LED-SIGNALS

1

2

4

5

The ORANGE LED fl ashes every second.

The ORANGE LED fl ashes 1 x.

The ORANGE LED fl ashes 2 x.

The ORANGE LED fl ashes 4 x.

The ORANGE LED fl ashes 5 x.

The sensor goes into security mode.

The sensor signals an internal fault.

Irregularities in the power supply

The sensor receives not enough IR-energy.

The sensor receives too much IR-energy.

The ORANGE LED is on.

The RED LED fl ashes quickly after an assisted setup.

The sensor encounters a memory problem.

The sensor sees the door during the assisted setup.

The sensor vibrates.

The RED LED lights up sporadically.

The sensor sees the door.

The sensor is disturbed by lamps or another sensor.

The sensor is disturbed by the rain.

1 Cut and restore power supply.

1

2

Cut and restore power supply.

If orange LED fl ashes again, replace sensor.

1

2

Check power supply.

Check wiring.

1

2

Use the 1 m prism if possible.

Check the angle of the IR-curtains.

1

2

Use a low energy prism if possible.

Check the angle of the IR-curtains.

1

2

Cut and restore power supply.

If orange LED lights up again, replace sensor.

1

2

Check the angle of the IR-curtains.

Launch a new assisted setup.

Attention: Do not stand in the detection fi eld!

1

2

1

Check if the sensor is fastened fi rmly.

Check position of prism and cover.

Launch an assisted setup and adjust the IR angle.

1 Choose a different frequency by remote control.

1

2

Increase the IR-immunity fi lter to value 2 or 3.

Select presetting 2 or 3 by push button.

Please keep for further use

Designed for colour printing

F I

Z I E R U N G

R

T I N

E

A

C

Z

H

U

B

T

DIN 1

865

0

C

E

E N

N A

A D

B L

O

R

E S

A C C

W

DESCRIPTION

Other use of the device is outside the permitted purpose and can not be guaranteed by the manufacturer.

The manufacturer cannot be held responsible for incorrect installations or inappropriate adjustments of the sensor.

IRIS PULSE

Safety sensor for automatic sliding doors

2

SAFETY INSTRUCTIONS

The manufacturer of the door system is responsible for carrying out a risk assessment and installing the sensor and the door system in compliance with applicable national and international regulations and standards on door safety and if applicable, the machinery directive 2006/42/EC.

Only trained and qualifi ed personnel may install and setup the sensor.

The warranty is void if unauthorized repairs are made or attempted by unauthorized personnel.

Avoid touching any electronic and optical components.

BEA SA | LIEGE Science Park | ALLÉE DES NOISETIERS 5 - 4031 ANGLEUR [BELGIUM] | T +32 4 361 65 65 | F +32 4 361 28 58 | [email protected] | WWW.BEA.BE

BEA hereby declares that the IRIS PULSE is in conformity with the basic requirements and the other relevant provisions of the directives 2004/108/EC and 2006/42/EC.

Notifi ed Body for EC inspection: 0044 - TÜV NORD CERT GmbH, Langemarckstr. 20, D-45141 Essen

Angleur, November 2010 Jean-Pierre Valkenberg, Authorized representative

The complete declaration of conformity is available on our website: www.bea.be

Only for EC countries: According to the European Guideline 2002/96/EC for Waste Electrical and Electronic Equipment (WEEE)

1

4. IR-curtain ajustment screw

2. cover

TECHNICAL SPECIFICATIONS

Supply voltage:

Power consumption:

Mounting height:

Temperature range:

Degree of protection:

Expected lifetime:

Norm conformity:

12 V - 24 V AC +/-10% ; 12 V - 30 V DC -5%/+10%

(to be operated from SELV compatible power supplies only)

< 3 W

1.8 m to 4 m

(< 3 m to enable DIN 18650-conformity)

-25 °C to +55 °C

IP54

5 years

EMC 2004/108/EC; MD 2006/42/EC; EN 12978

EN ISO 13849-1:2008 Performance Level «c» CAT. 2

(under the condition that the door control system monitors the sensor at least once per door cycle)

Detection mode:

Technology:

Angle:

Hold time output signal:

Output:

Input:

RED

LED

Presence

Typical response time: <128 ms (max. 500 ms)

Active infrared with background analysis

Spot diameter: 0.1 m (typ)

Number of spots: 24 or 12 by curtain; Number of curtains: 2

From -4 ° to +4 ° (adjustable)

0.3 s to 1 s (not adjustable)

Transistor (NPN open collector) requiring ext. pull-up resistor

Max. output current: 25 mA

Max. switching power: 40 V DC

Max. pulse amplitude (detection state or fail state): 0,8 V

Input Impedance: 100 kΩ; Max. input voltage: 30 V DC

External pull-up resistor: < 470 Ω (check compatibility)

Min. Pulse amplitude (Vpp): > 50% of sensor supply voltage

Max. Pulse duration: 100 μs @ 25 mA output current

Min. time interval between pulses: > pulse duration j g p

All values measured in optimal conditions.

3

4

5

IRIS PULSE

1

MOUNTING & WIRING

max 5 cm

The door control unit and the door cover profi le must be correctly earthed.

12-24 V

AC-DC

GREEN

BROWN

YELLOW*

GREY*

POWER SUPPLY

OPENING INPUT

OPENS DOOR

PINK

WHITE

SAFETY OUTPUT

BEAM TRANSMITTER

SAFETY INPUT

BEAM RECEIVER

* Connect to launch an assisted setup.

2

INFRARED FIELD - SAFETY

H H

0

1

2

3 3

2

W

1

2

0

1

2

3 3

W

1

2

2 m

H W

2.20 m 2.35 m

2.50 m 2.50 m

3.00 m 2.70 m

1 m

H W

2.20 m 1.35 m

2.50 m 1.50 m

3.00 m 1.70 m

Detection fi eld width indicated according to conditions defi ned in DIN 18650 and including dimension of test body CA.

«click»

RED

LED

max.

5 cm

DOOR

Check position of

IR-curtains with

Spotfi nder and adjust if necessary.

ORANGE

TIP : Launch an ASSISTED SETUP to verify wiring, position of the curtains and correct functioning of the sensor.

It is recommended to clean the optical parts at least once a year or more often if required due to environmental conditions.

3

SETTINGS

(by push buttons and/or remote control)

PRESETTINGS

3x GREEN LED

PUSH LEFT

(KEEP PUSHED)

RESETTING TO

FACTORY VALUES

STANDARD

CRITICAL ENVIRONMENT

SHOPPING STREET

PUSH

LEFT + RIGHT

>

RED-GREEN

1

OR

IRIS PULSE

RELEASE AFTER

FLASH OF DESIRED

SETTING

RED-GREEN OFF

PRESETTING

SELECTED

OUTPUT

REDIRECTION

NUMBER OF

CURTAINS

IMMUNITY FILTER*

PULSE FREQUENCY

MAX. PRESENCE

TIME safety safety

+ opening

0 presence detection on safety input

1 presence detection on safety and opening input service mode

1 freq A

2 normal medium high service mode = no detection is active during 15 minutes (maintenance).

freq B

> > freq A+

> > freq B+ immunity 3 is only suitable if a combined sensor is on each side of the door

30 s

1 min

2 min

5 min

10 min

20 min

60 min

FACTORY VALUES excludes DIN18650-conformity of the door system

* In immunity 2 and 3, the standard detection capability is the same as in immunity 1 (factory setting). Environmental and installation conditions can affect the detection capability of the sensor or can impact the availability of the door system. During harsh conditions, the sensor can temporarily adapt the detection capability to ensure the availability of the door system.

4

SETUP

(step out of the detection fi eld during setup)

QUICK SETUP =

RED-GREEN OFF

ASSISTED SETUP =

OPEN+CLOSE

+

RED-GREEN OFF

>

PUSH RIGHT UNTIL RED-GREEN

FLASHES

OR

IMPORTANT

:

Test the good functioning of the installation before leaving the premises.