
5-Pin
K37
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Industrial
Automation
PROFIBUS -DP Repeater
The REP-DP repeater serves to assemble two galvanically isolated PROFIBUS-DP segments in RS-485 technology with 32
participants each, and provides IP 67 protection. Up to four repeaters can be connected in series, so that up to 127 nodes
can be operated via a single master; thus PROFIBUS networks can be extended significantly by using repeaters (depending
on the baud rate).
The transmission rate is detected automatically (up to 12 Mbaud), and the signals are regenerated in amplitude. If there are
faulty protocols in one of the segments (a wire-break, short-circuit in the bus line or by a defective node), that segment is
decoupled and an error indication is provided by the LED.
Connection:
PROFIBUS-DP
Individual PROFIBUS segments are connected via M12 connectors (see technical guidelines for PROFIBUS connection
technology). The repeater is equipped with three female and one male connector; unused connections must be terminated
with a terminating resistor (type: RSSW 45-TR). The shield of the PROFIBUS cable can be grounded directly via a
grounding screw (internally the shield is coupled capacitively with the ground). Power (24 VDC) is supplied via standard
7/8 inch connectors.
Terminating Resistors
To next segment
From previous segment
To Power Supplies
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
K38
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
TURCK
Modular Industrial I/O PROFIBUS ®-DP Products
PROFIBUS-DP piconet Stations
TURCK’s PROFIBUS piconet stations are compact rugged stations designed for on-machine mounting. These stations allow
easy connection to standard I/O devices such as sensors, limit switches, valves and pilot lights to a PROFIBUS network,
typically without the need for a protective enclosure. This is made possible by epoxy-filled station housings, all-metal
connectors and visible rotary address switches, among other things.
piconet’s small size sets them apart from other stations. piconet stations are the smallest rugged I/O modules available, with
a standard housing footprint of 30 x 175 mm. They are also available with M8 connectors for I/O, making them ideally
suited for small-space applications.
piconet stations are able to create a small distributed subnetwork from the PROFIBUS system, allowing the user to choose a
gateway node (identified by the part number SDPL…) to connect to a PROFIBUS system. A fiber-optic network connects
the gateway to the chosen I/O modules, creating a distributed system visible to PROFIBUS stations as a single node.
Mechanical Specifications
TURCK PROFIBUS piconet stations are designed to be mounted directly on machines and work cells with no separate
enclosure or housing necessary. The epoxy-filled housing creates a durable station that allows it to be mounted in most
industrial environments. Detailed environmental specifications include:
•
•
•
•
Housing material: Glass filled nylon
Connector material: Nickel-plated brass
Protection level: NEMA 1,3,4,12,13; IEC IP 67
Operating temperature: 0 to +55°C
The station’s components are identified in the figure below.
PROFIBUS connector
Address switches
Diagnostic LEDs
I/O Connectors
Power Connectors
K39
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Industrial
Automation
Connectors
PROFIBUS piconet stations have connectors for the bus and I/O power, as well as for subnetwork communication for
gateways. piconet stations power all I/O from auxiliary power.
Bus Connector:
PROFIBUS piconet stations use eurofast (M12) connectors for bus connection.
PROFIBUS-DP Pinout
Female
1 = 5 VDC
2 = BUS_A
3 = Gnd
4 = BUS_B
5 = Shield
5-Pin
PI
PROFIBUS-DP
piconet stations with discrete I/O are available with picofast connectors.
PO
Mating cordset:
PSG 3M-*
Mating cordset:
PSG 3M-*
piconet stations with analog and special function I/O are available with eurofast connectors.
Auxiliary Power Connectors
piconet stations have two auxiliary power connectors, one male and one female, so the stations may be “daisy-chained”
without requiring a T-connector. 4-pin picofast auxiliary power connectors are used to connect two power supplies: one
for station electronics and inputs and one for outputs.
Aux. Power
picofast Male
picofast Female
4-Pin
4-Pin
1 = UB+
2 = UL+
3 = Gnd
4 = Gnd
Subnetwork Connectors (Gateway modules only)
The piconet subnetwork uses a fiber-optic medium for communication. This is a ring network
system, so it is important to connect the fiber-optic output from the last station back to the input
on the gateway. The fiber used is plastic and features a simple snap-in connector. Some stations
may be available with different connector options than the standards mentioned in this text.
Consult your local sales representative if you need different connector options.
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
K40
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
TURCK
Modular Industrial I/O PROFIBUS ®-DP Products
Power
Power ratings for piconet stations are listed below.
• Aux Power Voltage: 24 VDC (nominal)
• Input Voltage: 13-26 VDC (From auxiliary supply, VB)
• Output Voltage: From auxiliary supply, VL
Addressing
PROFIBUS stations must have a network address for communication. The address for piconet stations may be set via the
visible rotary switches under the clear plastic cover on the front of the station.
Address = 6x10 + 3x1 = 63
The pair of switches represents the address as a decimal number; the left switch being the 10’s multiplier and the right
switch the 1’s multiplier. To program the station, rotate the switches with a small slotted screwdriver until the arrows are
pointing at the appropriate numbers for the chosen address.
Diagnostics
piconet ® stations provide LEDs for diagnosing communication problems.
Bus
• Green - Normal operation
• Red - No communication
Module Status
• Green - OK
• Red - Error
There is an additional LED for each I/O point on the station. This LED indicates:
• Off - Point is off
• Green - Point is on
There is also an LED to indicate the status of each of the two auxiliary power supplies.
• Off - Power is missing
• On - Power is present
K41
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Industrial
Automation
TURCK’s USA website is your most complete and up-to-date source for product documentation,
CAD files and more. Search results produce downloadable documentation or request for quote
(RFQ). Additional product information or CAD files are easily requested and promptly filled.
Visit our site for new product releases, approvals, white papers, application support and more.
PROFIBUS-DP
Access to all TURCK catalogs, press
releases, white papers and tutorials
Complete category listing
of TURCK products
Search for products
by part number, ID
number or key word
Access to CAD, wiring
and pinout diagrams
Download or e-mail
files, request for quote
Option to
e-mail pages
Contact a
TURCK representative
www.turck.com
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
K42
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
TURCK
Modular Industrial I/O PROFIBUS ®-DP Products
Input Station
• Rugged, Fully Potted Stations
• Small Footprint
• IP 67 Protection
• Automatic Baud Rate Sensing
Electrical
• Operating Current: <75 mA plus sensor currents (from UB)
• Sensor Current: <500 mA total of all sensors (from UB)
Power Distribution
• Inputs: UB Power supply
Mechanical
• Operating Temperature: 0 to +55°C (+32 to +131°F)
• Protection: IP 67
• Vibration: IEC 68, part 2-6
Material
• Connectors: Nickel-plated brass
• Housing: Nylon
SDPB-0800D-0008
Diagnostics (Physical)
• One LED indicates an I/O fault for the entire station
• LEDs to indicate status of PROFIBUS-DP communication
PROFIBUS-DP Pinout
eurofast Female
1 = 5 VDC
2 = BUS_A
3 = Gnd
4 = BUS_B
5 = Shield
5-Pin
Aux. Power
picofast Male
picofast Female
4-Pin
4-Pin
1 = UB+
2 = UL+
3 = Gnd
4 = Gnd
K43
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Industrial
Automation
SDPB-0800D-0008
8
0-7
PI
1
PNP
Ma
p
Wi
re
De -Brea
tec
k
tion
Ind
iv
Dia idual
gno
stic
s
Gro
u
Dia p
gno
stic
s
sor
Sty
le
Data
Sen
Inp
u
C o ts per
nne
cto
r
Pin
out
Co
Inp
Part Number
nne
ut C
cto
oun
rs
t
Inputs
1
Input Connectors
PROFIBUS-DP
PI
Mating cordset:
PSG 3M-*
I/O Data Map 1
In
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0
I-7
I-6
I-5
I-4
I-3
I-2
I-1
I-0
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
K44
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
TURCK
Modular Industrial I/O PROFIBUS ®-DP Products
Input/Output Stations
• Rugged, Fully Potted Stations
• Small Footprint
• IP 67 Protection
• Automatic Baud Rate Sensing
Electrical
• Operating Current: <75 mA plus sensor currents (from UB)
• Sensor Current: <500 mA total of all sensors (from UB)
• Output Current: <500 mA per output (from UL)
Power Distribution
• Inputs: UB Power supply
• Outputs: UL Power supply
Mechanical
• Operating Temperature: 0 to +55°C (+32 to +131°F)
• Protection: IEC IP 67
• Vibration: IEC 68, part 2-6
Material
• Connectors: Nickel-plated brass
• Housing: Nylon
SDPB-0808D-0001
Diagnostics (Physical)
• One LED indicates an I/O fault for the entire station
• LEDs to indicate status of PROFIBUS-DP communication
Profibus-DP Pinout
eurofast Male
1 = 5 VDC
2 = BUS_A
3 = Gnd
4 = BUS_B
5 = Shield
5-Pin
Aux. Power
picofast Male
picofast Female
4-Pin
4-Pin
1 = UB+
2 = UL+
3 = Gnd
4 = Gnd
K45
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Industrial
Automation
SDPB-0808D-0001
8
0-7
PIO
1
PNP
8
0-7
PIO
1
0.5 A
I/O
Ma
p
Data
Ind
iv
Dia idual
gno
stic
s
Wi
reDe Brea
tec
k
tion
Ou
tp
C o uts p
n n e er
cto
r
Cu
rre
nt
Sty
le
Gro
u
Dia p
gno
stic
s
Ind
ivid
Dia ual
gno
stic
s
Wi
reB
r
De
tec eak
tion
Ou
tp
Co ut
unt
Co
unt
Co
nne
cto
rs
Pin
out
Outputs
sor
Sen
rs
Pin
out
Inp
u
C o ts per
nne
cto
r
cto
nne
Co
Part Number
Inp
ut C
oun
t
Inputs
1
Input/Output Connectors
PROFIBUS-DP
PIO
Mating cordset:
PSG 4M-*
I/O Data Map 1
In
Out
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0
I-7
I-6
I-5
I-4
I-3
I-2
I-1
I-0
0
O-7
O-6
O-5
O-4
O-3
O-2
O-1
O-0
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
K46
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
TURCK
Modular Industrial I/O PROFIBUS ®-DP Products
Output Stations
• Rugged, Fully Potted Stations
• Small Footprint
• IP 67 Protection
• Automatic Baud Rate Sensing
Electrical
• Operating Current: <75 mA plus sensor currents (from UB)
• Output Current: See table on facing page (from UL)
Power Distribution
• Outputs: UL Power supply
Mechanical
• Operating Temperature: 0 to +55°C (+32 to +131°F)
• Protection: IP 67
• Vibration: IEC 68, part 2-6
Material
• Connectors: Nickel-plated brass
• Housing: Nylon
SDPB-0008D-0006
SDPB-0008D-0002
Diagnostics (Physical)
• One LED indicates an I/O fault for the entire station
• LEDs to indicate status of PROFIBUS-DP communication
PROFIBUS-DP Pinout
eurofast Male
1 = 5 VDC
2 = BUS_A
3 = Gnd
4 = BUS_B
5 = Shield
5-Pin
Aux. Power
®
picofast Male
picofast ® Female
4-Pin
4-Pin
1 = UB+
2 = UL+
3 = Gnd
4 = Gnd
K47
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Industrial
Automation
I/O
Ma
p
Wi
re
De -Brea
tec
k
tion
Ind
iv
Dia idual
gno
stic
s
nt
Data
Cu
rre
Co
Pin
out
nne
Ou
tp
Co ut
unt
Part Number
cto
rs
Ou
tp
C o uts p
n n e er
cto
r
Outputs
SDPB-0008D-0006
8
0-7
PO
1
0.5 A
1
SDPB-0008D-0002
8
0-7
PO
1
2 A*
1
*Note: Total output current is limited to 4 A.
Output Connectors
PROFIBUS-DP
PO
Mating cordset:
PSG 3M-*
I/O Data Map 1
Out
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0
O-7
O-6
O-5
O-4
O-3
O-2
O-1
O-0
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
K48
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
TURCK
Modular Industrial I/O PROFIBUS ®-DP Products
Discrete Input/Output
Stations
• Rugged, Fully Potted Stations
• Small Footprint
• IP 67 Protection
• Automatic Baud Rate Sensing
Electrical
• Operating Current: <75 mA plus sensor currents (from UB)
• Sensor Current: <500 mA total of all sensors (from UB)
• Output Current: See table on facing page from UL
Power Distribution
• Inputs: UB Power supply
• Outputs: UL Power supply
Mechanical
• Operating Temperature: 0 to +55°C (+32 to +131°F)
• Protection: IP 67
• Vibration: IEC 68, part 2-6
Material
• Connectors: Nickel-plated brass
• Housing: Nylon
SDPB-0404D-0005
SDPB-0404D-0001
Diagnostics (Physical)
• One LED indicates an I/O fault for the entire station
• LEDs to indicate status of PROFIBUS-DP communication
PROFIBUS-DP Pinout
eurofast Male
1 = 5 VDC
2 = BUS_A
3 = Gnd
4 = BUS_B
5 = Shield
5-Pin
Aux. Power
®
picofast Male
picofast ® Female
4-Pin
4-Pin
1 = UB+
2 = UL+
3 = Gnd
4 = Gnd
K49
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Industrial
Automation
Data
I/O
Ma
p
Ind
iv
Dia idual
gno
stic
s
Wi
reB
r
De
tec eak
tion
nt
sor
Sen
Cu
rre
le
Gro
u
Dia p
gno
stic
s
Ind
ivid
Dia ual
gno
stic
s
Wi
reB
r
De
tec eak
tion
Ou
tp
Co ut
unt
Co
nne
cto
rs
Pin
out
Ou
tp
C o uts p
n n e er
cto
r
Outputs
Sty
rs
Pin
out
Inp
u
C o ts per
nne
cto
r
cto
nne
Co
Part Number
Inp
ut C
oun
t
Inputs
SDPB-0404D-0005
4
0-3
PI
1
PNP
4
4-7
PO
1
2 A*
1
SDPB-0404D-0001
4
0-3
PI
1
PNP
4
4-7
PO
1
0.5 A
1
*Note: Total output current is limited to 4 A.
Input/Output Connectors
PO
PROFIBUS-DP
PI
Mating cordset:
PSG 3M-*
Mating cordset:
PSG 3M-*
I/O Data Map 1
In
Out
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0
-
-
-
-
I-3
I-2
I-1
I-0
0
-
-
-
-
O-3
O-2
O-1
O-0
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
K50
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
TURCK
Modular Industrial I/O PROFIBUS ®-DP Products
Analog Input Stations
• Rugged, Fully Potted Stations
• Small Footprint
• IP 67 Protection
• Automatic Baud Rate Sensing
Electrical
• Operating Current: <75 mA plus sensor currents (from UB)
Power Distribution
• Inputs: UB Power supply
Mechanical
• Operating Temperature: 0 to +55°C (+32 to +131°F)
• Protection: IP 67
• Vibration: IEC 68, part 2-6
Material
• Connectors: Nickel-plated brass
• Housing: Nylon
SDPB-40A-0005
SDPB-40A-0007
Diagnostics (Physical)
• One LED indicates an I/O fault for the entire station
• LEDs to indicate status of PROFIBUS-DP communication
PROFIBUS-DP Pinout
eurofast Male
1 = 5 VDC
2 = BUS_A
3 = Gnd
4 = BUS_B
5 = Shield
5-Pin
Aux. Power
picofast Male
picofast Female
4-Pin
4-Pin
1 = UB+
2 = UL+
3 = Gnd
4 = Gnd
K51
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Industrial
Automation
I/O
Ma
p
Wi
re
De -Brea
tec
k
tion
Ind
iv
Dia idual
gno
stic
s
Data
Gro
u
Dia p
gno
stic
s
le
Sty
sor
Sen
Inp
u
C o ts per
nne
cto
r
Pin
out
Co
Inp
Part Number
nne
ut C
cto
oun
rs
t
Inputs
SDPB-40A-0005
4
0-3
AI
1
0 to 10 V
1
SDPB-40A-0007
4
0-3
AI
1
0 to 20 mA
1
Input/Output Connectors
PROFIBUS-DP
AI
Mating cordset:
RK 4.5T-*-RS 4.5T
Applications:
TURCK Sensors:
LU; RK 4.4T-*-RS 4.4T/S1118
LI; RK 4.4T-*-*RS 4.4T/S1120
I/O Data Map 1
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
In
0
Channel 0, MSB
1
Channel 0, LSB
2
Channel 1, MSB
3
Channel 1, LSB
4
Channel 2, MSB
5
Channel 2, LSB
6
Channel 3, MSB
7
Channel 3, LSB
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
K52
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
TURCK
Modular Industrial I/O PROFIBUS ®-DP Products
Temperature Input Stations
• Rugged, Fully Potted Stations
• Small Footprint
• IP 67 Protection
• Automatic Baud Rate Sensing
Electrical
• Operating Current: <75 mA plus sensor currents (from UB)
Power Distribution
• Inputs: UB Power supply
Mechanical
• Operating Temperature: 0 to +55°C (+32 to +131°F)
• Protection: IP 67
• Vibration: IEC 68, part 2-6
Material
• Connectors: Nickel-plated brass
• Housing: Nylon
SDPB-40A-0004
SDPB-40A-0009
Diagnostics (Physical)
• One LED indicates an I/O fault for the entire station
• LEDs to indicate status of Profibus-DP communication
DeviceNet Pinout
eurofast Female
1 = 5 VDC
2 = BUS_A
3 = Gnd
4 = BUS_B
5 = Shield
5-Pin
Aux. Power
®
picofast Male
picofast ® Female
4-Pin
4-Pin
1 = UB+
2 = UL+
3 = Gnd
4 = Gnd
K53
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Industrial
Automation
I/O
Ma
p
Wi
re
De -Brea
tec
k
tion
Ind
iv
Dia idual
gno
stic
s
Data
Gro
u
Dia p
gno
stic
s
le
Sty
sor
Sen
Inp
u
C o ts per
nne
cto
r
Pin
out
cto
Co
Inp
Part Number
nne
ut C
oun
rs
t
Inputs
SDPB-40A-0004
4
0-3
TC
1
TC
1
SDPB-40A-0009
4
0-3
RTD
1
RTD
1
Input/Output Connectors
RTD
Mating connector (field wireable):
WAS5-THERMO
PROFIBUS-DP
TC
Mating cordset:
RK 4.5T-*-RS 4.5T
(includes cold junction compensation)
I/O Data Map 1
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
In
0
Channel 0, MSB
1
Channel 0, LSB
2
Channel 1, MSB
3
Channel 1, LSB
4
Channel 2, MSB
5
Channel 2, LSB
6
Channel 3, MSB
7
Channel 3, LSB
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
K54
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
TURCK
Modular Industrial I/O PROFIBUS ®-DP Products
Analog Output Stations
• Rugged, Fully Potted Stations
• Small Footprint
• IP 67 Protection
• Automatic Baud Rate Sensing
Electrical
• Operating Current: <75 mA (from UB)
Power Distribution
• Outputs: UL Power supply
Mechanical
• Operating Temperature: 0 to +55°C (+32 to +131°F)
• Protection: IP 67
• Vibration: IEC 68, part 2-6
Material
• Connectors: Nickel-plated brass
• Housing: Nylon
SDPB-04A-0009
SDPB-04A-0007
Diagnostics (Physical)
• One LED indicates an I/O fault for the entire station
• LEDs to indicate status of Profibus-DP communication
Proximus-DP Pinout
eurofast Male
1 =5 VDC
2 = BUS_A
3 = Gnd
4 = BUS_B
5 = Shield
5-Pin
Aux. Power
picofast Male
picofast Female
4-Pin
4-Pin
1 = UB+
2 = UL+
3 = Gnd
4 = Gnd
K55
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Industrial
Automation
I/O
Ma
p
Wi
re
De -Brea
tec
k
tion
Ind
iv
Dia idual
gno
stic
s
Data
Ou
tp
C o uts p
n n e er
cto
r
Ou
tpu
t St
yle
Co
Pin
out
nne
Ou
tp
Co ut
unt
Part Number
cto
rs
Outputs
SDPB-04A-0009
4
0-3
AOI
0 to 20 mA
1
1
SDPB-04A-0007
4
0-3
AOV
-10/0 to 10 V
1
1
Output Connectors
AOV
AOI
PROFIBUS-DP
Applications:
TURCK Sensors:
LU; RK 4.4T-*-RS 4.4T/S1118
LI; RK 4.4T-*-*RS 4.4T/S1120
Mating cordset:
RK 4.5T-*-RS 4.5T
Mating cordset:
RK 4.5T-*-RS 4.5T
I/O Data Map 1
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Out
0
Channel 0, MSB
1
Channel 0, LSB
2
Channel 1, MSB
3
Channel 1, LSB
4
Channel 2, MSB
5
Channel 2, LSB
6
Channel 3, MSB
7
Channel 3, LSB
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
K56
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
TURCK
Modular Industrial I/O PROFIBUS ®-DP Products
Counter Station
• Rugged, Fully Potted Stations
• Small Footprint
• IP 67 Protection
• Automatic Baud Rate Sensing
Electrical
• Operating Current: <75 mA plus device currents (from UB)
• Input Current: <500 mA total of all sensors (from UB)
• Output Current: <500 mA per output (from UL)
Power Distribution
• Inputs: UB Power supply
• Outputs: UL Power supply
Mechanical
• Operating Temperature: 0 to +55°C (+32 to +131°F)
• Protection: IP 67
• Vibration: IEC 68, part 2-6
Material
• Connectors: Nickel-plated brass
• Housing: Nylon
SDPB-0202D-0003
Diagnostics (Physical)
• One LED indicates an I/O fault for the entire station
• LEDs to indicate status of PROFIBUS-DP communication
PROFIBUS-DP Pinout
eurofast Female
1 = 5 VDC
2 = BUS_A
3 = Gnd
4 = BUS_B
5 = Shield
5-Pin
Aux. Power
picofast Male
picofast Female
4-Pin
4-Pin
1 = UB+
2 = UL+
3 = Gnd
4 = Gnd
K57
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Industrial
Automation
SDPB-0202D-0003
2
0-3 PCNT
2
Counter
2
0-3 PCNT
2
0.5 A
Data
I/O
Ma
p
Ind
iv
Dia idual
gno
stic
s
Wi
reB
r
De
tec eak
tion
Cu
rre
nt
Outputs
Gro
u
Dia p
gno
stic
s
Ind
ivid
Dia ual
gno
stic
s
Wi
reB
r
De
tec eak
tion
Ou
tp
Co ut
unt
Co
nne
cto
rs
Pin
out
Ou
tp
C o uts p
n n e er
cto
r
le
Sty
sor
Sen
cto
rs
Pin
out
Inp
u
C o ts per
nne
cto
r
nne
Part Number
Co
Inp
ut C
oun
t
Inputs
1
Input/Output Connectors
Mating cordset:
RK 4.5T-*-RS 4.5T
Mating cordset:
RK 4.5T-*-RS 4.5T
PROFIBUS-DP
PCNT
Mating cordset:
RK 4.5T-*-RS 4.5T
Mating cordset:
RK 4.5T-*-RS 4.5T
I/O Data Map 1
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
In
Out
0
Channel 0 - Status
1
Channel 0, Byte 3 (MSB)
2
Channel 0, Byte 2
3
Channel 0, Byte 1
4
Channel 0, Byte 0 (LSB)
5
Channel 1 - Status
6
Channel 1, Byte 3 (MSB)
7
Channel 1, Byte 2
8
Channel 1, Byte 1
9
Channel 1, Byte 0 (LSB)
0
Channel 0 - Control
1
Channel 1 - Control
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
K58
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
TURCK
Modular Industrial I/O PROFIBUS ®-DP Products
Incremental Encoder Station
• Rugged, Fully Potted Stations
• Small Footprint
• IP 67 Protection
• Automatic Baud Rate Sensing
Electrical
• Operating Current: <75 mA plus device currents (from UB)
Power Distribution
• Inputs: UB Power supply
Mechanical
• Operating Temperature: 0 to +55°C
• Protection: IP 67
• Vibration: IEC 68, part 2-6
Material
• Connectors: Nickel-plated brass
• Housing: Nylon
Diagnostics (Physical)
SDPB-10S-0001
• One LED indicates an I/O fault for the entire station
• LEDs to indicate status of PROFIBUS-DP communication
PROFIBUS-DP Pinout
eurofast Female
1 = 5 VDC
2 = BUS_A
3 = Gnd
4 = BUS_B
5 = Shield
5-Pin
Aux. Power
picofast Male
picofast Female
4-Pin
4-Pin
1 = UB+
2 = UL+
3 = Gnd
4 = Gnd
K59
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Industrial
Automation
SDPB-10S-0001
1
0-1
ENC
1
Encoder
I/O
Ma
p
Wi
re
De -Brea
tec
k
tion
Ind
iv
Dia idual
gno
stic
s
Data
Gro
u
Dia p
gno
stic
s
le
Sty
sor
Sen
Inp
u
C o ts per
nne
cto
r
Pin
out
Co
Inp
Part Number
nne
ut C
cto
oun
rs
t
Inputs
1
Input/Output Connectors
PROFIBUS-DP
ENC
1 = V+
2 = Gate
3 = Gnd
4 = Latch
5 = Shield
1=B
2 = +5VDC
3 = Zero
4 = Zero
5=A
6=A
7 = Status
8=B
9 = NC
10 = Gnd
11 = Gnd
12 = V+
I/O Data Map 1
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
In
0
Counter - Status
1
Count Value - High (MSB)
2
Count Value - Low (LSB)
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
K60
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
TURCK
Modular Industrial I/O PROFIBUS ®-DP Products
Serial Interface Stations
• Rugged, Fully Potted Stations
• Small Footprint
• IP 67 Protection
• Automatic Baud Rate Sensing
Electrical
• Operating Current: <75 mA (from UB)
Mechanical
• Operating Temperature: 0 to +55°C (+32 to +131°F)
• Protection: IP 67
• Vibration: IEC 68, part 2-6
Material
• Connectors: Nickel-plated brass
• Housing: Nylon
Diagnostics (Physical)
• One LED indicates an I/O fault for the entire station
• LEDs to indicate status of PROFIBUS-DP communication
SDPB-10S-0002
SDPB-10S-0004
PROFIBUS-DP Pinout
eurofast Female
1= 5 VDC
2 = BUS_A
3 = Gnd
4 = BUS_B
5 = Shield
5-Pin
Aux. Power
®
picofast Male
picofast ® Female
4-Pin
4-Pin
1 = UB+
2 = UL+
3 = Gnd
4 = Gnd
K61
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Industrial
Automation
I/O
Ma
p
Wi
re
De -Brea
tec
k
tion
Ind
iv
Dia idual
gno
stic
s
Data
Da
ta
p e r bytes
tra
nsa
ctio
n
Int
er
T y p face
e
Ch
an
C o nels
n n e per
cto
r
Pin
out
Co
nne
Ch
an
Co n e l
unt
Part Number
cto
rs
I/O
SDPB-10S-0002
0
3
232
1
RS232
3 to 5
1
SDPB-10S-0004
0
3
485
1
RS485/422
3 to 5
1
Input/Output Connectors
485
PROFIBUS-DP
232
Mating cordset:
RK 4.5T-*-RS 4.5T
Mating cordset:
RK 4.5T-*-RS 4.5T
I/O Data Map 1
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0
In
Out
Data Byte 0
1
Status
2
Data Byte 2
3
Data Byte 1
0
Data Byte 0
1
Control
2
Data Byte 2
3
Data Byte 1
Note: Default configuration shown. Up to five bytes can be transferred.
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
K62
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
TURCK
Modular Industrial I/O PROFIBUS ®-DP Products
SSI Station
• Rugged, Fully Potted Stations
• Small Footprint
• IP 67 Protection
• Automatic Baud Rate Sensing
Electrical
• Operating Current: <75 mA plus sensor currents (from UB)
Mechanical
• Operating Temperature: 0 to +55°C (+32 to +131°F)
• Protection: IP 67
• Vibration: IEC 68, part 2-6
Material
• Connectors: Nickel-plated brass
• Housing: Nylon
Diagnostics (Physical)
• One LED indicates an I/O fault for the entire station
• LEDs to indicate status of PROFIBUS-DP communication
SDPB-10S-0005
PROFIBUS-DP Pinout
eurofast Female
1 = 5 VDC
2 = BUS_A
3 = Gnd
4 = BUS_B
5 = Shield
5-Pin
Aux. Power
picofast Male
picofast Female
4-Pin
4-Pin
1 = UB+
2 = UL+
3 = Gnd
4 = Gnd
K63
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Industrial
Automation
SDPB-10S-0005
1
0
SSI
1
SSI
4
I/O
Ma
p
Wi
re
De -Brea
tec
k
tion
Ind
iv
Dia idual
gno
stic
s
Data
Da
ta
p e r bytes
tra
nsa
ctio
n
Int
er
T y p face
e
Ch
an
C o nels
n n e per
cto
r
Co
Pin
out
nne
Ch
an
Co n e l
unt
Part Number
cto
rs
Inputs
1
Input/Output Connectors
SSI
PROFIBUS-DP
1 = Clock2 = Clock+
3 = Data+
4 = Data5 = NC
6 = NC
7 = NC
8 = NC
9 = NC
10 = NC
11 = V+
12 = Ground
Mating cordset:
CKM 12-12-*/S817
I/O Data Map 1
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
In
0
Data Byte 1
1
Data Byte 0 (LSB)
2
Data Byte 3 (MSB)
2
Data Byte 2
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
K64
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
TURCK
Modular Industrial I/O PROFIBUS ®-DP Products
Piconet Gateways
• Rugged, Fully Potted Stations
• Small Footprint
• IP 67 Protection
• Automatic Baud Rate Sensing
Electrical
• Operating Current: <75 mA plus sensor currents (from UB)
• Sensor Current: <500 mA total of all sensors (from UB)
• Output Current: <500 mA per output (from UL)
Power Distribution
• Inputs: UB Power supply
• Outputs: UL Power supply
Mechanical
• Operating Temperature: 0 to +55°C (+32 to +131°F)
• Protection: IP 67
• Vibration: IEC 68, part 2-6
Material
• Connectors: Nickel-plated brass
• Housing: Nylon
Diagnostics (Physical)
SDPL-0404D-0003
SDPL-0404D-0004
SDPL-0404D-1003
SDPL-0404D-1004
• One LED indicates an I/O fault for the entire station
• LEDs to indicate status of PROFIBUS-DP communication
PROFIBUS eurofast ® Pinouts
Male
Female
5-Pin
5-Pin
1 = 5 VDC
2 = BUS_A
3 = Gnd
4 = BUS_B
5 = Shield
...1003 and ...1004 have both male and
female PROFIBUS-DP connectors
Aux. Power
®
picofast Male picofast ® Female
4-Pin
1 = UB+
2 = UL+
K65
4-Pin
3 = Gnd
4 = Gnd
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Industrial
Automation
Data
Ind
iv
Dia idual
gno
stic
s
Wi
reDe Brea
tec
k
tion
I/O
Ma
p
Ou
tp
C o uts p
n n e er
cto
r
Cu
rre
nt
Outputs
Gro
u
Dia p
gno
stic
s
Ind
ivid
Dia ual
gno
stic
s
Wi
reB
r
De
tec eak
tion
Ou
tpu
Co t
unt
Co
nne
cto
rs
Pin
out
le
Sty
sor
Sen
rs
Pin
out
Inp
u
C o ts per
nne
cto
r
cto
Co
Inp
Part Number
nne
ut C
oun
t
Inputs
SDPL-0404D-0003
4
0-3
PI
1
PNP
4
4-7
PO
1
0.5 A
1
SDPL-0404D-0004
4
0-3
2S
2
PNP
4
2-3
2G
2
0.5 A
1
SDPL-0404D-1003
4
0-3
PI
1
PNP
4
4-7
PO
2
0.5 A
1
SDPL-0404D-1004
4
0-3
2S
1
PNP
4
2-3
2G
2
0.5 A
1
Input/Output Connectors
2G
Mating cordset:
RK 4.4T-*-RS 4.4T
Splitter:
VBRS 4.4-2RK 4T-*/*
PI
PROFIBUS-DP
2S
Mating cordset:
PSG 3M-*
Mating cordset:
RK 4.4T-*-RS 4.4T
Splitter:
VBRS 4.4-2RK 4T-*/*
PO
Mating cordset:
PSG 3M-*
I/O Data Map 1
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
In
Out
0
Data from next input
modules
I-3
I-2
I-1
I-0
0
Data for next output
modules
O-3
O-2
O-1
O-0
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
K66
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
TURCK
Modular Industrial I/O PROFIBUS ®-DP Products
PROFIBUS-DP to AS-interface Gateways
AS-I systems can be easily connected to a higher-level network, like PROFIBUS, through a gateway master. The gateway
acts as a master to the AS-I system(s) and a slave to the PROFIBUS system, mapping all of the AS-I data for PROFIBUS in a
single block.
For AS-I specifications and rating details see section E of this catalog.
PROFIBUS-DP System
(Gateway is the Slave)
AS-I System
(Gateway is the Master)
K67
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Industrial
Automation
Addressing
PROFIBUS ® stations must have a network address for communication. The address for AS-I/ PROFIBUS gateways may be
set via the on-unit display and push buttons. Please consult the manual for a particular gateway for instruction on the
procedure.
Diagnostics
AS-I/ PROFIBUS gateways contain LEDs for diagnosing I/O and communication problems for AS-I and PROFIBUS. For a
detailed description of the LED states please see the Bihl+Wiedemann AS-I/ PROFIBUS Gateway User Manual available for
download from www.bihl-wiedemann.com.
Power
PROFIBUS-DP
Most AS-I/ PROFIBUS gateways draw power from the AS-I power supply. The option to use a separate, non-AS-I power
supply is also available. Consult the gateway documentation to ensure that the gateway being selected meets the
requirements of your system.
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
K68
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
TURCK
Modular Industrial I/O PROFIBUS ®-DP Products
AS-I Profibus-DP Gateways in
Stainless Steel
• AS-I v3.0 Supported
• Integrated Ground-Fault Detection
• Graphical Display
• Integrated AS-I Diagnostics
Electrical
• Operating Current: 200 mA from VAS-I (Power Supply A)
200 mA from VAS-i1, 70mA from VAS-i2 (Power Supply A2)
250 mA from VAUX (Power Supply E)
Power Distribution
• From AS-I supply for each network (Power Supply A, A2)
• From external supply (Power Supply E)
Mechanical
• Operating Temperature: 0 to +55°C (+32 to +131°F)
• Protection: IP 20
ASI-DPG-SS BW1567*
ASI-DPG-SS BW1568*
ASI-DPG-SS BW1569*
ASI-DPG-SS-SE BW1773*
ASI-DPG-SS-SE BW1774*
ASI-DPG-SS-C1D2 BW1653
ASI-DPG-SS-C1D2 BW1654
ASI-DPG-SS-C1D2 BW1655
Material
• Housing: Stainless Steel
Diagnostics (Logical)
• Health of AS-I network is available via Proximus-DP interface
Diagnostics (Physical)
• LED to indicate status of network and AS-I communication and power supply
* Not ETL Listed
PROFIBUS-DP Connector
1 = Shield
3 = BUS_B
5 = DGnd
6 = +5 VDC
8 = BUS_A
K69
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
ASI-DPG-SS BW1567
PROFIBUS-DP
A
2.1
1
X
X
ASI-DPG-SS BW1568
PROFIBUS-DP
A2
2.1
2
X
X
ASI-DPG-SS BW1569
PROFIBUS-DP
E
2.1
2
X
X
ASI-DPG-SS-SE BW1773
PROFIBUS-DP
A
2.1
1
ASI-DPG-SS-SE BW1774
PROFIBUS-DP
A2
2.1
2
ASI-DPG-SS-C1D2 BW1653
PROFIBUS-DP
A
3.0
1
ASI-DPG-SS-C1D2 BW1654
PROFIBUS-DP
A2
3.0
2
ASI-DPG-SS-C1D2 BW1655
PROFIBUS-DP
E
3.0
2
A
A2
PROFIBUS-DP
Pro
g
Int ramm
erf
ace ing
Du
pl
Ad icate
dre
De ss
tec
tion
#o
f
Ma AS-I
ste
rs
ion
ers
ASIV
Part Number
Pow
er S
tyle
Hig
he
Ne r Lev
two el
rk
Industrial
Automation
E
A - Single AS-I network is powered by and AS-I power supply
A2 - Dual AS-I networks are each powered by their own AS-I power supply
E - Dual AS-I networks are both powered by a single 30 VDC supply, decoupled through the gateway
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
K70
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
TURCK
Modular Industrial I/O PROFIBUS ®-DP Products
AS-I PROFIBUS-D Economy
Gateways
• AS-I v3.0 Supported
• PROFIBUS-DP Support
• LED Display
• Integrated AS-I Diagnostics
Electrical
• Operating Current: <300 mA from AS-I
Power Distribution
• From AS-I supply
Mechanical
• Operating Temperature: 0 to +55°C (+32 to +131°F)
• Protection: IP 20
Material
• Housing: Stainless Steel
Diagnostics (Logical)
• AS-I diagnostic data is available via Network interface
Diagnostics (Physical)
• LEDs to indicate status of network and AS-I communication and power supply
ASI-DPG-SS-B BW1746
PROFIBUS-DP Connector
1 = Shield
3 = BUS_B
5 = DGnd
6 = +5 VDC
8 = BUS_A
K71
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
ASI-DPB-SS BW1746
PROFIBUS-DP
A
2.1
A
#o
f
Ma AS-I
ste
rs
Co
nn
Dia ectio
gra n
m
ion
ers
ASIV
Pow
er S
tyle
Part Number
Hig
he
Ne r Lev
two el
rk
Industrial
Automation
1
PROFIBUS-DP
A
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
K72
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
TURCK
Modular Industrial I/O PROFIBUS ®-DP Products
AS-I PROFIBUS-DP Gateways
• AS-I v2.1 Supported
• IP 65 Protection
• 2-Digit Display
• Integrated AS-I Diagnostics
Electrical
• Operating Current: 200 mA from VAS-I
Power Distribution
• From AS-I supply for each network
Mechanical
• Operating Temperature: 0 to +55°C (+32 to +131°F)
• Protection: IP 65
ASI-DPG BW1253
ASI-DPG BW1371
Material
• Housing: Plastic
Diagnostics (Logical)
• Health of AS-I network is available via Network interface
Diagnostics (Physical)
• LEDs to indicate status of network and AS-I communication and power supply
PROFIBUS eurofast ®
Pinouts
Female
1 = 5 VDC*
2 = BUS _A
3 = Gnd
4 = BUS_B
5 = Shield
* Female connector
only
5-Pin
BW1371 only
K73
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
ASI-DPG BW1253
PROFIBUS-DP
A
2.1
1
1
ASI-DPG BW1371
PROFIBUS-DP
A
2.1
1
1
Pro
g
Int ramm
erf
ace ing
Du
pl
Ad icate
dre
De ss
tec
tion
#o
f
Ma AS-I
ste
rs
Co
nn
Dia ectio
gra n
m
ion
ASIV
ers
Pow
er S
tyle
Part Number
Hig
he
Ne r Lev
two el
rk
Industrial
Automation
A - Single AS-I network is powered by and AS-I power supply
PROFIBUS-DP
1
1
BUS_A
2
BUS_B
3
BUS_A
4
BUS_B
5
0V
6
Shield
7
FG (Function Gnd)
8
FG (Function Gnd)
9
Shield
10
+5V
Note: AS-I connections are made via standard AS-I base modules ASI-BM BW1180 or ASI-BM BW1182 (see p. E103-104)
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
K74
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
TURCK
Modular Industrial I/O PROFIBUS ®-DP Products
BL67 Gateway
• Modular I/O
• IP 67 Protection
• Fieldbus Independent Configuration
• Various I/O Styles
Electrical
• Operating Current: <50 mA from VI
• Supply Current: <10 A to I/O (from VI and VO)
• Backplane Current: <1.5 A (from VI)
Mechanical
• Operating Temperature: -25 to +55°C (+32 to +131°F)
• Protection: IP 67
• Vibration: 5 g @ 10-500 Hz
Material
BL67-GW-DP
• Housing: PC-V0 (Lexan)
Diagnostics (Logical)
• Diagnostic information available through the PROFIBUS-DP interface
Diagnostics (Physical)
• LEDs to indicate status of PROFIBUS-DP and Module Bus communication
PROFIBUS eurofast ® Pinouts
1 = 5 VDC*
2 = BUS _A
3 = Gnd
4 = BUS_B
5 = Shield
* Female
connector only
Male
Female
5-Pin
5-Pin
minifast ® Power
Pinouts
Male
1 = Gnd
2 = Gnd
3 = PE
4 = VI
5 = VO
5-Pin
Note: Power feeding modules may be used for I/O current supply to prevent overloading the gateway power supply.
K75
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Industrial
Automation
PROFIBUS ®-DP BL67 Stations
TURCK's BL67 is a modular, user configurable network I/O system designed to allow installation of nodes containing
different types and sizes of I/O depending on the users needs for a particular area. Featuring IP 67 protection and metal
threaded connectors, the BL67 can often be mounted in the physical process environment or directly on a machine without
a separate enclosure for the I/O. This saves planning and installation time, as well as the cost of the enclosure itself.
The BL67 system supports several different network protocols, including PROFIBUS-DP. A BL67 station consists of a
gateway module that interfaces to the PROFIBUS system, and several I/O modules that interface with the physical I/O in the
field. Different connector options are available to allow a greater level of customization to the user.
For more details on the BL67 system, please see section G of this catalog.
PROFIBUS-DP
TURCK's I/O Assistant software package is used to configure the BL67 system.
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
K76
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
TURCK
Modular Industrial I/O PROFIBUS ®-DP Products
BL20 Gateway
• Modular I/O
• IP 20 Protection
• Fieldbus Independent Configuration
• Various I/O Styles
Electrical
• Operating Current: <430 mA from BR power supply (USYS)
• Supply Current: <10 A to I/O (from UL)
<1.5 A to backplane (from USYS)
Mechanical
• Operating Temperature: 0 to +55°C (+32 to +131°F)
• Protection: IP 20
• Vibration: 1 g @ 5...100 Hz
Material
• Housing: PC-V0 (Lexan)
Diagnostics (Logical)
BL20-GWBR-PBDP
• Diagnostic information available through the PROFIBUS-DP interface
Diagnostics (Physical)
• LEDs to indicate status of PROFIBUS-DP and Module Bus communication
Power Connectors
PROFIBUS-DP Connector
1 = Shield
3 = BUS_B
5 = Gnd
6 = +VDC
8 = BUS_A
K77
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Industrial
Automation
PROFIBUS ®-DP BL20 Stations
TURCK's BL20 is a modular, user configurable network I/O system designed to allow installation of nodes containing
different types and sizes of I/O depending on the users needs for a particular area. Featuring IP 20 protection and terminal
point connections, the BL20 is intended to be mounted in the control cabinet or in a field enclosure.
The BL20 system supports several different network protocols, including PROFIBUS-DP. A BL20 station consists of a
gateway module that interfaces to the PROFIBUS system, and several I/O modules that interface with the physical I/O in the
field. The terminal bases are available with tension clamp or screw terminal connector types.
For more details on the BL20 system, please see section H of this catalog.
PROFIBUS-DP
TURCK's I/O Assistant software package is used to configure the BL20 system.
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
K78
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
TURCK
Network Media Products
PROFIBUS®-DP
Media
L1
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708 www.turck.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Industrial
Automation
Cables
Terminating Resistors
Feed Through Connectors
L4 - L10
L12
L13
Bus Tees
Field Wireable Connectors
Receptacles
L14
L11, L15
L16
Wall Plate Adapters
PROFIBUS®-PA Media
L20
L19
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708 www.turck.com
PROFIBUS-DP Media
PROFIBUS®-DP, Selection Guide
L2
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
TURCK
Network Media Products
Notes:
L3
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708 www.turck.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Industrial
Automation
PROFIBUS®-DP, Cable Specifications
Braided Shield
Jacket
• Cable that Meets the Requirements of
Drain Wire
EN50170-2-2:1996 for Communications
Up to 12 Mbaud
White
Blue
Green
Red
Figure B
Mylar Tape
Aluminum Mylar Foil Shielded
Jacket
Inner Jacket
Jacket
Drain Wire
Drain Wire
Red
Figure A
Red
Green
Figure C
Green
Foil Shield
Foil Shield
Braided Shield
Baud Rate (k baud)
9.6
19.2
93.75
187.5
500
1500
1200
Maximum Trunk Length
1200 meters
1200 meters
1200 meters
1000 meters
400 meters
200 meters
100 meters
Data Pair
Type
455
AWM 2464
75°C 300 Volts
456
AWM 20233
80°C 300 Volts
457
75°C 300 Volts
458
AWM 20233
80°C 300 Volts
4511
AWM 2464
75°C 300 Volts
4510A
75°C 300 Volts
Approvals
590
AWM 2464
75°C 300 Volts
Shields
Material Color
Nominal O.D.
Type
Drain Wire
Bulk Cable
Part Number / Figure
Weight/300 M
2/22 AWG
RD/GN
16.5 Ohms
PE
None
N/A
PVC Purple
8.5 mm (.335 in)
Foil/Braid
22 AWG
RB50672-*M
62 lbs.
A
NEC AWM
CEC AWM-I/II A/B FT4
2/22 AWG
RD/GN
16.5 Ohms
PE
None
N/A
PUR Purple
7.9 mm (.310 in)
Foil/Braid
22 AWG
RB50683-*M
48 lbs.
A
NEC CMX
2/22 AWG
RD/GN
16.5 Ohms
PE
None
N/A
PUR Purple
8.0 mm (0.315 in)
Foil/Braid
No Drain
RB50708-*M
51 lbs.
A
NEC AWM
CEC AWM-I/II A/B FT4
2/22 AWG
RD/GN
16.5 Ohms
PE
None
N/A
TPU Plum
8.5 mm (0.335 in)
Foil/Braid
22 AWG
RB50692-*M
58 lbs.
flexlife-10 ® †
A
NEC PLTC
CEC AWM-I/II A/B FT4
2/22 AWG
RD/GN
16.5 Ohms
PE
None
N/A
PVC Purple
8.5 mm (.319 in)
Foil/Braid
22 AWG
RB50881-*M
64 lbs.
flexlife-10 †
A
NEC PLTC
CEC CM-CMG
HL ABCD
2/22 AWG
RD/GN
16.5 Ohms
PE
None
N/A
Aluminum
Armor/PVC
15.4 mm (.605 in)
Foil/Braid
22 AWG
RB50875-*M
112 lbs.
armorfast ®
C
2/22 AWG
RD/GN
16.5 Ohms
PE
None
N/A
PUR Purple
7.5 mm (0.295 in)
Foil/Braid
22 AWG
RB51225-*M
42 lbs.
Halogen-Free††
A
NEC PLTC/ISO
Open Wiring
CEC CMG
2/22 AWG
RD/GN
16.5 Ohms
PE
None
N/A
PVC Purple
11.1 mm (.435 in)
Foil/Braid
22 AWG
RB51259-*M
93 lbs.
A
NEC PLTC
CEC AWM-I/II A/B FT4
2/22 AWG
RD/GN
16.5 Ohms
PE
2/22 AWG
BU/WH
16.5 Ohms
PE
PVC Purple
9.6 mm (.380 in)
Foil/Braid
22 AWG
RB51057-*M
75 lbs.
B
80°C 300 Volts
4516
AWG
DCR (/1000 feet)
AWG
DCR (/1000 feet)
Color Code
Insulation
Color Code
Insulation
Outer Jacket
NEC PLTC
CEC AWM-I/II A/B FT4
4515
105° 300 Volt
2nd Data Pair
PROFIBUS-DP Media
Aluminum Armor
* Indicates length in meters.
Standard cable lengths are 1, 2, 4, 5, 6, 8, 10, 15, and in +5 meter increments from there. Consult factory for other lengths.
† See page A6 for flexlife performance.
†† Zero Halogen: to DIN VDE 0472 part 815 + IEC 60754-1
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708 www.turck.com
L4
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
TURCK
Network Media Products
PROFIBUS®-DP, (M12x1) eurofast ®Cable and Cordset Selection Matrix
eurofast
Pin (Male)
1
Socket (Female)
3
2
4
RSSW
WSSW
RKSW
WKSW
RSSW 45x-*M
WSSW 45x-*M
RKSW 45x-*M
WKSW 45x-*M
RSSW RSSW 45x-*M
RSSW WSSW 45x-*M
RSSW RKSW 45x-*M
RSSW WKSW 45x-*M
WSSW WSSW 45x-*M
WSSW RKSW 45x-*M
WSSW WKSW 45x-*M
RKSW RKSW 45x-*M
RKSW WKSW 45x-*M
Bare
RSSW
3
WSSW
Socket (Female)
eurofast
Pin (Male)
1
2
RKSW
4
WKSW WKSW 45x-*M
WKSW
See page L6 for dimensional drawings.
* Indicates length in meters.
x Indicates cable type.
Refer to the Cordset Builder at www.turck.com for assistance with cordset/cable combinations.
Standard cable lengths are 1, 2, 4, 5, 6, 8, 10, 15, and in +5 meter increments from there. Consult factory for other lengths.
For stainless steel coupling nuts change part number RSSW...RSSWV.
Change 45 to 59 for 59x series cordsets.
Pinouts
L5
eurofast
45 series pinout
59 series pinout
eurofast
Male
1. N/C
2. Green (TxD)
3. N/C
4. Red (RxD)
5. Bare (Shield Drain Wire)
1. Blue (TxD_1)
2. Green (TxD)
3. White (RxD_1)
4. Red (RxD)
5. Bare (Shield Drain Wire)
Female
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708 www.turck.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Industrial
Automation
PROFIBUS®-DP, (M12x1) eurofast ® Cable and Cordsets
Specifications
PUR (Polyurethane)
Nickel Plated CuZn or Stainless Steel
TPU (Polyurethane) or POM (Nylon)
Gold Plated CuZn
NEMA 1, 3, 4, 6P and IEC IP 68
250 V
4A
-40° to +75°C (-22° to +167°F)
1
RSSW ..
2
Page L5, L7, L8
RKSW ..
3
PROFIBUS-DP Media
Housing:
Coupling Nut:
Contact Carrier:
Contacts:
Protection:
Rated Voltage:
Rated Current:
Ambient Temperature:
Page L5, L7, L8
4
WSSW ..
Page L5, L7, L8
WKSW ..
Page L5, L7, L8
RSAW ..
(armorfast only)
RKAW ..
(armorfast only)
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708 www.turck.com
L6
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
TURCK
Network Media Products
PROFIBUS®-DP, (M12x1) eurofast ® Cable and Cordset Selection Matrix
eurofast
Socket (Female)
Pin (Male)
Terminator
7
3
2
4
10
Socket (Female)
11
Bare
RSSW
WSSW
RKSW
WKSW
FSSDWE
FKSDWE
D9S/T 45x-*M
RSSW D9S/T
45x-*M
WSSW D9S/T
45x-*M
RKSW D9S/T
45x-*M
WKSW D9S/T
45x-*M
FSSDWE D9S/T
45x-*M
FKSDWE D9S/T
45x-*M
D9SM/T 45x-*M
RSSW D9SM/T
45x-*M
WSSW D9SM/T
45x-*M
RKSW D9SM/T
45x-*M
WKSW D9SM/T
45x-*M
FSSDWE D9SM/T
45x-*M
FKSDWE D9SM/T
45x-*M
D9S/T
Master
9-Pin Sub D Connector
1
Pin (Male)
8
D9SM/T
See page L6 - L10 for dimensional drawings.
* Indicates length in meters.
x Indicates cable type.
Refer to the Cordset Builder at www.turck.com for assistance with cordset/cable combinations.
Standard cable lengths are 1, 2, 4, 5, 6, 8, 10, 15, and in +5 meter increments from there. Consult factory for other lengths.
For stainless steel coupling nuts change part number RSSW...RSSW.
Extension example:
Pinouts
eurofast
45 series pinout
Male
1. N/C
2. Green (TxD)
3. N/C
4. Red (RxD)
5. Bare (Shield Drain Wire)
L7
eurofast
D9
Female
Male
D9 pinout
1 = N/C
2 = N/C
3 = RD (RXD)
4 = N/C
5 = N/C
6 = N/C
7 = N/C
8 = GN (TXD)
9 = N/C
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708 www.turck.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Industrial
Automation
PROFIBUS®-DP, (M12x1) eurofast ® Cable and Cordset Selection Matrix
eurofast
Socket (Female)
Pin (Male)
1
Node
Bare
7
3
2
RSSW
WSSW
Pin (Male)
10
4
RKSW
WKSW
Socket (Female)
11
FSSDWE
FKSDWE
D9S 45x-*M
RSSW D9S RSSW WSSW D9S WSSW RKSW D9S RKSW WKSW D9S WKSW FSSDWE D9S FSSDWE FKSDWE D9S FKSDWE
45x-*M-*M
45x-*M-*M
45x-*M-*M
45x-*M-*M
45x-*M-*M
45x-*M-*M
SD9S 45x-*M
RSSW SD9S RSSW WSSW SD9S WSSW RKSW SD9S RKSW WKSW SD9S WKSW FSSDWE SD9S FSSDWE FKSDWE SD9S FKSDWE
45x-*M-*M
45x-*M-*M
45x-*M-*M
45x-*M-*M
45x-*M-*M
45x-*M-*M
Straight
D9S
9
Node
eurofast
Pin (Male)
7
PROFIBUS-DP Media
SD9S
Socket (Female)
1
3
10
2
4
11
Bare
RSSW/RKSW
WSSW/WKSW
RSSW/RKSW
D9S 45x-*M
RSSW D9S RKSW
45x-*M-*M
WSSW D9S WKSW
45x-*M-*M
FSSDWE D9S FKSDWE
45x-*M-*M
SD9S 45x-*M
RSSW SD9S RKSW
45x-*M-*M
WSSW SD9S WKSW
45x-*M-*M
FSSDWE SD9S FKSDWE
45x-*M-*M
Straight
D9S
9
SD9S
See page L6 - L10 for dimensional drawings.
* Indicates length in meters.
x Indicates cable type.
Refer to the Cordset Builder at www.turck.com for assistance with cordset/cable combinations.
Standard cable lengths are 1, 2, 4, 5, 6, 8, 10, 15, and in +5 meter increments from there. Consult factory for other lengths.
For stainless steel coupling nuts change part number RSSW...RSSW.
Pinouts
eurofast
45 series pinout
Male
1. N/C
2. Green (TxD)
3. N/C
4. Red (RxD)
5. Bare (Shield Drain Wire)
eurofast
D9
Female
Male
D9 pinout
1 = N/C
2 = N/C
3 = RD (RXD)
4 = N/C
5 = N/C
6 = N/C
7 = N/C
8 = GN (TXD)
9 = N/C
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708 www.turck.com
L8
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
TURCK
Network Media Products
PROFIBUS®-DP (M12x1), eurofast ® Retractile Cordsets
• Single or Double Ended
• Available in 1, 2, 5 Meter Extended Lengths
Part Number
Specs
RSSW 456SP-5M
Pinouts
(M12x1) eurofast male connector
1 M extended length
.25 M retracted length
RSSW 456SP-1M
RSSW 456SP-2M
Application
PUR (Polyurethane)
250 V, 4 A
-40° to +80°C
(M12x1) eurofast male connector
2 M extended length
.5 M retracted length
1.
2.
3.
4.
5.
NC
GN
NC
RD
Drain
(M12x1) eurofast male connector
5 M extended length
1.12 M retracted length
Single ended cordset part numbers shown. Also available in double ended (M12x1) eurofast connectors.
L9
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708 www.turck.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Industrial
Automation
PROFIBUS®-DP, Field Wireable D9 Connectors
Specifications - (D9)
Housing:
Terminating Switch:
Protection:
Rated Voltage:
Rated Current:
Temperature Rating:
Specifications (FKSDWE .. FSFDWE)
TPU (Polyurethane)
Yes
IEC IP 20
250 V
5A
-25° to +60°C
Housing:
Coupling Nut:
Contact Carrier:
Contacts:
Protection:
Rated Voltage:
Rated Current:
Temperature
Rating:
*Max. Cable diameter: 8.5 mm
-40° to +75°C
8
PROFIBUS-DP Media
7
PUR (Polyurethane)
Nickel Plated CuZn or Stainless Steel
TPU (Polyurethane) or POM (Nylon)
Gold Plated CuZn
NEMA 1, 3, 4, 6P and IEC IP 67
250 V
4A
Connector, PDP, D9S
Page L7
Connector, PDP, D9SM
Page L7
9
Note: Part numbers are for ordering connector only.
Cable must be ordered separately.
Connector, PDP, SD9S
Page L7
10
FSSDWE ..
11
Page L8
FKSDWE ..
Page L8
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708 www.turck.com
L10
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
TURCK
Network Media Products
PROFIBUS®-DP, Field Wireable D9 Connectors
• Provides Connection to Master or Node
in the field
• Maximum Cable O.D. is 8.5 mm
Housing
Part Number
Specs
Application
Pinouts
Right Angle,
Terminating Switch
Connector,PDP,D9S
250 V, 5 A
-25° to +80°C
Straight, Terminating
Switch
Connector,PDP,SD9S
Connector,PDP,D9SM
L11
250 V, 4 A
-25° to +80°C
1.
2.
3.
4.
5.
6.
7.
8.
9.
N/C
N/C
RD (Bus_B)
N/C
N/C
N/C
N/C
Green (Bus_A)
N/C
Male
Right Angle, Master,
Terminating Switch
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708 www.turck.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Industrial
Automation
PROFIBUS®-DP, Terminating Resistors
• Terminating Resistors Stabilize and
Minimize Reflections on the Bus Line
• A Terminating Resistor is Required at the
Beginning and End of the Main Bus Line
Part Number
Specs
Application
Pinouts
eurofast ® Terminating
Resistor
RSSW 45-TR
•
•
Internal resistor
•
Reverse keyed
Male eurofast
connector
eurofast Terminating
Resistor
RKSW 45-TR
Nickel Plated
Brass
250 V, 4 A
-40° to +75°C
•
•
Internal resistor
•
Reverse keyed
Female eurofast
connector
Active Terminating
Resistor
•
PDP-TRA
•
Pinout Diagram, RSSW 45-TR
Pinout Diagram, RKSW 45-TR
Ω
External power
supply minifast ®
and eurofast
connector
LED signal for
power status
1.
2.
3.
4.
5.
N/C
GN
N/C
RD
BARE
See Below
1.
2.
3.
4.
5.
N/C
GN
N/C
RD
BARE
See Below
1.
2.
3.
4.
5.
N/C
BUS_A
N/C
BUS_B
N/C
See Below
1.
2.
3.
4.
5.
N/C
GND
N/C
UI=24 VDC
N/C
PROFIBUS-DP Media
Housing
Male
Pinout Diagram, PDP-TRA
Ω
Ω
Ω
eurofast Male Connector
Ω
Ω
eurofast Female Connector
eurofast Male Connector
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708 www.turck.com
L12
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
TURCK
Network Media Products
PROFIBUS®-DP, eurofast ® Feed Through Receptacle
• Provides Bulkhead Panel Mount
Connection
Housing
Part Number
Specs
Application
Pinouts
Male
FKW FSW 45/M12
Nickel Plated Brass or
Stainless Steel
250 V, 4 A
-40° to +75°C
eurofast Feed Through
Connection
•
Straight male/female
connector
•
For pre-molded reverse
keyed eurofast cables
Female
For stainless steel change part number to FKWV FSWV 45/M12
L13
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708 www.turck.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Industrial
Automation
PROFIBUS®-DP, eurofast ® Bus Tees
• Creates a Branch from the Main Bus Line
Housing
Part Number
Specs
Application
Wiring Diagrams
RKSW 2RSSW 45
•
Male eurofast
drop connector
•
Fully shielded
eurofast tee
PROFIBUS-DP Media
eurofast Bus Tee
eurofast Terminating
Resistor
PUR
•
Male eurofast
connector
Nickel Plated
Brass
250 V, 4 A
-40° to +75°C
•
Fully shielded
eurofast tee
* RKSW 2RSSW 45-0001 (Polyurethane)
Y Junction
•
VB2/FSW/FKW/FSW 45
Fully shielded
eurofast
connectors
* This part must be used when joining two tees together directly. A female terminating resistor will not work with this tee since there is no ground and
power connection on the male side.
Pinouts
eurofast
Male
Female
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708 www.turck.com
L14
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
TURCK
Network Media Products
PROFIBUS®-DP, eurofast ® Field Wireable Connectors
• Allows Transition from Hard Wiring to
Quick Connection to Network
Housing
Part Number
BMSWS 8151-8.5
BMSWS 8251-8.5
BMWS 8151-8.5
BMWS 8251-8.5
L15
Specs
Application
Nickel Plated Brass
PG 9 cable gland,
accepts 4-9 mm cable diameter
Screw terminal
accepts up to 18 AWG conductors
85°C
125 V, 4 A
Nickel Plated Brass
PG 9 cable gland,
accepts 4-9 mm cable diameter
Screw terminal
accepts up to 18 AWG conductors
85°C
125 V, 4 A
Nickel Plated Brass
PG 9 cable gland,
accepts 4-9 mm cable diameter
Screw terminal
accepts up to 18 AWG conductors
85°C
125 V, 4 A
Pinouts
Male
•
Metal, fully
shielded
•
Mates with
reverse key 5-pin
cordsets and
receptacles
Female
Nickel Plated Brass
PG 9 cable gland,
accepts 4-9 mm cable diameter
Screw terminal
accepts up to 18 AWG conductors
85°C
125 V, 4 A
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708 www.turck.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Industrial
Automation
PROFIBUS®-DP, Circuit Board Connectors and OEM Receptacles
• Provides (M12x1) eurofast ® Connection
to Field Devices
Housing
Part Number
Specs
Application
Pinouts
13
Male eurofast PCB
pins
FSFDW 45 PCB
12
PROFIBUS-DP Media
Male
Male eurofast solder
cups
FSFDLW 45
14
WFSW 45 PCB
Nickel Plated CuZn Male eurofast right
or Stainless Steel
angle PCB pins
250 V, 4 A
-40° to +75°C
1.
2.
3.
4.
5.
N/C
GN
N/C
RD
BARE
16
FKFDW 45 PCB
Female eurofast PCB
pins
Female
15
FKFDLW 45
Male eurofast solder
cups
See pages L18 for dimensional drawings.
Standard housing material is nickel plated brass "FKFD .."; "FKFDV .." indicates 316 stainless steel.
Panel Cutout
FKFD ... FSFD
Board Layout (reference only)
FKFD ... FSFD
Panel Cutout
WFS
Board Layout (reference only)
WFS
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708 www.turck.com
L16
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
TURCK
Network Media Products
PROFIBUS®-DP, Circuit Board Connectors and OEM Receptacles
• Provides (M12x1) eurofast ® Connection
to Field Devices
Housing
Part Number
Specs
Application
Pinouts
17
•
Male eurofast with
mounting kit
•
Reverse key
•
•
Male eurofast
FSW 45 PCB KIT
Male
18
FSW 45 PCB
Nickel Plated CuZn
or Stainless Steel
250 V, 4 A
-30° to +75°C
19
Reverse key
1.
2.
3.
4.
5.
•
Female eurofast
with mounting kit
•
Reverse key
•
•
Female eurofast
FKW 45 PCB KIT
N/C
GN
N/C
RD
BARE
Female
20
FK 45 PCB
Reverse key
See pages L19 for dimensional drawings.
Standard housing material is nickel plated brass "FKFD .."; "FKFDV .." indicates 316 stainless steel.
Board Layout (reference only)
FK ... FS
L17
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708 www.turck.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Industrial
Automation
eurofast ® PCB Mount Male and Female Receptacles
12
FSFDLW ..
15
Page L16
FKFDLW ..
16
PROFIBUS-DP Media
13
Page L16
FSFDW ..PCB
Page L16
FKFDW ..PCB
Page L16
14
WFSW ..PCB
Page L16
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708 www.turck.com
L18
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
TURCK
Network Media Products
eurofast ® PCB Mount Male and Female Receptacles
17
FSW 45 PCB KIT
18
Page L17
FSW 45 PCB
19
FKW 45 PCB KIT
L19
Page L17
20
Page L17
FK 45 PCB
Page L17
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708 www.turck.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Industrial
Automation
PROFIBUS®-DP, eurofast ® Wall Plate Adapters
• Gasket and Mounting Screws Provided
• For Use with a Single Gang Electrical Box
Part Number
Specs
Stainless Steel
250 V, 4.0 A
BPA-45-E113 -40 to +70°C
(-40 to +158°F)
Application
Pinouts
Attaches to standard
single gang electrical
box for transition to
5-wire (M12x1)
eurofast connector
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708 www.turck.com
PROFIBUS-DP Media
Housing
L20
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
TURCK
Network Media Products
PROFIBUS®-PA
L21
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708 www.turck.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Industrial
Automation
PROFIBUS®-PA Overview
PROFIBUS-PA (Process Automation) uses synchronous transfer mode technology, as defined in IEC 61158-2, to
communicate between field devices and the RS 485 backbone of PROFIBUS®-DP. A segment coupler, or gateway is
installed to bridge PROFIBUS-DP with PROFIBUS-PA. Otherwise, the protocols are identical, allowing transparent
communication between general purpose automation systems and decentralized field devices.
PROFIBUS-PA is a master-slave bus. Transmitters used in the process industry are typically slave devices or passive stations
which only communicate at the request of the master.
General Layout Topologies
PROFIBUS-PA Media
The topology for PROFIBUS-DP is a linear bus. Branching can be accomplished with repeaters or, in the case of
PROFIBUS-PA, this can be accomplished with the segment couplers. The PROFIBUS-PA topology follows the physical
layer as defined in ISA SP50.02. Daisy chain or star topologies are allowed.
Process Control System
PROFIBUS-DP RS-485 Transmissions
JBBS-48SC-M633
PROFIBUS-PA IEC
61158-2 transmissions
FLDP-IOM 88-0001
Transmitters
RKV 40-1M
RSV RKV 48-1M
Trunk Line
RSV RKV 48-1M
RSV 48TR
RSV RKV 48-1M
RSFK BC
Segment
coupler/link
Transmitters
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708 www.turck.com
L22
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
TURCK
Network Media Products
PROFIBUS®-PA, Selection Guide
L23
Cables
Terminating Resistors
Feed Through Connectors
L24 - L28
L29
L30
Junctions
Conduit Adapters
Tees
L31 - L43
L45
L47
Gender Changers
Surge Suppressor
Field Wireable Tees
L48
L49
L50
Receptacles
Field Wireable Connectors
L51 - L58
L59
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708 www.turck.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Industrial
Automation
PROFIBUS®-PA, Cable Specifications
• Cable that Meets the Requirements of ISA/SP50
and PROFIBUS-PA Requirements for Type A Cable
• All Cables are Rated -40° to +105°C and are
Sunlight Resistant
• Available in 3-wire Versions with a Device Ground
or 2-wire Versions
Jacket
Braid Shield
Type A Cable Specifications
Designed for harsh environments
Data
Temperature range: -40° to +105°C
Foil Shield
Governed by: ISA SP50.02 specification
Sunlight resistant per test
PLTC and ITC rated (CSA FT4)
Jacket
Impedence [Z0 at fr (31.25 kHz)] = 100 Ohms + 20 %
Inner Jacket
Foil Shield
Maximum attenuation at 1.25 fr (39 kHz) = 3.0 dB/km
Drain Wire
Blue
Brown
Green/Yellow
Figure B
Maximum capacitive unbalance to shield = 2 nF/km
Maximum DC resistance (per conductor) = 24 Ohms /km
Maximum propagation delay variance 0.25 fr to 1.25 fr = 1.7 μs/km
PROFIBUS-PA Media
•
•
•
•
•
•
•
•
•
•
•
•
Drain Wire
Brown
Blue
Figure A
Data
Aluminum Armor
Conductor cross-sectional area (wire size) = nominal 0.8 mm2 (#18 AWG)
Minimum shield coverage shall be 90%.
Data Pair
Type
483
105°C 300 Volts
483B
105°C 300 Volts
482A
105°C 300 Volts
482BA
105°C 300 Volts
483BK
105°C 300 Volts
Approvals
Device Ground
Outer Jacket
Shields
Bulk Cable
Part Number / Figure
Weight/300 M
AWG
Color Code
DCR (/1000 feet)
Insulation
AWG
Color Code
Material Color
Nominal O.D.
Type
Drain Wire
NEC ITC PLTC
Open Wiring
CEC [CMG]
2/18 AWG
BU/BN
6.5 Ohms
XLPE
None
PVC Orange
7.9 mm (.310 in)
Foil/Braid
20 AWG
RB50785-*M
59 lbs.
A
NEC ITC PLTC
Open Wiring
CEC [CMG]
2/18 AWG
BU/BN
6.5 Ohms
XLPE
None
PVC Blue
7.9 mm (.310 in)
Foil/Braid
20 AWG
RB50786-*M
59 lbs.
A
NEC ITC PLTC/CM
CEC [CMG HLBCD]
2/18 AWG
BU/BN
6.5 Ohms
PVC
18 AWG
GN/YE
Armor/PVC Orange
14.9 mm (0.585 in)
Foil
20 AWG
RB50929-*M
96 lbs.
B
NEC ITC PLTC
CEC [CMG]
2/18 AWG
BU/BN
6.5 Ohms
PE
18 AWG
GN/YE
Armor/PVC Blue
14.9 mm (0.585 in)
Foil
20 AWG
RBS50929-*M
96 lbs.
B
NEC ITC PLTC
Open Wiring
CEC [CMG]
2/18 AWG
BU/BN
6.5 Ohms
PE
None
PVC Black
7.9 mm (.310 in)
Foil/Braid
20 AWG
RB50860-*M
59 lbs.
A
* Indicates length in meters.
Standard cable lengths are 1, 2, 4, 5, 6, 8, 10, 15, and in +5 meter increments from there. Consult factory for other lengths.
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708 www.turck.com
L24
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
TURCK
Network Media Products
PROFIBUS®-PA, Cable and Cordset Selection Matrix
minifast ®
Pin (Male)
1
eurofast ®
Pin (Male)
Socket (Female)
2
3
4
5
RSV
WSV
RKV
WKV
RSCV
RSV 48x-*M
WSV 48x-*M
RKV 48x-*M
WKV 48x-*M
RSCV 48x-*M
RSV RSV 48x-*M
RSV WSV 48x-*M
RSV RKV 48x-*M
RSV WKV 48x-*M
RSV RSCV 48x-*M
WSV WSV 48x-*M
WSV RKV 48x-*M
WSV WKV 48x-*M
WSV RSCV 48x-*M
RKV RKV 48x-*M
RKV WKV 48x-*M
RKV RSCV 48x-*M
WKV WKV 48x-*M
WKV RSCV 48x-*M
Bare
minifast
Pin (Male)
1
RSV
2
Socket (Female)
WSV
3
RKV
4
WKV
RSCV RSCV 48x-*M
RSCV
6
eurofast
Pin (Male)
5
Socket (Female)
WSCV
7
RKCV
8
WKCV
*
x
See pages L27 - L28 for dimensional drawings.
Indicates length in meters.
Indicates cable type.
Refer to the Cordset Builder at www.turck.com for assistance with cordset/cable combinations.
Standard cable lengths are 1, 2, 4, 5, 6, 8, 10, 15, and in +5 meter increments from there. Consult factory for other lengths.
minifast
Male
Pinouts
Female
eurofast
Male
Female
1. Brown (+ Voltage)
2. N/C
3. Blue (- Voltage)
4. Bare (Shield Drain Wire)
L25
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708 www.turck.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Industrial
Automation
PROFIBUS®-PA, Cable and Cordset Selection Matrix
Pin (Male)
6
7
minifast ® Bulkhead
Pin (Male)
Socket (Female)
8
9
10
eurofast Bulkhead
Pin (Male)
Socket (Female)
11
12
WSCV
RKCV
WKCV
RSFPV
RKFPV
FSFDV
FKFDV
WSCV 48x-*M
RKCV 48x-*M
WKCV 48x-*M
RSFPV 48x-*M
RKFPV 48x-*M
FSFDV 48x-*M
FKFDV 48x-*M
RSV WSCV 48x-*M
RSV RKCV 48x-*M
RSV WKCV 48x-*M
RSV RSFPV 48x-*M
RSV RKFPV 48x-*M
RSV FSFDV 48x-*M
RSV FKFDV 48x-*M
WSV WSCV 48x-*M
WSV RKCV 48x-*M
WSV WKCV 48x-*M
WSV RSFPV 48x-*M
WSV RKFPV 48x-*M
WSV FSFDV 48x-*M
WSV FKFDV 48x-*M
RKV WSCV 48x-*M
RKV RKCV 48x-*M
RKV WKCV 48x-*M
RKV RSFPV 48x-*M
RKV RKFPV 48x-*M
RKV FSFDV 48x-*M
RKV FKFDV 48x-*M
WKV WSCV 48x-*M
WKV RKCV 48x-*M
WKV WKCV 48x-*M
WKV RSFPV 48x-*M
WKV RKFPV 48x-*M
WKV FSFDV 48x-*M
WKV FKFDV 48x-*M
RSCV WSCV 48x-*M
RSCV RKCV 48x-*M
RSCV WKCV 48x-*M
RSCV RSFPV 48x-*M RSCV RKFPV 48x-*M RSCV FSFDV 48x-*M RSCV FKFDV 48x-*M
WSCV WSCV 48x-*M
WSCV RKCV 48x-*M
WSCV WKCV 48x-*M
WSCV RSFPV 48x-*M WSCV RKFPV 48x-*M WSCV FSFDV 48x-*M WSCV FKFDV 48x-*M
RKCV RKCV 48x-*M
RKCV WKCV 48x-*M
RKCV RSFPV 48x-*M RKCV RKFPV 48x-*M RKCV FSFDV 48x-*M RKCV FKFDV 48x-*M
WKCV WKCV 48x-*M
WKCV RSFPV 48x-*M WKCV RKFPV 48x-*M WKCV FSFDV 48x-*M WKCV FKFDV 48x-*M
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708 www.turck.com
PROFIBUS-PA Media
eurofast ®
Socket (Female)
L26
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
TURCK
Network Media Products
PROFIBUS®-PA, minifast ® Cordset and Receptacle Connector Dimensions
Specifications
Housing:
Coupling Nut:
Contact Carrier:
Contacts:
Protection:
Rated Voltage:
Rated Current:
Ambient Temperature:
PUR (Polyurethane)
Nickel Plated CuZn or Stainless Steel
TPU (Polyurethane)
Gold Plated CuZn
NEMA 1, 3, 4, 6P and IEC IP 68
300 V
9A
-40°C to +105°C (-40° to +221°F)
1
RSV ..
3
Pages L25 - L26
RKV ..
2
WSV ..
4
Pages L25 - L26
WKV ..
9
RSFPV ..
L27
Pages L25 - L26
Pages L25 - L26
10
Pages L25 - L26
RKFPV ..
Pages L25 - L26
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708 www.turck.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Industrial
Automation
PROFIBUS®-PA, eurofast ® Cordset and Receptacle Connector Dimensions
Specifications
Housing:
Coupling Nut:
Contact Carrier:
Contacts:
Protection:
Rated Voltage:
Rated Current:
Ambient Temperature:
PUR (Polyurethane)
Nickel Plated CuZn or Stainless Steel
TPU (Polyurethane) or POM (Nylon)
Gold Plated CuZn
NEMA 1, 3, 4, 6P and IEC IP 68
250 V
4A
-40° to +105°C (-40° to +221°F)
7
PROFIBUS-PA Media
5
RSCV ..
Pages L25 - L26
RKCV ..
6
WSCV ..
8
Pages L25 - L26
WKCV ..
11
FSFDV ..
Pages L25 - L26
Pages L25 - L26
12
Pages L25 - L26
FKFDV ..
Pages L25 - L26
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708 www.turck.com
L28
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
TURCK
Network Media Products
PROFIBUS®-PA, Terminating Resistors
• Terminating Resistors Stabilize and
Minimize Reflections on the Bus Line
• A Terminating Resistor is Required at the
Beginning and End of the Main Bus Line
Housing
L29
Part Number
Specs
RSV 48-TR
Nickel Plated Brass or
Stainless Steel
300 V, 9 A
-40° to +75°C
RSEV 48-TR
Nickel Plated Brass or
Stainless Steel
250 V, 4 A
-40° to +75°C
Application
Pinouts
Male
®
minifast Terminating Resistor
•
Male minifast connector
Male
eurofast ® Terminating Resistor
•
Male eurofast connector
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708 www.turck.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Industrial
Automation
PROFIBUS®-PA, Feed Through Connectors
• Receptacles Provide Transition from
Male to Female Connectors
• Available for Bulkhead and Feed Through
Applications
Part Number
Specs
Nickel Plated CuZn
or Stainless Steel
RSFV RKFV 48/22 300 V, 9 A
-40° to +75°C
Application
minifast ® Bulkhead
Receptacle
•
Straight male/female
feed through
•
For use with
DeviceNet minifast
cordsets
eurofast ® Feed Through
Connection
Nickel Plated CuZn
or Stainless Steel
•
straight male/female
connector
-40° to +75°C
•
for pre-molded
eurofast cables
FKV FSV 48/M12 250 V, 4 A
Pinouts
Male
Female
Male
Female
PROFIBUS-PA Media
Housing
Standard housing material is nickel plated brass. "RSF RKF.."; "RSFV RKFV.." indicates stainless steel housing.
Panel Cutout
RSFV RKFV 48/22
Panel Cutout
FKV FSV 48/M12
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708 www.turck.com
L30
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
TURCK
Network Media Products
PROFIBUS®-PA, minifast ® Passive Multiport Junctions (Bricks)
• Rugged, Fully Encapsulated Enclosure
• For Connecting I/O in Concentrated
Areas
• Suitable for Outdoor Applications
Part Number
Specs
JBBS-48-M413
Application
Wiring Diagrams
No short-circuit protection
4-port Junction
Electrical
JBBS-48SC-M413
•
•
•
Open circuit voltage: 35 VDC
Current consumption: 5 mA
Diagnostic
•
JBBS-48-M613
•
Bus in/bus out connections
(7/8-16UN) minifast
•
Four (7/8-16UN) minifast
connectors for field devices
•
CL I, Div 2; Groups A-D see
TURCK drawing N1-2.400
T6, Ta = 70°C (SC Only)
Short-circuit protection: 55 mA (Isc)
LED indicators
Power: Green = On
Short-circuit: Red = Shorted
No short-circuit protection
6-port Junction
Electrical
JBBS-48SC-M613
•
•
•
Open circuit voltage: 35 VDC
Current consumption: 5 mA
Diagnostic
•
JBBS-48-M813
•
Bus in/bus out connections
(7/8-16UN) minifast
•
Six (7/8-16UN) minifast
connectors for field devices
•
CL I, Div 2; Groups A-D see
TURCK drawing N1-2.400
T6, Ta = 70°C (SC Only)
Short-circuit protection: 55 mA (Isc)
LED indicators
Power: Green = On
Short-circuit: Red = Shorted
No short-circuit protection
8-port Junction
Electrical
JBBS-48SC-M813
•
•
•
Open circuit voltage: 35 VDC
Current consumption: 5 mA
Diagnostic
•
L31
•
Bus in/bus out connections
(7/8-16UN) minifast
•
Eight (7/8-16UN) minifast
connectors for field devices
•
CL I, Div 2; Groups A-D see
TURCK drawing N1-2.400
T6, Ta = 70°C (SC Only)
Short-circuit protection: 55 mA (Isc)
LED indicators
Power: Green = On
Short-circuit: Red = Shorted
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708 www.turck.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Industrial
Automation
Specifications
Housing:
Coupling Nut:
Contact Carrier:
Contacts:
Protection:
Rated Voltage:
Rated Current:
Ambient Temperature:
Anodized Aluminum
Nickel Plated CuZn or Stainless Steel
TPU (Polyurethane)
Gold Plated CuZn
NEMA 1, 3, 4, 6P and IEC IP 67, IP 68, IP 69K
300 V
9A
-40° to +75°C (-40° to +167°F)
Dimensions
6-Port
PROFIBUS-PA Media
8-Port
4-Port
Pinouts
minifast
Male
Female
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708 www.turck.com
L32
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
TURCK
Network Media Products
PROFIBUS®-PA, minifast ® Passive Multiport Junctions (Bricks)
• Rugged, Fully Encapsulated Enclosure
• For Connecting I/O in Concentrated
Areas
• Suitable for Outdoor Applications
Part Number
Specs
Application
Wiring Diagrams
4-port Junction
JBBS-48-M423
No short-circuit protection
Fiberglass housing
•
Bus in/bus out connections
(7/8-16UN) minifast
•
Four (7/8-16UN) minifast
connectors for field devices
CL I, Div 2; Groups A-D see TURCK
drawing N1-2.400
T6, Ta = 70°C (SC Only)
6-port Junction
JBBS-48-M623
No short-circuit protection
Fiberglass housing
•
Bus in/bus out connections
(7/8-16UN) minifast
•
Six (7/8-16UN) minifast
connectors for field devices
CL I, Div 2; Groups A-D see TURCK
drawing N1-2.400
T6, Ta = 70°C (SC Only)
L33
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708 www.turck.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Industrial
Automation
Specifications
Housing:
Coupling Nut:
Contact Carrier:
Contacts:
Protection:
Rated Voltage:
Rated Current:
Ambient Temperature:
Fiberglass
Nickel Plated CuZn or Stainless Steel
TPU (Polyurethane)
Gold Plated CuZn
NEMA 1, 3, 4, 6P and IEC IP 67, IP 68, IP 69K
300 V
9A
-40° to +75°C (-40° to +167°F)
Dimensions
6-Port
PROFIBUS-PA Media
4-Port
Pinouts
minifast
Male
Female
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708 www.turck.com
L34
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
TURCK
Network Media Products
PROFIBUS®-PA, eurofast ® Passive Multiport Junctions (Bricks)
• Rugged, Fully Encapsulated Enclosure
• For Connecting I/O in Concentrated
Areas
• Suitable for Outdoor Applications
Part Number
Specs
JBBS-48-E413
Application
Wiring Diagrams
No short-circuit protection
4-port Junction
Electrical
JBBS-48SC-E413
•
•
•
Open circuit voltage: 35 VDC
Current consumption: 5 mA
Diagnostic
•
JBBS-48-E613
•
Bus in/bus out connections
(M12x1) eurofast
•
Four (M12x1) eurofast
connectors for field devices
•
CL I, DIv 2; Groups A-D see
TURCK drawing N1-2.400
T6, Ta = 70°C (SC Only)
Short-circuit protection: 55 mA (Isc)
LED indicators
Power: Green = On
Short-circuit: Red = Shorted
No short-circuit protection
6-port Junction
Electrical
JBBS-48SC-E613
•
•
•
Open circuit voltage: 35 VDC
Current consumption: 5 mA
Diagnostic
•
JBBS-48-E813
•
Bus in/bus out connections
(M12x1) eurofast
•
Six (M12x1) eurofast
connectors for field devices
•
CL I, Div 2; Groups A-D see
TURCK drawing N1-2.400
T6, Ta = 70°C (SC Only)
Short-circuit protection: 55 mA (Isc)
LED indicators
Power: Green = On
Short-circuit: Red = Shorted
No short-circuit protection
8-port Junction
Electrical
JBBS-48SC-E813
•
•
•
Open circuit voltage: 35 VDC
Current consumption: 5 mA
Diagnostic
•
L35
•
Bus in/bus out connections
(M12x1) eurofast
•
Eight (M12x1) eurofast
connectors for field devices
•
CL I, Div 2; Groups A-D see
TURCK drawing N1-2.400
T6, Ta = 70°C (SC Only)
Short-circuit protection: 55 mA (Isc)
LED indicators
Power: Green = On
Short-circuit: Red = Shorted
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708 www.turck.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Industrial
Automation
Specifications
Housing:
Coupling Nut:
Contact Carrier:
Contacts:
Protection:
Rated Voltage:
Rated Current:
Ambient Temperature:
Anodized Aluminum
Nickel Plated CuZn or Stainless Steel
TPU (Polyurethane)
Gold Plated CuZn
NEMA 1, 3, 4, 6P and IEC IP 67, IP 68, IP 69K
250 V
4A
-40° to +75°C (-40° to +167°F)
Dimensions
6-Port
PROFIBUS-PA Media
8-Port
4-Port
Pinouts
eurofast
Male
Female
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708 www.turck.com
L36
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
TURCK
Network Media Products
PROFIBUS®-PA, eurofast ® Passive Multiport Junctions (Bricks), Short-Circuit Protected
• Rugged, Fully Encapsulated Enclosure
• For Connecting I/O in Concentrated
Areas
• Suitable for Outdoor Applications
Part Number
Specs
Diagnostic
JBBS-48SC-E613/EX
L37
•
LED indicators
Power: Green = On
Short-circuit: Red = Shorted
•
•
•
Short-Circuit Protection ≤35 mA
Current consumption ≤7 mA
Voltage drop ≤0.3 V
Application
Wiring Diagrams
6-port Junction
•
Bus in/bus out connections
(M12x1) eurofast
•
Six (M12x1) eurofast
connectors for field devices
CL I, Div 2; Groups A-D see TURCK
drawing N1-2.400
T6, Ta = 70°C (SC Only)
FISCO/ENTITY Field Device
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708 www.turck.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Industrial
Automation
Specifications
Housing:
Coupling Nut:
Contact Carrier:
Contacts:
Protection:
Rated Voltage:
Rated Current:
Ambient Temperature:
Anodized Aluminum
Nickel Plated CuZn
TPU (Polyurethane)
Gold Plated CuZn
NEMA 1, 3, 4, 6P and IEC IP 67, IP 68, IP 69K
250 V
4A
-40° to +75°C (-40° to +167°F)
Dimensions
PROFIBUS-PA Media
6-Port
Pinouts
eurofast
Male
Female
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708 www.turck.com
L38
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
TURCK
Network Media Products
PROFIBUS®-PA, eurofast ® Passive Multiport Junctions (Bricks)
• Rugged, Fully Encapsulated Enclosure
• For Connecting I/O in Concentrated
Areas
• Suitable for Outdoor Applications
Part Number
Specs
Application
Wiring Diagrams
4-port Junction
JBBS-48-E414
No short-circuit protection
•
Bus in/bus out connections
(M12x1) eurofast
•
Four (M12x1) eurofast
connectors for field devices
CL I, DIv 2; Groups A-D see TURCK
drawing N1-2.400
T6, Ta = 70°C (SC Only)
6-port Junction
JBBS-48-E614
No short-circuit protection
•
Bus in/bus out connections
(M12x1) eurofast
•
Six (M12x1) eurofast
connectors for field devices
CL I, Div 2; Groups A-D see TURCK
drawing N1-2.400
T6, Ta = 70°C (SC Only)
8-port Junction
JBBS-48-E814
No short-circuit protection
•
Bus in/bus out connections
(M12x1) eurofast
•
Eight (M12x1) eurofast
connectors for field devices
CL I, Div 2; Groups A-D see TURCK
drawing N1-2.400
T6, Ta = 70°C (SC Only)
L39
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708 www.turck.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Industrial
Automation
Specifications
Housing:
Coupling Nut:
Contact Carrier:
Contacts:
Protection:
Rated Voltage:
Rated Current:
Ambient Temperature:
Anodized Aluminum
Nickel Plated CuZn or Stainless Steel
TPU (Polyurethane)
Gold Plated CuZn
NEMA 1, 3, 4, 6P and IEC IP 67, IP 68, IP 69K
250 V
4A
-40° to +75°C (-40° to +167°F)
Dimensions
6-Port
PROFIBUS-PA Media
8-Port
4-Port
Pinouts
eurofast
Male
Female
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708 www.turck.com
L40
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
TURCK
Network Media Products
PROFIBUS®-PA, minifast ® Junction Tees
• Indoor Use Only
(for outdoor applications use JBBS family)
• Multi-port Junction Provides a Rugged
Connection to Network Devices
• Bus-in/Bus-out Feature Eliminates Need for
Splitter Tee
Part Number
Specs
JTBS-48-M433
Application
Wiring Diagrams
No short-circuit protection
4-port Junction Tee
•
(7/8-16UN) minifast bus in/bus
out connections
•
Four (7/8-16UN) minifast
device ports
•
For nickel plated brass
connectors change part number
to JTBS 48SC-M434
•
CL I, Div 2; Groups A-D see
TURCK drawing N1-2.400
T6, Ta = 70°C (SC Only)
Electrical
JTBS-48SC-M433
•
•
•
Short-circuit protection: 55 mA (Isc)
Open circuit voltage: 35 VDC
Current consumption: 5 mA
Diagnostic
•
JTBS-48-M633
LED indicators
Power: Green = On
Short-circuit: Red = Shorted
No short-circuit protection
6-port Junction Tee
•
(7/8-16UN) minifast bus in/bus
out connections
•
Six (7/8-16UN) minifast
device ports
•
For nickel plated brass
connectors change part number
to JTBS 48SC-M634
•
CL I, Div 2; Groups A-D see
TURCK drawing N1-2.400
T6, Ta = 70°C (SC Only)
Electrical
JTBS-48SC-M633
•
•
•
Short-circuit protection: 55 mA (Isc)
Open circuit voltage: 35 VDC
Current consumption: 5 mA
Diagnostic
•
L41
LED indicators
Power: Green = On
Short-circuit: Red = Shorted
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708 www.turck.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Industrial
Automation
Specifications
Housing:
Coupling Nut:
Contact Carrier:
Contacts:
Protection:
Rated Voltage:
Rated Current:
Ambient Temperature:
PUR (Polyurethane)
Nickel Plated CuZn or Stainless Steel
POM (Nylon)
Gold Plated CuZn
NEMA 1, 3, 4, 6P and IEC IP 67
250 V
4A
-40° to +75°C (-40° to +167°F)
Dimensions
6-port
PROFIBUS-PA Media
4-port
Pinouts
minifast
Male
Female
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708 www.turck.com
L42
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
TURCK
Network Media Products
PROFIBUS®-PA, eurofast ® Junction Tee
• Indoor Use Only
(for outdoor applications use JBBS family)
• Multi-port Junction Provides a Rugged
Connection to Network Devices
• Bus-in/Bus-out Feature Eliminates Need for
Splitter Tee
Part Number
Specs
JTBS-48-E433
Application
Wiring Diagrams
No short-circuit protection
4-port Junction Tee
•
(M12x1) eurofast bus in/bus out
connections
•
Four (M12x1) eurofast
device ports
•
For nickel plated brass
connectors change part number
to JTBS 48SC-E434
•
CL I, Div 2; Groups A-D see
TURCK drawing N1-2.400
T6, Ta = 70°C (SC Only)
Electrical
JTBS-48SC-E433
•
•
•
Short-circuit protection: 55 mA (Isc)
Open circuit voltage: 35 VDC
Current consumption: 5 mA
Diagnostic
•
JTBS-48-E633
LED indicators
Power: Green = On
Short-circuit: Red = Shorted
No short-circuit protection
6-port Junction Tee
•
(M12x1) eurofast bus in/bus out
connections
•
Six (M12x1) eurofast
device ports
•
For nickel plated brass
connectors change part number
to JTBS 48SC-E634
•
CL I, Div 2; Groups A-D see
TURCK drawing N1-2.400
T6, Ta = 70°C (SC Only)
Electrical
JTBS-48SC-E633
•
•
•
Short-circuit protection: 55 mA (Isc)
Open circuit voltage: 35 VDC
Current consumption: 5 mA
Diagnostic
•
L43
LED indicators
Power: Green = On
Short-circuit: Red = Shorted
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708 www.turck.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Industrial
Automation
Specifications
Housing:
Coupling Nut:
Contact Carrier:
Contacts:
Protection:
Rated Voltage:
Rated Current:
Ambient Temperature:
PUR (Polyurethane)
Nickel Plated CuZn or Stainless Steel
POM (Nylon)
Gold Plated CuZn
NEMA 1, 3, 4, 6P and IEC IP 67
250 V
4A
-40° to +75°C (-40° to +167°F)
Dimensions
6-port
PROFIBUS-PA Media
4-port
Pinouts
minifast
Male
eurofast
Female
Female
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708 www.turck.com
L44
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
TURCK
Network Media Products
PROFIBUS®-PA, minifast ® Conduit Adapters
• Gasket and Mounting Screws Provided
• Same Housing Style for Single or Double
Port
Housing
Part Number
Specs
Application
Pinout
Attaches to standard conduit
body* for transition to 4-wire
(7/8-16UN) minifast connector
BCA 48-M123
*Crouse-Hinds 3/4" Form 8, or
Mark 9 or equivalent.
Male
Nylon Housing
300 V, 9 A
-40° to +75°C
BCA 48-M223
Attaches to standard conduit
body* for transition to 4-wire
(7/8-16UN) minifast connector
*Crouse-Hinds 3/4" Form 8, or
Mark 9 or equivalent.
1-port Wiring Diagram
L45
2-port Wiring Diagram
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708 www.turck.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Industrial
Automation
PROFIBUS®-PA, eurofast ® Conduit Adapters
• Gasket and Mounting Screws Provided
• Same Housing Style for Single or Double
Port
Part Number
Specs
Application
Pinout
Attaches to standard conduit
body* for transition to 4-wire
(M12x1) eurofast connector
BCA 48-E123
PROFIBUS-PA Media
Housing
*Crouse-Hinds 3/4" Form 8, or
Mark 9 or equivalent.
Female
Nylon Housing
250 V, 4 A
-40° to +75°C
BCA 48-E223
Attaches to standard conduit
body* for transition to 4-wire
(M12x1) eurofast connector
*Crouse-Hinds 3/4" Form 8, or
Mark 9 or equivalent.
1-port Wiring Diagram
2-port Wiring Diagram
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708 www.turck.com
L46
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
TURCK
Network Media Products
PROFIBUS®-PA, Tees
• Creates a Drop or Branch from the Main
Bus Line
• minifast ® Connectors on Bus or Drop
Lines
Housing
Part Number
Specs
Application
Wiring Diagrams
minifast Tee
•
•
RSV 2RKV 48
RSV FKV RKV 48
PUR
(Polyurethane)
250 V, 4 A
-40° to +75°C
Data, ground, shield
Stainless steel
coupling nuts
minifast to eurofast ® Drop
•
•
Data, ground, shield
Stainless steel coupling
nuts
eurofast Tee
RSCS 2RKCS 48
•
Stainless steel
coupling nuts
Pinouts
minifast
Male
L47
eurofast
Female
Male
Female
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708 www.turck.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Industrial
Automation
PROFIBUS®-PA, Gender Changers and Elbow Connectors
• Allows Quick and Easy Changes from
Male to Female minifast ® Connectors
Housing
Part Number
Specs
Application
Male minifast Gender Changer
RKV RKV 48
•
Changes female cordset to male receptacle
PROFIBUS-PA Media
RSV RSV 48
TPU (Polyurethane) Female minifast Gender Changer
250 V, 4 A
• Changes female cordset to male receptacle
-40° to +75°C
minifast Elbow
WSV RKV 48
•
Right angle male to female connector
Pinouts
minifast
Male
Female
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708 www.turck.com
L48
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
TURCK
Network Media Products
PROFIBUS®-PA, Surge Suppressor
• Protects Data Communication Lines (V+ and V-)
• Absorbs the Front End of the Transient,
Responding in Less Than a Nanosecond
• Diverts the Surge Energy to Ground
• Automatically Resets and waits for Next Surge
Housing
Part Number
Specs
Application
Pinouts
Electrical
See Drawing 1
RSV RKV 48 SS
•
•
•
•
•
•
•
•
•
Male
Maximum operating voltage: 27 Volts
Maximum operating current: 200 mA
Clamping Action Turn-on: 28.5 Volts
Maximum clamping at 2 kA: (8 x 20 Sec): 44 Volts
Maximum surge voltage: 20 kV
Maximum surge current: 2.5 kA
Current leakage/line at operating voltage: 5 A
Male and female
minifast ®, 4-pin
Female
Capacitance /line at operating voltage: 500 pF
Response time: Less than 1 nanosecond
Mechanical
•
•
Ground Stud: 10-32 stainless steel
Operating temperature: -40° to +85°C
1
L49
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708 www.turck.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Industrial
Automation
PROFIBUS®-PA, Field Wireable Tee
• A Hybrid Connection System Offering
Reliable Connections on the Short Drops and
Ease of Installation on the Long Trunk Runs
• Features Standard minifast ® Connector for
the Drop Connection and Terminal
Connectors on the Trunk Connections
See Drawing 1
Part Number
Specs
SPTT1-A48
Pinout
Female
Anodized Aluminum
250 V, 4 A
-40° to +75°C
NEMA 1, 3, 4, 6P and IEC IP 68
See Drawing 2
Application
(7/8-16UN) minifast connector for drop
connection, and field wireable terminals on
the trunk connections.
PROFIBUS-PA Media
Housing Style
SPTTM13-A48
1
2
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708 www.turck.com
L50
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
TURCK
Network Media Products
PROFIBUS®-PA, (7/8-16UN) minifast ® Male Receptacles
• Provides Quick Connection to Field
Devices
• Available for 1/2-14NPT, 1/2-14NPSM,
3/4-14NPT and M20 Threads
Housing
Part Number
Specs
Application
Pinouts
13
RSFV 48-*M/14.5
1/2-14NPT full length
threads
RSFV 48-*M/14.75
3/4-14NPT full length
threads
15
14
Male
RSFV 48-*M/M20
Nickel Plated CuZn
or Stainless Steel
M20x1.5 threads
600 V, 9 A
-40° to +105°C
1.
2.
3.
4.
BN
N/C
BU
N/C
16
RSFV 48-*M
1/2-14NPSM threads
RSFV 48-*M/NPT
1/2-14NPT modified
length threads
17
See page L53 for dimensional drawings.
Standard cable length is 0.3 Meters. Consult factory for other lengths.
Receptacles require a 13/16" (21 mm) clearance hole for panel mounting.
Standard housing material is nickel plated brass. "RKFV .."; indicates 316 stainless steel housing.
For locknuts to be included, add "W/LN" to the end of the part number.
L51
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708 www.turck.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Industrial
Automation
PROFIBUS®-PA, (7/8-16UN) minifast ® Female Receptacles
• Provides Quick Connection to Field Devices
• Available for 1/2-14NPT, 1/2-14NPSM,
3/4-14NPT and M20 Threads
Housing
Part Number
Specs
Application
Pinouts
RKFV 48-*M/14.5
1/2-14NPT full length
threads
RKFV 48-*M/14.75
3/4-14NPT full length
threads
PROFIBUS-PA Media
18
20
19
RKFV 48-*M/M20
Nickel Plated CuZn
or Stainless Steel
M20x1.5 threads
600 V, 9 A
-40° to +105°C
Female
1.
2.
3.
4.
BN
N/C
BU
GY
21
RKFV 48-*M
1/2-14NPSM threads
RKFV 48-*M/NPT
1/2-14NPT modified
length threads
22
See page L54 for dimensional drawings.
Standard cable length is 0.3 Meters. Consult factory for other lengths.
Receptacles require a 13/16" (21 mm) clearance hole for panel mounting.
Standard housing material is nickel plated brass. "RKFV .."; indicates 316 stainless steel housing.
For locknuts to be included, add "W/LN" to the end of the part number.
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708 www.turck.com
L52
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
TURCK
Network Media Products
PROFIBUS®-PA, (M12x1) eurofast ® Male Receptacles
• Mounted for Quick Connection to
Enclosures
• Available for 1/2-14NPT, 1/2-14NPSM,
3/4-14NPT and M20 Threads
Housing
Part Number
Specs
Application
Pinout
23
FSV 48-*M/14.5
1/2-14NPT full length
threads
FSV 48-*M/14.75
3/4-14NPT full length
threads
25
Male
24
FSV 48-*M/M20
Nickel Plated CuZn
or Stainless Steel
M20x1.5 threads
250 V, 4 A
-40° to +105°C
1.
2.
3.
4.
BN
N/C
BU
N/C
26
FSV 48-*M
PG 9 threads
FSV 48-*M/NPT
1/2-14NPT modified
length threads
27
See page L55 for dimensional drawings.
Standard cable length is 0.3 Meters. Consult factory for other lengths.
Receptacles require a 13/16" (21 mm) clearance hole for panel mounting.
Standard housing material is nickel plated brass. "RKFV .."; indicates 316 stainless steel housing.
L53
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708 www.turck.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Industrial
Automation
PROFIBUS®-PA, (M12x1) eurofast ® Female Receptacles
• Mounted for Quick Connection to
Enclosures
• Available for 1/2-14 NPT, 1/2-14 NPSM,
3/4-14 NPT and M20 Threads
Housing
Part Number
Specs
Application
Pinouts
FKV 48-*M/14.5
1/2-14NPT full length
threads
FKV 48-*M/14.75
3/4-14NPT full length
threads
PROFIBUS-PA Media
28
30
Female
29
FKV 48-*M/M20
Nickel Plated CuZn
or Stainless Steel
M20x1.5 threads
250 V, 4 A
-40° to +105°C
1.
2.
3.
4.
BN
N/C
BU
GY
31
FKV 48-*M
PG 9 threads
FKV 48-*M/NPT
1/2-14NPT modified
length threads
32
See page L56 for dimensional drawings.
Standard cable length is 0.3 Meters. Consult factory for other lengths.
Receptacles require a 13/16" (21 mm) clearance hole for panel mounting.
Standard housing material is nickel plated brass. "RKFV .."; indicates 316 stainless steel housing.
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708 www.turck.com
L54
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
TURCK
Network Media Products
minifast ® Male Receptacles
13
RSFV .. 14.5
15
Page L49
RSFV .. 14.75
14
RSFV .. M20
Page L49
16
Page L49
RSFV ..
Page L49
17
RSFV .. NPT
L55
Page L49
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708 www.turck.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Industrial
Automation
minifast ® Female Receptacles
18
RKFV .. 14.5
20
Page L50
RKFV .. 14.75
21
PROFIBUS-PA Media
19
Page L50
RKFV .. M20
Page L50
RKFV ..
Page L50
22
RKFV .. NPT
Page L50
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708 www.turck.com
L56
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
TURCK
Network Media Products
eurofast ® Male Receptacles
23
FSV .. 14.5
25
Page L51
FSV .. 14.75
24
FSV .. M20
Page L51
26
Page L51
FSV ..
Page L51
27
FSV .. NPT
L57
Page L51
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708 www.turck.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Industrial
Automation
eurofast ® Female Receptacles
28
FKV .. 14.5
30
Page L52
FKV .. 14.75
31
PROFIBUS-PA Media
29
Page L52
FKV .. M20
Page L52
FKV ..
Page L52
32
FKV .. NPT
Page L52
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708 www.turck.com
L58
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
TURCK
Network Media Products
PROFIBUS®-PA, minifast ® Field Wireable Connectors
• Screw Terminals Accept up to 16 AWG
Conductors
Housing
Part Number
BS 4148-0/9
BS 4148-0/13.5
BK 4140-0/9
B 4148-0/13.5
Specs
Application
Glass filled nylon
PG 9 cable gland,
accepts 6-8 mm cable diameter
85°C
250 V, 9 A
Glass filled nylon
PG 13.5 cable gland
accepts 10-12 mm cable diameter
85°C
250 V, 9 A
Glass filled nylon
PG 9 cable gland,
accepts 6-8 mm cable diameter
85°C
250 V, 9 A
Pinout
Female
Mates with all 4-pin
minifast cordsets and
receptacles
Male
Glass filled nylon
PG 13.5 cable gland
accepts 10-12 mm cable diameter
85°C
250 V, 9 A
For stainless steel coupling nuts change part number BS ... to BSV … BK … To BV
L59
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708 www.turck.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Industrial
Automation
PROFIBUS®-PA, eurofast ® Field Wireable Connectors
• Screw Terminals Accept up to 18 AWG
Conductors
Part Number
BS 8141-0/PG9
BS 8241-0/PG9
Specs
Application
Pinouts
PBT, Black
PG 7 cable gland,
accepts 4-8 mm cable diameter
85°C
125 V, 4 A
Male
PROFIBUS-PA Media
Housing
PBT, Black
PG 7 cable gland,
accepts 4-8 mm cable diameter
85°C
125 V, 4 A
Mates with standard key
4-pin eurofast cordsets
and receptacles
B 8141-0/PG9
B 8241-0/PG9
PBT, Black
PG 7 cable gland,
accepts 4-8 mm cable diameter
85°C
250 V, 4 A
Female
PBT, Black
PG 7 cable gland,
accepts 4-8 mm cable diameter
85°C
250 V, 4 A
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708 www.turck.com
L60
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
TURCK
Network Media Products
PROFIBUS®-PA, Gender Changers and Elbow Connectors
• Allows Quick and Easy Changes from
Male to Female and minifast ®
to eurofast ® Connectors
Housing
Part Number
Specs
Application
Nickel plated brass
CuZn or Stainless Steel
RSM 48-FK 4.4 250 V, 4 A
-40° to +80°C
Wiring Diagram
Female eurofast, male
minifast, 4-pin
Pinouts
L61
minifast
eurofast
Male
Female
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708 www.turck.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Industrial
Automation
PROFIBUS-PA Media
Notes:
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708 www.turck.com
L62
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertisement